Honeywell TH8321R1001, TH8320R1003, TH8110R1008, THM5421R1021 Specifications

VisionPRO® 8000 with RedLINK
SUBMITTAL SHEET
APPLICATION
RedLINK VisionPRO is a 7-Day programmable thermostat with auto changeover that is designed for single stage and multistage control of conventional and heat pump equipment such as rooftop units and split systems in residential and commercial applications. RedLINK VisionPRO can be used with or without an equipment interface module. The thermostat controls up to 3 heat / 4 cool conventional systems and up to 4 heat / 2 cool heat pump systems. The thermostat controls
humidication, dehumidication, ventilation, an economizer and a
lighting panel. Universal sensor inputs are used with remote indoor air
temperature sensor(s), an outdoor air temperature sensor, a discharge air temperature sensor, a return air temperature sensor, an occupancy
sensor for remote setback and dry contact devices for displaying alerts.
The thermostat is equipped with a touchscreen display with a 2 line message center.
• Provides a microSD card port to upload Dealer Information, Custom Reminders, Custom Event Schedules, Holiday Schedule and
Software Updates and to download Data Logs.
Provides remote access to the thermostat when used with the RedLINK internet gateway.
Provides control using optional remote temperature and humidity sensors.
Thermostat integrates with the Niagara-AX framework.
SPECIFICATIONS
Terminal Designations:
Equipment Interface Module: R, RC, RH, C, W-O/B, W2-AUX 1, W3-
AUX 2, Y, Y2, G, A-L/A, U1 U1, U2 U2, U3 U3, S1 S1, S2 S2, S3 S3, S4 S4, A, B, C, D
TH8321 Thermostat: R, RC, C, W-O/B, W2-AUX/E, Y, Y2, G, A-L/A, K,
U1 U1, S1 S1
TH8320 Thermostat: R, RC, C, W-O/B, W2-AUX/E, Y, Y2, G, A-L/A, K,
S1 S1
TH8110 Thermostat: R, RC, C, W-O/B, Y, G, K, S1 S1
Electrical Ratings (for VisionPRO and Equipment Interface Module):
Terminal Voltage
(50/60 Hz)
W - O/B 18 to 30 VAC
and 750 mVDC
Y (cooling) 18 to 30 VAC 1.00A
G (fan) 18 to 30 VAC 0.50A
W2 - Aux 1 (heating) 18 to 30 VAC 0.60A
W3 - Aux 2 (heating) 18 to 30 VAC 0.60A
Y2 (cooling) 18 to 30 VAC 0.60A
A-L/A (Output) 18 to 30 VAC 1.00A
(U1, U1), (U2, U2), (U3, U3) 30 VAC max. 0.50A
Power Consumption of TH8321/TH8320/TH8110 Thermostat:
Backlight on: 1.44 VA Backlight off: 1.32 VA
Power Consumption of Equipment Interface Module: 2.0 VA
RedLINK Communication:
Frequency: 900 Mhz frequency range
Re-Sync Time: RedLINK devices re-establish communication
within 6 minutes after AC power resumes.
Temperature Setting Range:
Heating: 40 to 90 °F (4.5 to 32 °C)
Cooling: 50 to 99 °F (10 to 37 °C)
Temperature Sensor Accuracy:
± 1.5 °F at 70 °F (0.75 °C at 21.0 °C)
Humidication Setting Range: 10% to 60% RH
Dehumidication Setting Range: 40% to 80% RH
Humidity Display Range: 0% to 99%
Humidity Sensor Accuracy:
± 5% RH from 30% to 50% RH at 75 °F (24 °C)
Cool Indication:
Displays “Cool On” when the thermostat turns the cooling on.
Max. Current Rating
1.00A
Job Name
Engineer
Mechanical Contractor
Contractor’s P.O. No.
Notes
Model(s) Qty.
TH8321R1001 TH8320R1003 TH8110R1008 THM5421R1021
Approval
Service
Tag No.
33-00016-01
SPECIFICATIONS (CONTINUED)
Heat Indication:
Displays “Heat On” when the thermostat turns the heating on.
Auxiliary Heat Indication:
Displays “Aux Heat On” when the thermostat turns the auxiliary heat on.
Interstage Differential:
Comfort: The thermostat keeps the indoor temperature within 1 degree of the
setpoint (droop less control). The thermostat turns on stage 2 when the
capacity on stage 1 reaches 90%.
When the interstage differential is set to 1.0 or higher, the thermostat stages
the equipment based on how far the indoor temperature is from the setpoint.
Clock Accuracy:
1 minute per month at 77 °F (25 °C). ± 2 minutes per month over
the operating ambient temperature range.
Mounting Means:
Thermostat mounts directly on the wall in the living space using
mounting screws and anchors provided. Fits a horizontal 2 x 4 in. junction box. Use a cover plate and its mounting bracket to mount the thermostat onto a vertical 2 x 4 in. junction box.
Equipment Interface Module (EIM) mounts on HVAC equipment
or on a wall in the equipment room.
Product Part Number Operating Ambient
Temperature
Thermostat TH8321R1001 32 to 120 °F
TH8320R1003 32 to 120 °F
TH8110R1008 32 to 120 °F
Equipment
Interface
Module
YTHM5421R1010 THM5421R1021
(0 to 48.9 °C)
(0 to 48.9 °C)
(0 to 48.9 °C)
-40 to 165 °F (-40 to 73.9 °C)
Dimensions of thermostat in in. (mm).
4-5/8 (118)
Operating
Relative
Shipping
Temperature
Humidity
5% to 90% Non-Condensing
5% to 90% Non-Condensing
5% to 90% Non-Condensing
5% to 95% Non-Condensing
-20 to 120 °F (-28.9 to 48.9 °C)
-20 to 120 °F (-28.9 to 48.9 °C)
-20 to 120 °F (-28.9 to 48.9 °C)
-20 to 165 °F (-28.9 to 73.9 °C)
Dimensions of VisionPRO cover plate in in. (mm).
6-5/32
5-3/4 (146)
1-1/2
(38)
(156)
25/32
(20)
Physical Dimensions in
Color(s)
in. (mm)
4-15/16 x 4-5/8 x 1-1/8 (126 x 118 x 29)
4-15/16 x 4-5/8 x 1-1/8 (126 x 118 x 29)
4-15/16 x 4-5/8 x 1-1/8 (126 x 118 x 29)
9-11/32 x 4-53/64 x 1-19/32 (237 x 123 x 41)
Arctic White
Arctic White
Arctic White
Gray
Dimensions of Equipment Interface Module in in. (mm).
4-53/64 (123)
8-7/8 (225)
9-11/32
(237)
1-19/32
(41)
4-15/16 (126)
3-5/16 (84)