Installation Manual of Room Air Conditioner

Read this manual before installation

Explain sufficiently the operating means to the user according to this manual.

NecessaryTools for Installation

1.Driver

5.Torque wrench(17mm,22mm,26mm)

9.Nipper

12.Reamer

2.Hacksaw

6.Pipe cutter

10.Gas leakage detector or

 

3.Hole core drill

7.Flaring tool

soap-and-water solution

 

4.Spanner(17,19 and 26mm)

8.Knife

11.Measuring tape

 

Accessory parts

Number

No. Accessory parts of

articles

1

Remote controller

1

2

 

R-03 dry battery

2

3

 

 

 

1

 

 

 

Mounting plate

 

4

 

 

Drain hose

1

 

 

 

 

5

4X25

Plastic cap

4

 

Screw

 

 

 

 

 

 

6

 

 

Drain-elbow

1

7

 

 

Cushion

4

8

 

Change for

1

 

 

 

 

 

fresh air box

 

9

Change for

1

fresh air tube(suit)

10

 

Outlet joint

2

Drawing for the installation of indoor and outdoor units

The models adopt HFC free refrigerant R410A

Optional parts for piping

Mark

Parts name

re th

 

 

 

 

mo

an

 

A

Non-adhesive tape

 

1

0cm

 

 

 

 

 

BAdhesive tape

CSaddle(L.S) with screws

DConnecting electric cable for indoor and outdoor

EDrain hose

F Heating insulating material

GPiping hole cover

Arrangement of piping directions

 

Rear left

Left

Rear

 

right

 

Right

 

Below

more than 5cm

m

 

 

or

 

 

e

 

 

t

 

 

h

 

 

a

 

 

n

 

 

1

 

 

0

 

 

c

 

 

m

G

mo

 

re

 

than

 

1

0cm

 

Attention must be paid to

F

A

the rising up of drain hose

C

 

 

 

 

 

cm

 

 

 

 

10

 

 

 

an

 

 

 

th

 

 

 

e

 

 

 

or

 

 

 

 

m

 

 

 

 

 

9

10

D

E

 

 

 

m

 

 

0c

 

n6

 

retha

 

 

mo

 

 

 

mo

 

re

 

th

 

an 1

5cm

 

 

The marks from A to G in the figure are the parts numbers.

No.00105

The distance between the indoor unit and the floor should be

more than 2m.

256

140

500

140

Floor fixing dimensions of the outdoor unit

(Unit:mm)

Fixing of outdoor unit

Fix the unit to concrete or block with bolts(10mm) and nuts firmly and horizontally.

When fitting the unit to wall surface, roof or rooftop, fix a supporter surely with nails or wires in consideration of earthquake and strong wind.

If vibration may affect the house, fix the unit by attaching a vibration-proof mat.

Indoor Unit

Selection of Installation Place Outdoor Unit

Place, robust not causing vibration, where the body can be supported sufficiently.

Place, not affected by heat or steam generated in the vicinity, where inlet and outlet of the unit are not disturbed.

Place, possible to drain easily, where piping can be connected with the outdoor unit.

Place, where cold air can be spread in a room entirely.

Place, nearby a power receptacle, with enough space around. (Refer to drawings).

Place where the distance of more than lm from televisions, radios, wireless apparatuses and fluorescent lamps can be left.

In the case of fixing the remote controller on a wall, place where the indoor unit can receive signals when the fluorescent lamps in the room are lightened.

Place, which is less affected by rain or direct sunlight and is sufficiently ventilated.

Place, possible to bear the unit, where vibration and noise are not increased.

Place, where discharged wind and noise do not cause a nuisance to the neighbors.

Place, where a distance marked is available as illustrated in the above figure.

Power Source

Before inserting power plug into receptacle, check the voltage without fail. The power source is the same as the corresponding name plate.

Install an exclusive branch circuit of the power.

A receptacle shall be set up in a distance where the power cable can be reached. Do not extend the cable by cutting it.

Selection of pipe

To this unit, both liquid and gas pipes shall be insulated as they become Iow temperature in operation.

Use optional parts for piping set or pipes covered with

equivalent insulation material.

Liquid pipe( )

6.35mm(1/4")

The thickness of the pipe must be 0.8 mm at least.

Gas pipe( )

9.52mm(3/8")

Indoor unit

1.Fitting of the Mounting Plate and Positioning of the wall Hole

When the mounting plate is first fixed

1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail.

2.Make sure once more the proper level of the plate, by hanging a thread with a weight from the central top of the plate, then fasten securely the plate with the attachment steel nail.

3.Find the wall hole location A using a measuring tape

A=80mm

35

 

Fit the level line

70mm

70mm

120mm

For the units with fresh air function

When the mounting plate is fixed side bar and lintel

Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten the plate to the fixed mounting bar.

Refer to the previous article, " When the mounting plate is first fixed ", for the position of wall hole.

2.Making a Hole on the Wall and Fitting the Piping Hole Cover

Make a hole of 70 mm in diameter, slightly descending to outside the wall. Install piping hole cover and seal it

off with putty after installation

Indoor side

Outdoor side

Wall hole

Thickness

70mm

of wall

 

(Section of wall hole) G Piping hole pipe

3.Installation of the Indoor Unit

Drawing of pipe

[ Rear piping ]

Draw pipes and the drain hose, then fasten them with the adhesive tape

[ Left Left-rear piping ]

In case of left side piping, cut away, with a nipper, the lid for left piping.

In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear piping which is marked on heat insulation materials.

Indoor unit

1.Insert the drain hose into the dent of heat insulation materials of indoor unit.

2.Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it out on the front side, then connect them.

3.Coat the flaring seal face with refrigerant oil and connect pipes.

Cover the connection part with heat insulation materials closely, and make sure fixing with adhesive tape

 

Heat insulation

 

 

material

Piping

 

signal wire

 

 

Lid for right piping

Drain hose

 

Lid for left piping

 

 

 

Lid for under piping

Indoor/outdoor

 

 

Change-for-fresh-air tube

 

electric cable

Fix with adhesive tape

Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping by protecting tape.

[Other direction piping]

Cut away, with a nipper, the lid for piping according to the piping direction and then bend the pipe according to the position of wall hole. When bending, be careful not to crash pipes.

Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulation of connecting part specially.

Fixing the indoor unit body

Hang surely the unit body onto the upper notches of the mounting plate. Move the body from side to side to verify its secure fixing.

In order to fix the body onto the mounting plate,hold up the body aslant from the underside and then put it down perpendicularly.

4.Connecting the indoor/outdoor Electric Cable Removing the wiring cover

Remove terminal cover at right bottom corner of indoor unit, then take off wiring cover by removing its screws.

When connecting the cable after installing the indoor unit

1. Insert from outside the room cable into left side of the wall hole, in which the pipe has already existed.

2. Pull out the cable on the front side, and connect the cable making a loop.

When connecting the cable before installing the indoor unit

Insert the cable from the back side of the unit, then pull it out on the front side.

Loosen the screws and insert the cable ends fully into terminal block, then tighten the screws.

Pull the cable slightly to make sure the cables have been properly inserted and tightened.

After the cable connection, never fail to fasten the connected cable with the wiring cover.

Note: When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wiring is not correct, proper operation can not be carried out and will cause defect.