Flowserve URB 1 User Manual

URB 1
Installation Instructions 810375-03
Operating Terminal and Display Unit URB 1
1
Contents
Page
Important Notes
Usage for the intended purpose ......................................................................................8
Safety note ......................................................................................................................8
Scope of supply ..............................................................................................................8
System description ......................................................................................................8, 9
Function .......................................................................................................................... 9
Technical data ............................................................................................................... 10
Installation
URB 1 ...........................................................................................................................10
Example of installation ................................................................................................ 79
Wiring
Wiring diagram ........................................................................................................ 4, 12
Basic Settings
CAN bus ...................................................................................................................... 13
Node ID for GESTRA bus-based devices URB 1 ....................................................... 13
Factory set default values ............................................................................................ 13
Adjusting display brightness ................................................................................. 14, 15
Changing factory set node ID of URB 1 / adjusting & changing node ID of URB 1 . 16– 18
Possibilities to display bus devices ............................................................................. 18
Setting / changing node IDs of bus-based equipment.......................................... 19– 22
Visual display / parameterisation of bus-based equipment ................................. 23–28
0 %/100 % calibration for capacitance level monitoring system .......................... 29–31
Calibrating feedback potentiometer of an external control valve ......................... 32– 35
Establishing switchpoints and proportional coefficient X
Adjusting sensitivity of response ........................................................................... 40, 41
Setting relay delay times .......................................................................................42– 44
Adjusting conductivity controller ........................................................................... 45– 57
Adjusting LIN (linear) temperature compensation ................................................ 58– 60
Adjusting NORM (standard curve) temperature compensation ........................... 61–65
Enabling AUTO temperature compensation ............................................................ 66, 67
Disabling temperature compensation ................................................................... 68, 69
.................................... 36–39
P
2
Contents
Page
Operation
Manual operation via external control valve ............................................................... 70
Stand-by operation with the steam boiler disconnected............................................. 71
System Malfunctions
Systematic malfunction analysis for troubleshooting .................................................. 72
Fault finding list ...................................................................................................... 73, 74
Annex
Establishing / changing node ID ................................................................................. 75
Factory set node IDs .............................................................................................. 75, 76
Table: standard curves ................................................................................................ 77
Declaration of conformity............................................................................................. 78
3
Wiring Diagram
Terminating resistor 120 Ω,
Fig.1
Paired cable
Operating terminal URB 1
Level switch
NRS
CEP*)
Voltage supply CAN data line
Terminating resistor 120
*) CEP = central earthable point
Fig. 2
4
Conductivity controller LRR 1-40
Conductivity electrode LRG 16-40
Terminating resistor 120
Electrode
NRG .. .
Functional Elements
6
Fig. 3
1 2 3 4
5
5
Functional Elements
7
B
Fig. 4
6
A
A
Key
Program button for switching between operating mode and parameterisation mode
1
Increase button
2
3
Decrease button
4
Enter button
5
Manual / automatic button
6
Illuminated LCD display, resolution 128 x 64 pixels
Code switch for baud rate setting
7
A
Fixing screws for panel mounting
Five-pole connector
B
7
Important Notes
Usage for the intended purpose
Use operating terminal & display unit URB 1 only in conjunction with GESTRA Spector bus systems (CANopen).
Safety Note
Use operating terminal and display unit URB 1 only for operating and viewing GESTRA CAN bus systems.
The equipment must only be installed by qualified staff. Qualified staff are those persons who – through adequate training in electrical engineering, the use and application of safety equipment in accordance with regulations concerning electrical safety systems, and first aid & accident prevention – have achieved a recognised level of competence appropriate to the installation and commissioning of this device.
Explanatory Notes
Scope of supply
URB 1
1 Operating terminal and display unit URB 1 (in plastic case) 2 Fixing screws for panel mounting 1 Installation manual
System description
The URB 1 is a user-friendly operating terminal and display unit for GESTRA CAN bus systems using the CANopen protocol. The equipment makes retrieving and processing standard functions of associated system components very easy.
In addition, the URB 1 simplifies the parameterisation procedure: The switchpoints, proportional band and response sensitivity can be adjusted by means of the keypad regardless of the actual level. The energizing and de-energizing times of the relays can be set individually for their respective switchpoints.
The following tables specifiy the GESTRA systems that can be displayed by the URB 1.
8
Explanatory Notes – continued –
System description – continued –
Standard display information
Actual value (bar chart) ●● ● Actual value (numerical value) ●● ● Switchpoint (symbol) ●●● ● High level alarm (electrode HW) ●●● ● Low level alarm (electrode LW) ●●● ● Manual/automatic operation ●● ● Stand-by mode Unit [µS/cm] or [ppm] Low level limit High level limit Alarm (warning triangle) ●●
Further display information
Actual value (continuous) ●● ● Switchpoints ●●● ● Setpoint ●● Deviation ●● Valve position ●● Intermittent blowdown Intermittent blowdown interval Purging pulse 24 h Current CAN bus addresses ●●●●● ●
NRS 1-40 NRS 1-41 NRS 1-42
NRS 1-40 NRS 1-41 NRS 1-42
Level Conductivity
NRS 2-40 NRR 2-40
Level Conductivity
NRS 2-40 NRR 2-40
LRR 1-40
LRR 1-40
Function
The URB 1 communicates with other GESTRA system components via a designated CAN bus using the CANopen protocol to DIN ISO 11898.
The URB 1 can also be used to operate and display further system components during operation.
Capacitance level switch type NRS 2-40 CANopen
Level controller type NRR 2-40 CANopen
Conductivity level switch type NRS 1-42 CANopen
Low-level alarm to TRD 604/EN type NRS 1-40 CANopen
High-level alarm to TRD 604/EN type NRS 1-41 CANopen
Conductivity controller and limiter to TRD 604/EN type NRS 1-41 CANopen
9
Explanatory Notes – continued –
Technical data
Type approval no.
TÜV · 98-399 (level) TÜV · WÜL · 02-007 (conductivity)
Input
Power supply: 18 V – 36 V DC Interface for CAN bus using CANopen protocol to DIN ISO 11898
Output
Interface for CAN bus using CANopen protocol to DIN ISO 11898
Indicators and adjustors
1 illuminated display, resolution: 128 x 64 pixels 5 push buttons 1 three-pole code switch for baud rate setting
Supply voltage
18 V – 36 V DC
Protection
Front panel: IP 54 to DIN EN 60529 Back: IP 00 to DIN EN 60529
Admissible ambient temperature
0°C – 55 °C
Case material
Front face: Aluminium with polyester membrane Casing: Noryl GFN 2 SE 1, glass-fibre reinforced
Weight
Approx. 0.3 kg
Installation
URB 1
Panel mounting
1. Provide panel cut-out, dimensions: 92
2. Install URB 1 using the fixing clips supplied with the equipment.
Tool
Screwdriver (5.5/100)
10
+0.8
x 92
+0.8
.
Wiring
Note that multi-core control cable with conductors linked in pairs, e. g. UNITRONIC BUS CAN 2 x 2 x .. mm
2
or RE-2YCYV-fl 2 x 2 x .. mm2 .
®
The baud rate (data transfer rate) dictates the cable length between the bus nodes and the total power consumption of the sensors dictates the conductor size.
8S9S01SetarduaBhtgnelelbaC
FFO NO FFO s/tiBk052 m521
sgnittesyrotcaF
NONOFFOs/tiBk521m0525,0x2x2
FFOFFONOs/tiBk001m53357,0x2x2
NOFFONOs/tiBk05m005
FFONONOs/tiBk02m0001
NONONOs/tiBk01m0001
sriapforebmuN
2
]
mm[ezisrotcudnocdna
43,0x2x2
notnedneped,tseuqerno
noitarugifnocsub
The baud rate is set via a code switch. Reduce baud rate if cable is longer than specified in the table above. Make sure that all bus nodes feature the same settings.
To protect the switching contacts fuse circuit with 2.5 A (anti-surge fuse) or according to TRD regulations (1.0 A for 72 hrs operation).
When a max. cable length of more than 125 m (up to 1000 m) is desired, make sure to modify the baud rate accordingly. Refer to pages 75 and 76 for more details.
Wiring diagram
For wiring diagram refer to page 4.
Attention
Wire equipment in series. Star-type wiring is not permitted.
Interlink screens of control cables such that electrical continuity is
ensured and connect them once to the central earthing point (CEP).
If more than one system component is connected to a CAN bus
network provide the first and last equipment with a terminating resistor of 120 Ω, Fig. 2
The CAN bus line must not be interrupted while operating with one or
more system components.
Any interruption will open the control circuit!
If the switching controller has to be replaced be sure to remove first the terminal strips , Fig. 4
B
Note: Make sure that all system components connected are
operating
UNITRONIC® is a registered trademark of LAPP Kabelwerke GmbH, Stuttgart.
before removing the CAN bus line from the terminal strip!
not
11
Wiring – continued –
Note
Connect screen only to terminal 3, ensuring electrical continuity and connect equipment once to the central earthing point (CEP).
The loop resistance must be under 10 Ω.
The rated voltage is stated on the name plate.
Despite correct wiring H.F. interference caused by the installation may lead to system breakdowns and malfunction messages. If necessary refer to the fault finding lists of the respective bus equipment.
Tools
Screwdriver for slotted screws, size 2.5, completely insulated according to
VDE 0680
12
Basic Settings
CAN-Bus
All level and conductivity controllers and associated electrodes are interconnected by means of a CAN bus using the CANopen protocol. Every item of equipment features an electronic address (node ID). The four-core bus cable serves as power supply and data highway for high-speed data exchange.
The CAN address (node ID) can be set between 60 and 123. The URB 1 is configured at our works and ready for service with other GESTRA
system components without having to set the node ID.
If several systems of the same kind are to communicate in one CAN bus network, be sure to assign one node ID for each individual system component (e. g. controller). Refer to page 75 and 76 for more information.
Node ID for GESTRA bus-based device URB 1
Example: Conductivity monitoring and control
Example: Level monitoring and control
Factory set default values
The URB 1 features the following factory default settings:
Baud rate: 250 kb/s
Node ID: 060 (Do not change this node ID unless required; highest permissible
setting: 123)
13
Basic Settings – continued –
Adjusting display brightness
The brightness of the LCD display can be adjusted as necessary.
Press and hold the button for a few seconds.
The URB 1 enters the address parameterisation mode.
Press button several times to reduce the brightness.
14
several times briefly
several times briefly
Basic Settings – continued –
Adjusting display brightness – continued –
Press button several times to increase the brightness.
Press button briefly to save settings and return to the main window.
several times briefly
twice briefly
15
Basic Settings – continued –
Changing factory set node ID of the URB 1 / Adjusting & changing node ID
The factory set node ID of the URB 1 is “060”. Node IDs below this value are reserved for other GESTRA bus components.
If additional operating terminals type URB 1 are used in a CAN bus system, you have to set their node IDs to values above “060”.
Note that the newly established node IDs must not be identical with node IDs of other bus components.
Press and hold button for a few seconds to enter the address parameterisation mode.
Press button briefly to activate the line selection mode.
16
a few seconds
briefly
Basic Settings – continued –
Changing factory set node ID of the URB 1 / Adjusting & changing node ID – continued –
Press button briefly to activate the line editing mode.
Use button or to increase or decrease the first digit.
flashing
briefly
Press button briefly to move the cursor two steps further.
flashing
twice briefly
Press button once briefly to select the digit “1”.
flashing
once briefly
17
Basic Settings – continued –
Changing factory set node ID of the URB 1 / Adjusting & changing node ID – continued –
Press button briefly to activate the line selection mode.
In our example the node ID was set to “061”.
briefly
Press button twice briefly to save settings and return to the main window.
twice briefly
Possibilities to display bus devices
The URB 1 can display only one level monitoring device, one low-level alarm, one high-level alarm and one conductivity monitoring device per vessel (e. g. steam boiler or feedwater deaerator).
If the monitoring systems of more than one vessel are to be displayed, provide one
URB 1 per vessel.
18
Basic Settings – continued –
Setting /changing node IDs of bus-based equipment
The standard default node ID setting of all bus devices that can be displayed is “O This setting acts as a wild card for all bus devices which are not displayed with the URB 1.
For each bus device that shall be displayed by the URB 1 a node ID has to be established manually.
We recommend to accept the factory set node IDs of GESTRA bus devices. For the relevant node ID setting please refer to the corresponding installation manual of the device.
Press button briefly to show the address list and activate the parameterisation mode.
FF”.
Press button briefly to activate the line selection mode.
briefly
briefly
19
Basic Settings – continued –
Setting /changing node IDs of bus-based equipment – continued –
Press button briefly to activate the line editing mode. Use button or to increase or decrease the first digit.
flashing
briefly
Press button once briefly to select the digit “0”.
flashing
once briefly
Press button briefly to move the cursor one step further.
Press button twice briefly to select the digit “0”.
20
flashing
briefly
flashing
twice briefly
Basic Settings – continued –
Setting /changing node IDs of bus-based equipment – continued –
Press button briefly to move the cursor one step further.
flashing
Press button seven times briefly to select the digit “1”.
flashing
briefly
7 times briefly
Press button briefly to activate the line selection mode.
Press button once briefly to move to the next line.
The node ID of the NRS 1-41 can now be adjusted.
briefly
once briefly
21
Basic Settings – continued –
Setting /changing node IDs of bus-based equipment – continued –
Press button briefly to activate the parameterisation mode.
In this example the node IDs of all bus devices have already been adjusted.
If the display of the NRS 1-42 is required set the node IDs of the NRS 2-40 and NRR 2-40 to “O
Press button twice briefly to save the settings and return to the main window.
FF”.
briefly
twice briefly
22
Basic Settings – continued –
Visual display / Parameterisation of bus devices
The split-screen display window shows which GESTRA bus devices can be indicated:
High-level limiter type NRS 1-41
Low-level limiter type NRS 1-40
Level switch type NRS 2-40
Level controller type NRR 2-40
Conductivity controller type LRR 1-40
Press button briefly to enter the display window of the level controller NRR 2-40.
Actual level (graphical representation)
1
Actual level (percentage)
2 3
Setpoint deviation
4
Proportional band X
5
Switchpoints NRR 2-40
6
Valve position
p
Press button briefly to enter the display window of the level switch NRS 2-40.
1
Actual level (graphical representation)
2
Actual level (percentage)
3
Control unit 2 highlighted
4
Switchpoints for control unit 2
5
Low-level signal (flashes in the event of an LW alarm)
6
High-level signal (flashes in the event of an HW alarm)
LW = low water (limiter NRS 1-40) HW = high water (limiter NRS 1-41
5
4
1
2
3
6
briefly
4
6
3
1
2
5
briefly
23
Basic Settings – continued –
Visual display / Parameterisation of bus devices – continued –
Press button briefly to enter the parameterisation mode for the following settings:
0 % – 100 % calibration NRG 26-40
Switchpoints NRR 2-40
Proportional band NRR 2-40
Switchpoints NRS 2-40
Press button briefly to enter the parameterisation mode for the following settings:
Relay energizing delay times
Relay de-energizing delay times
briefly
briefly
Press button briefly to enter the error messages window.
For more information see section
Malfunction, Troubleshooting, Fault Finding List on pages 72 and 74.
Press button briefly to return to the main window.
1
Actual conductivity value
2
Actual conductivity (graphical representation)
24
briefly
1
2
briefly
Basic Settings – continued –
Visual display / Parameterisation of bus devices – continued –
Press button briefly to enter the display window of the conductivity controller LRR 1-40.
Actual conductivity value
1 2
Conductivity setpoint
3
M
AX conductivity value
24 h purging pulse for continuous
4
blowdown valve
5
Operating position of continuous blowdown valve
Valve position of continous blowdown valve
6
Press button briefly to enter the parameterisation mode for the following settings:
µS/cm or ppm
Indication range of actual value
graphical representation
MAX conductivity value
Setpoint
MIN conductivity value
2 3 4
1
5
6
briefly
briefly
Press button briefly to enter the parameterisation mode for the following settings:
Proportional band X
Controller hysteresis
24 h purging pulse for continuous
p
blowdown valve
Operating position of intermittent
blowdown valve
Relay contact 4: MIN limit /
Automatic intermittent boiler blowdown
Press button briefly to enter the parameterisation mode for the following settings:
Linear temperature compensation LIN
Automatic temperature compensation AUTO
Standard curve temperature compensation
NORM
Temperature compensation disabled OFF
briefly
briefly
25
Basic Settings – continued –
Visual display / Parameterisation of bus devices – continued –
Press button briefly to enter the error messages window.
For more information refer to section
Malfunction, Troubleshooting, Fault Finding List on pages 72 and 74.
Press button briefly to return to the main window.
briefly
briefly
26
Basic Settings – continued –
Visual display / Parameterisation of bus devices – continued –
The split-screen display window shows which GESTRA bus devices can be indicated:
Level switch type NRS 1-42
This window appears if, as in our example, only the NRS 1-42 is displayed.
Press button briefly to enter the display window of the level switch NRS 1-42.
H
IGH LEVEL switchpoint
1 2
Switchpoints
3
L
OW LEVEL switchpoint
1
2
2
3
Press button briefly to select either of the following two settings:
Minimum conductivity of the fluid 0.5 µS/cm
Minimum conductivity of the fluid 10 µS/cm
briefly
briefly
27
Basic Settings – continued –
Visual display / Parameterisation of bus devices – continued –
Press button briefly to enter the parameterisation mode for the following settings:
Relay energizing delay times
Relay de-energizing delay times
Press button briefly to enter the error messages window.
For more information please refer to section Malfunction, Troubleshooting, Fault Finding List on pages 72 and 74.
briefly
briefly
Press button briefly to return to the main window.
In this example only the bus device NRS 1-42 is displayed.
If the node IDs of the bus devices NRS 2-40 and NRR 2-40 have been established such that the equipment can be displayed on the URB 1, the indication of these devices will take priority over the NRS 1-42 and the display window of the NRS 1-42 will be blanked.
28
briefly
Basic Settings – continued –
0 % /100 % calibration for capacitance level monitoring system
The split-screen main window shows which GESTRA bus devices can be displayed:
High level limiter NRS 1-41 Low level limiter NRS 1-40 Level switch NRS 2-40 Level controller NRR 2-40 Conductivity controller LRR 1-40
Before commissioning the installation establish the measuring range of the capacitance level electrode NRG 26-40 by calibrating the 0 % and 100 % settings.
Press button three times briefly to enter the window for calibrating the 0 % and 100 % settings.
Press button twice briefly to enter the line editing mode.
Lower the water level in the vessel to 0 %.
3 times briefly
flashing
twice briefly
29
Basic Settings – continued –
0 % /100 % calibration for capacitance level monitoring system – continued –
Press button briefly to save the 0 % level setting.
once briefly
Press button once briefly.
once briefly
Press button once briefly to activate the line editing mode.
Raise the water level in the vessel to 100 %.
If, for practical reasons, it is not possible to raise the water level to 100 % please proceed as follows:
30
flashing
once briefly
Basic Settings – continued –
0 % /100 % calibration for capacitance level monitoring system – continued –
Press button five times briefly. Pressing the button in program mode
will decrement the calibration level in steps of 10 to a minimum of 50 %.
In our example the calibration level is 50 %.
This calibration method saves time and prevents the loss of feedwater.
Press button three times briefly to enter the main window.
flashing
5 times briefly
3 times briefly
31
Basic Settings – continued –
Calibrating the feedback potentiometer of an external control valve
The split-screen window shows which GESTRA bus devices can be displayed:
High-level limiter NRS 1-41
Low-level limiter NRS 1-40
Level switch NRS 2-40
Level controller NRR 2-40
Conductivity controller LRR 1-40
Before commissioning the installation calibrate the 0 % ( range of the feedback potentiometer of an external control valve.
Press button briefly to enter the display window of the level controller NRR 2-40.
CLOSED) and 100 % (OPEN)
Press button briefly to activate the manual mode.
Pressing button or in this mode allows the manual opening or closing of an external control valve.
32
briefly
briefly
Basic Settings – continued –
Calibrating the feedback potentiometer of an external control valve – continued –
Press button three times briefly to activate the line editing mode for calibrating the signal of the feedback potentiometer.
flashing
3 times briefly
Press and hold down button until the control valve is closed.
flashing
hold down
Press button once briefly to save the current resistance value of the feedback potentiometer as 0 % setting (valve closed).
once briefly
33
Basic Settings – continued –
Calibrating the feedback potentiometer of an external control valve – continued –
Press button briefly to select the calibration of the 100 % setting.
briefly
Press button once briefly to activate the line editing mode for calibrating the signal of the feedback potentiometer.
flashing
once briefly
Press and hold down button until the control valve is open.
34
flashing
hold down
Basic Settings – continued –
Calibrating the feedback potentiometer of an external control valve – continued –
Press button three times briefly to save the current resistance value of the feedback potentiometer as 100 % setting (valve
OPEN).
3 times briefly
Press button briefly to deactivate the manual mode.
briefly
Press button once briefly to return to the main window.
once briefly
35
Basic Settings – continued –
Establishing switchpoints and proportional coefficient X
The split-screen main window shows which GESTRA bus devices can be indicated:
High-level limiter NRS 1-41
Low-level limiter NRS 1-40
Level switch NRS 2-40
Level controller NRR 2-40
Conductivity electrode LRR 1-40
Before commissioning the installation establish proportional band and the M M
IN switchpoints for the level controller
AX/
NRR 2-40. For level switch NRS 2-40 you can
establish four switchpoints.
Press button three times briefly to enter the window where you can establish the switchpoints and the X
value.
p
p
3 times briefly
Press button once briefly to activate the line editing mode.
Use button or to scroll back and forth through the lines
36
once briefly
Basic Settings – continued –
Establishing switchpoints and proportional coefficient Xp – continued –
Press button twice briefly to select the switchpoint 1 (M NRR 2-40.
Press button once briefly to activate the line editing mode.
AX switchpoint) of the
twice briefly
flashing
once briefly
Press button once briefly to move to the next digit in the same line.
flashing
once briefly
37
Basic Settings – continued –
Establishing switchpoints and proportional coefficient Xp – continued –
Press button once briefly. In our example switchpoint 1
(M
AX switchpoint) shall be established at
70 %.
flashing
once briefly
Press button once briefly. The last digit in the line is selected and
remains “0” for our example switchpoint M
AX 70 %.
flashing
once briefly
Press button once briefly to deactivate the line editing mode.
Press button to go to the next line.
38
once briefly
Basic Settings – continued –
Establishing switchpoints and proportional coefficient Xp – continued –
Press button once briefly. Switchpoint 2 marks the upper limit of the
proportional band for the level controller NRR 2-40.
The difference between switchpoint 2 and switchpoint 3 gives the proportional band X
. The example setting corresponds to
p
proportional band of 20 % (060 - 040). Note that the proportional band must be greater than “0”.
Press button once briefly. Switchpoint 3 marks the lower limit of the
proportional band for the level controller NRR 2-40.
The proportional coefficient and the M switchpoint of the NRR 2-40 as well as the switchpoints of the NRS 2-40 can be adjusted as described above.
IN
once briefly
once briefly
Press button twice briefly to return to the main window.
twice briefly
39
Basic Settings – continued –
Adjusting sensitivity of response
The split-screen window shows which GESTRA bus devices can be indicated:
High-level limiter NRS 1-41
Low-level limiter NRS 1-40
Level switch NRS 1-42
Conductivity controller LRR 1-40
Before commissioning the installation adjust the response sensitivity of the NRS 1-42.
The response sensitivities of the high­level and low-level limiters are factory set and cannot be changed.
Press button twice briefly to select either of the following two response sensitivities:
0.5 µS/cm
10 µS/cm
Press button twice briefly to activate the line editing mode.
Use buttons and to toggle between the two settings.
40
twice briefly
flashing
twice briefly
Basic Settings – continued –
Adjusting sensitivity of response – continued –
Press button briefly. In our example the response sensitivity
0.5 µS/cm has been selected.
Press button three times briefly to save the setting and return to the main window.
flashing
briefly
3 times briefly
41
Basic Settings – continued –
Setting relay delay times
The split-screen window shows which GESTRA bus devices can be indicated:
High-level limiter NRS 1-41
Low-level limiter NRS 1-40
Level switch NRS 2-40
Level controller NRR 2-40
Conductivity controller LRR 1-40
Before commissioning the installation set the relay delay times for the individual switchpoints.
Note that the relay delay times of the low-level and high-level limiters are factory set and the URB 1.
Press button four times briefly to enter the window for setting the relay delay times of the switchpoints.
The symbol stands for relay energizing delay.
The symbol stands for relay de­energizing delay.
A number, for instance “001” corresponds to a delay time of 100 “030” corresponds to 3 sec and the max. value “255” corresponds to 25.5 sec.
cannot be changed with
m
sec. The value
4 times briefly
Press button once briefly to activate the line editing mode.
Use button or to scroll back and forth through the lines.
42
once briefly
Basic Settings – continued –
Setting relay delay times – continued –
Press button once briefly to activate the line editing mode.
Press button once briefly. Press button to move to the next digit in
the same line.
flashing
once briefly
flashing
once briefly
Press button once briefly. In our example the digit “2” has been
selected.
flashing
once briefly
43
Basic Settings – continued –
Setting relay delay times – continued –
Press button twice briefly to deactivate the line editing mode.
In our example the relay delay time for the M
AX switchpoint of the NRR 2-40 is 2 sec.
Press button once briefly. Switchpoint 2 and switchpoint 3 of the
NRR 2-40 mark the upper and lower limit of the proportional band. The relay energizing and de-energizing delays cannot be adjusted and feature the number “000”.
The relay delay times of all other switchpoints can be adjusted as described above.
twice briefly
once briefly
Press button twice briefly to save the settings and return to the main window.
44
twice briefly
Basic Settings – continued –
Adjusting conductivity controller
The split-screen main window shows which GESTRA bus devices can be indicated:
High-level limiter NRS 1-41
Low-level limiter NRS 1-40
Level switch NRS 2-40
Level controller NRR 2-40
Conductivity controller LRR 1-40
Press button twice briefly to enter the parameterisation mode for the following settings:
µS/cm or ppm
Indicating range of actual value graphics
Max. conductivity
Setpoint
Min. conductivity
Press button twice briefly to activate the line editing mode.
Use button or to scroll back and forth through the lines.
twice briefly
flashing
twice briefly
45
Basic Settings – continued –
Adjusting conductivity controller – continued –
Press button once briefly to select the desired unit of measurement (here: ppm).
Press button once briefly to deactivate the line editing mode.
All conductivity values metered will now be indicated in [ppm].
flashing
once briefly
once briefly
Press button once briefly. In this line you can calibrate the graphical
representation (bar chart) of the conductivity value shown in the main window. This setting will also calibrate the actual value output (4 - 20 mA).
First ascertain the conductivity measuring range used in your installation (e. g. 0.5 µS/cm up to 20 µS/cm).
Press button once briefly to activate the line editing mode.
You can choose between the following ranges:
0.5 to 20 µS/cm 0.5 to 1000 µS/cm
0.5 to 100 µS/cm 0.5 to 2000 µS/cm
0.5 to 200 µS/cm 0.5 to 6000 µS/cm
0.5 to 500 µS/cm 0.5 to 12000 µS/cm
46
once briefly
flashing
once briefly
Basic Settings – continued –
Adjusting conductivity controller – continued –
Press button seven times briefly to select the range 0.5 to 20 µS/cm.
Press button once briefly to deactivate the line editing mode.
flashing
7 times briefly
once briefly
Press button once briefly to enter the line where the conductivity setpoint of the LRR 1-40 can be adjusted.
Press button once briefly to activate the line editing mode.
once briefly
flashing
once briefly
47
Basic Settings – continued –
Adjusting conductivity controller – continued –
Press button once briefly to move the cursor one step further.
Press button twice briefly to select the digit “3”.
flashing
once briefly
flashing
twice briefly
Press button five times briefly. In our example a conductivity setpoint of
3000 µS/cm has been adjusted.
Press button once briefly to enter the line where the M
IN conductivity limit of the LRR 1-40 can be
adjusted. The M
IN switchpoint of the LRR 1-40 can be
adjusted in the same way as the conductivity setpoint.
48
5 times briefly
once briefly
Basic Settings – continued –
Adjusting conductivity controller – continued –
Press button once briefly to enter the line where the M LRR 1-40 can be adjusted.
The M
AX switchpoint of the LRR 1-40 can
be adjusted in the same way as the conductivity setpoint.
Press button once briefly to deactivate the line editing mode.
AX conductivity limit of the
once briefly
once briefly
Press button once briefly to enter the parameterisation window for the following settings:
Proportional band X
Control hysteresis
24 h purging pulse for continuous
p
blowdown valve
Operating position of intermittent
blowdown valve
Relay contact 4 / automatic intermittent
boiler blowdown
Press button twice briefly to activate the line editing mode.
In this line you can set the proportional band X X
= 0: Two-position (on-off) control
p
X
> 0: Modulating control
p
once briefly
.
p
flashing
twice briefly
49
Basic Settings – continued –
Adjusting conductivity controller – continued –
Press button once briefly to move the cursor one step further.
Press button twice briefly to select the digit “2”.
flashing
once briefly
flashing
twice briefly
Press button twice briefly. In our example the proportional band X
p
was set to 20 %.
Press button once briefly to enter the line where the control hysteresis of the LRR 1-40 can be adjusted.
The hysteresis can be adjusted within a range of 0 % – 25 %.
The control hysteresis of the LRR 1-40 can be adjusted the same way as the proportional band X
If X
.
p
> 0 this function is deactivated.
p
50
twice briefly
once briefly
Basic Settings – continued –
Adjusting conductivity controller – continued –
Press button once briefly to enter the line where the 24 h purging pulse for the continuous blowdown valve can be adjusted.
Use buttons and to enable or, respectively, disable the 24 h purging pulse.
Press button once briefly to enter the line where the operating position of the continuous blowdown valve can be changed.
once briefly
once briefly
Press button once briefly to enter the window where the operating position and the feedback potentiometer of the continuous blowdown valve can be adjusted.
If X
> 0 the operating position setting
p
is deactivated. The window shows also the reference values
(in %) as indicated by the scale of the GESTRA continuous blowdown valve BAE (000 = 0 %, 035 = 35 %) and the current position of the continuous blowdown valve (in %).
Press button twice briefly to activate the line editing mode.
Use button or to change the values of the digits. Press to go to the next digit.
The value 008 corresponds to an opening position of 8 %. (Max. opening position 25 %)
once briefly
flashing
twice briefly
51
Basic Settings – continued –
Adjusting conductivity controller – continued –
Press button once briefly. The value 008 = 8
now selected.
Press button once briefly. In this line you can establish the 0
value of the feedback potentiometer of the continuous blowdown valve.
% operating position is
%
once briefly
once briefly
Press button once briefly to activate the line editing mode.
Press and hold down button until the continuous blowdown valve is closed.
52
flashing
once briefly
flashing
hold down
Basic Settings – continued –
Adjusting conductivity controller – continued –
Press button once briefly. The current resistance value of the
feedback potentiometer is saved as 0% position (valve CLOSED).
Press button once briefly to activate the 100% adjustment position.
once briefly
once briefly
Press button once briefly to activate the line editing mode.
Press and hold down button until the continuous blowdown valve is completely open.
flashing
blinkt
flashing
blinkt
flashing
once briefly
hold down
53
Basic Settings – continued –
Adjusting conductivity controller – continued –
Press button once briefly. The current resistance value of the
feedback potentiometer is now saved as 100% position (valve OPEN).
Press button three times briefly.
once briefly
3 times briefly
Press button once to activate the line selection mode.
Press button four times briefly. In this line you can decide whether you want
to use relay contact 4 (LRR 1-40) for MIN alarm or for automatic intermittent boiler blowdown.
The relay contact 4 of the LRR 1-40 is located across terminals „28“, „29“ and „30“.
Please observe the wiring diagram of the LRR 1-40.
54
once briefly
4 times briefly
Basic Settings – continued –
Adjusting conductivity controller – continued –
Press button once briefly to activate the line editing mode.
Press button once briefly to activate relay contact 4 for establishing MIN alarm.
The relay contact 4 of the LRR 1-40 is located across terminals „28“, „29“ und „30“.
Please observe the wiring diagram of the LRR 1-40.
flashing
once briefly
flashing
once briefly
Press button once briefly to activate the automatic intermittent blowdown function.
Press button once briefly to enter the window where the following parameters can be set:
Frequency of the intermittent blowdown
(in hours)
Duration of the intermittent blowdown
(in seconds)
flashing
once briefly
once briefly
55
Basic Settings – continued –
Adjusting conductivity controller – continued –
Press button once briefly to activate the line selection mode.
The frequency of the intermittent blowdown can be adjusted in the line editing mode in the same way as the proportional band X
.
p
once briefly
56
Basic Settings – continued –
Adjusting conductivity controller – continued –
Press button once briefly. The duration of the intermittent
blowdown can be adjusted in the line editing mode in the same way as the proportional band X
In our example the blowdown frequency was set to 1 hour and the blowdown duration to 1 second.
Press button twice briefly to accept the configuration.
.
p
once briefly
twice briefly
Press button once briefly to return to the main window.
once briefly
57
Basic Settings – continued –
Adjusting LIN (linear) temperature compensation
The split-screen main window shows which GESTRA bus devices can be indicated:
High-level limiter NRS 1-41
Low-level limiter NRS 1-40
Level switch NRS 2-40
Level controller NRR 2-40
Conductivity controller LRR 1-40
Press button four times briefly to enter the window where the following parameters can be set:
Linear temperature compensation [% / °C]
Recording a temperature curve
Cell constant C of the conductivity
electrode
The factory set default setting is “TK:LIN”.
Press button once briefly to activate the line editing mode.
58
4 times briefly
once briefly
Basic Settings – continued –
Adjusting LIN (linear) temperature compensation – continued –
Press button once briefly to enter the line where the linear temperature compensation [% /°C] can be adjusted.
The factory set gradient 2.1 [%/ °C] is normally used for steam boilers operating with constant pressure.
When the boiler is at full working pressure compare the indicated value with the reading of a calibrated conductivity meter – the two values must tally.
Press button once briefly to activate the line editing mode.
If the reading of the calibrated conductivity meter does not tally the value indicated by the URB 1 the compensation gradient has to be changed until the two values agree.
Example: With a gradient of 1.9 %/ °C the two readings tally.
flashing
once briefly
once briefly
Press button once briefly to select the digit “1”.
Press button once briefly to move the cursor one step further.
flashing
once briefly
flashing
once briefly
59
Basic Settings – continued –
Adjusting LIN (linear) temperature compensation – continued –
Press button twice briefly to select the digit “9”.
flashing
Press button once briefly to accept the configuration.
In our example a gradient of 1.9 %/ °C was adjusted.
twice briefly
once briefly
Press button twice briefly to return to the main window.
60
twice briefly
Basic Settings – continued –
Adjusting NORM (standard curve) temperature compensation
The split-screen main window shows which GESTRA bus devices can be indicated:
High-level limiter NRS 1-41
Low-level limiter NRS 1-40
Level switch NRS 2-40
Level controller NRR 2-40
Conductivity controller LRR 1-40
Press button four times briefly. The NORM (standard curve) temperature compen-
sation is suitable for steam boilers operating with variable pressures, which means that the steam boilers do not feature fixed working pressures/ temperatures (e. g. low load 10 bar, peak load 15 bar).
The standard curves of 11 feedwater conditioning agents with different conductivities compensate the thermal influences of the measurement within the rated operating range. In our example we have started
from the factory set “TK:LIN” mode.
4 times briefly
Press button twice briefly to activate the line editing mode.
flashing
twice briefly
61
Basic Settings – continued –
Adjusting NORM (standard curve) temperature compensation – continued –
Press button twice briefly to select the function NORM.
The function NORM allows the retrieval of 11 different standard curves stored in the URB 1. The curves are applicable for different feedwater conditioning agents with different basic conductivities.
For more information see Annex (page 77).
Press button once briefly to activate the line editing mode.
In this window the following parameters can be set:
Standard curve temperature compensation
[% /°C]
Recording/adding a temperature curveCell constant of the conductivity electrode
Our example shows the factory setting “00”, which means that no standard curve has been selected and activated.
flashing
twice briefly
once briefly
Press button once briefly to enter the line where you can select a standard curve.
For more information see Annex (page 77).
Press button once briefly to activate the line editing mode.
62
once briefly
flashing
once briefly
Basic Settings – continued –
Adjusting NORM (standard curve) temperature compensation – continued –
Press button once briefly to move the cursor one step further.
flashing
Press button once briefly to select the digit “1”.
flashing
once briefly
once briefly
Press button once briefly to accept the configuration.
The standard curve “01” is now active. The temperature values of the standard
curve “01” are based on the conditioning agent caustic soda with a basic conductivity of 260 µS/cm at 25°C.
For more information see Annex (page 77).
Press button once briefly to enter the line where you can start recording the temperature/ conductivity curve that is characteristic of your steam boiler. The temp./conductivity values recorded by the system cover the whole room temp. to service temp. range. In case of variable pressure operation we recommend that you also record the AUTO curve. If the standard curves are not suitable you can then still use the AUTO curve.
once briefly
once briefly
63
Basic Settings – continued –
Adjusting NORM (standard curve) temperature compensation – continued –
Press button once briefly to activate the line editing mode.
flashing
once briefly
Press button once briefly to select the function “start”.
flashing
once briefly
Press button once briefly to finish the configuration.
Raise temp./ pressure until the steam boiler settles at full working pressure (in case of variable pressure operation until the highest operating pressure is reached).
The LRR 1-40 will now record the temperature/conductivity values and saves them as AUTO curve in the URB 1.
The number of recorded temp./conductivity values is indicated in the line “Temp.”.
Press button once briefly. The recording of the AUTO curve is
finished once the steam boiler has reached its working pressure.
In our example 15 temp./conductivity values were recorded. A temperature of
181.7 °C was detected at the measuring point of the conductivity electrode LRG 16-40, which corresponds to a boiler pressure of 10.3 bar.
64
once briefly
flashing
once briefly
Basic Settings – continued –
Adjusting NORM (standard curve) temperature compensation – continued –
Press button twice briefly to select the function “Stop”.
The recording of the temperature/ conductivity values is now finished.
The boiler specific AUTO curve can be activated on the display “TK:AUTO”.
For more information see page 77.
Press button three times briefly to return to the main window.
flashing
once briefly
3 times briefly
65
Basic Settings – continued –
Enabling AUTO temperature compensation
The split-screen main window shows which GESTRA bus devices can be indicated:
High-level limiter NRS 1-41
Low-level limiter NRS 1-40
Level switch NRS 2-40
Level controller NRR 2-40
Conductivity controller LRR 1-40
Press button four times briefly. The AUTO curve temperature compensation is
suitable for steam boilers operating with variable pressures, which means that the steam boilers do not feature fixed working pressures/temperatures (e. g. low load 10 bar, peak load 15 bar).
The procedure for recording an AUTO curve is described on pages 63 to 65.
In our example we have started from the setting “TK:NORM”.
4 times briefly
Press button twice briefly to activate the line editing mode.
66
flashing
twice briefly
Basic Settings – continued –
Enabling AUTO temperature compensation – continued –
Press button once briefly to select the function “Auto”.
flashing
Press button once briefly to finish the configuration.
In our example we have activated an AUTO curve with 15 temp./conductivity values which has been recorded and stored in the URB 1.
A new AUTO curve can always be recorded which will then overwrite the old one.
The procedure of recording an AUTO curve has been described on pages 63 to 65.
once briefly
once briefly
Press button once briefly to return to the main window.
once briefly
67
Basic Settings – continued –
Disabling temperature compensation
The split-screen main window shows which GESTRA bus devices can be indicated:
High-level limiter NRS 1-41
Low-level limiter NRS 1-40
Level switch NRS 2-40
Level controller NRR 2-40
Conductivity controller LRR 1-40
Press button four times briefly. Some industrial applications may require
disabling the temperature compensation. Note that with this mode all conductivity values displayed by the URB 1 are absolute readings of the current conductivity.
In our example we start from the factory set “TK:LIN” mode.
Press button twice briefly to activate the line editing mode.
68
4 times briefly
flashing
twice briefly
Basic Settings – continued –
Disabling temperature compensation – continued –
Press button three times briefly to select the function “OFF”.
Press button once briefly to save settings and finish the configuration.
The temperature compensation is now disabled.
flashing
3 times briefly
once briefly
Press button once briefly to return to the main window.
once briefly
69
Operation
Manual operation via external control valve
The split-screen main window shows which GESTRA bus devices can be indicated:
High-level limiter NRS 1-41
Low-level limiter NRS 1-40
Level switch NRS 2-40
Level controller NRR 2-40
Conductivity controller LRR 1-40
Press button briefly to enter the display window of the level controller NRR 2-40.
Press button briefly to activate the manual mode.
Use buttons and in this mode to manually open and close an external control valve.
Press button a second time to disable the manual mode and to move the control valve back into the position dictated by the controller NRR 2-40.
70
briefly
briefly
Operation – continued –
Stand-by operation with the steam boiler disconnected
The split-screen main window shows which GESTRA bus devices can be indicated:
High-level limiter NRS 1-41
Low-level limiter NRS 1-40
Level switch NRS 2-40
Level controller NRR 2-40
Conductivity controller LRR 1-40
Use an external switch to enable the stand-by mode of the conductivity control.
After switching off the burner of the steam boiler you can deactivate the control of the continuous and intermittent blowdown valves in order to avoid loss of boiler water (stand-by operation).
After returning to normal operation the continuous blowdown valve moves into the control position and an intermittent blowdown pulse is given (if activated).
Please take the wiring diagram of the installation manual for the LRR 1-40 into consideration.
71
System Malfunctions
Troubleshooting
The sources of malfunctions occurring in CAN bus systems operating with several bus­based stations must be analysed systematically since faulty components or incorrect settings can give rise to negative interactions with intact bus devices in the CAN bus system. These unwanted interactions can cause error messages in fully functional bus devices, which will make fault detection even more difficult.
We recommend the following systematic fault location procedure:
Step 1 (Start)
Detach terminal strips in all sensing units of bus devices.
Level electrode Conductivity electrode Pressure sensor Temperature sensor
Check
Use fault-finding list to correct fault(s).
Final test: have all faults been eliminated?
System Malfunction
Use fault-finding list to identify the fault(s).
Cut off power supply to the equipment.
72
Step 2
Plug in terminal strip of the sensing unit of one system, e. g.
NRS ...
and
NRG ... (sensor).
Step 3
Apply mains voltage to bus devices of the system e. g.
NRS ...
and
NRG ...
System O.K.
Detach terminal strips between bus devices of the sytem e. g.
NRS ...
and
NRG ...
System Malfunctions – continued –
Fault Finding List
The data communication in the CAN bus line is disrupted.
Check that the CAN bus line has been
wired according to the wiring diagram. Check that the CAN bus line is not
interrupted due to conductor breakage. Check that the controllers and
electrodes feature the correct node IDs.
The thermal fuse of one of the level electrodes has been triggered.
Check that the level electrode has been
mounted as specified in the installation manual.
Check whether external influences have caused built-up of heat in the electrode casing.
flashing flashing
5 times briefly
The thermal fuse of the conductivity electrode has been triggered.
Check that the conductivity electrode
has been mounted as specified in the installation manual.
Check whether external influences have caused built-up of heat in the electrode casing.
The conductivity electrode is defective.
The temperature sensor of the conductivity electrode is short circuited or interrupted.
Replace conductivity electrode LRG 16-40.
5 times briefly
5 times briefly
73
System Malfunctions – continued –
Fault Finding List – continued –
The conductivity electrode is defective.
The internal connecting cables of the conductivity electrode are short circuited or interrupted.
Replace conductivity electrode LRG 16-40.
The CAN bus communication of a controller is disrupted.
Check that the controller and the level
or conductivity electrode have been mounted as specified in the wiring diagram.
In our example there is a disruption in the CAN bus communication of the low­water level electrode 2 type NRG 16-40.
5 times briefly
once briefly
The CAN bus communication of a controller is disrupted.
Check that the controller and the level
or conductivity electrode have been mounted as specified in the wiring diagram.
In our example there is a disruption in the CAN bus communication of the switching controller type NRS 1-40.
If faults occur that are not listed above, please contact our subsidiary or agency in your country.
74
once briefly
Annex
Establishing / changing node ID
If several systems of the same kind are to communicate in one CAN bus network establish one node ID for each individual system (e. g. controller).
Factory set node IDs
Controller
The individual node IDs must be adjusted manually on the respective devices. Please observe the relevant installation instructions.
Attention
Do not assign the same node ID twice within the CAN bus network.
Electrode
75
Annex – continued –
Fig. 5 Rear panel of the URB 1
76
S8
OFF
ON
OFF
ON
OFF
ON
Fig. 6 Default factory setting 250 kBit/s
S9 S0
OFF
ON
ON
OFF OFF OFF
ON ON
ON ON
ON ON
Baud rate
250 kBit/s
125 kBit/s 100 kBit/s
50 kBit/s 20 kBit/s 10 kBit/s
Cable length
125 m
250 m 335 m 500 m
1000 m 1000 m
Annex – continued –
Table: Standard Curves
.oNtnegagninoitidnoCC°52ta]mc/Sm[ytivitcudnoccisaB
1adoscitsuaC062 2adoscitsuaC0801 3adoscitsuaC0045 4adoscitsuaC00011 5etahpsohpmuidosirT091 6etahpsohpmuidosirT0011 7etahpsohpmuidosirT0095 8etahpsohpmuidosirT00211 9etiflusmuidoS089
01444euqilopiD002
11nixoveL591
77
Annex – continued –
Declaration of conformity
We hereby declare that the equipment URB 1 conforms to the following European guidelines:
LV directive 73/23/eec version 93/68/eec
EMC guideline 89/336/eec version 93/68/eec
which are based on the following harmonised standards:
LV standard EN 50178
EMC standard EN 50081-2, EN 50082-2
This declaration is no longer valid if modifications are made to the equipment without consultation with us.
Bremen, 23rd May 2002
GESTRA GmbH
Dipl.-Ing. Stefan Bode
(Academically qualified engineer)
Head of R & D Dept. Electronics
Key
Fixing screw for panel mounting
A
Dipl.-Ing. Lars Bohl
(Academically qualified engineer)
Quality Assurance Manager
78
Example of Installation
95
A
63
Fig. 7
95
79
GESTRA Gesellschaften · GESTRA Companies · Sociétés GESTRA · Sociedades Gestra · Società GESTRA
Vertretungen weltweit · Agencies all over the world · Représentations dans le monde entier · Representaciones en todo el mundo · Agenzie in tutto il mondo
Great Britain Flowserve Flow Control (UK) Ltd.
Burrel Road, Haywards Heath West Sussex RH 16 1TL Tel. 00 44 14 44 / 31 44 00 Fax 00 44 14 44 / 31 45 57 E-mail: sales@flowserve.com
France Flowserve Flow Control S. A.S.
10 Avenue du Centaure, BP 8263 F-95801 CERGY PONTOISE CEDEX Tél. 00.33.1 / 34 4326 60 Fax 00.33.1 / 34 43 26 87 E-mail: contact@gestra.fr
España GESTRA ESPAÑOLA S.A.
Luis Cabrera, 86-88 E-28002 Madrid Tel. 00 34 91/ 5 152 032 Fax 003491/4136747; 5152036 E-mail: gestra@gestra.es
Italia
Flowserve S.p. A
Divisione Italgestra Via Prealpi, 30 – 20032 Cormano (MI) Tel. 00 39 02 /66 3251 Fax 0039 02 / 66 32 55 60 E-mail: info@italgestra.it
Portugal
Flowserve Portuguesa, Lda.
Av. Dr. Antunes Guimarães, 1159 Porto 4100-082 Tel. 0035122/6198770 Fax 00351 22 / 61075 75 E-mail: gestra@gestra.pt
®
GESTRA GmbH
Postfach 10 54 60, D-28054 Bremen, Münchener Str. 77, D-28215 Bremen Telefon +49 (0) 421 35 03- 0, Telefax +49 (0) 421 35 03- 393 E-Mail gestra.gmbh@flowserve.com, Internet www.gestra.de
A Unit of Flowserve Corporation
810375-03/304 · © 2002 GESTRA GmbH · Bremen · Printed in Germany
80
Loading...