Adjusting LIN (linear) temperature compensation ................................................ 58– 60
Adjusting NORM (standard curve) temperature compensation ........................... 61–65
Enabling AUTO temperature compensation ............................................................ 66, 67
Disabling temperature compensation ................................................................... 68, 69
.................................... 36–39
P
2
Contents
Page
Operation
Manual operation via external control valve ............................................................... 70
Stand-by operation with the steam boiler disconnected............................................. 71
System Malfunctions
Systematic malfunction analysis for troubleshooting .................................................. 72
Fault finding list ...................................................................................................... 73, 74
Annex
Establishing / changing node ID ................................................................................. 75
Factory set node IDs .............................................................................................. 75, 76
Table: standard curves ................................................................................................ 77
Declaration of conformity............................................................................................. 78
3
Wiring Diagram
Terminating resistor 120 Ω,
Fig.1
Paired cable
Operating
terminal
URB 1
Level switch
NRS
CEP*)
Voltage supplyCAN data line
Terminating resistor
120 Ω
*) CEP = central earthable point
Fig. 2
4
Conductivity
controller
LRR 1-40
Conductivity
electrode
LRG 16-40
Terminating resistor
120 Ω
Electrode
NRG .. .
Functional Elements
6
Fig. 3
1234
5
5
Functional Elements
7
B
Fig. 4
6
A
A
Key
Program button for switching between operating mode and parameterisation mode
1
Increase button
2
3
Decrease button
4
Enter button
5
Manual / automatic button
6
Illuminated LCD display, resolution 128 x 64 pixels
Code switch for baud rate setting
7
A
Fixing screws for panel mounting
Five-pole connector
B
7
Important Notes
Usage for the intended purpose
Use operating terminal & display unit URB 1 only in conjunction with GESTRA
Spector bus systems (CANopen).
Safety Note
Use operating terminal and display unit URB 1 only for operating and viewing
GESTRA CAN bus systems.
The equipment must only be installed by qualified staff.
Qualified staff are those persons who – through adequate training in electrical
engineering, the use and application of safety equipment in accordance with
regulations concerning electrical safety systems, and first aid & accident prevention –
have achieved a recognised level of competence appropriate to the installation and
commissioning of this device.
Explanatory Notes
Scope of supply
URB 1
1 Operating terminal and display unit URB 1 (in plastic case)
2 Fixing screws for panel mounting
1 Installation manual
System description
The URB 1 is a user-friendly operating terminal and display unit for GESTRA CAN
bus systems using the CANopen protocol. The equipment makes retrieving and
processing standard functions of associated system components very easy.
In addition, the URB 1 simplifies the parameterisation procedure: The switchpoints,
proportional band and response sensitivity can be adjusted by means of the keypad
regardless of the actual level. The energizing and de-energizing times of the relays
can be set individually for their respective switchpoints.
The following tables specifiy the GESTRA systems that can be displayed by the
URB 1.
8
Explanatory Notes – continued –
System description – continued –
Standard display information
Actual value (bar chart)●● ●
Actual value (numerical value)●● ●
Switchpoint (symbol)●●● ●
High level alarm (electrode HW)●●● ●
Low level alarm (electrode LW)●●● ●
Manual/automatic operation●● ●
Stand-by mode●
Unit [µS/cm] or [ppm]●
Low level limit●
High level limit●
Alarm (warning triangle)●●
Further display information
Actual value (continuous)●● ●
Switchpoints●●● ●
Setpoint●●
Deviation●●
Valve position●●
Intermittent blowdown●
Intermittent blowdown interval●
Purging pulse 24 h●
Current CAN bus addresses●●●●● ●
NRS 1-40 NRS 1-41 NRS 1-42
NRS 1-40 NRS 1-41 NRS 1-42
LevelConductivity
NRS 2-40 NRR 2-40
LevelConductivity
NRS 2-40 NRR 2-40
LRR 1-40
LRR 1-40
Function
The URB 1 communicates with other GESTRA system components via a designated
CAN bus using the CANopen protocol to DIN ISO 11898.
The URB 1 can also be used to operate and display further system components
during operation.
■ Capacitance level switch type NRS 2-40 CANopen
■ Level controller type NRR 2-40 CANopen
■ Conductivity level switch type NRS 1-42 CANopen
■ Low-level alarm to TRD 604/EN type NRS 1-40 CANopen
■
High-level alarm to TRD 604/EN type NRS 1-41 CANopen
■
Conductivity controller and limiter to TRD 604/EN type NRS 1-41 CANopen
Power supply: 18 V – 36 V DC
Interface for CAN bus using CANopen protocol to DIN ISO 11898
Output
Interface for CAN bus using CANopen protocol to DIN ISO 11898
Indicators and adjustors
1 illuminated display, resolution: 128 x 64 pixels
5 push buttons
1 three-pole code switch for baud rate setting
Supply voltage
18 V – 36 V DC
Protection
Front panel: IP 54 to DIN EN 60529
Back:IP 00 to DIN EN 60529
Admissible ambient temperature
0°C – 55 °C
Case material
Front face: Aluminium with polyester membrane
Casing: Noryl GFN 2 SE 1, glass-fibre reinforced
Weight
Approx. 0.3 kg
Installation
URB 1
Panel mounting
1. Provide panel cut-out, dimensions: 92
2. Install URB 1 using the fixing clips supplied with the equipment.
Tool
■ Screwdriver (5.5/100)
10
+0.8
x 92
+0.8
.
Wiring
Note that multi-core control cable with conductors linked in pairs, e. g. UNITRONIC
BUS CAN 2 x 2 x .. mm
2
or RE-2YCYV-fl 2 x 2 x .. mm2 .
®
The baud rate (data transfer rate) dictates the cable length between the bus nodes
and the total power consumption of the sensors dictates the conductor size.
8S9S01SetarduaBhtgnelelbaC
FFONOFFOs/tiBk052m521
sgnittesyrotcaF
NONOFFOs/tiBk521m0525,0x2x2
FFOFFONOs/tiBk001m53357,0x2x2
NOFFONOs/tiBk05m005
FFONONOs/tiBk02m0001
NONONOs/tiBk01m0001
sriapforebmuN
2
]
mm[ezisrotcudnocdna
43,0x2x2
notnedneped,tseuqerno
noitarugifnocsub
The baud rate is set via a code switch. Reduce baud rate if cable is longer than
specified in the table above. Make sure that all bus nodes feature the same settings.
To protect the switching contacts fuse circuit with 2.5 A (anti-surge fuse) or according
to TRD regulations (1.0 A for 72 hrs operation).
When a max. cable length of more than 125 m (up to 1000 m) is desired, make
sure to modify the baud rate accordingly. Refer to pages 75 and 76 for more
details.
Wiring diagram
For wiring diagram refer to page 4.
Attention
■ Wire equipment in series. Star-type wiring is not permitted.
■ Interlink screens of control cables such that electrical continuity is
ensured and connect them once to the central earthing point (CEP).
■ If more than one system component is connected to a CAN bus
network provide the first and last equipment with a terminating resistor
of 120 Ω, Fig. 2
■ The CAN bus line must not be interrupted while operating with one or
more system components.
Any interruption will open the control circuit!
If the switching controller has to be replaced be sure to remove first
the terminal strips , Fig. 4
B
Note: Make sure that all system components connected are
operating
UNITRONIC® is a registered trademark of LAPP Kabelwerke GmbH, Stuttgart.
before removing the CAN bus line from the terminal strip!
not
11
Wiring – continued –
Note
■
Connect screen only to terminal 3, ensuring electrical continuity and
connect equipment once to the central earthing point (CEP).
■
The loop resistance must be under 10 Ω.
■
The rated voltage is stated on the name plate.
■
Despite correct wiring H.F. interference caused by the installation may
lead to system breakdowns and malfunction messages. If necessary
refer to the fault finding lists of the respective bus equipment.
Tools
■ Screwdriver for slotted screws, size 2.5, completely insulated according to
VDE 0680
12
Basic Settings
CAN-Bus
All level and conductivity controllers and associated electrodes are interconnected by
means of a CAN bus using the CANopen protocol. Every item of equipment features
an electronic address (node ID). The four-core bus cable serves as power supply and
data highway for high-speed data exchange.
The CAN address (node ID) can be set between 60 and 123.
The URB 1 is configured at our works and ready for service with other GESTRA
system components without having to set the node ID.
If several systems of the same kind are to communicate in one CAN bus
network, be sure to assign one node ID for each individual system component
(e. g. controller). Refer to page 75 and 76 for more information.
Node ID for GESTRA bus-based device URB 1
Example: Conductivity monitoring and control
Example: Level monitoring and control
Factory set default values
The URB 1 features the following factory default settings:
■ Baud rate: 250 kb/s
■ Node ID: 060 (Do not change this node ID unless required; highest permissible
setting: 123)
13
Basic Settings – continued –
Adjusting display brightness
The brightness of the LCD display can be
adjusted as necessary.
Press and hold the button for a few
seconds.
The URB 1 enters the address
parameterisation mode.
Press button several times to reduce
the brightness.
14
several times briefly
several times briefly
Basic Settings – continued –
Adjusting display brightness – continued –
Press button several times to
increase the brightness.
Press button briefly to save settings
and return to the main window.
several times briefly
twice briefly
15
Basic Settings – continued –
Changing factory set node ID of the URB 1 / Adjusting & changing node ID
The factory set node ID of the URB 1 is
“060”. Node IDs below this value are
reserved for other GESTRA bus
components.
If additional operating terminals type URB 1
are used in a CAN bus system, you have to
set their node IDs to values above “060”.
Note that the newly established node IDs
must not be identical with node IDs of other
bus components.
Press and hold button for a few
seconds to enter the address
parameterisation mode.
Press button briefly to activate the
line selection mode.
16
a few seconds
briefly
Basic Settings – continued –
Changing factory set node ID of the URB 1 / Adjusting & changing node ID – continued –
Press button briefly to activate the line
editing mode.
Use button or to increase or
decrease the first digit.
flashing
briefly
Press button briefly to move the
cursor two steps further.
flashing
twice briefly
Press button once briefly to select the
digit “1”.
flashing
once briefly
17
Basic Settings – continued –
Changing factory set node ID of the URB 1 / Adjusting & changing node ID – continued –
Press button briefly to activate the line
selection mode.
In our example the node ID was set to
“061”.
briefly
Press button twice briefly to save
settings and return to the main window.
twice briefly
Possibilities to display bus devices
The URB 1 can display only one level monitoring device, one low-level alarm, one
high-level alarm and one conductivity monitoring device per vessel (e. g. steam
boiler or feedwater deaerator).
If the monitoring systems of more than one vessel are to be displayed, provide one
URB 1 per vessel.
18
Basic Settings – continued –
Setting /changing node IDs of bus-based equipment
The standard default node ID setting of all
bus devices that can be displayed is “O
This setting acts as a wild card for all bus
devices which are not displayed with the
URB 1.
For each bus device that shall be displayed
by the URB 1 a node ID has to be
established manually.
We recommend to accept the factory set
node IDs of GESTRA bus devices. For the
relevant node ID setting please refer to the
corresponding installation manual of the
device.
Press button briefly to show the
address list and activate the
parameterisation mode.
FF”.
Press button briefly to activate the line
selection mode.
briefly
briefly
19
Basic Settings – continued –
Setting /changing node IDs of bus-based equipment – continued –
Press button briefly to activate the line
editing mode.
Use button or to increase or
decrease the first digit.
flashing
briefly
Press button once briefly to select the
digit “0”.
flashing
once briefly
Press button briefly to move the
cursor one step further.
Press button twice briefly to select
the digit “0”.
20
flashing
briefly
flashing
twice briefly
Basic Settings – continued –
Setting /changing node IDs of bus-based equipment – continued –
Press button briefly to move the
cursor one step further.
flashing
Press button seven times briefly to
select the digit “1”.
flashing
briefly
7 times briefly
Press button briefly to activate the line
selection mode.
Press button once briefly to move to
the next line.
The node ID of the NRS 1-41 can now
be adjusted.
briefly
once briefly
21
Basic Settings – continued –
Setting /changing node IDs of bus-based equipment – continued –
Press button briefly to activate the
parameterisation mode.
In this example the node IDs of all bus
devices have already been adjusted.
If the display of the NRS 1-42 is required
set the node IDs of the NRS 2-40 and
NRR 2-40 to “O
Press button twice briefly to save the
settings and return to the main window.
FF”.
briefly
twice briefly
22
Basic Settings – continued –
Visual display / Parameterisation of bus devices
The split-screen display window shows which
GESTRA bus devices can be indicated:
■ High-level limiter type NRS 1-41
■ Low-level limiter type NRS 1-40
■ Level switch type NRS 2-40
■ Level controller type NRR 2-40
■ Conductivity controller type LRR 1-40
Press button briefly to enter the display
window of the level controller NRR 2-40.
Actual level (graphical representation)
1
Actual level (percentage)
2
3
Setpoint deviation
4
Proportional band X
5
Switchpoints NRR 2-40
6
Valve position
p
Press button briefly to enter the display
window of the level switch NRS 2-40.
1
Actual level (graphical representation)
2
Actual level (percentage)
3
Control unit 2 highlighted
4
Switchpoints for control unit 2
5
Low-level signal
(flashes in the event of an LW alarm)
6
High-level signal
(flashes in the event of an HW alarm)
LW = low water (limiter NRS 1-40)
HW = high water (limiter NRS 1-41
5
4
1
2
3
6
briefly
4
6
3
1
2
5
briefly
23
Basic Settings – continued –
Visual display / Parameterisation of bus devices – continued –
Press button briefly to enter the
parameterisation mode for the following
settings:
■ 0 % – 100 % calibration NRG 26-40
■ Switchpoints NRR 2-40
■ Proportional band NRR 2-40
■ Switchpoints NRS 2-40
Press button briefly to enter the
parameterisation mode for the following
settings:
■ Relay energizing delay times
■ Relay de-energizing delay times
briefly
briefly
Press button briefly to enter the error
messages window.
For more information see section
Malfunction, Troubleshooting, Fault
Finding List on pages 72 and 74.
Press button briefly to return to the
main window.
1
Actual conductivity value
2
Actual conductivity
(graphical representation)
24
briefly
1
2
briefly
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.