Flowserve NRS1-9 User Manual

NRS 1-9
Installation Instructions 810831-00
Water-Level Limiter / Controller NRS 1-9
1
Contents
Page
Important Notes
Usage for the intended purpose .................................................................................... 7
Safety note.....................................................................................................................7
Danger ........................................................................................................................... 7
Scope of supply ............................................................................................................. 8
Description .....................................................................................................................8
Function ......................................................................................................................... 8
Design ............................................................................................................................ 9
Technical data ............................................................................................................... 9
Installation
NRS 1-9 ....................................................................................................................... 10
Example of installation ................................................................................................ 15
Wiring
Wiring diagram......................................................................................................... 3, 10
Basic Adjustments
Change-over for sensitivity .......................................................................................... 11
Commissioning
Check wiring ................................................................................................................ 11
Apply power ................................................................................................................. 11
Performance Tests
Low level limiter ........................................................................................................... 12
High level limiter .......................................................................................................... 12
Water level controller ................................................................................................... 12
Annex
Fault finding list for troubleshooting ............................................................................ 13
Declaration of conformity............................................................................................. 14
2
Wiring Diagram
NRS 1-9
Fig. 1
NRG 16-36
3
Functional Elements / Dimensions
A
1 2
MAX 55 °C
Fig. 2
95
158
3
MAX 95 %
4 5 6
A
C
BF
D
D
4
D
Fig. 3
37.5
75
E
120
5
Fig. 4
Functional Elements
Fig. 5
G
5
Key
A
Cover screws
B
Cover
C
Base
D
Cable entry
E
Mounting clip
F
Hole for wall mounting
G
Code switch for setting sensitivity
1
LED “High level alarm”
2
Switch “Test 2 / Inspection”
3
LED “Low level alarm”
4
Test button “Test 1”
5
LED “Pump ON”
6
LED “Power”
6
Important Notes
Usage for the intended purpose
Water level controllers and water level limiters serve as safety equipment in installations requiring official approval. Use switching controller/limiter NRS 1-9 only for monitoring and indicating liquid levels.
Safety Note
Installation must only be performed by qualified staff. Qualified staff are those persons who – through adequate training in electrical
engineering, the use and application of safety equipment in accordance with regula­tions concerning electrical safety systems, and first aid & accident prevention – have achieved a recognised level of competence appropriate to the installation and commissioning of this critical safety device.
Danger
The terminal strip of the NRS 1-9 is live during operation. This presents the danger of electric shock. Cut off power supply before fixing or removing the housing cover.
7
Explanatory Notes
Scope of supply
NRS 1-9
1 Water level controller/water level limiter (plug-in unit for installation in control
cabinets)
1 Installation manual
Description
Self-monitoring water level controller & limiter with automatic self-testing routine designed for use in conjunction with level electrode NRG 16-36. This equipment combination controls the water level, detects the max. allowable water level (high level alarm) and the min. allowable water level (low level alarm).
Application in compliance with the German regulations for use in steam and hot-water plants according to TRD 602 and TRD 604, sheets 1 and 2.
Function
The switching controller NRS 1-9 features a two channel circuit and is provided with a self-monitoring and routine testing function in accordance with DIN 57116/VDE
0116. The two channels are designed to monitor the operation of each other (redundancy). The periodic self-checking logic unit checks the integrity of the cable between the electrode and the switching controller, and the two channel circuits for malfunction. Unless it finds a fault, this internal test does not interfere with the output contacts of the controller and therefore the boiler operation is not interrupted. A manual test push button is also provided. When the push button “TEST 1” is pressed, it simulates a fault in the electrode. There is also a toggle switch “TEST 2/ Inspection” for checking the function of the self-checking circuitry. The output contact relays of the switching controller are of the normally closed type and will therefore signal alarm condition in the event of mains failure.
The switching controller can signal the following four operating conditions:
Normal operation (feedwater control)
Alarm (high water level)
Alarm (low water level)
Alarm (fault in switching controller or level electrode)
A green LED indicates power ON. Low water level alarm or malfunction of the low water level limiter system is indicated by the two red LEDs. The failure of one channel (loss of redundancy) is signalled by the lighting up of one red LED. The other green LED indicates feedwater pump is running. High water level alarm is signalled by another red LED.
The use of SMART combination electrode NRG 16-36 in conjunction with switching controller NRS 1-9 provides fail safe protection against a first fault, i. e. the system will still continue to provide the safety function even after the occurrence of a first
fault.
8
Explanatory Notes – continued –
Design
NRS 1-9b:
Plug-in unit in plastic case for snapping onto a 35 mm rail (TS 35 x 15 according to DIN EN 50022-35) or for installation in control
Technical Data
Type approval no.
TÜV · WR/WB · 99-370
Input
8 connections for one level electrode NRG 16-36, PN 40
Output contacts For level limiter part:
Two volt-free relay contacts
For level controller part:
One volt-free working contact for feedwater on-off control. One volt-free relay contact for high level alarm. Contact material silver, hard gold plated. Max. contact rating with switching voltages of 24 V, 115 V and 230 V a.c.: 4 A resistive, 0.75 A inductive at cos ϕ 0.5 Max. contact rating with switching voltage of 24 V d.c.: 4 A
Delay of response
The low water level alarm signal is factory set to react after a time delay of 1 or 3 seconds (up to 25 sec. delay is possible). The controller as well as the high water level alarm signal is factory set to react after a time delay of 2 seconds.
Sensitivity
Range 1: 10 µS/cm at 25°C Range 2: 0.5 µS/cm at 25°C The selection of the above range is done via a code switch.
Indicators and adjustors
One green LED “Power”, two LEDs “Low level alarm”, one test button “TEST 1”, one toggle switch “TEST 2/INSPECTION”, one LED “Feedwater control on”, one LED “High level alarm” and one four-pole code switch.
Mains supply
230 V +/– 10 %, 50/60 Hz (please state voltage when ordering) Special voltage: 115 V +/– 10 %, 50/60 Hz or 24 V +/– 10 %, 50/60 Hz; 24 V d. c. supply is also possible with the inverter type URN-1.
Protection
IP 20 in accordance with DIN 40050
Admissible ambient temperature
0 to 55 °C
Case materials
Base: ABS plastic, black. Cover: polystyrene, highly shock resistant, stone grey.
Weight
0.6 kg 9
Installation
NRS 1-9
On supporting rail
1. Snap switching controller onto supporting rail.
2. Loosen cover screws and unplug cover from its base .
3. Select cable entry and remove corresponding seal.
A B
D
C
On mounting panel
1. Loosen cover screws and unplug cover from its base .
2. Unscrew mounting clip .
3. Drill the hole marked in the base to 4.3 mm diameter.
F
4. Select cable entry and remove corresponding seal.
A
E
D
B
C
5. Fasten base with two screws M4 onto mounting panel.
Tools
Screwdriver (5.5/100)
Wiring
NRS 1-9
Use four-core overall screened cable, e. g. IY(ST)Y 2 x 2 x 0.9 or LIYCY 4 x 0.5 mm². Max. cable length 250 m.
Connect terminal strip in accordance with wiring diagram, fig. 1
Wiring Diagram
see page 3
Attention
To protect the switching contacts fuse circuit with 2.5 A (slow blow fuse)
or according to TRD regulations (1.0 A for 72 hrs operation).
The screen must not make any other electrical contact.
10
Note
Connect screen only to terminals 16 and 21 of the switching controller.
The mains voltage is indicated on the name plate.
When switching off inductive loads, voltage spikes are produced that
may impair the operation of control and measuring systems. Inductive loads should be provided with commercial arc suppressor RC combinations, e. g. 0.1 µF/100 W.
Wiring – continued –
Tools
Screwdriver for slotted screws, size 2.5, completely insulated according to
VDE 0680.
Basic Adjustments
Change-over for sensitivity
The switching controller can be set to two different sensitivities. For this purpose a code switch consisting of four individual switches is provided on the rear of the controller.
Range 1: Sensitivity from 10 µS/cm (factory setting) Range 2: Sensitivity from 0.5 µS/cm
1. Cut off power supply to switching controller.
2. Loosen cover screws and unplug cover from its base , fig. 1.
A
3. Move all four individual switches of the code switch to the desired range using
B
G
a small screwdriver, fig. 5.
Tools
Screwdriver for slotted screws, size 2.5, completely insulated according to
VDE 0680.
C
Commissioning
Check wiring
Check whether switching controller NRS 1-9 and the associated electrode NRG 16-36 are wired in accordance with wiring diagram, fig. 1.
Apply power
Apply mains voltage. The green LED lights up, fig. 2.
6
11
Performance Tests
Low-level limiter
1. Check length of electrode tip (see installation instructions for NRG 16-36).
2. When switching on the mains voltage the green LED should light permanently,
fig. 2.
3. Completely open valves of water-level gauge glass on steam boiler.
4. Fill boiler with feedwater (2 cm above required min. level).
5. Decrease level in boiler until the level falls below min. level. After the response delay the two red LEDs must light up.
3
6. A low-level alarm can be simulated by pushing the button “TEST I” whilst the electrode tip is submerged. Push the button until the response delay has expired. Both red LEDs must light up.
3
7. To check the function of the checking circuitry of the switching controller proceed as follows: Operate switch “TEST II/INSPECTION” in the direction of the arrow with the electrode tip submerged. After max. two minutes the two red LEDs should signal low-level alarm. The button “TEST I” must not be operated during this test nor must the level
4
fall below the low level mark. After the test return switch into its original position. After the response delay the two red LEDs must extinguish.
3
High-level limiter
1. Check length of electrode tip (see installation instructions for NRG 16-36).
2. Completely open valves of water-level gauge glass on steam boiler.
3. Fill boiler with feedwater until the level exceeds the required max. level.
After the response delay of 2 sec. the red LED must light up, fig. 2.
4. Decrease level in the boiler until the level falls below high level, the red LED must extinguish.
6
4
2
3
1
1
Water level controller
1. Check length of electrode tips (see installation instructions for NRG 16-36).
2. Lower water level in boiler until electrode tip “2” (lower switch point) is completely exposed, fig. 1.
3. The green led must light up, fig. 2.
5
Simultaneously the switching function for feedwater control (PUMP ON) is released.
4. When the water level reaches electrode tip “3” (upper switch point), LED must
5
extinguish. Simultaneously the switching function for feedwater control (PUMP OFF) is released.
12
Annex
Danger
The terminal strip of the NRS 1-9 is live during operation. This presents the danger of electric shock. Cut off power supply before fixing or removing the housing cover.
Fault finding list for troubleshooting
Fault:
Remedy:
Fault:
Remedy:
Fault:
Remedy:
Fault:
Remedy:
The switching controller signals low-level alarm before the level in the boiler has fallen below the low level mark.
Check length of low-water level electrode tip. Measure the conductivity of the process or boiler water and compare the values obtained with the marking on the name plate. Check correct wiring of switching controller and electrode in accordance with wiring diagram, fig. 1.
After raising the water level above the low-level mark, the red LEDs
3
are not extinguished or only after quite a considerable period. Check whether a vent hole has been provided in the protection tube. If the
electrode is fitted in an external chamber, check position of isolating valves.
One or both red LED(s) light up without the level having fallen below
3
the low-level mark. This means electronic failure within the switching controller, i. e. failure of
one or both channels. Replace switching controller.
The switching controller signals high-level alarm before the level in the boiler has reached the high level mark.
Check length of high water level electrode tip. Check whether the electrode tip has contact with the chamber/protection tube or other boiler internals. Check correct wiring of level switch and electrode in accordance with wiring diagram, fig. 1.
Fault:
After decreasing the water level below the high-level mark, the red LED is not extinguished or only extinguishes after quite a considerable period.
Remedy:
Check whether a vent hole has been provided in the protection tube. If the electrode is fitted in an external chamber, check position of isolating valves.
If faults occur that are not listed above please contact our subsidiary or agency in your country.
4
13
Annex – continued –
Declaration of conformity
We hereby declare that the equipment NRS 1-9 conforms to the following European guidelines:
LV guideline 73/23/eec version 93/68eec
EMC guideline 89/336/eec version 93/68/eec
which are based on the following harmonized standards:
LV standard EN 60947-5-1: 1991
EMC standard EN 50 081-2, EN 50 082-2
This declaration is no longer valid if modifications are made to the equipment without consultation with us.
Bremen, 1st January 2000
GESTRA GmbH
Dr. Anno Krautwald
Key
A
Cover screws
B
Cover
C
Base
F
Hole for wall mounting
H
Mounting clip
I
Support rail TS 35 x 15 to DIN EN 50022-35
Dipl.-Ing. Uwe Bledschun
(Academically qualified engineer)
14
Example of Installation
B
CH
MAX 55°C
MAX 95%
Fig. 6
I
A
F
F
Fig. 7
15
GESTRA Gesellschaften · GESTRA Companies · Sociétés GESTRA · Sociedades Gestra · Società GESTRA
Vertretungen weltweit · Agencies all over the world · Représentations dans le monde entier · Representaciones en todo el mundo · Agenzie in tutto il mondo
Great Britain Flowserve Flow Control (UK) Ltd.
Burrel Road, Haywards Heath West Sussex RH 16 1TL Tel. 00 44 14 44 / 31 44 00 Fax 00 44 14 44 / 31 45 40 E-mail: sales@flowserve.com
France Flowserve Flow Control S.A.S.
10 Avenue du Centaure, BP 8263 F-95801 CERGY PONTOISE CEDEX Tél. 003 31 / 34 4326 60 Fax00331/34432687 E-mail: gnation@flowserve.com
España GESTRA ESPAÑOLA S.A.
Luis Cabrera, 86-88 E-28002 Madrid Tel. 00 34 91/5 152 032 Fax 00 34 91/ 4 136 747; 5152 036 E-mail: gestra@gestra.es
Italia
Flowserve S.p. A
Divisione Italgestra Via Prealpi, 30 – 20032 Cormano (MI) Tel. 00 39 02/66 32 51 Fax 00 39 02 /66 32 55 60 E-mail: info@italgestra.it
Portugal
Flowserve Portuguesa, Lda.
Av. Dr. Antunes Guimarães, 1159 Porto 4100-082 Tel. 0035122/6198770 Fax 00351 22 /61075 75 E-mail: gestra@gestra.pt
®
GESTRA GmbH
P. O. Box 10 54 60, D-28054 Bremen, Münchener Str. 77, D-28215 Bremen Telephone +49 (0) 421 35 03-0, Fax +49 (0) 421 35 03 - 393 E-Mail gestra.gmbh@flowserve.com, Internet www.gestra.de
A Unit of Flowserve Corporation
810831-00/903c · © 2000 GESTRA GmbH · Bremen · Printed in Germany