Fire-Lite SLC Manual

0 (0)
Fire-Lite SLC Manual

PN 51309:K

ECN 08-118

Intelligent Control Panel

S L C

Wiring Manual

Document 51309

K

2/14/2008

Rev:

PrecauLarge.PMD 02/26/2007

Fire Alarm System Limitations

An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.

The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guides for Proper Use of System Smoke Detectors, which are made available at no charge to all installing dealers. These documents can be found at http:/www.systemsensor.com/html/ applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm

systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:

Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.

Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because:

Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.

Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.

Smoke particles may be blown away from detectors by air outlets.

Smoke particles may be drawn into air returns before reaching the detector.

The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.

Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.

Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper stor-

While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!

age of flammable materials, etc.).

Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.

IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.

Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:

Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.

Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.

In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.

A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.

Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel.

Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.

The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.

Installation Precautions

WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.

CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.

All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.

This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F and at a relative humidity of 93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.

Verify that wire sizes are adequate for all initiating and indicating device loops. Refer to manual Specifications section for maximum allowable I.R. drop from the specified device voltage.

Adherence to the following will aid in problem-free installation with long-term reliability:

Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.

Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.

Consult with the Technical Services Department if any problems are anticipated or encountered.

Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.

Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.

This system contains static-sensitive components.

Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.

Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.

FCC Warning

WARNING: This equipment generates, uses, and can

Canadian Requirements

radiate radio frequency energy and if not installed and

This digital apparatus does not exceed the Class A

used in accordance with the instruction manual, may

limits for radiation noise emissions from digital

cause interference to radio communications. It has

apparatus set out in the Radio Interference Regulations

been tested and found to comply with the limits for class

of the Canadian Department of Communications.

A computing device pursuant to Subpart B of Part 15 of

Le present appareil numerique n'emet pas de bruits

FCC Rules, which is designed to provide reasonable

radioelectriques depassant les limites applicables aux

protection against such interference when operated in a

appareils numeriques de la classe A prescrites dans le

commercial environment. Operation of this equipment

Reglement sur le brouillage radioelectrique edicte par

in a residential area is likely to cause interference, in

le ministere des Communications du Canada.

which case the user will be required to correct the

 

interference at their own expense.

 

PrecauLarge.PMD 02/26/2007

This Page Intentionally Left Blank

4

The SLC Wiring Manual PN 51309:K 2/14/08

Introduction 8

 

Scope ............................................................................................................................

8

Reference Documentation .....................................................................................

9

Overview ...................................................................................................................

10

Polling Protocols ......................................................................................................

10

Available Protocols .............................................................................................

10

Devices .......................................................................................................................

10

Isolator Module ...................................................................................................

10

Monitor Modules .................................................................................................

10

Control Modules .................................................................................................

11

Relay Modules ....................................................................................................

11

Intelligent Detectors ............................................................................................

11

Manual Pull Station .............................................................................................

12

300 Series Addressable Devices .........................................................................

12

SLC Performance .....................................................................................................

12

Surge Suppression ....................................................................................................

12

Wiring Requirements 13

 

Wire Sizing ................................................................................................................

13

CLIP (Classic Loop Interface Protocol) Mode ...................................................

13

LiteSpeed Mode ..................................................................................................

13

Measuring Resistance & Length .............................................................................

14

Two-Wire SLC - Style 4 (Class B) .....................................................................

14

Loop Resistance ...........................................................................................

14

Total Wire Length ........................................................................................

14

Four-Wire SLC Style 6 & 7 (Class A) ................................................................

15

Loop Resistance ...........................................................................................

15

Total Wire Length ........................................................................................

15

Shield Wire Termination .........................................................................................

16

Control Panel Terminal Blocks ...............................................................................

17

MS-9200 ..............................................................................................................

17

MS-9600, MS-9600LS, MS-9600LSC & MS-9600UDLS .................................

17

MS-9200UD & MS-9200UDLS .........................................................................

18

MS-9050UD ........................................................................................................

18

Non-Isolated Circuits 19

 

Overview ...................................................................................................................

19

NFPA Style 4 SLC ....................................................................................................

19

NFPA Style 6 SLC ....................................................................................................

20

SLC Circuits with Isolators 21

 

Fault Isolator Module - I300 ...................................................................................

21

Isolating an SLC Branch .....................................................................................

21

Wiring an Isolator Module ..................................................................................

21

NFPA Style 4 SLC Using an I300 Module .............................................................

22

NFPA Style 6 SLC Using an I300 Module .............................................................

23

NFPA Style 7 SLC Using an I300 Module .............................................................

24

Monitor Modules 25

 

Descriptions ...............................................................................................................

25

MMF-300 Monitor Module ................................................................................

25

MMF-302 Monitor Module ................................................................................

25

MDF-300 Dual Monitor Module ........................................................................

26

MMF-301 Monitor Module ................................................................................

26

MMF-300-10 .......................................................................................................

27

The SLC Wiring Manual PN 51309:K 2/14/08

5

MMF-302-6 .........................................................................................................

28

Installation .................................................................................................................

29

Setting an SLC address for a Single Point Module .............................................

29

Setting an SLC address for a Multi-Point Module ..............................................

30

MMF-300 Wiring Diagrams ....................................................................................

31

Wiring a NFPA Style B IDC with an MMF-300 ...............................................

31

Wiring a NFPA Style D IDC with an MMF-300 ...............................................

32

MMF-300-10 Wiring Diagrams ...............................................................................

33

Wiring a NFPA Style B IDC with an MMF-300-10 ..........................................

33

Wiring a NFPA Style D IDC with an MMF-300-10 ..........................................

34

MDF-300 Wiring Diagrams .....................................................................................

35

Wiring a NFPA Style B IDC with an MDF-300 ................................................

35

MMF-302 Wiring Diagrams ....................................................................................

36

Wiring a NFPA Style B IDC with an MMF-302 ................................................

36

Wiring a NFPA Style D IDC with an MMF-302 ................................................

37

MMF-302-6 Wiring Diagrams .................................................................................

38

Wiring a NFPA Style B IDC with an MMF-302-6 .............................................

38

Wiring a NFPA Style D IDC with an MMF-302-6 .............................................

39

Control Modules 40

 

Description ................................................................................................................

40

CMF-300 Installation ...............................................................................................

40

Setting an SLC address for an CMF-300 Module ...............................................

40

Wiring a Notification Appliance Circuit (NAC) with an CMF-300 ...................

40

Wiring a CMF-300 Module .....................................................................................

41

Wiring a Style Y NAC (Two-Wire) ...................................................................

41

Wiring a Style Z NAC (Four-Wire) ....................................................................

42

CMF-300-6 Installation ............................................................................................

43

Cabinet Installation .............................................................................................

43

Setting an SLC address for an CMF-300-6 Module ...........................................

43

Setting NACs as Style Y or Style Z ....................................................................

43

Disabling Unused Module Addresses .................................................................

43

Short Circuit Protection .......................................................................................

43

Features Not Supported .......................................................................................

44

Circuit Board Information .................................................................................

44

Wiring a CMF-300-6 Module ..................................................................................

45

Wiring a Style Y NAC (Two-Wire) ...................................................................

45

Wiring a Style Z NAC (Four-Wire) ....................................................................

46

Relay Modules 47

 

Description ................................................................................................................

47

CRF-300 Installation & Wiring ..............................................................................

47

Setting an SLC address for a CRF-300 Module ..................................................

47

Wiring a CRF-300 Module (Form-C Relay) .......................................................

47

CRF-300-6 Circuit Board Information .................................................................

48

CRF-300-6 Installation & Wiring ...........................................................................

49

Cabinet Installation .............................................................................................

49

Setting an SLC address for a CRF-300-6 Module ..............................................

49

Disabling Unused Module Addresses ................................................................

49

Wiring a CRF-300-6 Module (Form-C Relay) ...................................................

49

Intelligent Detector Bases 50

 

Description ................................................................................................................

50

Installation and Wiring ............................................................................................

50

Setting the Detector Address ...............................................................................

50

6

The SLC Wiring Manual PN 51309:K 2/14/08

Wiring a Detector Base .......................................................................................

50

Addressable Beam Detectors 51

 

Description ................................................................................................................

51

Installation and Wiring ............................................................................................

51

Setting an SLC Address for a Beam Detector .....................................................

51

Wiring a Beam Detector .....................................................................................

51

Addressable Manual Pull Station 52

 

Description ................................................................................................................

52

Installation ................................................................................................................

52

Setting an SLC address .......................................................................................

52

Wiring a Manual Pull Station ..............................................................................

52

Appendix A: Power Considerations 53

 

Supplying Power to 24 VDC Detectors ..................................................................

53

Resistance and Size .............................................................................................

53

Supervising 24 VDC Power .....................................................................................

54

Appendix B: Surge Suppression 55

 

Introduction ..............................................................................................................

55

Installation ................................................................................................................

55

Wiring Diagram for MS-9200 .............................................................................

56

DTK-2LVLP-F Connections ......................................................................

56

PLP-42N Connections ................................................................................

56

SLCP-030 Connections ...............................................................................

56

Wiring Diagram for MS-9600, MS-9600LS, MS-9600LSC, MS-9600UDLS,

 

MS-9200UD, MS-9200UDLS and MS-9050UD ................................................

57

DTK-2LVLP-F Connections ......................................................................

57

PLP-42N Connections ................................................................................

57

SLCP-030 Connections ...............................................................................

57

Appendix C: Terminal Conversion Charts for New & Legacy Devices 58

 

CRF-300 ....................................................................................................................

58

CMF-300 and MMF-302 ..........................................................................................

59

MMF-300 ...................................................................................................................

60

The SLC Wiring Manual PN 51309:K 2/14/08

7

Introduction

Scope

Introduction

Scope

This document describes the operation, installation and wiring of various Signaling Line Circuit (SLC) devices when used with the Fire•Lite MS-9200/MS-9200E, the Fire•Lite MS-9600/MS-9600E, the FireLite MS-9600LS, the Fire-Lite MS-9600LSC, the Fire-Lite MS-9600LSE, the Fire-Lite MS-9600UDLS/ MS-9600UDLSE, the Fire•Lite MS-9200UD/MS-9200UDE, the Fire•Lite MS-9200UDLS/MS- 9200UDLSE and the Fire-Lite MS-9050UD control panels. It also provides basic information that applies to Fire•Lite SLC loops in general, such as the branch resistance measurements.

Note: Any reference in this manual to the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600, MS-9600LS or MS9600UDLS includes the MS-9200E, MS-9200UDE, MS-9200UDLSE, MS-9600E, MS-9600LSE or MS-9600UDLSE respectively.

Additional information about the specific control panel and the modules and detectors referenced in this document can be found in the respective installation manual as listed in Table 1, “Reference Documentation,” on page 9.

Currently, there are two styles of Modules available, legacy version and newer version. The obvious difference between the two styles is the orientation of the rotary dials. Refer to the diagram below for an example of each.

CMF-300

 

 

CMF-300

 

 

 

 

Legacy Version Module

Newer Version Module

(Vertical Rotary Dial)

(Horizontal Rotary Dial)

Note: Only MMF-300, MMF-302, CRF-300 and CMF-300 modules are available as newer type modules. Both the legacy and newer versions share the same part numbers. The newer version modules will be phased in, replacing the legacy version. This manual contains information and wiring diagrams for the newer version of the modules. Refer to "Appendix C: Terminal Conversion Charts for New & Legacy Devices" on page 58 for additional information.

8

The SLC Wiring Manual PN 51309:K 2/14/08

Scope

Introduction

Reference Documentation

The table below accommodates a list of document sources containing additional information regarding the devices used on a Signaling Line Circuit:

For information on...

Refer to...

Part Number

 

 

 

MS-9200/MS-9200E

Instruction Manual

51003

 

 

 

MS-9600/MS-9600E

Instruction Manual

51335

 

 

 

MS-9200UD/MS-9200UDE

Instruction Manual

51906

 

 

 

MS-9200UDLS/MS-9200UDLSE

Instruction Manual

52750

 

 

 

MS-9600LS/MS-9600LS(C/E) & MS-9600UDLS/MS9600UDLSE

Instruction Mnual

52646

 

 

 

MS-9050UD

Instruction Manual

52413

 

 

 

Compatible Devices

Device Compatibility Document

15384

 

 

 

BG-12LX Pull Station

Installation Instructions

51094

 

 

 

MMF-300 Monitor Module

Installation Instructions

F300-02-00

 

 

 

MMF-300-10 Monitor Module

Installation Instructions

F300-20-00

 

 

 

MMF-301 Mini Monitor Module

Installation Instructions

F300-05-00

 

 

 

MMF-302 Monitor Module

Installation Instructions

F300-03-00

 

 

 

MMF-302-6 Interface Module

Installation Instructions

F300-22-00

 

 

 

MDF-300 Dual Monitor Module

Installation Instructions

F300-09-00

 

 

 

CMF-300 Control Module

Installation Instructions

F300-07-00

 

 

 

CMF-300-6 Control Module

Installation Instructions

F300-21-00

 

 

 

CRF-300 Relay Module

Installation Instructions

F300-04-00

 

 

 

CRF-300-6 Relay Module

Installation Instructions

F300-19-00

 

 

 

I300 Isolator Module

Installation Instructions

F300-06-00

 

 

 

AD350 Multicriteria Detector

Installation Instructions

F300-17-00

 

 

 

AD355 Multicriteria Detector

Installation Instructions

F300-24-00

 

 

 

SD350 & SD350T Photo Detector

Installation Instructions

F300-14-00

 

 

 

SD355 & SD355T Photo Detector

Installation Instructions

F300-24-00

 

 

 

CP350 Ionization Detector

Installation Instructions

F300-15-00

 

 

 

CP355 Ionization Detector

Installation Instructions

F300-23-00

 

 

 

H350 Heat Detector

Installation Instructions

F300-12-00

 

 

 

H350R Heat Detector w/ROR

Installation Instructions

F300-13-00

 

 

 

H355 Heat Detector (135°)

Installation Instructions

F300-25-00

 

 

 

H355R Heat Detector w/ROR

Installation Instructions

F300-25-00

 

 

 

H355HT Heat Detector (190°)

Installation Inatructions

F300-25-00

 

 

 

D350P Duct Detector

Installation Instructions

F300-10-00

 

 

 

D350PL(A) Duct Detector - low flow

Installation Instructions

F300-27-00

 

 

 

D350RP Duct Detector w/Relay

Installation Instructions

F300-11-00

 

 

 

D350RPL(A) Duct Detector w/Relay - low flow

Installation Instructions

F300-28-00

 

 

 

BEAM355(S) Addressable Beam Detector

Installation Instructions

F300-29-00

 

 

 

B350LP Plug-in Detector Base

Installation Instructions

F400-21-00

 

 

 

B501BH Sounder Detector Base

Installation Instructions

D650-03-00

 

 

 

B224RB Relay Detector Base

Installation Instructions

D450-16-01

 

 

 

B224BI Isolator Detector Base

Installation Instructions

D450-15-00

Table 1 Reference Documentation

The SLC Wiring Manual PN 51309:K 2/14/08

9

Introduction

Overview

Overview

Communication between the control panel and intelligent addressable monitor and control devices takes place through a Signaling Line Circuit (SLC), which can be wired to meet the requirements of NFPA Style 4, Style 6, or Style 7.

At least one secondary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. For detailed information refer to "Appendix B: Surge Suppression" on page 55.

Polling Protocols

The MS-9200UDLS/E, MS-9600LS(C/E) and MS-9600UDLS/E support LiteSpeed protocol or Classic Loop Interface Protocol (CLIP). The MS-9200/E, MS-9600/E, MS-9200UD/E and MS-9050UD support Classic Loop Interface Protocol (CLIP) only.

Available Protocols

LiteSpeed is a communication protocol that greatly enhances the speed of communication between analog intelligent devices. Only the MS-9200UDLS/E, MS-9600LS(C/E) and MS-9600UDLS/E are capable of operating in LiteSpeed mode.

CLIP (Classic Loop Interface Protocol) polls devices in sequential order. All Fire-Lite addressable fire alarm control panels can operate in CLIP mode. This is the default mode of operation for the FACPs.

Protocol Use

Use one of the following options with LiteSpeed/CLIP mode:

1.Program all modules and detectors on an FACP as LiteSpeed.

2.Program all modules and detectors on an FACP as CLIP.

Note: FACPs with more than one SLC loop must be programmed for only LiteSpeed or CLIP mode of operation. Communication protocols cannot be split between SLC loops.

Devices

Isolator Module

The I300 Isolator Module permits a zone of detectors and modules to be fault isolated from the remainder of the SLC loop, allowing critical components to function in the event of a circuit fault. Isolator modules are required to meet the requirements of an NFPA Style 7 circuit.

Monitor Modules

Addressable modules that allow the control panel to monitor entire circuits of conventional alarm initiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow and supervisory devices.

MMF-300 - Monitors a Style B (Class B) or Style D (Class A) circuit of dry-contact input devises.

MMF-300-10 - Monitors ten (10) Style B (Class B) or five (5) Style D (Class A) normally open contact device circuits.

MMF-301 - Same as the MMF-300 except offered in a smaller package for mounting with Style B wired devices. This module does not have an LED.

MMF-302 - Monitors a single IDC of two-wire smoke detectors.

MMF-302-6 - An addressable module that provides an interface between the control panel and six (6) Style B (Class B) or three (3) Style D (Class A) IDCs of two-wire smoke detectors.

MDF-300 - Similar to MMF-300, but provides for two independent Style B IDCs.

10

The SLC Wiring Manual PN 51309:K 2/14/08

Control Modules

Through the CMF-300addressable control module, the control panel can selectively activate a Notification Appliance Circuit (NAC).

CMF-300-6 - Similar in operation to the CMF-300, except it can activate six (6) Style Y (Class B) or three

(3) Style Z (Class A) NACs.

Relay Modules

The CRF-300 addressable relay module provides the control panel with a dry-contact output for activating a variety of auxiliary devices.

CRF-300-6 - Similar in operation to the CRF-300, except it provides six (6) Form-C relays.

Intelligent Detectors

AD350 - A multicriteria smoke sensor that combines a photoelectric sensing chamber and 135°F (57.2°C) fixed temperature heat detection. The sensor uses addressable communication to transmit smoke density and other information to the control panel. It adjusts its detection parameters and alarm threshold depending on the ambient conditions it samples in its environment.

AD355 - A multicriteria smoke sensor that combines a photoelectric sensing chamber and 135°F (57.2°C) fixed temperature heat detection. The sensor uses addressable communication to transmit smoke density and other information to the control panel. It adjusts its detection parameters and alarm threshold depending on the ambient conditions it samples in its enviornment.

CP350 - An addressable ionization smoke detector which measures the level of combustion products in its chamber using the ‘ionization principle.’

CP355 - An addressable ionization smoke detector which measures the level of combustion products in its chamber using the ‘ionization principle.’

D350P - An addressable photoelectric duct detector. The D350RP includes an alarm relay. Air velocity rating is 500 to 4,000 feet per minute.

D350PL -An addressable low flow photoelectric duct detector (D350PLA for Canada). The D350RPL includes an alarm relay (D350RPLA for Canada). Low Flow refers to the air velocity rating of 100 to 4,000 feet per minute (0.5 to 20.32 m/sec.)

H3501 - An addressable detector using a thermistor sensing circuit for fast response. H350R incorporates a thermal rate of rise of 15°F (9.4°C)/minute.

H3551 - An addressable 135° fixed temperature heat detector using a thermistor sensing circuit for fast response. H355R incorporates a thermal rate of rise of 15° F (9.4° C)/minute.

H355HT1 - An addressable 190° fixed temperature heat detector using a thermistor sensing circuit for fast response.

SD350-An addressable photoelectric smoke detector which provides smokesensing utilizing optical sense technology. The SD350T includes a 135° F fixed thermal sensor.

SD355 - An addressable photoelectric smoke detector which provices smoke sensing utilizing optical sense technology. The SD355T includes a 135° F fixed thermal sensor.

BEAM355 - An addressable long range projected beam smoke detector designed to provide open area protection. The BEAM355S has an integral sensitivity test feature that consists of a test filter attached to a servomotor inside the detector optics.

1Addressable Heat Detectors are not compatible with the MS-9200(E).

The SLC Wiring Manual PN 51309:K 2/14/08

11

Introduction

SLC Performance

Manual Pull Station

The BG-12LX is a dual-action pull station that, when activated, provides an addressable identification and its location to the control panel. An addressable monitor module is mounted inside the pull station to facilitate servicing and replacement.

300 Series Addressable Devices

Fire•Lite’s 300 series of addressable devices are fully compatible with the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600, MS-9600LS(C/E), MS-9600UDLS/E and MS-9050UD FACPs. The devices must be configured for CLIP (Classic Loop Interface Protocol) Mode operation. The address of 300 series devices cannot be set above 99. Compatible devices include:

SD300 Photo

• M300 Monitor Module

SD300T Photo w/Thermal

• M301 Mini Monitor Module

CP300 Ionization

• M302 2-wire Monitor Module

BG-10LX Pull Station

• C304 Control/Relay Module

SLC Performance

SLC performance depends on the type of circuit (Style 4, Style 6, or Style 7) and the components on the circuit.

Note: SLC operation meeting Style 7 requirements isolates each device on the SLC from faults that may occur within other areas of the SLC.

Wiring style requirements are determined by national and local codes. Consult with the Authority Having Jurisdiction before wiring the SLC. The table below (derived from NFPA 72-1999) lists the trouble conditions that result when a fault exists on an SLC.

Type of Fault

Style 4

Style 6

Style 7

 

 

 

 

Single Open

Trouble

Alarm, Trouble

Alarm, Trouble

 

 

 

 

Single Ground

Alarm, Trouble

Alarm, Trouble

Alarm, Trouble

 

(ground)

(ground)

(ground)

 

 

 

 

Short

Trouble

Trouble

Alarm, Trouble

 

 

 

 

Short and open

Trouble

Trouble

Trouble

 

 

 

 

Short and ground

Trouble

Trouble

Alarm, Trouble

 

 

 

 

Open and ground

Trouble

Alarm, Trouble

Alarm, Trouble

 

 

 

 

Communications

Trouble

Trouble

Trouble

loss

• Trouble - The control panel will indicate a trouble condition for this type of fault.

• Alarm - The control panel must be able to process an alarm input signal in the presence of this type of fault.

Table 2 SLC Performance

Surge Suppression

One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. For detailed information refer to "Appendix B: Surge Suppression" on page 55.

12

The SLC Wiring Manual PN 51309:K 2/14/08

Wire Sizing

Wiring Requirements

Wiring Requirements

Wire Sizing

The SLC requires use of a specific wire type, depending on the mode of operation, to ensure proper circuit functioning. Wire size should be no smaller than 18 AWG (0.75 mm2) and no larger than 12 AWG (3.25 mm2) wire. The wire size depends on the length of the SLC circuit. It is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical interference.

CLIP (Classic Loop Interface Protocol) Mode

All addressable FACPs can operated in CLIP (Classic Loop Interface Protocol) mode. It is recommended that all SLC wiring be twisted-pair and shielded when operating in CLIP mode to reduce the effects of electrical interference. Use the table below to determine the specific wiring requirements for the SLC.

Wire Requirements

Distance in Feet (meters)

Wire Size

Wire Type

 

 

 

 

 

10,000 feet (3,048 m)

12 AWG (3.1 mm2)

Belden 9583, Genesis 4410,

 

 

 

Signal 98230, WPW D999

 

 

 

 

 

8,000 feet (2,438 m)

14 AWG (2.0 mm2)

Belden 9581, Genesis 4408,

 

 

 

Signal 98430, WPW D995

 

 

 

 

Twisted-pair, shielded

4,875 feet (1,486 m)

16 AWG (1.3 mm2)

Belden 9575, Genesis 4406,

 

 

& 4606, Signal 98630, WPW

 

 

 

 

 

 

D991

 

 

 

 

 

3,225 feet (983 m)

18 AWG (0.75 mm2)

Belden 9574, Genesis 4402 &

 

 

 

4602, Signal 98300, WPW

 

 

 

D975

 

 

 

 

 

MS-9200 = 1,000 feet (305 m)

 

 

 

 

 

 

Untwisted, unshielded

MS-9600, MS-9600LS(C) &

 

 

MS-9600UDLS = 3,000 feet (914 m)

 

 

wire, inside conduit or

12 to 18 AWG

 

 

 

MS-9200UD & MS-9200UDLS =

 

not in conduit

 

 

3,000 feet (914 m)

 

 

 

 

 

 

 

 

 

 

MS-9050UD = 3,000 feet (914 m)

 

 

 

 

 

 

Table 3 SLC Wiring Requirements in CLIP Mode

LiteSpeed Mode

The MS-9200UDLS, MS-9600LS(C) and MS-9600UDLS SLC can be programmed to operate in LiteSpeed mode for a quicker device response time. While shielded wire is not required, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical interference. Use the following table to determine the specific wiring requirements for the SLC.

Wire Requirements

Distance in Feet (meters)

Wire Size

Wire Type

 

 

 

 

 

10,000 feet (3,048 m)

12 AWG (3.1 mm2)

Belden 5020UL & 6020UL,

 

 

 

Genesis WG-4315 & WG-4515

 

 

 

 

 

8,000 feet (2,438 m)

14 AWG (2.0 mm2)

Belden 5120UL & 6120UL,

Twisted-pair,

 

 

Genesis WG-4313 & WG-4513

unshielded

4,875 feet (1,486 m)

16 AWG (1.3 mm2)

Belden 5220UL & 6220UL,

 

 

 

Genesis WG-4311 & WG-4511

 

 

 

 

 

3,225 feet (983 m)

18 AWG (0.75 mm2)

Belden 5320UL & 6320UL,

 

 

 

Genesis WG-4306 & WG-4506

 

 

 

 

Table 4 SLC Wiring Requirements in LiteSpeed Mode

The SLC Wiring Manual PN 51309:K 2/14/08

13

Wiring Requirements

Measuring Resistance & Length

Measuring Resistance & Length

Two-Wire SLC - Style 4 (Class B)

Loop Resistance

T-tapping of the SLC wiring is permitted for 2-wire Style 4 configurations. The total DC resistance from the control panel to each branch end cannot exceed 40 ohms. Measure DC resistance as detailed and shown below:

1.With power removed, short the termination point of one branch at a time and measure the DC resistance from the beginning of the SLC to the end of that particular branch.

2.Repeat this procedure for all remaining branches in the SLC.

Short Point

SLC Out

Branch

SLC-meas1.cdr

Figure 1 Measuring DC Resistance of a Two-Wire SLC

Total Wire Length

The total wire length of all combined branches of one SLC cannot exceed the limits set forth in each system’s instruction manual. Determine the total length in each SLC by summing the wire lengths of all branches of one SLC.

In the following figure, the total length of the SLC is determined by adding the lengths of Branch A plus Branch B plus Branch C.

Branch A

Branch B

Branch C

SLC Terminal

Block

Figure 2 Measuring the Total Wire Length - Two-Wire SLC

SLC-meas2.cdr

14

The SLC Wiring Manual PN 51309:K 2/14/08

Measuring Resistance & Length

Wiring Requirements

Four-Wire SLC Style 6 & 7 (Class A)

Loop Resistance

The total DC resistance of the SLC pair cannot exceed 40 ohms. Measure DC resistance as detailed and shown below.

1.Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel.

2.Short the two leads of SLC channel A (Return).

3.Measure the resistance across the SLC channel B (Out) leads.

SLC Out

Short Point

SLC Return

SLC-meas3.cdr

Figure 3 Measuring DC Resistance of a Four-Wire SLC

Total Wire Length

The total wire length in a four-wire SLC cannot exceed the limits set forth in each system’s instruction manual. The figure below identifies the output and return loops from SLC terminal on the control panel:

SLC channel B

SLC channel A

(output loop)

(return loop)

SLC Terminal

 

 

 

 

 

 

B+ B– A– A+

Block

 

 

 

 

 

 

 

SLC-meas4.cdr

Figure 4 Measuring the Wire Length – Four-Wire SLC

The SLC Wiring Manual PN 51309:K 2/14/08

15

Wiring Requirements

Shield Wire Termination

Shield Wire Termination

The drawing below shows the method of proper termination of the shield.

Connect the metal conduit to the cabinet by using the proper connector. Feed the shielded wire through the conduit, into the control box. The shield drain wire must be connected to the “shield” terminal on the SLC terminal block.

Note: Use of good wiring practice consistent with local electrical codes is expected.

CAUTION: Do not let the shield drain wire or the shield foil touch the system cabinet or be connected to earth ground at any point.

MS-9600

MS-9600LS

MS-9600LSC

MS-9600UDLS

MS-9200UD

MS-9200UDLS

MS-9050UD MS-9200

Shield Drain Wire

Cabinet

Shield Foil

Conduit

SLC-shieldterm.cdr

Figure 5 Shield Termination

16

The SLC Wiring Manual PN 51309:K 2/14/08

Control Panel Terminal Blocks

The terminal blocks on the control panel circuit board that concern the SLC circuit are described below. For more information on this subject refer to the control panel’s Instruction Manual.

MS-9200

TB4 provides three types of 24 VDC power; Unregulated, Nonresettable and Resettable.

TB6 provides connections for the SLC wiring.

Unregulated Power

Nonresettable Power

 

Resettable Power

Connections for wire shield

 

SHIELD SLC

TB4

TB6

SLC Out

SLC 9200tb.cdr-SLC

SLC

Return

Figure 6 MS-9200 Terminal Blocks

MS-9600, MS-9600LS, MS-9600LSC & MS-9600UDLS

TB3 provides two types of 24 VDC power; Nonresettable and Resettable.

TB8 provides connections for the SLC wiring.

 

 

 

 

 

 

Resettable Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nonresettable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB3

 

 

 

 

 

 

 

 

 

 

 

 

 

TB8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLC Out

Connections for wire shield

SLC SLC SLC SLC SHIELD

SLC-9600tb.cdr

SLC Return

Figure 7 MS-9600 Series Terminal Blocks

The SLC Wiring Manual PN 51309:K 2/14/08

17

Wiring Requirements

Control Panel Terminal Blocks

MS-9200UD & MS-9200UDLS

TB1 provides two types of 24 VDC power; Nonresettable and Resettable. TB10 provides connections for the SLC wiring.

 

 

Nonresettable Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Resettable

Connections for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

wire shield

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB1

 

 

 

TB10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLC Return

 

SLC Out

SLC Out

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLC-9200udtb.cdr

Figure 8 MS-9200UD & MS-9200UDLS Terminal Blocks

MS-9050UD

24 VDC power may be supplied by a remote power supply such as the Fire-Lite FCPS-24FS6/8.

TB2 provides connections for the SLC wiring.

Connections for wire shield

SLC-9050udtb.cdr

SLC Return

SLC Out

Figure 9 MS-9050UD Terminal Block

18

The SLC Wiring Manual PN 51309:K 2/14/08

Non-Isolated Circuits

Overview

This chapter concerns itself with the two styles of circuits that do not require isolation devices:

NFPA Style 4

NFPA Style 6

NFPA Style 4 SLC

NFPA Style 4 requirements can be met by using the diagram below.

• T-tapping of the SLC wiring is allowed for Style 4 configuration.

B+ B–

Control Panel

SLC

Two-wire Addressable Detector

Addressable Module

T-tapped Circuits

SLC-style4.cdr

Figure 10 Basic NFPA Style 4 SLC

The SLC Wiring Manual PN 51309:K 2/14/08

19

Non-Isolated Circuits

NFPA Style 6 SLC

NFPA Style 6 SLC

NFPA Style 6 requirements can be met by using the diagram below.

• T-tapping of the SLC wiring is NOT allowed for Style 6 configuration.

Two-wire Addressable Detector

SLC Out

Addressable Module

SLC Return

B+ B– A– A+

Control Panel

SLC

Figure 11 Basic NFPA Style 6 SLC

SLC-style6.cdr

20

The SLC Wiring Manual PN 51309:K 2/14/08

Loading...
+ 44 hidden pages