Fire-Lite FCPS User Manual

0 (0)

Field Charger/Power Supply

FCPS-24FS6 & FCPS-24FS8 FCPS-24FS6E & FCPS-24FS8E

FCPS-24FS6C & FCPS-24FS8C

Installation Manual

Document 51883-L8 J1

8/30/13 Rev:

P/N 51883-L8:J1

ECN 13-201

Fire Alarm & Emergency Communication System Limitations

While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!

An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notification capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.

An emergency communication system—typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice communication, and other various interoperable communication methods—can broadcast a mass notification message.

Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.

The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. This document can be found at http://www.systemsensor.com/appguides/. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:

Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a firstfloor or basement fire.

Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:

Barriers such as closed or partially closed doors, walls, chimneys, even wet or humid areas may inhibit particle or smoke flow.

Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.

Smoke particles may be blown away from detectors by air outlets, such as air conditioning vents.

Smoke particles may be drawn into air returns before reaching the detector.

The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.

Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion- izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type

of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.

Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).

Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.

IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, compromising its ability to report a fire.

Audible warning devices such as bells, horns, strobes, speakers and displays may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol, or medication. Please note that:

An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.

Voice messaging systems must be designed to meet intelligibility requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).

Language and instructional requirements must be clearly disseminated on any local displays.

Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.

Studies have shown that certain people, even when they hear a fire alarm signal, do not respond to or comprehend the meaning of the signal. Audible devices, such as horns and bells, can have different tonal patterns and frequencies. It is the property owner's responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.

In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.

A life safety system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.

Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.

Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.

The most common cause of life safety system malfunction is inadequate maintenance. To keep the entire life safety system

2

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

Installation Precautions

Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.

CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.

This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity . However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.

Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.

Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.

Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.

Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.

This system contains static-sensitive components.

Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.

Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.

Precau-D1-9-2005

FCC Warning

WARNING: This equipment generates, uses, and can

Canadian Requirements

radiate radio frequency energy and if not installed and

This digital apparatus does not exceed the Class A limits

used in accordance with the instruction manual may

for radiation noise emissions from digital apparatus set

cause interference to radio communications. It has been

out in the Radio Interference Regulations of the Cana-

tested and found to comply with the limits for class A

dian Department of Communications.

computing devices pursuant to Subpart B of Part 15 of

Le present appareil numerique n'emet pas de bruits radi-

FCC Rules, which is designed to provide reasonable

protection against such interference when devices are

oelectriques depassant les limites applicables aux appa-

operated in a commercial environment. Operation of this

reils numeriques de la classe A prescrites dans le

equipment in a residential area is likely to cause interfer-

Reglement sur le brouillage radioelectrique edicte par le

ence, in which case the user will be required to correct

ministere des Communications du Canada.

the interference at his or her own expense.

 

LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.

©2013 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

3

Software Downloads

In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.

Documentation Feedback

Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.

Please include the following information:

•Product name and version number (if applicable) •Printed manual or online Help

•Topic Title (for online Help) •Page number (for printed manual)

•Brief description of content you think should be improved or corrected •Your suggestion for how to correct/improve documentation

Send email messages to:

FireSystems.TechPubs@honeywell.com

Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.

4

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

Table of Contents

 

Section 1: System Overview....................................................................................................

8

1.1: General...........................................................................................................................................................

8

1.2: Features..........................................................................................................................................................

8

1.3: Start-up Procedure .........................................................................................................................................

9

1.4: Jumpers ........................................................................................................................................................

10

1.4.1: Jumper JP1 - Ground Fault Detection ...............................................................................................

10

1.4.2: Jumpers JP2 and JP3: Coded/Noncoded Input Selection ..................................................................

10

1.5: LED Indicators.............................................................................................................................................

10

1.6: Specifications...............................................................................................................................................

10

1.7: General.........................................................................................................................................................

12

Section 2: Installation.............................................................................................................

14

2.1: Backbox Mounting ......................................................................................................................................

14

2.2: NAC Circuit Wiring.....................................................................................................................................

16

2.2.1: Style Y (Class B) ...............................................................................................................................

16

2.2.2: ZNAC-4 Class A Option Module......................................................................................................

16

2.3: Addressable Module Mounting ...................................................................................................................

17

2.4: NEC Power-limited (Class 2) Wiring Requirements...................................................................................

18

Section 3: Programming Options..........................................................................................

19

3.1: DIP Switch Settings.....................................................................................................................................

20

3.2: Programmable Features Description............................................................................................................

21

3.2.1: Synchronization Type Selection........................................................................................................

21

Maximum Number of Strobes for Synchronization .............................................................................

21

3.2.2: Synchronization Mode - Master/Slave ..............................................................................................

21

3.2.3: AC Fail Delay/Aux. Trouble Relay Function....................................................................................

22

3.2.4: Input/Output Function .......................................................................................................................

22

Auxiliary Power Control ......................................................................................................................

23

3.2.5: Charger Enable/Disable.....................................................................................................................

23

3.2.6: Door Closers......................................................................................................................................

23

Section 4: Trouble Supervision .............................................................................................

25

4.1: Supervision via FACP Notification Appliance Circuit................................................................................

25

4.1.1: Supervision of FACP to FCPS wiring...............................................................................................

25

4.1.2: Supervision of FCPS-24FS Faults.....................................................................................................

25

4.1.3: Aux. Trouble Relay/AC Fail Relay ...................................................................................................

25

4.2: AC Loss Reporting Delay............................................................................................................................

26

Section 5: Applications ..........................................................................................................

27

5.1: Controlling Four NACs With One Input and Selective Silence ..................................................................

27

5.2: Controlling Three NACs and One Door Holder With One Input................................................................

29

5.3: Split Temporal Mode of Operation..............................................................................................................

31

5.4: Remote Supply With Resettable and Nonresettable Power.........................................................................

33

5.5: Master FACP with Slave FCPS-24FS Power Supply..................................................................................

35

5.6: Master FCPS-24FS Power Supply Connected to FACP..............................................................................

36

5.7: Canadian Applications.................................................................................................................................

36

Section 6: Power Supply Requirements...............................................................................

38

6.1: Overview......................................................................................................................................................

38

6.2: Calculating the AC Branch Circuit..............................................................................................................

38

6.3: Calculating the System Current Draw .........................................................................................................

39

6.3.1: Overview ...........................................................................................................................................

39

6.3.2: How to Calculate System Current Draw ...........................................................................................

39

6.4: Calculating the Battery Size ........................................................................................................................

41

6.4.1: NFPA Battery Requirements.............................................................................................................

41

6.4.2: Selecting and Locating Batteries .......................................................................................................

41

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

5

Table of Contents

 

Appendix A: Wire Requirements...........................................................................................

43

Index ........................................................................................................................................

44

6

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:

Underwriters Laboratories Standards

NFPA 72 National Fire Alarm Code

Before proceeding, the installer should be familiar with the following documents.

NFPA Standards

NFPA 72 National Fire Alarm Code

NFPA 70 National Electrical Code

Underwriters Laboratories Documents:

UL 464 Audible Signaling Appliances

UL 864 Standard for Control Units for Fire Protective Signaling Systems

UL 1638 Visual Signaling Appliances

UL 1971 Signaling Devices for Hearing Impaired

UL 2572 Standard for Mass Notification Systems

NOTE: Mass Notification is not listed in Canada. Any part number that has a suffix of “C” is a Canadian part number and will not have Mass Notification.

CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems

CAN/ULC-S527-99 Standard for Control Units for Fire Alarm Systems

Other:

NEC Article 250 Grounding

NEC Article 300 Wiring Methods

NEC Article 760 Fire Protective Signaling Systems

Applicable Local and State Building Codes

Requirements of the Local Authority Having Jurisdiction (LAHJ)

Canadian Electrical Code, Part 1

Other Fire•Lite Documents:

 

Device Compatibility Document

Document #15384

This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

7

Section 1: System Overview

The FCPS-24FS6 is a 6 amp power supply and the FCPS-24FS8 is an 8 amp power supply. Each FCPS-24FS power supply is a compact, cost-effective, remote power supply and battery charger which provides ADA compatible strobe synchronization. Each remote power supply consists of a filtered 24 VDC output that can be configured to drive four Style Y (Class B) NACs (Notification Appliance Circuits). The four circuits can be configured for Style Z (Class A) with the optional ZNAC-4 Class A converter module. Alternatively, the four output circuits may be configured as 24 VDC resettable or nonresettable power outputs. The input circuits, which control the power supply operation, are triggered by the reverse polarity of an NAC or by a 12 VDC or 24 VDC power source. The power supplies are compatible with 12 VDC and 24 VDC control panels.

The FCPS-24FS6E and FCPS-24FS8E offer the same features as the FCPS-24FS6 and FCPS24FS8 respectively but allow connection to 220/240 VAC. Unless otherwise specified, the information in this manual applies to both the 110/120 VAC versions and the 220/240 VAC versions of the power supplies.

The FCPS-24FS6C and FCPS-24FS8C are the Canadian versions which offer the same features as the FCPS-24FS6 and FCPS-24FS8 respectively. Unless otherwise specified, the information in this manual also applies to the Canadian versions of the power supplies.

1.1 General

The FCPS-24FS power supplies can be used as remotely mounted power supplies and battery chargers to power four noncoded or coded NACs. The Main FACP (Fire Alarm Control Panel) NAC(s) is connected to the remote power supply input circuit(s). When the control input circuit activates due to reverse polarity of the NAC from the FACP, the power supply will activate its Notification Appliance Circuits.

During the inactive or nonalarm state, the power supply supervises its NAC field wiring for short and open conditions. AC fail, battery, charger and ground fault troubles will also be monitored by the power supply. If an NAC or power supply fault is detected, the power supply Normally-Closed Trouble contact will open.

If an alarm condition occurs and the NAC is activated, the supervision is disabled and the Notification Appliance Circuit is no longer supervised (except for shorts). Supervision of other power supply faults such as low battery, AC loss, ground fault and battery charger trouble will continue and may be monitored via the Trouble relay contacts.

1.2Features

Self-contained in a lockable cabinet

24 VDC remote power supply

Outputs are completely power-limited (Class 2)

Two optically-isolated input/control circuits, compatible with 12 VDC and 24 VDC control panel NACs

Four output circuits:

Fully filtered power

Four 24 VDC Style Y (Class B) NACs

Optional ZNAC-4 Class A converter module for conversion to Style Z NACs

Alternatively, all four circuits may be configured as 24 VDC special application power outputs

Output circuits may be configured as resettable or nonresettable

NAC Trouble LED - blinks to indicate the number of the circuit in trouble

8

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

Start-up Procedure

System Overview

 

 

Maximum current available for any one output circuit: 3.0 amps, special application, 300mA regulated

Maximum total continuous current available:

4.0 amps for FCPS-24FS6

6.0 amps for FCPS-24FS8

Maximum total short term current (one hour maximum):

6.0 amps for FCPS-24FS6

8.0 amps for FCPS-24FS8

Integral supervised battery charger for lead acid batteries only

Capable of charging 7.0 AH to 18.0 AH (Amp Hour) batteries

Fully supervised power supply, battery and NACs

Selectable Strobe Synchronization for NACs (System Sensor, Gentex and Wheelock)

Coded signal synchronization

Fixed terminal blocks for field wiring capable of accepting 12 - 22 AWG wire

Selectable Ground Fault detection by jumper JP1

Power supply trouble Form-C relay contacts (fail-safe)

Optional delay of AC loss reporting for 2 hours

Auxiliary Special Application Power Output for SLC modules (500 mA maximum) with optional reset for 4-wire smoke detectors

Mounting location for optional addressable control module

1.3Start-up Procedure

1.Configure the power supply jumpers as described in “Jumpers” on page 10.

2.Install the power supply as described in“Installation” on page 14.

3.Program the power supply as described in “Programming Options” on page 19.

4.Wire the power supply circuits, referring to the options described in“Trouble Supervision” on page 25 and the application examples in“Applications” on page 27.

5.Connect primary power source wiring while observing the following:

Make certain that the AC mains circuit breaker is off before making any wiring connections between the mains and the power supply.

Make certain primary power source is 120 VAC, 60 Hz, 3.2 amps.

Run a pair of wires (with ground conductor) from the protected premises main breaker box to TB1 of the power supply main circuit board.

Use 14 AWG (1.6 mm O.D.) or heavier gauge wire with 600V insulation.

6.Apply power to the power supply using the following procedure:

Apply AC power by turning on the AC mains circuit breaker connected to the power supply.

Connect a properly charged battery to connector JP4 on the power supply main circuit board.

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

9

System Overview

Jumpers

 

 

1.4Jumpers

!CAUTION: DISCONNECT POWER

REMOVE ALL POWER (AC & DC) BEFORE CUTTING OR MOVING ANY JUMPERS.

1.4.1 Jumper JP1 - Ground Fault Detection

The Ground Detection circuit monitors for zero impedance between the power supply and ground. Jumper JP1 is located in the top right section of the power supply circuit board. Cutting JP1 will disable ground fault detection by the power supply. This should only be done if ground faults are being monitored by a panel connected to the FCPS power supply.

1.4.2 Jumpers JP2 and JP3: Coded/Noncoded Input Selection

Jumpers JP2 and JP3 are located in the top right section of the power supply circuit board. JP2 is used for Control Input Circuit #1 and JP3 is used for Control Input Circuit #2. The position of these jumpers will depend on the type of signal being fed to the input circuits:

If the source voltage to the input circuit is a noncoded (steady voltage) input signal, the jumper for the corresponding input circuit should be in the default position which jumpers the bottom two pins (as illustrated in drawing at left).

If the source voltage to the input circuit is coded (variable voltage), the jumper for the corresponding input circuit should be moved to jumper the top two pins.

JP3 JP2

 

 

 

 

 

 

 

24s8jp3b.wmf

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

jumpers

 

 

 

 

 

Jumper positions shown for noncoded (steady) source voltage

1.5LED Indicators

AC Power on (green) LED - indicates AC power is present

Ground Fault (yellow) LED - indicates a ground fault condition (zero impedance to ground)

Battery Trouble (yellow) LED - indicates low or no battery

NAC Trouble (yellow) LED - indicates a Notification Appliance Circuit trouble (blinks once for Circuit 1 trouble, twice for Circuit 2 trouble, three times for Circuit 3 trouble and four times for Circuit 4 trouble. Note that multiple circuits in trouble will cause the LED to blink the number of the circuit with the highest number)

ChargerTrouble/AC Loss (yellow) LED - indicates a charger fault or loss of AC power:

If AC is applied to the power supply without a battery connected, both the Charger Trouble/AC Loss LED and Battery Trouble LED will turn on simultaneously, indicating that a battery is not connected.

When a battery is connected and the power supply is in Normal Mode, if the battery voltage drops too low or the battery is disconnected, only the Battery Trouble LED will turn on.

When a battery is connected and the charger develops a problem, only the Charger Trouble/AC Loss LED will turn on.

1.6Specifications

Refer to Figure 1.1 on page 12 for terminal locations.

Primary AC Power - TB1

FCPS-24FS6(C) & FCPS-24FS8(C): 120 VAC, 60 Hz, 3.2 amps maximum

FCPS-24FS6E & FCPS-24FS8E: 240 VAC, 50 Hz, 1.6 amps maximum

Wire size: minimum #14 AWG with 600V insulation

10

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

Specifications

System Overview

 

 

Control Input Circuits - TB4, Terminals 3 (+) & 4 (-) and 7 (+) & 8 (-)

Trigger Input Voltage: 9 to 32 VDC

Input Current Draw in Alarm Polarity:

16 to 32 volts, 2.0 mA maximum per input

9 to 16 volts, 1.0 mA maximum per input

NAC/Output Circuits - TB2, Terminals 1 (+) & 2 (-), 3 (+) & 4 (-), 5 (+) & 6 (-) and 7 (+) & 8 (-) alarm polarity

Supervised, and power-limited (Class 2)

Voltage Rating: 24 VDC filtered

Current:

Maximum for any one circuit - 3.0 amps, special application, 300mA, regulated

Maximum total continuous current for all output: FCPS-24FS6 - 4.0 amps

FCPS-24FS8 - 6.0 amps

Maximum total short term current (one hour maximum) for all outputs: FCPS-24FS6 - 6.0 amps

FCPS-24FS8 - 8.0 amps

Output Circuit Types:

Four Style Y NACs (require 4.7 KΩ End-of-Line Resistors) or Style Z NACs using the optional ZNAC-4 Class A converter module

OR

Four resettable or nonresettable 24 VDC power outputs

Refer to the Fire•Lite Device Compatibility Document #15384 for listed compatible devices.

For wiring requirements, refer to “Wire Requirements” on page 43.

Trouble Relay Contact Rating - TB5

Fail-safe Form-C relay (normally energized, transfers with loss of power)

5.0 amps @ 24 VDC or 5.0 amps @ 30 VAC

Secondary Power (battery) Charging Circuit - JP4

Supervised, nonpower-limited

Supports lead acid type batteries only

Float Charge Voltage: 27.6 VDC

Maximum Charge Current: 1.5 A

Battery fuse (F1) 15A, 32V (Canadian version is nonreplaceable 12A, 32V)

Maximum Battery Capacity: 18.0 AH

Minimum Battery Capacity: 7.0 AH

Power supply draws maximum standby current of 65 mA from batteries

Auxiliary Special Application Power Output - TB4 Terminals 9 (+) & 10 (-)

Special application power

Power-limited (Class 2), nonsupervised

Voltage Rating: 24 VDC

Current:

– 170 mA maximum with internal 7.0 Amp Hour batteries

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

11

Fire-Lite FCPS User Manual

System Overview

General

 

 

– 500 mA maximum with external 18.0 Amp Hour batteries

Power-limited (Class 2), Supervised,

Special Application or regulated

Nonpower-limited

To Transformer #1

To Transformer #2

Supervised,

Nonpower-limited

Earth

AC Neutral

AC Hot

EARTH NEUT HOT

TB1

J2

2 TRANSFORMER

J1

1 TRANSFORMER

F1

 

 

 

 

-

+

AC

GND

NAC AC/

 

JP4

FLT

BATT TRBL CHGR

 

 

 

 

BATTERY

 

 

 

 

JP4 Supervised

 

 

 

 

+ Battery

 

 

 

 

- Battery

 

 

 

 

18 AH, 24 VDC

 

 

 

F1

Nonpower-

 

 

 

limited

 

 

 

Battery Fuse 15A, 32V

(Canadian version is nonreplaceable

12 A, 32V)

NAC/Out 1 +

 

 

 

 

 

 

 

 

 

 

 

NAC/Out 1 -

 

 

 

 

 

 

 

 

 

 

Trouble Relay

NAC/Out 2 +

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Form-C Fail-safe

NAC/Out 2 -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nonsupervised

NAC/Out 3 +

 

 

 

 

 

 

 

 

 

 

(shown energized)

NAC/Out 3 -

 

 

 

 

 

 

 

 

 

 

Normally Open

NAC/Out 4 +

 

 

 

 

 

 

 

 

 

 

Normally Closed

NAC/Out 4 -

 

 

 

 

 

 

 

 

 

 

Common

OUT4

 

OUT3

OUT2

OUT1

 

 

 

 

- NAC4 +

- NAC3 +

- NAC2 +

- NAC1 + TB2

AUX TBL

 

 

 

 

 

 

 

 

 

NO

NC

COM

TB5

 

 

 

 

 

 

 

 

 

 

 

8

7

6

5

4

3

2

1

 

 

 

JP1 Ground Fault

 

 

 

 

 

 

 

 

3

2

1

 

 

 

 

 

 

 

 

Detection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(cut to disable)

 

 

 

JP1

J3

 

 

 

J3

 

 

 

 

 

ZNAC-4 Connector

 

 

 

JP2

 

 

 

JP3

JP2 & JP3

 

 

 

 

Coded/Noncoded

 

 

 

 

 

 

 

 

 

Input Selection

 

 

Auxiliary Output

AUX -

10

- Aux. Common

 

 

500 mA Special

 

 

 

 

Application Power*

AUX +

9

+ Aux. 24 VDC*

 

 

 

 

 

 

 

IN2-

8

- Control Input 2

 

 

 

 

7

 

 

 

IN2+

+ Control Input 2

 

 

 

 

6

 

 

 

OUT1-

- Out Common

 

 

 

 

5

 

 

 

OUT1+

+ Out/Trouble Contact

 

 

 

4

 

 

IN1-

- Control Input 1

 

 

 

 

3

 

 

 

IN1+

+ Control Input 1

 

 

 

 

2

24fs8brd.wmf

 

 

SYNC IN -

- Sync Input

 

 

 

 

O N

SYNC IN +

1

+ Sync Input

SW1

 

 

 

1 2 3 4 5 6 7 8

 

TB4

 

 

 

SW1

*Note: Auxiliary Power

LEDs

Output is power-limited

Programming

Charger Trouble/AC Loss (yellow)

DIP Switches

(Class 2) but not

supervised

NAC Trouble (yellow)

(change switch

 

settings only

 

Battery Trouble (yellow)

 

when all power

 

Ground Fault (yellow)

(AC & DC) is

 

AC Power (green)

removed)

 

 

 

Figure 1.1 FCPS-24FS Board Layout

1.7 General

The FCPS may be used in a number of different applications. It may be used as a remotelymounted power supply and battery charger where it can provide up to four coded or noncoded, synchronized or nonsynchronized NACs (Notification Appliance Circuits). Alternatively, output #4

12

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

General

System Overview

 

 

can be used as a door holder circuit which will provide a steady 24 VDC output until an alarm condition or AC fail condition causes it to drop to 0 VDC following a 10 second delay. All four outputs can also provide power.

Note: All NAC

Style Y NAC

 

 

 

 

 

or Door

 

 

 

 

 

outputs can be

 

 

 

 

 

Holder Power

Style Y NAC

Style Y NAC

Style Y NAC

FCPS Trouble

converted to Style Z

Output #4

Output #3

Output #2

Output #1

Contact Output

with a ZNAC-4

option module

 

 

 

 

 

 

 

 

 

 

 

 

24 VDC Specific

 

 

 

 

 

 

AC Power

 

 

 

 

 

Application Power

 

 

Input/Output Functions are Programmable

 

 

 

 

by SW1 DIP Switch Settings

 

NAC Control

 

 

 

 

 

 

Input #2

 

 

 

 

 

 

(from FACP)

 

 

 

 

 

 

NAC Control

 

 

 

 

 

 

Input #1

 

 

 

 

 

 

(from FACP)

 

 

 

 

 

 

Sync. Input

 

 

 

 

 

 

24fsblok.wmf

 

 

 

 

 

 

 

Battery Charger

Figure 1.2 Simplified FCPS Block Diagram

One possible application for the FCPS remote power supply utilizes the NAC repeater feature. In this application, one or two NACs are connected from the main FACP to the remote power supply control input circuits. When the control input circuits are activated by the reverse polarity of the NACs, the power supply will activate its corresponding output circuits as programmed by SW1 DIP switch configuration (refer to Table 3.1 on page 20).

During the inactive state, the remote power supply supervises its NAC field wiring for short and open conditions. If a fault is detected, the power supply will enter a trouble condition and illuminate the NAC Trouble LED. When the NACs are activated, the supervision is disabled and the circuits are no longer supervised (except for short circuit conditions). Supervision of other power supply faults such as low battery, battery charger trouble, ground fault and AC loss will continue and may be monitored via the power supply trouble relay.

If an application requires that all four outputs activate at the same time, only one NAC is required from the FACP. For this application, the NAC is connected to control input circuit #1 and SW1 DIP switch is set for this operation.

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

13

Section 2: Installation

Carefully unpack the system and check for shipping damage. Select a location for the cabinet that is in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the power supply. Locate the top of the cabinet approximately five feet above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed and determine the appropriate knockouts. All wiring must be in accordance with the National and/or Local codes for fire alarm systems and power supplies.

2.1Backbox Mounting

!CAUTION: STATIC SENSITIVE COMPONENTS

THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS. ALWAYS GROUND YOURSELF WITH A PROPER WRIST STRAP BEFORE HANDLING ANY BOARDS SO THAT STATIC CHARGES ARE REMOVED FROM THE BODY. USE STATIC SUPPRESSIVE PACKAGING TO PROTECT ELECTRONIC ASSEMBLIES.

1.Remove the PC board and transformers from the backbox before installing backbox. Set the board and transformers aside in a safe, clean place. Avoid static discharge which may damage static sensitive components on the board.

2.Mark and predrill holes for the top two keyhole mounting bolts.

3.Install two upper fasteners in the wall with the screw heads protruding approximately ¼”.

4.Using the upper keyholes, mount the backbox over the two screws.

5.Mark the lower two holes, remove the backbox from the wall and drill the mounting holes.

6.Mount the backbox, install the remaining fasteners and tighten all screws.

7.When the location is dry and free of construction dust, reinstall the PC board and transformers and continue with the installation.

8.IMPORTANT! Make certain to connect the supplied grounding strap between the Earth terminal on TB1 (AC Terminal Block) of the main circuit board and the chassis ground stud as illustrated in Figure 2.1:

Earth Terminal on TB1 (AC Terminal Block)

Mounting Plate

Grounding Strap

Ground Stud

Backbox

Figure 2.1 Grounding Strap

24fsgrnd.wmf

14

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

Backbox Mounting

Installation

 

 

 

 

 

 

Top

2.875” (7.3 cm)

 

 

 

 

 

 

 

Depth = 3.050”

 

 

Backbox = 14.5”

 

(7.75 cm)

 

 

(36.8 cm)

 

 

0.75”

 

 

 

(1.9 cm)

 

2.7”

 

 

 

 

 

 

 

9.1” (23.1 cm)

(6.86cm)

 

 

 

 

 

 

 

Ground Stud

 

 

 

10.625”

 

 

 

Height=15.00”

(26.99 cm)

Mounting Plate Pem Studs

 

(38.10 cm)

 

 

 

 

 

 

Backbox Mounting Holes

 

fcpscabb.wmf

 

 

 

 

 

Bottom

 

 

1.125” (2.868 cm)

Figure 2.2 Backbox Mounting Dimensions

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

15

Loading...
+ 33 hidden pages