Fire-Lite MS-10UD User Manual

5 (1)

Fire Alarm Control Panels

MS-5UD Series

MS-10UD Series

Manual

Document 52626

Rev: C4

3/7/2014

P/N 52626:C4

ECN 14-167

Fire Alarm & Emergency Communication System Limitations

While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!

An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notification capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.

An emergency communication system—typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice communication, and other various interoperable communication meth- ods—can broadcast a mass notification message. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.

The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. This document can be found at http:// www.systemsensor.com/appguides/. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:

Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.

Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:

Barriers such as closed or partially closed doors, walls, chimneys, even wet or humid areas may inhibit particle or smoke flow.

Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.

Smoke particles may be blown away from detectors by air outlets, such as air conditioning vents.

Smoke particles may be drawn into air returns before reaching the detector.

The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.

Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.

Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions

(caused by escaping gas, improper storage of flammable materials, etc.).

Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.

IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, compromising its ability to report a fire.

Audible warning devices such as bells, horns, strobes, speakers and displays may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol, or medication. Please note that:

An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.

Voice messaging systems must be designed to meet intelligibility requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).

Language and instructional requirements must be clearly disseminated on any local displays.

Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.

Studies have shown that certain people, even when they hear a fire alarm signal, do not respond to or comprehend the meaning of the signal. Audible devices, such as horns and bells, can have different tonal patterns and frequencies. It is the property owner's responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.

In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.

A life safety system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.

Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.

Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.

The most common cause of life safety system malfunction is inadequate maintenance. To keep the entire life safety system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt, or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional life safety system installers only. Adequate written records of all inspections should be kept.

Limit-D-1-2013

2

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Installation Precautions

Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.

CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.

This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.

Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.

Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.

Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.

Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.

This system contains static-sensitive components.

Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.

Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.

Precau-D1-9-2005

FCC Warning

WARNING: This equipment generates, uses, and can

Canadian Requirements

radiate radio frequency energy and if not installed and

This digital apparatus does not exceed the Class A limits

used in accordance with the instruction manual may

for radiation noise emissions from digital apparatus set

cause interference to radio communications. It has been

out in the Radio Interference Regulations of the Cana-

tested and found to comply with the limits for class A

dian Department of Communications.

computing devices pursuant to Subpart B of Part 15 of

Le present appareil numerique n'emet pas de bruits radi-

FCC Rules, which is designed to provide reasonable

protection against such interference when devices are

oelectriques depassant les limites applicables aux appa-

operated in a commercial environment. Operation of this

reils numeriques de la classe A prescrites dans le

equipment in a residential area is likely to cause interfer-

Reglement sur le brouillage radioelectrique edicte par le

ence, in which case the user will be required to correct

ministere des Communications du Canada.

the interference at his or her own expense.

 

LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.

©2014 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

3

Software Downloads

In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.

Documentation Feedback

Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.

Please include the following information:

•Product name and version number (if applicable) •Printed manual or online Help

•Topic Title (for online Help) •Page number (for printed manual)

•Brief description of content you think should be improved or corrected •Your suggestion for how to correct/improve documentation

Send email messages to:

FireSystems.TechPubs@honeywell.com

Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.

4

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Table of Contents

 

Section 1: Product Description .............................................................................................

13

1.1: Product Features ..........................................................................................................................................

14

1.2: Specifications...............................................................................................................................................

15

1.3: Controls and Indicators................................................................................................................................

20

1.4: Digital Alarm Communicator/Transmitter ..................................................................................................

21

1.5: Components .................................................................................................................................................

21

1.6: Optional Modules and Accessories .............................................................................................................

21

1.7: Telephone Requirements and Warnings.......................................................................................................

23

1.7.1: Telephone Circuitry...........................................................................................................................

23

1.7.2: Digital Communicator .......................................................................................................................

23

1.7.3: Telephone Company Rights and Warnings .......................................................................................

24

1.7.4: For Canadian Applications ................................................................................................................

24

Section 2: Installation.............................................................................................................

26

2.1: Backbox Mounting ......................................................................................................................................

26

2.2: Operating Power ..........................................................................................................................................

28

2.3: Input Circuits ...............................................................................................................................................

30

2.4: Output Circuits.............................................................................................................................................

32

2.4.1: Notification Appliance Circuits.........................................................................................................

32

2.4.2: Special Application DC Power Output Connections.........................................................................

33

2.4.3: Relays - Programmable .....................................................................................................................

33

2.4.4: Remote Synchronization Output .......................................................................................................

34

2.5: Power-limited Wiring Requirements ...........................................................................................................

35

2.6: Digital Communicator .................................................................................................................................

36

2.7: Installation of Optional Modules .................................................................................................................

37

2.7.1: CAC-5X Class A Converter Module.................................................................................................

37

Installation ............................................................................................................................................

37

Wiring NACs and IDCs for Class A ....................................................................................................

38

2.7.2: 4XTMF Option Module ....................................................................................................................

39

4XTMF Transmitter Module Installation.............................................................................................

39

2.7.3: ANN-SEC Option Card.....................................................................................................................

40

2.8: ANN-BUS Devices......................................................................................................................................

41

Guidelines.............................................................................................................................................

41

2.8.1: ANN-BUS Wiring .............................................................................................................................

41

Calculating Wiring Distance for ANN-BUS Modules.........................................................................

41

Wiring Configuration ...........................................................................................................................

44

Powering ANN-BUS Devices from Auxiliary Power Supply .............................................................

45

2.8.2: ANN-BUS Device Addressing..........................................................................................................

45

2.8.3: ANN-80(C) Remote Fire Annunciator/Indicator ..............................................................................

46

Specifications .......................................................................................................................................

46

Installation ............................................................................................................................................

46

Opening/Closing Annunciator..............................................................................................................

46

Mounting ..............................................................................................................................................

47

Wiring ANN-80 to FACP.....................................................................................................................

47

2.8.4: ANN-S/PG Serial/Parallel Printer Interface Installation...................................................................

48

Specifications .......................................................................................................................................

49

PRN-6F Printer Installation..................................................................................................................

49

2.8.5: ANN-I/O LED Driver Module ..........................................................................................................

51

ANN-I/O Board Layout........................................................................................................................

51

Specifications .......................................................................................................................................

51

ANN-I/O Connection to FACP ............................................................................................................

52

ANN-I/O Module LED Wiring ............................................................................................................

52

2.8.6: ANN-LED Annunciator Module.......................................................................................................

53

Specifications .......................................................................................................................................

53

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

5

Table of Contents

 

Mounting/Installation ...........................................................................................................................

54

ANN-LED Board Layout and Connection to FACP ............................................................................

54

2.8.7: ANN-RLY Relay Module..................................................................................................................

54

Specifications........................................................................................................................................

54

Mounting/Installation ...........................................................................................................................

55

ANN-RLY Board Layout and Connection to FACP............................................................................

56

2.9: ANN-BUS Audio Panel...............................................................................................................................

56

Section 3: Programming ........................................................................................................

58

3.1: User Programming .......................................................................................................................................

58

3.2: Initial Power-up............................................................................................................................................

59

3.3: Programming Screens Description ..............................................................................................................

59

3.4: Programming and Passwords.......................................................................................................................

60

3.5: Master Programming Level .........................................................................................................................

61

3.5.1: Input Zones ........................................................................................................................................

61

3.5.2: NAC (Notification Appliance Circuit) ..............................................................................................

66

Enabled .................................................................................................................................................

66

NAC Coding .........................................................................................................................................

67

Silence...................................................................................................................................................

68

Auto Silence..........................................................................................................................................

69

Silence Inhibited ...................................................................................................................................

69

3.5.3: Relays ................................................................................................................................................

69

3.5.4: System Setup .....................................................................................................................................

69

Timers...................................................................................................................................................

70

Banner...................................................................................................................................................

72

Time-Date .............................................................................................................................................

72

Trouble Reminder.................................................................................................................................

74

Canadian Option ...................................................................................................................................

74

Charger Disable ....................................................................................................................................

74

3.5.5: Option Modules ................................................................................................................................

75

ANN-BUS.............................................................................................................................................

75

ANN-RLY Options Screen...................................................................................................................

78

ANN-AUDIO Options Screen..............................................................................................................

79

ANN-SEC Enable.................................................................................................................................

79

Onboard DACT ....................................................................................................................................

79

3.5.6: History ...............................................................................................................................................

90

View Events..........................................................................................................................................

90

Erase History ........................................................................................................................................

91

3.5.7: Walktest .............................................................................................................................................

91

3.5.8: Clear Program....................................................................................................................................

92

Printer/PC .............................................................................................................................................

92

3.5.9: Password Change...............................................................................................................................

92

3.6: Maintenance Programming Level................................................................................................................

93

3.6.1: Input Zones - Enable/Disable ............................................................................................................

93

3.6.2: History ...............................................................................................................................................

94

3.6.3: Walktest .............................................................................................................................................

94

3.6.4: Time-Date ..........................................................................................................................................

95

Section 4: Operating Instructions .........................................................................................

96

4.1: Panel Control Buttons ..................................................................................................................................

96

4.1.1: Acknowledge/Step.............................................................................................................................

96

4.1.2: Alarm Silenced ..................................................................................................................................

96

4.1.3: Drill/Hold 2 Sec.................................................................................................................................

96

4.1.4: Reset ..................................................................................................................................................

96

4.2: LED Indicators.............................................................................................................................................

96

4.3: Normal Operation ........................................................................................................................................

97

4.4: Trouble Operation ........................................................................................................................................

97

4.5: Alarm Operation ..........................................................................................................................................

99

6

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

 

Table of Contents

4.6: Supervisory Operation .................................................................................................................................

99

4.7: Process Monitor Operation ........................................................................................................................

100

4.8: Hazard/Tornado Condition Operation .......................................................................................................

100

4.9: Medical Alert Condition Operation ...........................................................................................................

101

4.10: Disable/Enable Operation........................................................................................................................

101

4.11: Waterflow Circuits Operation ..................................................................................................................

101

4.12: Detector Functions...................................................................................................................................

102

4.13: Time Functions: Real-Time Clock...........................................................................................................

102

4.14: Coded Operation......................................................................................................................................

102

4.15: Presignal ..................................................................................................................................................

102

4.16: Positive Alarm Sequence.........................................................................................................................

103

4.17: Special System Timers.............................................................................................................................

103

4.17.1: Silence Inhibit Timer.....................................................................................................................

103

4.17.2: Autosilence Timer .........................................................................................................................

103

4.17.3: Trouble Reminder..........................................................................................................................

103

4.17.4: Waterflow Retard Timer................................................................................................................

104

4.17.5: Alarm Verification (None or One Minute)....................................................................................

104

4.18: Walktest ...................................................................................................................................................

104

4.19: Read Status ..............................................................................................................................................

105

4.19.1: Input Zones....................................................................................................................................

105

4.19.2: NAC...............................................................................................................................................

106

4.19.3: Relays ............................................................................................................................................

106

4.19.4: System Settings .............................................................................................................................

107

4.19.5: Timers............................................................................................................................................

107

4.19.6: Daylight Savings ...........................................................................................................................

107

4.19.7: History ...........................................................................................................................................

107

4.19.8: Print ...............................................................................................................................................

107

4.19.9: ANN-BUS .....................................................................................................................................

108

4.19.10: Central Station .............................................................................................................................

108

4.19.11: Phone Line...................................................................................................................................

109

4.19.12: Service Terminal..........................................................................................................................

109

Section 5: Central Station Communications ......................................................................

110

5.1: Transmittal Priorities .................................................................................................................................

111

Section 6: Local/Remote Site Upload/Download ...............................................................

113

6.1: Remote Download .....................................................................................................................................

113

6.2: Transferring a Program ..............................................................................................................................

114

6.2.1: Security Features .............................................................................................................................

114

Section 7: Power Supply Calculations................................................................................

116

7.1: Overview....................................................................................................................................................

116

7.2: Calculating the AC Branch Circuit............................................................................................................

116

7.3: Calculating the System Current Draw .......................................................................................................

117

7.3.1: Overview .........................................................................................................................................

117

7.3.2: How to Use Table 7.3 on page 118 to Calculate System Current Draw .........................................

117

7.4: Calculating the Battery Size ......................................................................................................................

119

7.4.1: NFPA Battery Requirements...........................................................................................................

119

7.4.2: Selecting and Locating Batteries .....................................................................................................

119

Appendix A: Ademco Contact ID Format Event Code Descriptions................................

120

A.1: Transmission Format Between DACT and Receiver................................................................................

120

A.2: Ademco Contact ID Typical Printout .......................................................................................................

120

Appendix B: NFPA Standard-Specific Requirements .......................................................

125

B.1: Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts....................................

130

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

7

Table of Contents

 

Appendix C: FACP with Keltron ..........................................................................................

131

Appendix D: Wire Requirements.........................................................................................

132

D.1: MS-5UD-3(E) & MS-10UD-3(E) NAC Wiring .......................................................................................

132

D.2: MS-5UD-7(C/E) & MS-10UD-7(C/E) NAC Wiring................................................................................

133

Appendix E: Default Programming .....................................................................................

134

Appendix F: Canadian Application .....................................................................................

136

F.1: ANN-LED Annunciator Installation for Canadian Applications...............................................................

136

Index ......................................................................................................................................

138

8

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:

Underwriters Laboratories/Underwriters Laboratories Canada

National Fire Protection Association

Before proceeding, the installer should be familiar with the following documents.

NFPA Standards

This Fire Alarm Control Panel complies with the following NFPA Standards:

NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module)

Underwriters Laboratories Documents for Reference:

UL 38 Manually Actuated Signaling Boxes

UL 217 Smoke Detectors, Single and Multiple Station

UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems

UL 268A Smoke Detectors for Duct Applications

UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances

UL 521 Heat Detectors for Fire Protective Signaling Systems

UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems

UL 1638 Visual Signaling Appliances

UL 1971 Signaling Devices for Hearing Impaired

UL 2017 General-Purpose Signaling Devices and Systems

CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems

CAN/ULC - S559 Standard for Equipment for Fire Signal Receiving Centers and Systems

This Class (A) digital apparatus complies with Canadian ICES-003.

Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.

Other:

Canadian Electrical Code, Part I NEC Article 250 Grounding NEC Article 300 Wiring Methods

NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes

Requirements of the Local Authority Having Jurisdiction (LAHJ)

Fire•Lite Documents

 

Fire•Lite Device Compatibility Document

Document #15384

CHG-120F Battery Charger Manual

Document #50888

CHG-75 Battery Charger Manual

Document #51315

411UD Manual

Document #50759

411UDAC Manual

Document #51073

ANN-80 Product Installation Doc.

Document #52749

ANN-(R)LED Product Installation Doc.

Document #53032

ANN-I/O Product Installation Doc.

Document #151416

ANN-RLY Product Installation Doc.

Document #53033

ANN-S/PG Product Installation Doc.

Document #151417

ACC-25/50 Series Audio Panel

Document #51889

This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

9

10

3/7/2014 52626:C4 P/N — Manual Series 10UD-MS & 5UD-MS

 

Notification Appliance Circuits (see note 1)

 

 

Special Application Power

Basic System Connections

NAC #1, #2, #3, & #4, Style Y (Class B) (Supervised, Power-

5-Zone Panel

Limited) (See Style Z illustrated near right edge of board.)

 

4.7Kohm, ½ watt End-of-Line Resistor

 

NAC #1 NAC #2

PN 71252

NAC #3 NAC #4

 

 

 

Notes:

1.MS-5UD-3(E) = 2.5 amps max. per NAC MS-5UD-7(C/E)= 3 amps max. per NAC

2.Remote Sync Output is required only for the MS-5UD-3(E): Refer to “Remote Synchronization Output” on page 34.

3.18 Amp Hour max. for MS-5UD-3(E)

26 Amp Hour max. for MS-5UD-7(E) 18 Amp Hour max. for MS-5UD-7C

Important! Removing Ground Fault Disable Jumper JP43 voids UL/NFPA Style/Class indentifications for circuits. Remove jumper JP43 only with the approval of the local AHJ (Authority Having Jurisdiction).

Special Application

DC Power Outputs 24 VDC)

Nonsupervised, power-limited circuits Supervise with a power supervision relay EOLR-1

Resettable Power - 24 VDC filtered,

 

 

 

 

 

power-limited (0.5 amp maximum) to

4

 

 

 

smoke detectors (IDC). Supervision

{

3

 

 

 

required.

 

 

 

 

 

 

 

 

 

 

Nonresettable or Resettable Power {2 Jumper selectable by JP31, 24 VDC 1 filtered, power-limited (0.5 amp maximum). Supervision required. Nonresettable Power suitable for powering smoke detectors.

Configure TB9, Terminals 1 & 2 as Resettable or Nonresettable Power.

Resettable Power - jumper JP31 pins 2 & 3

Nonresettable Power - jumper JP31 pins 1 & 2 (as shown)

Initiating Device Circuits

Special Application

Power

IDCs 1 through 5, Style B (Class B) (Supervised, Power-Limited) (See Style D illustrated near right edge of board.) 4.7Kohm, ½ watt End-of- Line Resistor

PN 71252

Class A Converter Module

Remove jumper JP43 to disable Ground Fault Detection circuit (only with approval of AHJ)

For more specific UL wiring information, refer to page 35.

Power Supply Connector

Battery (see note 3)

24 VDC, supervised, nonpower-limited

Remote

Synchronization Output (see note 2)

Special Application

Power

24 VDC filtered, supervised, and powerlimited. 0.040 amp maximum. Requires 4.7K ohm ELR.

3 Programmable Relays

Nonsupervised relay contacts Contact Ratings

2.0 amps @ 30 VDC (resistive)

0.5 amp @ 30 VAC (resistive)

Contacts shown below in normal condition (AC power with no alarm, trouble, or supervisory activity)

A Fail Safe Trouble relay switches to the NC position during trouble conditions and under loss of all power.

(*Factory default relay programming)

Alarm* Trouble* Supervisory*

Cut this jumper to enable Supervisory Relay when 4XTMF module is installed

Dummy load all unused circuits with 4.7K , ½ watt End-of-Line resistors

Style Z (Class A) NAC

Style D (Class A) IDC

SW1

 

 

Push switch down to

Kiss-off LED

 

upgrade software

 

 

 

 

Auxiliary

 

 

Trouble Input

Class A Converter Module

 

 

Cut this jumper to supervise

 

the 4XTMF module when

USB port for local programming using a

installed (see J4 & J5)

 

 

personal computer and PK-5X Utility

ANN-SEC option card connector

Primary Phone

Secondary Phone

Active LED

Active LED

Primary Secondary

DACT Phone Line Jacks

Nonpower-Limited

wmf.5udlayout-ms

Board Circuit Main Series 5UD-MS

NAC #3 NAC #4
NAC #1 NAC #2

3/7/2014 52626:C4 P/N — Manual Series 10UD-MS & 5UD-MS

11

Basic System Connections

10-Zone Panel

Notes:

1.MS-10UD-3(E) = 2.5 amps max. per NAC MS-10UD-7(C/E) = 3 amps max. per NAC

2.Remote Sync Output is required only for the MS-10UD-3(E): refer to “Remote Synchronization Output” on page 34.

3.18 Amp Hour max. for MS-10UD-3(E) 26 Amp Hour max. for MS-10UD-7(E) 18 Amp Hour max. for MS-10UD-7C

Important! Removing Ground Fault Disable Jumper JP43 voids UL/NFPA Style/Class indentifications for circuits. Remove jumper JP43 only with the approval of the local AHJ (Authority Having Jurisdiction).

Notification Appliance Circuits (see note 1)

Special Application Power

NAC #1, #2, #3, & #4, Style Y (Class B) (Supervised, PowerLimited) (See Style Z illustrated near right edge of board.)

4.7Kohm, ½ watt End-of-Line Resistor PN 71252

Initiating Device Circuits

Special Application

Power

IDCs 1 through 5, Style B (Class B) (Supervised, Power-Limited) (See Style D illustrated near right edge of board.) 4.7Kohm, ½ watt End-of-

Line Resistor

PN 71252

4 4

Initiating Device Circuits

Special Application Power IDCs 1 through 5, Style B (Class B) (Supervised, PowerLimited) (See Style D illustrated near right edge of board.)

4.7Kohm, ½ watt End-of-Line Resistor

PN 71252

Remote

Synchronization Output (see note 2)

Special Application Power 24 VDC filtered, supervised, and power-limited. 0.040 amp maximum. Requires 4.7K ohm ELR.

6

6

3 Programmable Relays

Dummy load all unused circuits

Nonsupervised relay contacts

 

with 4.7K , ½ watt End-of-Line

Contact Ratings

 

resistors

2.0 amps @ 30 VDC (resistive)

 

 

0.5 amp @ 30 VAC (resistive)

Style Z (Class A) NAC

Contacts shown below in normal

 

condition (AC power with no alarm,

 

trouble, or supervisory activity)

Style D (Class A) IDC

 

A Fail Safe Trouble relay switches to the NC position during trouble conditions and under loss of all power.

(*Factory default relay programming)

Alarm* Trouble* Supervisory*

Special Application

 

 

 

 

 

 

 

 

 

 

TB6

ZONE

ZONE

ZONE ZONE ZONE

DC Power Outputs 24 VDC)

6

7

8

9

10

 

Nonsupervised, power-limited circuits Supervise with a power supervision relay EOLR-1

Resettable Power - 24 VDC filtered,

 

4

power-limited (0.5 amp maximum) to

smoke detectors (IDC). Supervision

{

3

required.

 

 

Nonresettable or Resettable Power {2 Jumper selectable by JP31, 24 VDC 1 filtered, power-limited (0.5 amp maximum). Supervision required. Nonresettable Power suitable for powering smoke detectors.

Configure TB9, Terminals 1 & 2 as Resettable or Nonresettable Power.

Resettable Power - jumper JP31 pins 2 & 3

Nonresettable Power - jumper JP31 pins 1 & 2 (as shown)

For more specific UL wiring information, refer to page 35.

Class A Converter Module

Cut this jumper to

 

enable Supervisory

Remove jumper JP43 to

Relay when 4XTMF

module is installed

disable Ground Fault

 

Detection circuit (only with

 

approval of AHJ)

 

 

 

 

 

 

 

 

SW1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Push switch down to

 

 

 

 

 

 

 

 

upgrade software

Kiss-off LED

Auxiliary

Trouble Input

Cut this jumper to supervise the 4XTMF module when installed (see J4 & J5)

ANN-SEC option card connector

Primary Phone

Secondary Phone

Active LED

Active LED

Power Supply Connector

 

Primary

Secondary

Battery (see note 3)

DACT Phone Line Jacks

24 VDC, supervised,

Nonpower-Limited

nonpower-limited

 

 

TB4/

TB6

1/6

2/7

3/8

4/9

5/10

Class A Converter Module

USB port for local programming using a personal computer and PK-5X Utility

wmf.10udlayout-ms

Board Circuit Main Series 10UD-MS

ANN-80(C)

ANN-I/O

LED Driver

LCD Text Annunciator/Indicator

Doc. #

Doc. #

 

ACK

STEP

ALARM

TROUBLE

FIRE ALARM ANNUNCIATOR

SW1

JP2

J1

 

 

 

 

 

 

 

 

P1

 

P2

 

P3

 

P4

TB2

 

 

 

 

 

 

 

1

10

11

20

21

30

31

40

TB4

 

 

 

 

 

 

 

TB5

 

 

 

 

 

 

 

TB3

TB6

ANN-BUS

TB1

ANN-RLY

10 Form-C Relay Card

Doc. #

ANN-S/PG

Printer Driver

Doc. #

Alarm

NAC 1

NAC2

NAC 3

NAC 4

Silenced

Fault

Fault

Fault

Fault

Earth

Battery

Charger

Disabled

 

Fault

Fault

Fault

 

ZONE 1

ZONE 2

ZONE 3

ZONE 4

ZONE 5

1

2

3

4

5

ZONE 6

ZONE 7

ZONE 8

ZONE 9

 

6

7

8

9

 

 

FIRE ALARM ANNUNCIATOR

 

ANN-(R)LED

LED Display

 

Doc. #

 

ANN-BUS - TB3

IPDACT

Internet Communicator

Doc. #53109

J8 & J9 Telephone Connections

POWERLIMITED1

5

6

7

TB1

 

 

 

J4 & J5

J1

Sw1

J2

TBL

 

 

4XTM Reverse Polarity Module

USB

Local PC

Battery Connector - J12

JP1

CUT FOR 240VAC

F1

TB1

HOT

NEUT

EARTH

510udperi.wmf

 

 

 

 

 

 

 

AM-1 ENABLE

J4

 

 

 

 

 

JP3

ENABLE

 

JP5

 

 

 

 

 

 

 

AC DELAY

AM-1

 

 

 

 

 

 

 

 

F2

 

 

 

 

 

 

 

 

 

TB2

TENS

 

 

 

 

 

15

 

BAT

 

 

 

 

 

 

 

 

 

 

+

1011 0 5 7

8

 

 

JP4

 

 

 

-

14

 

 

 

 

 

 

 

BAT

12

 

 

1

 

 

16 HR

 

 

 

+

13

 

 

6

 

 

DELAY

 

15

 

OUT

159 4 3 2

 

ADDRESS

 

 

OUT

 

 

 

 

-

1011

0

5 7

 

SW1

 

 

 

F3

 

 

 

8

ON

OFF

 

 

 

 

14

 

 

 

 

 

 

JP2

 

12

 

 

1

 

 

 

 

 

GND FLT

13

 

 

6

 

 

 

 

 

DISABLE

159 4 3 2

 

 

 

 

 

 

 

 

ONES

 

TB3

TB4

J1

J2

J3

 

 

 

 

 

 

 

 

 

 

A- B- A+ B+

NC NO C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

+

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHG-75 Charger

CHG-120 Charger

 

 

 

 

Doc. #

 

Doc. # 51315

12

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Section 1: Product Description

The MS-5UD is a five zone FACP (Fire Alarm Control Panel) and the MS-10UD is a ten zone FACP. The information in this manual refers to both the MS-5UD and MS-10UD unless otherwise specified. The combination control and digital communicator panels provide reliable fire signaling protection for small to medium sized commercial, industrial and institutional buildings. The FACP is compatible with System Sensor’s i3 detectors which are conventional smoke detectors that can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating of approximately 45o F (refer to System Sensor i3 Installation and Maintenance Instructions). In addition, the control panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to the Fire•Lite Device Compatibility Document for a complete listing of compatible devices.

Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application resettable and nonresettable power outputs. The FACP supervises all wiring, AC voltage, battery level and telephone line integrity. Available accessories include local and remote upload/download software, remote annunciators and reverse polarity/city box transmitter.

The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote programming or interrogation of the control panel using the PS-Tools Upload/Download utility via the public switched telephone network. Local programming interrogation is also possible using the PS-Tools and the USB port on the FACP. Any personal computer with Windows® XP or newer, compatible modem with a speed of 2400 baud and PS-Tools may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data and current status.

Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicating LED, display alarm information on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate an auxiliary control function.

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

13

Product Description

Product Features

 

 

The following versions of the MS-5UD and MS-10UD are available:

FACP Version

Description

 

 

MS-5UD-3

Five Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps total 24

 

VDC output current

 

 

MS-5UD-7

Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24

 

VDC output current

 

 

MS-5UD-7C

Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24

 

VDC output current. Includes built-in ANN-LED Annunciator. This panel is approved

 

for Canadian applications

 

 

MS-5UD-3E

Five Zone Panel: 240 VAC with FLPS-3 power supply providing 3.0 amps total 24

 

VDC output current

 

 

MS-5UD-7E

Five Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps total 24

 

VDC output current

 

 

MS-10UD-3

Ten Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps total 24

 

VDC output current

 

 

MS-10UD-3E

Ten Zone Panel: 240 VAC with FLPS-3 power supply providing 3.0 amps total 24

 

VDC output current

 

 

MS-10UD-7

Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24

 

VDC output current

 

 

MS-10UD-7C

Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24

 

VDC output current. Includes built-in ANN-LED Annunciator. This panel is approved

 

for Canadian applications.

 

 

MS-10UD-7E

Ten Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps total 24

 

VDC output current

 

 

NOTE: Unless otherwise specified, the information in this manual applies to all versions of the panels.

1.1 Product Features

Built-in DACT (Digital Alarm Communicator/Transmitter)

• Style B (Class B) IDC (Initiating Device Circuit)MS-5UD - five programmable IDCs

MS-10UD - ten programmable IDCs

• Four Style Y (Class B) NAC (Notification Appliance Circuit) - special application power

• Three programmable Form-C relays

Built-in Programmer

• Touchtone/Rotary dialing

Programmable Make/Break Ratio

Optional Dress Panel: DP-51050

A modified Dress Panel is provided standard with Canadian models: includes an ANN-LED Annunciator module

Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet

ANN-BUS for connection to optional:

ANN-80 Remote LCD Annunciator

ANN-I/O LED Driver

ANN-S/PG Printer Module

14

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Specifications

Product Description

 

 

ANN-RLY Relay Module

ANN-LED Annunciator Module

80-character LCD display (backlit)

Real-time clock/calendar with daylight savings time control

History log with 256 event storage

Control Buttons

ACK (Acknowledge)

Alarm Silence

System Reset/Lamp Test

Drill

LED Indicators

Fire Alarm

Supervisory

Trouble

AC Power

Alarm Silence

Primary and Secondary Phone Line Active LEDs

Piezo sounder for alarm, trouble and supervisory

24 volt operation

Low AC voltage sense

Alarm Verification

NACs Programmable for:

Silence Inhibit

Auto-Silence

Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)

Selective Silence (horn-strobe mute)

Temporal or Steady Signal

Silenceable or Nonsilenceable

Automatic battery charger with charger supervision

Silent or audible walktest capabilities

Optional PK-CD (contains PS-Tools utility) for local or remote Upload/Download of program and data

Optional CAC-5X Class A Converter Module for NACs and IDCs

Optional 4XTMF Transmitter Module

Optional ANN-SEC card for a secondary ANN-BUS

1.2Specifications

NOTE: For wiring specifications, refer to“Wire Requirements” on page 132.

AC Power

MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps

MS-5UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps

MS-5UD-7C (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps

MS-10UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps

MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps

MS-10UD-7C (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

15

Product Description

Specifications

 

 

MS-5UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps MS-5UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps MS-10UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation Supervised, nonpower-limited

Battery (sealed lead acid only) - J12

Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp Supervised, nonpower-limited

Maximum Charger Capacity: 18 Amp Hour battery for MS-5UD-3(E), MS-5UD-7C, MS-10UD- 3(E), and MS-10UD-7C, and 26 Amp Hour battery for MS-5UD-7(E) and MS-10UD-7(E) [two 18 Amp Hour batteries can be housed in FACP cabinet. Larger batteries require a separate battery box such as the BB-26 or BB-55F and the CHG-75 or CHG-120F Battery Charger.]

Minimum Battery Size: 7 Amp Hour (12 Amp Hour for MS-5UD-7C & MS-10UD-7C)

Initiating Device Circuits - TB4 (and TB6 on MS-10UD only)

Alarm Zones 1 - 5 on TB 4 (MS-5UD and MS-10UD) Alarm Zones 6 - 10 on TB6 (MS-10UD only) Supervised and power-limited circuitry

Operation: All zones Style B (Class B) Normal Operating Voltage: Nominal 20 VDC Alarm Current: 15 mA minimum

Short Circuit Current: 40 mA max.

Maximum Loop Resistance: 100 ohms (700 ohms per zone for linear heat detection - See Section 2.3, “Input Circuits” for more information.)

End-of-Line Resistor: 4.7K , 1/2 watt (Part #71252) Standby Current: 2 mA

Refer to the Fire•Lite Device Compatibility Document for listed compatible devices

Notification Appliance Circuit(s) - TB5 and TB7

Four NACs

Operation: Style Y (Class B) Special Application power

Supervised and power-limited circuitry Normal Operating Voltage: Nominal 24 VDC

Maximum Signaling Current: 3.0 amps for MS-5UD-3(E), MS-10UD-3(E) (2.5 amp maximum per NAC); 7.0 amps for MS-5UD-7(E), MS-10UD-7(E) (3.0 amps maximum per NAC)

End-of-Line Resistor: 4.7K , 1/2 watt (Part #71252)

Refer to the Fire•Lite Device Compatibility Document for compatible listed devices

Form-C Relays - Programmable - TB8

Relay 1 (factory default programmed as Alarm Relay)

Relay 2 (factory default programmed as fail-safe Trouble Relay) Relay 3 (factory default programmed as Supervisory Relay)

Relay Contact Ratings: 2 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)

Special Application Resettable Power - TB9

Operating Voltage: Nominal 24 VDC

Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors Power-limited Circuitry

Refer to the Fire•Lite Device Compatibility Document for compatible listed devices

16

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Specifications

Product Description

 

 

Special Application Resettable or Nonresettable Power - TB9

Operating Voltage: Nominal 24 VDC

Maximum Available Current: 500 mA

Power-limited Circuitry

Jumper selectable by JP31 for resettable or nonresettable power:

Jumper pins 1 & 2 on JP31 for nonresettable power

Jumper pins 2 & 3 on JP31 for resettable power

Refer to the Fire•Lite Device Compatibility Document for compatible listed devices

Special Application Primary ANN-BUS Power - TB3

Operating voltage: Nominal 24 VDC Maximum Available Current: 500mA Power-limited circuit

Special Application Secondary ANN-BUS Power - ANN-SEC - TB1

Operating voltage: Nominal 24 VDC Maximum Available Current: 500mA Power-limited circuit

Remote Sync Output - TB2

Remote power supply synchronization output, only required for the MS-5UD-3(E), MS-10UD-

3(E) (refer to“Remote Synchronization Output” on page 34)

24 VDC nominal special application power Maximum current is 40 mA

End-of-Line Resistor: 4.7K Supervised and power-limited circuit

Auxiliary Trouble Input - J6

The Auxiliary Trouble Input is an open collector circuit which can be used to monitor an external device for trouble conditions. It can be connected to the trouble bus of a peripheral, such as a power supply, which is compatible with open collector circuits.

All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

17

Product Description

Specifications

 

 

The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available from the FACP with the FLPS-3 power supply. This applies to the MS-5UD-3, MS-10UD-3, MS-5UD-3E, and MS-10UD-3E.

TB9

Special Application

0.5 amp max

 

Nonresettable or

 

Resettable Power

per circuit

Standby

 

Special Application

0.5 amp max

1.0 amp max

Resettable Power

per circuit

per panel

TB5

 

 

NAC #1

2.5 amps max

 

per circuit

 

NAC #2

2.5 amps max

 

 

per circuit

 

TB7

 

 

NAC #3

2.5 amps max

 

per circuit

 

NAC #4

2.5 amps max

Alarm

 

per circuit

 

 

3.0 amps

 

 

max

TB3

 

per panel

 

 

Primary

 

 

ANN-BUS

0.5 amp max

 

 

 

 

per circuit

 

TB1

 

Standby

 

 

1.0 amp max

ANN-SEC

 

per panel

Option Card

 

 

 

0.5 amp max

 

 

per circuit

 

TB2

 

 

Remote

0.040 amp max

 

Synchronization

 

per circuit

 

Output

 

 

 

powerdist510.wmf

Refer to the battery calculations section for additional information.

Figure 1.1 Current Availability with FACP and FLPS-3 Power Supply

18

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Specifications

Product Description

 

 

The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available from the FACP with the FLPS-7 power supply. This applies to the MS-5UD-7, MS-5UD-7C, MS-10UD-7, MS-10UD-7C, MS-5UD-7E, and MS-10UD-7E.

Special Application

TB9

0.5 amp max

Nonresettable or

Resettable Power

per circuit

Special Application

0.5 amp max

Resettable Power

per circuit

 

TB5

NAC #1

3.0 amps max

per circuit

 

NAC #2

3.0 amps max

 

per circuit

 

TB7

NAC #3

3.0 amps max

per circuit

NAC #4

3.0 amps max

 

per circuit

 

TB3

Primary

 

ANN-BUS

0.5 amp max

 

 

per circuit

 

TB1

ANN-SEC

 

Option Card

0.5 amp max

 

per circuit

Standby 1.0 amp max

per panel

Standby 1.0 amp max

per panel

Alarm 7.0 amps max

per panel

Refer to the battery calculations section for additional information.

Figure 1.2 Current Availability with FACP and FLPS-7 Power Supply

powerdistmrp.wmf

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

19

Product Description

Controls and Indicators

 

 

1.3 Controls and Indicators

LCD Display

The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries.

Key Panel

SYSTEM ALL NORMAL 10:00A 012105

Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.

Function keys:

Acknowledge/Step

Alarm Silence

Drill

System Reset (lamp test)

Service/program keys:

Keys labeled 1 to 9

* key

# key

0 (recall) key

1st Event key

Clear key

Escape key

Mode key

Four cursor keys (up, down, left and right)

Enter key

LED Indicators

9050udkypd.cdr

Figure 1.3 Membrane/Display Panel

LEDs are provided to annunciate the following conditions:

Fire Alarm - red LED

Supervisory - yellow LED

AC Power - green LED

System Trouble - yellow LED

Alarm Silence - yellow LED

Primary Phone Line Active (on circuit board) - red LED

Secondary Phone Line Active (on circuit board) - red LED

Kiss-off (on circuit board) - green LED

Local Piezo Sounder

A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance, process monitor and supervisory conditions as follows:

Alarm - on steady

Trouble - pulse 1 second on and 1 second off

Maintenance - pulse 1 second on and 1 second off

Supervisory - pulse ½ second on and ½ second off

Process Monitor - pulse ¼ second on and ¼ second off

20

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Digital Alarm Communicator/Transmitter

Product Description

 

 

1.4 Digital Alarm Communicator/Transmitter

Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs are provided as well as a green Kissoff LED. The integral digital communicator provides the following functions:

Line Seizure: takes control of the phone lines disconnecting any premises phones

Off/On Hook: performs on and off-hook status to the phone lines

Listen for dial tone: 440 Hz tone typical in most networks

Dialing the Central Station(s) number: default is Touch-Tone®, programmable to rotary

For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly.

Communicate in the following formats:

Ademco Contact ID

SIA-DCS-8

SIA-DCS-20

1.5Components

Main Circuit Board

The main circuit board contains the system’s CPU, DACT and other primary components and wiring interface connectors. Optional modules plug in and are mounted to the main circuit board.

Power Supply

One power supply is provided standard with each FACP, mounted to a chassis.

FLPS-3 for the MS-5UD-3(E), MS-10UD-3(E)

FLPS-7 for the MS-5UD-7(C/E), MS-10UD-7(C/E)

Cabinet

The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides space for two batteries (up to 18 Amp Hours). Also available are an optional dress panel (DP51050) which mounts inside the cabinet and trim-ring (TR-CE). The Canadian version is supplied standard with a modified dress panel and one ANN-LED annunciator module.

Batteries

The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL listed battery box such as the BB-26 or BB-55). Batteries must be ordered separately.

1.6 Optional Modules and Accessories

CAC-5X Class A Converter Module

The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The module connects to J2 on the MS-5UD and MS-10UD main circuit board and to J7 on the MS10UD. Note that two Class A Converter modules are required for the 10 zone panel.

4XTMF Transmitter Module

The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

21

Product Description

Optional Modules and Accessories

 

 

ANN-80 LCD Annunciator

The ANN-80 is a remote LCD annunciator which mimics the information displayed on the FACP LCD display and provides remote RESET, SILENCE, ACKNOWLEDGE, and DRILL.

ANN-80C LCD Indicator (Canadian applications)

The ANN-80C is a remote LCD indicator which mimics the information displayed on the FACP LCD display but does not allow remote control of the FACP.

ANN-LED Annunciator Module

The ANN-LED Annunciator Module provides three LEDs for each zone: Alarm, Trouble and Supervisory. ANN-LED module is installed in dress panel for Canadian version.

ANN-RLY Relay Module

The ANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.

ANN-S/PG Serial/Parallel Printer Gateway

The ANN-S/PG module provides a connection for a serial or parallel printer.

ANN-I/O LED Driver Module

The ANN-I/O module provides connections to a user supplied graphic annunciator.

ANN-SEC Secondary ANN-BUS Module

The ANN-SEC module provides another ANN-BUS port for more wiring flexibility and for Canadian applications requiring remote annunciation.

DP-51050 Dress Panel

A dress panel DP-51050 is available as an option. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel. The Canadian version is supplied standard with a modified dress panel.

TR-CE Trim-ring

A trim-ring TR-CE is available as an option. The trim-ring allows semi-flush mounting of the cabinet.

Battery Box

The BB-26 or BB-55F battery box may be used to house two batteries greater than 18 Amp Hour. The battery box mounts directly below the control panel cabinet, centered to the main circuit board.

Battery Charger

CHG-75 Battery Charger

The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the FACP. The FACP battery charger must be disabled, through software programming, when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Refer to the CHG-75 Manual for additional information.

CHG-120F Battery Charger

The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the FACP. The FACP battery charger must be disabled, through software programming, when using the CHG-120F. The batteries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Note that when using a BB-55F for housing the charger and batteries greater than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for additional information.

22

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Telephone Requirements and Warnings

Product Description

 

 

PS-Tools Programming Utility

The PS-Tools Programming Utility can be used to locally or remotely program the FACP directly from most IBM compatible personal computers (PC), running Windows® XP (or newer). FACP program files can also be created and stored on the PC and then downloaded later to the control panel. The P/N: PK-CD includes the Windows-based Programming Utility software on CD-ROM with on-line help file. A standard USB cable with male-A to male-B connectors, which must be purchased separately, is required for local connection of the PC to the USB port J11 on the FACP main circuit board. Remote programming requires that the PC have a 2400 baud (or faster) modem.

Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to “Remote Download” on page 113). Remote interrogation of panel programming, history logs, detector status, etc., is possible without enabling the remote download option.

1.7 Telephone Requirements and Warnings

1.7.1 Telephone Circuitry

Ringer Equivalence Number (REN) = 0.0B AC Impedance: 10.0 Mega Ohm Complies with FCC Part 68

Mates with RJ31X Male Connector

Supervision Threshold: loss of phone line voltage for 2 minutes

The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.

1.7.2 Digital Communicator

Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty information, please contact:

Manufacturer: Fire•Lite Alarms One Fire-Lite Place Northford, CT 06472 (203) 484-7161

Product Model Number: MS-5UD/MS-10UD

FCC Registration Number: 1W6AL00B10UD Ringer Equivalence: 0.0B

Important! The DACT must not be used to dial a phone number that is call-forwarded.

This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company.

Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

23

Product Description

Telephone Requirements and Warnings

 

 

instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to “Digital Communicator” on page 36 for an illustration of the proper installation of this equipment.

1.7.3 Telephone Company Rights and Warnings

The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.

If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary.

DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.

When the control panel activates, premise phones will be disconnected.

Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.

The control panel must be connected to the public switched telephone network upstream (as first device) of any private telephone system at the protected premises.

A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and requirements adopted by ACTA. This equipment is designed to be connected to the telephone network or premises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant.

1.7.4 For Canadian Applications

The following is excerpted from CP-01 Issue 5:

NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the users’s satisfaction.

Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.

Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.

Users should ensure, for their own protection, that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.

CAUTION

Users should not attempt to make such connections themselves, but should contact the appropriate electric inspections authority, or electrician.

24

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Telephone Requirements and Warnings

Product Description

 

 

“The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. the termination of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”

DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.”

Representative: NOTIFIER/FIRE•LITE, CANADA

10 Whitmore Road Woodbridge, Ontario L4L7Z4 Phone: (905) 856-8733

FAX: (905) 856-9687

IC Certificate Number: 2132A-10UD

Ringer Equivalence Number (REN): 0.0B

Load Number: 2

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

25

Section 2: Installation

The cabinet can be surface mounted or semi-flush mounted. The door is removable during the installation period by opening and lifting it off the hinges. The cabinet mounts using two key slots at the top of the backbox and two additional securing holes located at the bottom.

Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.

2.1Backbox Mounting

!CAUTION: STATIC SENSITIVE COMPONENTS

THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS. ALWAYS GROUND YOURSELF WITH A PROPER WRIST STRAP BEFORE HANDLING ANY BOARDS SO THAT STATIC CHARGES ARE REMOVED FROM THE BODY. USE STATIC SUPPRESSIVE PACKAGING TO PROTECT ELECTRONIC ASSEMBLIES.

To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis assembly in a protective antistatic bag in a safe location until it can be reinstalled in the backbox.

Mark and predrill hole in the wall for the center top keyhole mounting bolt using the dimensions illustrated in Figure 2.2 on page 27.

Install center top fastener in the wall with the screw head protruding.

Place backbox over the top screw, level and secure.

Mark and drill the left and right upper and lower mounting holes.

Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting.

Install remaining fasteners and tighten.

MS-5UD Board on Chassis mounting holes

mounting slots

 

mounting studs

mounting tabs

 

grounding stud:

attach solid earth ground wire (refer to

Figure 2.4 on page 29) mounting slots

MS-5UD Backbox

5udbrdinbox.wmr

Figure 2.1 Chassis Mounting in Backbox

26

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Fire-Lite MS-10UD User Manual

Backbox Mounting

Installation

 

 

Hinge Slot for optional Dress Panel

Mounting

slots for optional Trim Ring

Semi- Flush mounting

hole

Hinge Slot for optional Dress Panel

Semi-Flush Mounting

Do not recess box more than 3.875” into wall to avoid covering venting holes on top of box.

9050UDencl.wmf

Figure 2.2 Cabinet Dimensions

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

27

Installation

Operating Power

 

 

Top

 

Depth = 5.207” (13.23 cm)

 

 

 

Door = 16.821” (42.73 cm)

Depth = 5.257”

 

(13.353 cm)

 

Backbox = 16.65” (42.29 cm)

 

 

Door = 19.26” (48.92 cm)

Backbox = 19.0” (48.26)

9050UDcab2.wmf

Left Side

Right Side

 

 

Bottom

Figure 2.3 Backbox and Battery Box

2.2 Operating Power

WARNING: RISK OF ELECTRICAL SHOCK AND/OR EQUIPMENT DAMAGE

SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED.

Primary Power Source (AC) and Earth Ground Connections

AC power connections are made inside the control panel cabinet. Refer to AC Power in the section titled “Specifications” on page 15, for power and current requirements for each FACP version. Run a pair of wires (with ground conductor) from the protected premises main breaker box to the AC terminal block TB1 on the main power supply. As per the National Electrical Code, use 14 AWG (2.00 mm2, 1.6 mm O.D.) or heavier gauge wire with 600V insulation. No other equipment

28

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Operating Power

Installation

 

 

may be connected to this circuit. In addition, this circuit must be provided with overcurrent protection and may not contain any power disconnect devices. An Earth Ground connection must be made to ensure proper panel operation and lightning and transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00 mm2)] to the grounding stud in the backbox and then run the wire to TB1. Do not use conduit for the Earth Ground connection since this does not provide reliable protection.

Secondary Power Source (Batteries)

Observe polarity when connecting the battery. Connect the battery cable to J12 on the main circuit board using the plug-in connector and cable provided. The battery charger is current-limited and capable of charging sealed lead acid batteries. The charger shuts off when the system is in alarm.

WARNING: SULFURIC ACID

BATTERIES CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND CAN DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID, IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK IMMEDIATE MEDICAL ATTENTION.

MS-5UDC-7(C)(E)

MS-5UD-3(E)

MS-10UD-7(C)(E)

MS-10UD-3(E)

 

FLPS-7

 

 

FLPS-3

 

 

Power Supply

 

 

Power Supply

 

 

AC Power

 

 

AC Power

 

 

Hot (L1)

 

 

AC Hot

 

 

Earth

 

 

AC Neutral

 

 

Neutral (L2)

 

 

Earth

 

 

 

 

 

 

 

10udacpower.wmf

 

 

 

 

 

5ud

Ground Stud

-

+

Ground Stud

-

+

 

J12

 

 

J12

 

 

 

 

 

 

 

to batteries

 

to batteries

Figure 2.4 Operating Power Connections

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

29

Installation

Input Circuits

 

 

2.3 Input Circuits

The MS-5UD has five IDCs (Initiating Device Circuits) and the MS-10UD has ten IDCs. Each circuit is compatible with System Sensor’s i3 smoke detectors which generate a maintenance signal when the detector becomes dirty and a separate supervisory ‘freeze’ signal when ambient temperature falls below the detector rating of approximately 45oF. The maximum loop resistance limit for each IDC is 100 ohms (700 ohms per zone for linear heat detection). Do not use 2-wire smoke detectors on input zones used for linear heat detection. The field wiring for each zone is supervised for opens, shorts and ground faults. All conditions are visually and audibly annunciated.

Each circuit is configured for Style B (Class B) operation and will accept i3 smoke detectors, any normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors. Refer to the Fire•Lite Device Compatibility Document for a list of compatible devices.

Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A Converter module. Refer to “CAC-5X Class A Converter Module” on page 37.

Class B Initiating Device Circuits (supervised and power-limited) 4.7 K , ½ watt resistor P/N:71252

UL listed Power Supervision Relay (refer to Device Compatibility Document for list of compatible relays)

UL listed compatible 4-wire smoke detector

manual pull stations

Resettable 24 VDC

 

4-wire smoke

 

detector power

heat detectors

(500 mA maximum)

 

UL listed compatible 2-wire smoke detectors

Dummy load all unused circuits - 4.7 K , ½ watt resistor (P/N: 71245)

ms-10UDidc.wmf

Figure 2.5 IDC Connections

30

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Loading...
+ 114 hidden pages