Fire-Lite I300A User Manual

0 (0)
Figure 1. Montior and Control Module
Conrols and Indicators

M300(A) MONITOR MODULE, C304(A) CONTROL MODULE, AND

I300(A) FAULT ISOLATOR MODULE INSTALLATION INSTRUCTIONS

This information is included as a quick reference installation guide. Refer to the appropriate Fire-Lite control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

M300(A) MONITOR MODULES provide a two-wire, or fault-tolerant, initiating circuit for normally open contact fire alarm and supervisory devices, or either normally open or normally closed security devices. The LED indicator can be latched on or returned to the normal mode by code command from the panel. Rotary decade switches are used to set the address of each module.

C304(A) CONTROL MODULES allow a compatible control panel to switch discrete contacts by code command. The control module offers a status LED that can be latched on or returned to the normal mode by code command from the panel. Rotary decade switches are used to set the address of each module.

STATUS LED

ROTARY DECADE

ADDRESS SWITCHES

M300(A) MAGNET

TEST POSITION

MODE TABS

A78-2318-01

The control module offers two modes of switching operation. As shipped, the module is configured for switching an external power source to notification ap-

pliances. The external power source can be a DC power supply or an audio amplifier (up to 70.7 Vrms). In this mode, the module reports supervision status of the connected loads to the control panel. Load circuit status is reported as a normal, open, or shorted circuit. Two pairs of output termination points are available for fault-tolerant wiring. The second mode of switching operation allows the panel to control one Form-C (SPDT) set of contacts. Circuit connections to the contacts are not supervised by the module. This mode is enabled by breaking two external tabs on the module.

I300(A) FAULT ISOLATOR MODULES enable part of the communications loop to continue operating when a short circuit occurs on it. An LED indicator blinks in the normal condition and turns on during a short circuit condition. The module will automatically restore the entire communications loop to the normal condition when the short circuit is removed. (The isolator module does not have decade switches.)

COMPATIBILITY REQUIREMENTS

To insure proper operation, these modules must be connected to addressable,

MOUNTING M300(A), C304(A), AND I300(A) DEVICES

M300(A), C304(A), and I300(A) modules mount directly to 4 inch square electrical boxes as shown in Figure 2A. The box must have a min. depth of 21 /8".

WIRING

NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. When using control modules in nonpower limited applications, the CB500 Module Barrier must be used to meet UL requirements for the separation of power-limited and nonpower-limited terminals and wiring. The barrier must be inserted in a 4"x4"x21 /8" junction box, and the control module must be placed into the barrier and attached to the junction box (Figure 2A). The power-limited wiring must be placed into the isolated quadrant of the module barrier (Figure 2B).

1.Install module wiring in accordance with the job drawings and appropriate wiring diagrams (Figures 3 - 10).

2.Set the address on the M300 and C304 per job drawings. Record this address and loop on the front of the module, if desired.

3.Secure module to electrical box (supplied by installer), as shown in Figure 2A.

M300(A) MAGNET TEST

The M300(A) Monitor module can be tested with Fire-Lite's M02-04-01 Test Magnet (see Figure 1). The magnet test checks the module electronics and connections to the control panel. Interfaced initiating and indicating devices must be tested independently.

listed compatible Fire-Lite control panels only.

ISOLATED

QUADRANT

A78-2611-00

Figure 2B.

A78-2610-00

Figure 2A. Module

Mounting with Barrier

F300-03-01

1

I56-570-05

 

Fire-Lite Alarms, Inc., 12 Clintonville Rd, Northfield , CT 06472-1652 (203) 484-7161

Fire-Lite I300A User Manual

FROM PANEL OR

(–)

 

(–)

TO NEXT

(+)

 

(+)

 

 

PREVIOUS DEVICE

 

DEVICE

 

 

 

 

 

MONITOR

ANY NUMBER OF UL LISTED CONTACT CLOSURE

 

 

 

DEVICES MAY BE USED. DO NOT MIX FIRE

 

 

MODULE

 

 

 

 

ALARM INITIATING, SUPERVISORY, OR

CONNECT MODULES TO LISTED COMPATIBLE

M300(A)

 

 

SECURITY DEVICES ON THE SAME MODULE.

FIRE-LITE CONTROL PANELS ONLY

 

 

 

 

 

(–)

1 (–)

(+)

2 (+)

COMMUNICATION LINE

SEE FIRE-LITE PRODUCT

MANUAL FOR WIRE SPECIFICATIONS

(–)9

 

(+)8

 

(+)7

 

(–)6

47 K EOL

 

RESISTOR

 

A2143-00

INITIATING DEVICE CIRCUIT - NFPA STYLE A OR B

 

POWER LIMITED: 230 A MAX @ 12 VDC MAX

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

IDC INSTALLATION WIRING SHALL NOT

EXCEED 40 OHMS OR 2500 FEET, 12 - 18 AWG.

 

 

INSTALL CONTACT CLOSURE DEVICES PER

 

MANUFACTURER'S INSTALLATION INSTRUCTIONS.

A78-2280-05

FIGURE 3. TYPICAL M300 2-WIRE INITIATING CIRCUIT CONFIGURATION, NFPA STYLE A OR B

CONNECT MODULES TO LISTED COMPATIBLE

FIRE-LITE CONTROL PANELS ONLY

FROM PANEL OR

(-)

(+)

PREVIOUS DEVICE

 

COMMUNICATION LINE

SEE FIRE-LITE PRODUCT MANUAL FOR WIRE SPECIFICATIONS

 

(–)

TO NEXT

 

(+)

 

DEVICE

 

 

MONITOR

ANY NUMBER OF UL LISTED CONTACT CLOSURE

 

DEVICES MAY BE USE. DO NOT MIX FIRE

MODULE

 

 

ALARM INITIATING, SUPERVISORY, OR

M300(A)

 

 

SECURITY DEVICE ON THE SAME MODULE.

 

 

(–)

(–)9

 

 

 

1 (–)

(+)8

 

(+)

 

 

2 (+)

(+)7

 

 

(–)6

EOL RESISTOR

 

 

IS INTERNAL AT

 

 

TERMINALS 8 & 9.

INITIATING DEVICE CIRCUIT - NFPA STYLE D

 

POWER LIMITED: 230 A MAX @ 12 VDC MAX

 

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

IDC INSTALLATION WIRING SHALL NOT

 

 

EXCEED 40 OHMS OR 2500 FEET, 12 - 18 AWG.

 

 

INSTALL CONTACT CLOSURE DEVICES PER

A78-2281-03

 

MANUFACTURER'S INSTALLATION INSTRUCTIONS.

FIGURE 4. TYPICAL M300 FAULT TOLERANT INITIATING CIRCUIT CONFIGURATION, NFPA STYLE D

COMMUNICATION LINE

SEE FIRE-LITE PRODUCT

MANUAL FOR

CONNECT MODULES TO LISTED COMPATIBLE WIRE SPECIFICATIONS ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED FIRE-LITE CONTROL PANELS ONLY

FROM PANEL OR

(-)

(-)

TO NEXT

(+)

(+)

PREVIOUS DEVICE

DEVICE

 

 

 

 

 

CONTROL

INDICATING APPLIANCE CIRCUIT (IAC) - NFPA STYLE W

BRANCH CIRCUIT

 

 

MODULE

USE UL LISTED INDICATING APPLIANCES

 

 

C304(A)

MAXIMUM LOAD:

RESISTIVE: 2 A @ 30 VDC

DO NOT LOOP WIRE ON TERMINALS

 

 

 

 

 

INDUCTIVE: 1 A @ 30 VDC (.6 PF)

3 & 4. BREAK WIRE RUN TO PROVIDE

 

 

 

(+) 9

 

PILOT DUTY: .6 A @ 30 VDC (.35 PF)

SUPERVISION OF CONNECTIONS.

 

(-)

 

 

 

 

 

1 (-)

(-) 8

 

 

 

 

(+)

 

 

ISOLATED, REGULATED

 

2 (+)

(-) 7

(-)

(-)

(-)

 

POWER SUPPLY, LISTED FOR FIRE

 

3 (-)

(+) 6

 

 

 

 

 

 

PROTECTION WITH BATTERY BACKUP

(+)

 

 

47K EOL

 

4 (+)

XXX 5

 

(MONITOR LOSS OF PRIMARY POWER)

 

 

 

RESISTOR

EXTERNAL POWER SOURCE MUST BE

 

 

 

 

 

A2143-00

 

 

 

 

 

 

POWER LIMITED PER NFPA 70

 

 

 

 

(+)

(+)

 

 

 

 

 

 

UL LISTED EOL RELAY

 

 

 

XXX - DO NOT

 

SHOWN ENERGIZED

 

 

 

USE TERMINAL 5

 

A77-716B

TO NEXT CONTROL MODULE OR END

OF LINE RELAY (EOLR); ONE EOLR

REQUIRED PER BRANCH CIRCUIT

MODULE POLARITIES ARE

SHOWN IN ALARM

A78-2282-05

FIGURE 5. TYPICAL C304 INDICATING CIRCUIT CONFIGURATION, NFPA STYLE W

F300-03-01

2

I56-570-05

Loading...
+ 2 hidden pages