Edco TCS-HW Series
Power Switching & Controls
For Business-Critical ContinuityTM
Point-of-Application Protection
Utilizing bipolar Silicon Avalanche Diode (SAD) technology, the Edco TCS-HW Series features a two-stage design that provides superior protection for sensitive equipment and for ANSI/IEEE C62.41 Location Category A applications. The Edco TCS-HW Series can be incorporated into larger power protection or used as point-of-application protection. Hardwired into a single 15 or 20 amp AC circuit, the TCS-HW Series places protection at,
or near, the critical load. The field-tested design ensures continuous protection in the most demanding environments, with configurations available for 120 and 240 VAC, single-phase applications.
Features
■Provides superior, nondegrading protection using bipolar SAD technology
■Provides independent secondary stage for maximum continued protection
■ Includes remote status indication via RJ-11 jack |
■ Protects individual circuits |
■ Withstands demanding environments with its |
■ Installs easily |
rugged metal enclosure |
|
General Technical Specifications
Enclosure Dimensions |
|
(not including tabs) |
4H x 4H x 2.5D in., 10H x 10W x 6D cm |
Weight |
1.24 lb; 562 grams |
Enclosure Type |
Extruded Aluminum |
Interface |
Hardwire |
Primary Technology |
Silicon Avalanche Diode (SAD) |
ANSI/IEEE c62.41-1991 |
|
Location Category |
Category A22.2 |
Line Configuration |
1 Phase, 2 wire & ground |
Operating Temperature |
-40°C to +50°C |
Operating Frequency |
50/60 HZ |
Response Time |
< 5 ns |
EM/RFI Noise Attenuation |
-13dB maximum, 150 kHz-200 MHz |
Remote Failure Indication |
RJ-11 Jack/Form C Dry Contact |
Performance Technical Specifications
Part Number |
TCS-HWD |
TCS-HWR |
Nominal Line Voltage |
240 V |
120 V |
Max. Continuous Line Voltage |
264 Vrms |
132 Vrms |
Nominal Clamping Voltage † |
424 Vpk |
216 Vpk |
Protection Modes |
L-N |
L-N |
|
L-G |
L-G |
|
N-G |
N-G |
Peak Pulse Energy Dissipation |
L-N: 560 J |
L-N: 300 J |
|
L-G: 140 J |
L-G: 75 J |
|
N-G: 140 J |
N-G: 75 J |
Max. Transient Current (8/20m) |
L-N: 32 kA |
L-N: 32 kA |
|
L-G: 8 kA |
L-G: 8 kA |
|
N-G: 8 kA |
N-G: 8 kA |
† Clamping voltage reflects ANS/IEEE C62.41-1991 Wave Shape Testing with 100 kHz ringwave 6 kV 200 A as parameters for static and dynamic testing.
Emerson Network Power. |
|
AC Power |
|
Embedded Computing |
|
InfrastructureManagement&Monitoring |
|
Thermal Management |
|
|
|
|
|||||
The global leader in enabling |
|
Connectivity |
|
Embedded Power |
|
Outside Plant |
|
Racks and Integrated Cabinets |
|
|
|
|
|||||
Business-Critical Continuity . |
|
DC Power |
|
Industrial Power |
|
Power Switching & Controls |
|
Service |
TM |
|
|
|
|
|
|
|
|
Emerson Network Power Contact information |
|
|
|
www.EmersonNetworkPower.com/Surge |
Surge Protection
100 Emerson Parkway
Binghamton, NY 13905
T: (607) 721-8840 (Outside U.S.)
T: (800) 288-6169 (Inside U.S. & Canada Only)
F: (607) 722-8713
E: SurgeTech@Emerson.com