Emerson TCS-HW Brochures and Data Sheets

0 (0)
Emerson TCS-HW Brochures and Data Sheets

Edco TCS-HW Series

Power Switching & Controls

For Business-Critical ContinuityTM

Point-of-Application Protection

Utilizing bipolar Silicon Avalanche Diode (SAD) technology, the Edco TCS-HW Series features a two-stage design that provides superior protection for sensitive equipment and for ANSI/IEEE C62.41 Location Category A applications. The Edco TCS-HW Series can be incorporated into larger power protection or used as point-of-application protection. Hardwired into a single 15 or 20 amp AC circuit, the TCS-HW Series places protection at,

or near, the critical load. The field-tested design ensures continuous protection in the most demanding environments, with configurations available for 120 and 240 VAC, single-phase applications.

Features

Provides superior, nondegrading protection using bipolar SAD technology

Provides independent secondary stage for maximum continued protection

Includes remote status indication via RJ-11 jack

Protects individual circuits

Withstands demanding environments with its

Installs easily

rugged metal enclosure

 

General Technical Specifications

Enclosure Dimensions

 

(not including tabs)

4H x 4H x 2.5D in., 10H x 10W x 6D cm

Weight

1.24 lb; 562 grams

Enclosure Type

Extruded Aluminum

Interface

Hardwire

Primary Technology

Silicon Avalanche Diode (SAD)

ANSI/IEEE c62.41-1991

 

Location Category

Category A22.2

Line Configuration

1 Phase, 2 wire & ground

Operating Temperature

-40°C to +50°C

Operating Frequency

50/60 HZ

Response Time

< 5 ns

EM/RFI Noise Attenuation

-13dB maximum, 150 kHz-200 MHz

Remote Failure Indication

RJ-11 Jack/Form C Dry Contact

Performance Technical Specifications

Part Number

TCS-HWD

TCS-HWR

Nominal Line Voltage

240 V

120 V

Max. Continuous Line Voltage

264 Vrms

132 Vrms

Nominal Clamping Voltage †

424 Vpk

216 Vpk

Protection Modes

L-N

L-N

 

L-G

L-G

 

N-G

N-G

Peak Pulse Energy Dissipation

L-N: 560 J

L-N: 300 J

 

L-G: 140 J

L-G: 75 J

 

N-G: 140 J

N-G: 75 J

Max. Transient Current (8/20m)

L-N: 32 kA

L-N: 32 kA

 

L-G: 8 kA

L-G: 8 kA

 

N-G: 8 kA

N-G: 8 kA

† Clamping voltage reflects ANS/IEEE C62.41-1991 Wave Shape Testing with 100 kHz ringwave 6 kV 200 A as parameters for static and dynamic testing.

Emerson Network Power.

 

AC Power

 

Embedded Computing

 

InfrastructureManagement&Monitoring

 

Thermal Management

 

 

 

 

The global leader in enabling

 

Connectivity

 

Embedded Power

 

Outside Plant

 

Racks and Integrated Cabinets

 

 

 

 

Business-Critical Continuity .

 

DC Power

 

Industrial Power

 

Power Switching & Controls

 

Service

TM

 

 

 

 

 

 

 

 

Emerson Network Power Contact information

 

 

 

www.EmersonNetworkPower.com/Surge

Surge Protection

100 Emerson Parkway

Binghamton, NY 13905

T: (607) 721-8840 (Outside U.S.)

T: (800) 288-6169 (Inside U.S. & Canada Only)

F: (607) 722-8713

E: SurgeTech@Emerson.com

SL-60105 1/14 Rev. 2 Printed in USA

Business-Critical Continuity, Emerson Network Power and the Emerson Network Power

logo are trademarks and service marks of Emerson Electric Co. ©2014 Emerson Electric Co.

Loading...