GE
Measurement & Control Solutions
LP 1000 Series
Druck Ultra Low
Pressure Sensor
The LP 1000 Series wet/wet dierential pressure
transmitter is ideally suited for use in clean room
HVAC monitoring and control. The device oers
several improvements over traditional sensors
such as user-accessible damping, excellent longterm stability, and wet/wet dierential operation
where conductive uids may be exposed to the
measurement diaphragm.
The LP 1000 Series oers a dramatic improvement
in reliability with improved stability and the ability
to tolerate condensing media. The design has been
eld proven with more than 10 years in applications
where high humidity and condensing media are a
daily occurrence. The damping adjustment feature
allows the user to slow the response time to eliminate
nuisance trips of alarms when doors are opened and
closed.
The DC version adds the ability to switch the pressure
ports to the front of the device, thus permitting
calibration to be performed from the front of the
panel, eliminating the need for additional personnel
behind the panel. Optional adjustable set-point Red
and Green Status LEDs are available.
Features
• Ranges: ±0.1 inH2O to ±1 psi
(0.25 to 70 mbar)
• Accuracy to ±0.25 % Full Scale (FS)
• Wet/wet dierential pressure
• User-accessible damping (10 ms to 2 s)
• LCD display models available
• Red/green status LEDs
LP 1000 Series
Specications
Load Impedance
Voltage output 5 kW minimum
Current output RL ( kW) < (Vsupply - Vs) 20
Pressure Measurement
Operating Ranges
0.25, 0.5, 1.0, 1.25, 2.0, 2.5, 5.0, 6.25, 7.5, 10, 12.5, 15, 20,
25, 40, 50, 70 mbar
(0.1, 0.2, 0.25, 0.5, 0.8, 1, 2, 2.5, 3, 4, 5, 6, 8, 10, 16, 20
inH2O and 1 psi)
unidirectional and bidirectional (other pressure units
available, see ordering information).
Overpressure
• 250 mbar (3.5 psi) for ranges 0.25 to 2.5 mbar (0.1 to
1 inH2O)
• 700 mbar (10 psi) for ranges 5 to 15 mbar (2 to 6
inH2O)
• 1200 mbar (17 psi) for ranges 20 to 70 mbar (8 inH2O
to 1 psi)
Maximum Static (Line) Pressure
2 bar (30 psi) for all ranges
Electrical Supply Voltage
Power Supply (Vs) (at the terminals)
Current output without display 10 to 30 VDC
Current output with display 15 to 30 VDC
Current output with display and
LED indicators 20 to 30 VDC
Voltage output 10 to 30 VDC
Voltage output (0 to 10 VDC) 15 to 30 VDC
Performance
Combined Eects of Non-linearity,
Hysteresis and Repeatability
±0.5% FS Best Straight Line (BSL )
±0.25% FS BSL (optional)
Static Pressure Eects
Eects may be zeroed out at operating line
pressure
Stability
At standard conditions will not change by more than
1% FS averaged over one year
Supply Sensitivity
<0.05% FS per volt
Compensated Temperature Range
0 to 50° C (32 to 122° F)
Temperature Eects
Over the range 32 to 122 °F (0 to 50° C)
• Ranges from 0.1 inH2O to 0.5 inH2O ±0.01 inH2O
• Ranges from 0.8 inH2O to 1 inH2O ±0.02 inH2O
• Ranges from 2 inH2O to 3 inH2O ±0.05 inH2O
• Ranges from 4 inH2O to 6 inH2O ±0.10 inH2O
• Ranges from 8 inH2O to 14 inH2O ±0.20 inH2O
• Ranges from 16 inH2O to 28 inH2O ±0.40 inH2O
Output Signal Option
Unidirectional Voltage 0 to 2.5 VDC
0 to 5 VDC
0 to 10 VDC
1 to 6 VDC
Current 4 to 20 mA
Bidirectional Voltage 2.5 ±2.5 VDC
5 ±5 VDC
Current 12 ±8 mA
Note: Voltage outputs are three wire, current outputs are
two wire.
Zero Oset Adjustment
±5% FS
Span Adjustment
±5% FS
Response Time
User-adjustable 10 ms to 2 s
(factory default setting 10 ms)
Environmental
Protection
Type 3 IP 64
(Except with C2 screw terminals)
Temperature Range
0 to 50° C (32 to 122° F)
Humidity
0 to 100% RH, non condensing.
Mounting Position Eect
No eect on span, possible zero shift correctable by
potentiometer adjustment.
Note: Factory calibrated with diaphragm in the vertical
plane.