Bosch D8132LT Specsheet

Fire Alarm Systems | D8132 Battery Charger Modules
D8132 Battery Charger Modules
www.boschsecurity.com
u Provide additional standby power for control panels
u 1200 mA battery recharging circuit
u Suitable for 12 VDC and up to 27 Ah of batteries
The D8132 Battery Charger modules work with external batteries to increase standby time and provide additional power to the auxiliary output of compatible control panels.
Notice
The modules are UL rated as battery charger modules. They can also be used as standalone power supplies (not UL rated for this purpose).
System overview
The modules use a 16.5 VAC, 40 VA plug‑in transformer (D1640) to supply 1.2 A of battery charging current. A green LED lights to indicate the presence of AC voltage.
Functions
Provide additional standby time
In applications where the control panel cannot recharge its secondary batteries or when additional power is needed for auxiliary outputs, the module can provide up to 27 Ah at 12 V.
(not UL rated for this application)
Standalone Power Supply
The modules can work as standalone, 12 VDC 1 A power supplies for ancillary devices in non‑critical applications that do not require battery supervision, load shed capability, or UL Listing.
Certifications and approvals
NYC/BSA 582-85-SA
Notice
The D8132 is UL rated as a battery charger.
Region Certification
USA UL AMCX: Central Station Alarm Units (IAN-
SI/UL1610), 4), AOTX: Local Alarm Units (ANSI/UL609), APAW: Police Sta­tion Alarm Units (ANSI/UL365), APOU: Proprietary Alarm Units (ANSI/UL1076), NBSX: Household Burglar Alarm System Units (ANSI/UL1023), UOJZ: Control Units, System (ANSI/UL 864), UTOU: Control Units and Accessories - House­hold System Type (I/UL985)
FM D8132
CSFM see our website
2 | D8132 Battery Charger Modules
Region Certification
NYC­MEA
NYC­MEA
Canada ULC AMCX7: Central Station Alarm Units Cer-
12-92-E, Vol. IV
12-92-E, Vol. 15
tified for Canada (CAN/ULC-S304), AOTX7: Local Alarm Units Certified for Canada (CAN/ULC-S303), APAW7: Po­lice Station Alarm Units Certified for Canada (CAN/ULC -S303, CAN/ULC­S304), APOU7, Proprietary Alarm Units Certified for Canada (ULC/ORD-C1076), NBSX7: Household Burglar Alarm Sys­tem Units Certified for Canada (ULC/ ORD-C1023)
Installation/configuration notes
Compatibility Information
Control Panels
Active products:
D9412GV4, D7412GV4, D7212GV4, D9412GV3, D7412GV3, and D7212GV3 panels
B5512, B4512, and B3512 panels
D6412 and D4412 panels
Legacy products:
D9412GV2, D7412GV2, D7212GV2, D9412G, D7412G, and D7212G panels
D9412, D7412, D7212, and D7212B1 panels
D9112B1, D9112, D8112, and D6112 panels
D912 panel4
D2812, D2412, D2212, D2212B, D2212BE, and D2012 panels
Application Considerations
Two additional 12 V, 7 Ah batteries or up to two 12 V,
13.5 Ah batteries can be installed with the module. The module is ideal for systems requiring extended battery standby time, such as UL Bank Safe and Vault applications, and systems requiring additional auxiliary current output. The module can also be installed as a non‑UL Listed 12 V, 1 A stand‑alone power supply.
Wiring Considerations
Installers can use a four‑wire harness to connect one or two batteries to the module.
Mounting Considerations
Installers can mount the battery charger module and batteries inside a separate approved Bosch Security Systems, Inc. enclosure such as the D8103, D8108A, or D8109. These enclosures have a rectangular knockout on the door, allowing installers to view the green AC power LED on the battery charger module. The D137 Mounting Bracket allows installers to mount a battery charger module into enclosures from other manufacturers.
Parts included
D8132 Battery Charger Module
Quantity Component
1 D8132LT module
2 Cables (one 4‑connector and one 6‑connector)
1 D1640 Transformer
1 Hardware pack containing:
• 4 lock washers
• 4 nuts
• 4 screws
• 4 terminal lugs
The cables connect the D8132 to the transformer, one or two batteries, and the control panel. Additional hardware is provided for connecting larger batteries. This hardware is not required when connecting 12 VDC, 7 Ah batteries.
D8132LT Battery Charger Module Less Transformer
Quantity Component
1 D8132LT module
2 Cables (one 4‑connector and one 6‑connector)
1 Hardware pack containing:
• 4 lock washers
• 4 nuts
• 4 screws
• 4 terminal lugs
Technical specifications
Electrical
Float Voltage
Supplied Voltage 16.5 VAC, 40 VA supplied by D1640 plug‑in
Current 1.2 A
Ampere-Hours 27 Ah maximum
1
measured with batteries in circuit
1
13.9 VDC maximum
transformer
Mechanical
Dimensions (hxwxd) 0.75 in. x 3.0 in. x 5.0 in. (1.9 cm x 7.6 cm x
12 cm)
Ordering information
D8132 Battery Charger Module
The module uses a supplied D1640 16.5 VAC, 40 VA Plug‑in Transformer and up to two 12 V batteries (each up to 13.5 Ah) to supply 1.2 A of battery charging current.
Order number D8132
Loading...