Battery charger modules Notices | en 3
Bosch Security Systems, Inc. Installation manual 2018.05 | 4.0 | F.01U.036.305
These instructions cover the installation of the D8132 Battery Charger and the D8132LT Battery Charger Less Transformer modules in an alarm system supervised by a fire alarm control panel (FACP), an intrusion alarm panel, or a combination Burglary/Fire control panel. These modules are UL Listed for use in Central Station, Household Fire and Burglary Alarm, Police Connection, and Electrically Actuated Transmitter applications. They can also be installed as non-UL Listed , 12V, 1A, standalone power supplies. To obtain any of the documents referenced in this document, download them from the Bosch website (www.boschsecurity.com). Install, test and maintain the module according to these instructions, NFPA codes, local codes, and the authority having jurisdiction (AHJ). Failure to follow these instructions can result in failure of a detector to initiate an alarm event. Bosch Security Systems, Inc. is not responsible for improperly installed, tested or maintained devices. Before installing the module, become familiar with the Installation and Operation Guide for the control panel you are using.
!
Warning!
Follow these instructions to avoid personal injury and damage to equipment.
NFPA72 requires that you perform a complete system wide functional test following any modifications, repair, upgrades or adjustments made to the system’s components, hardware, wiring, programming and software/firmware.
Copyright
This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved.
Trademarks
All hardware/software product names used in this document are likely to be registered trademarks and must be treated accordingly.
4 en | Description Battery charger modules
2018.05 | 4.0 | F.01U.036.305 Installation manual Bosch Security Systems, Inc.
2 Description
The module, combined with external batteries, increases the standby time and provides additional power to the auxiliary output of the compatible control panels listed in the following table.
Control Panels See section:
Active products:
GV4 and GV3 panels
1
Wiring, page 6
Legacy products:
GV2 and G panels
2
See control panel’s documentation on the
Bosch website (http://
www.boschsecurity.com)
D6412 and D4412 panels
D9412, D7412, D7212, D7212B1
D9112B1, D9112, D8112, D6112
D9124
2000-series panels
3
1
GV4 = D9412GV4, D7412GV4, & D7212GV4; GV3 = D9412GV3, D7412GV3, & D7212GV3
2
GV2 = D9412GV2, D7412GV2, & D7212GV2; G = D9412G, D7412G, & D7212G
3
2000-series = D2812, D2412, D2212, D2212B, D2212BE, & D2012
In addition to the batteries that can be installed with the control panel, two additional 12V, 7Ah batteries (D126) or up to two 12V, 13.5Ah batteries can be installed with the module. The module is ideal for systems requiring extended battery standby time, such as UL Bank Safe and Vault applications, and systems requiring additional auxiliary current output. In addition to providing increased standby time and auxiliary power, the batteries also filter the AC power supply. The amount of ripple that appears on the control panel outputs is dependent on the condition of the batteries.
Notice!
Bosch does not recommend using the module to power devices that are sensitive to excessive ripple.
A 16.5V, 40VA transformer (D1640, supplied with the D8132) is required to power the module. A green LED on the module lights to indicate the presence of AC power. Provided with the D8132LT are two cables, and two sets of lockwashers, nuts, screws, and terminal lugs. The cables connect the module to the transformer, two batteries, and the control panel. The hardware is provided for connecting the battery cable to 12V, and up to two 13.5Ah batteries (this hardware is not used when connecting 12V, 7Ah batteries).