Bosch D8130 Specsheet

Fire Alarm Systems | D8130 Door Release Module
D8130 Door Release Module
www.boschsecurity.com
u Two Form C (5 A rated) contacts
u Remotely controls fire system devices
u Instant or delayed relay activation and restoral
The D8130 Door Release Module is an accessory for fire alarm control panels (FACPs) that controls system functions commonly required in National Fire Prevention Association (NFPA) 72 fire alarm installations. Two independent Form C dry contacts, each rated at 5 A, connect low-voltage circuits to magnetic door holders, pilot relays, or contactor units for function control. Typical applications are:
• releasing fire doors, emergency exit doors, and stairwell doors
• elevator recall
• HVAC control
Functions
Contact Activation
The control panel indicating output activates the contacts of the D8130. A red Alarm Input LED indicates contact activation. The duration of the contact activation follows the programmed indicating circuit time. Use a jumper to set the contact activation to be instant or delayed by 14 sec when there is an alarm condition. With the delay option selected, a 14 sec delay also occurs upon restoral. This delay feature is useful for momentary bell tests.
u Disable switch supervised for system testing
If the user silences the alarm output, the D8130 contacts deactivate. Latching features must be provided for pilot relays or contactor units requiring control beyond the programmed indicating device time or after manual silencing of the indicating circuits.
Supervised Disable Switch
To facilitate fire alarm installation testing, the D8130 Module contains a supervised disable switch that prevents operation of the relay contacts. An amber Disable LED indicates when the switch is in the disable position. Connect one or more D8130 modules to any unused 1 kΩ zone or point of the control panel to detect module disabling. A trouble is indicated when the D8130 switch is in the disable position, and a restoral signal is sent when the switch is returned to the normal position. (Refer to the control panel’s Program Entry Guide for details on programming a trouble signal for an open or short condition.) When the contacts are activated with the switch in the normal position, no trouble indications are sent to the control panel.
Release Contact Outputs
A normally-open (NO) terminal, a normally-closed (NC) terminal, and a common (COM) terminal are provided for each D8130 contact. In the inactive state of the contact, the NC terminal has continuity with the COM terminal. In the active state of the contact, the NO terminal has continuity with the COM terminal.
2 | D8130 Door Release Module
Certifications and approvals
Complies with NFPA 72
Region Certification
USA UL AMCX: Central Station Alarm Units
CSFM see our website
FDNY­CoA
NYC­MEA
NYC­MEA
(UL1610, UL1635), AOTX: Local Alarm Units (UL464, UL609), APAW: Police Station Alarm Units (UL365, UL464), APOU: Proprietary Alarm Units (UL1076), NBSX: Household Burglar Alarm System Units (UL1023), UOJZ: Control Units, System (UL864, 9th edi­tion), UTOU: Control Units and Accesso­ries - Household System Type (UL985)
6174
12-92-E, Vol. 12 12-92-E, Vol. 12
12-92-E, Vol. XV
Installation/configuration notes
Compatible Products
The following products are compatible with the D8130 Release Module:
Category Product ID Product Description
Control Panels
D9412 Control panel
D7412 Control panel
D7212** Control panel
D9124 Addressable fire alarm control panel
Modules D191C Bell supervision module
D192G Notification Appliance Circuit (NAC)
G Series* Control panels
Module
* G Series included B9512G, B8512G, D9412GV4, D8412GV4, D7212GV4**, D9412GV3, D8412GV3, D7212GV3**, D9412GV2, D8412GV2, D7212GV2**, D9412G, D8412G, D7212G** ** The D7212 models are not listed for commercial fire applications.
Mounting Considerations
The D8130 Door Release Module mounts in the control panel enclosure or in a separate approved enclosure. Up to four modules can be installed using the mounting locations provided.
Notice
Use a D138 Mounting Bracket to mount the D8130 in the D9124 FACP.
Wiring
Use the following table to determine correct contact wire size:
Maximum Wire Impedance: 6 Ω
Distance (maximum) Wire Size
350 ft 22 AWG
800 ft 18 AWG
Parts included
Quant. Component
1 Door release module
1 Hardware pack
1 Literature pack
Technical specifications
Mechanical Properties
Dimensions (H x W x D): 5 in. x 3 in. x 0.75 in.
(12.7 cm x 7.6 cm x 1.9 cm)
Outputs
Relays: Two Form C dry contact
Relay Rating: 5.0 A at 30 VDC maximum for resistive loads
Power Requirements
Current
Alarm: 60 mA maximum
Contacts Disabled: 15 mA
Standby: 7 mA
Voltage
Nominal: 12 VDC nominal
Ordering information
D8130 Door Release Module
Provides two independent Form C dry contacts, each rated at 5 A, to connect low-voltage circuits to magnetic door holders, pilot relays, or contactor units for function control
Order number D8130
Accessories
D137 Mounting Bracket
Used to mount accessory modules in D8103, D8108A, and D8109 enclosures.
Order number D137