Fire Alarm Systems | D8130 Door Release Module
D8130 Door Release Module
www.boschsecurity.com
u Two Form C (5 A rated) contacts
u Remotely controls fire system devices
u Instant or delayed relay activation and restoral
The D8130 Door Release Module is an accessory for
fire alarm control panels (FACPs) that controls system
functions commonly required in National Fire
Prevention Association (NFPA) 72 fire alarm
installations. Two independent Form C dry contacts,
each rated at 5 A, connect low-voltage circuits to
magnetic door holders, pilot relays, or contactor units
for function control.
Typical applications are:
• releasing fire doors, emergency exit doors, and
stairwell doors
• elevator recall
• HVAC control
Functions
Contact Activation
The control panel indicating output activates the
contacts of the D8130. A red Alarm Input LED
indicates contact activation.
The duration of the contact activation follows the
programmed indicating circuit time. Use a jumper to
set the contact activation to be instant or delayed by
14 sec when there is an alarm condition. With the
delay option selected, a 14 sec delay also occurs upon
restoral. This delay feature is useful for momentary
bell tests.
u Relay closure follows indicating circuit duration
u Disable switch supervised for system testing
If the user silences the alarm output, the D8130
contacts deactivate. Latching features must be
provided for pilot relays or contactor units requiring
control beyond the programmed indicating device time
or after manual silencing of the indicating circuits.
Supervised Disable Switch
To facilitate fire alarm installation testing, the D8130
Module contains a supervised disable switch that
prevents operation of the relay contacts. An amber
Disable LED indicates when the switch is in the
disable position. Connect one or more D8130 modules
to any unused 1 kΩ zone or point of the control panel
to detect module disabling.
A trouble is indicated when the D8130 switch is in the
disable position, and a restoral signal is sent when the
switch is returned to the normal position. (Refer to the
control panel’s Program Entry Guide for details on
programming a trouble signal for an open or short
condition.) When the contacts are activated with the
switch in the normal position, no trouble indications
are sent to the control panel.
Release Contact Outputs
A normally-open (NO) terminal, a normally-closed (NC)
terminal, and a common (COM) terminal are provided
for each D8130 contact. In the inactive state of the
contact, the NC terminal has continuity with the COM
terminal. In the active state of the contact, the NO
terminal has continuity with the COM terminal.
2 | D8130 Door Release Module
Certifications and approvals
Complies with NFPA 72
Region Certification
USA UL AMCX: Central Station Alarm Units
CSFM see our website
FDNYCoA
NYCMEA
NYCMEA
(UL1610, UL1635), AOTX: Local Alarm
Units (UL464, UL609), APAW: Police
Station Alarm Units (UL365, UL464),
APOU: Proprietary Alarm Units
(UL1076), NBSX: Household Burglar
Alarm System Units (UL1023), UOJZ:
Control Units, System (UL864, 9th edition), UTOU: Control Units and Accessories - Household System Type (UL985)
6174
12-92-E, Vol. 12 12-92-E, Vol. 12
12-92-E, Vol. XV
Installation/configuration notes
Compatible Products
The following products are compatible with the D8130
Release Module:
Category Product ID Product Description
Control
Panels
D9412 Control panel
D7412 Control panel
D7212** Control panel
D9124 Addressable fire alarm control panel
Modules D191C Bell supervision module
D192G Notification Appliance Circuit (NAC)
G Series* Control panels
Module
* G Series included B9512G, B8512G, D9412GV4,
D8412GV4, D7212GV4**, D9412GV3, D8412GV3,
D7212GV3**, D9412GV2, D8412GV2, D7212GV2**,
D9412G, D8412G, D7212G**
** The D7212 models are not listed for commercial fire
applications.
Mounting Considerations
The D8130 Door Release Module mounts in the control
panel enclosure or in a separate approved enclosure.
Up to four modules can be installed using the
mounting locations provided.
Notice
Use a D138 Mounting Bracket to mount the D8130
in the D9124 FACP.
Wiring
Use the following table to determine correct contact
wire size:
Maximum Wire Impedance: 6 Ω
Distance (maximum) Wire Size
350 ft 22 AWG
800 ft 18 AWG
Parts included
Quant. Component
1 Door release module
1 Hardware pack
1 Literature pack
Technical specifications
Mechanical Properties
Dimensions (H x W x D): 5 in. x 3 in. x 0.75 in.
(12.7 cm x 7.6 cm x 1.9 cm)
Outputs
Relays: Two Form C dry contact
Relay Rating: 5.0 A at 30 VDC maximum for resistive loads
Power Requirements
Current
Alarm: 60 mA maximum
Contacts Disabled: 15 mA
Standby: 7 mA
Voltage
Nominal: 12 VDC nominal
Ordering information
D8130 Door Release Module
Provides two independent Form C dry contacts, each
rated at 5 A, to connect low-voltage circuits to
magnetic door holders, pilot relays, or contactor units
for function control
Order number D8130
Accessories
D137 Mounting Bracket
Used to mount accessory modules in D8103, D8108A,
and D8109 enclosures.
Order number D137