Bosch D7212GV4K7 Installation Manual

1 | Overview
The B208 Octo-input Module is an 8 point supervised expansion device that connects to control panels through the SDI2 bus. This module communicates back to the control panel all point status changes. The inputs are accessed through on-board screw terminal connections.
6
Figure 2.1: Address switches
= Inputs 11 to 18
= Inputs 111 to 118
3 | Installation
After you set the address switches for the proper address, install the module in the enclosure, and then wire it to the control panel.
CAUTION!
Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage.
1
2
TMPR
PWR A B COM
3 4 5
Figure 1.1: Board overview
1 COM 2
3 COM 4 5 COM 6
7 COM 8
Callout ― Description
1 ― Heartbeat LED (blue)
2 ― SDI2 interconnect wiring connectors (to control panel or additional modules)
3 ― SDI2 terminal strip (to control panel or additional modules)
4 ― Tamper switch connector
5 ― Terminal connector (point inputs)
6 ― Address switches
2 | SDI2 address settings
Two address switches determine the address for the B208 Octo-input Module. The control panel uses the address for communications. The address also determines the output numbers. Use a slotted screwdriver to set the two address switches.
NOTICE!
The module reads the address switch setting only during power up. If you change the switches after you apply power to the module, you must cycle the power to the module to enable the new setting.
Set the address switches per the control panel confi guration. If multiple B208 modules reside on the same system, each B208
The module’s address switches provide a tens and ones value for the module’s address. For single-digit address numbers 1 through 9, set the tens switch to 0 and the ones digit to the appropriate number. Figure 2.1 shows the address switches setting for addresses 1 and 11.
2.1 | Valid addresses and input numbers per control panel
Valid B208 addresses are dependent on the number of points allowed by a particular control panel. Addresses higher than 32 require B208 fi rmware version 1.03.003 or higher.
Control panel
B9512G 01 - 59 11 - 18, 21 - 28, 31 - 38, 41 - 48,
B8512G 01 - 09 11 - 18, 21 - 28, 31 - 38, 41 - 48,
B5512 01 - 04 11 - 18, 21 - 28, 31 - 38, 41 - 48
B4512 01 - 02 11 - 18, 21 - 28
D9412GV4 01 - 24 11 - 18, 21 - 28, 31 - 38, 41 - 48,
D7412GV4 01 - 07 11 - 18, 21 - 28, 31 - 38, 41 - 48,
D7212GV4 01 - 03 11 - 18, 21 - 28, 31 - 38
To determine the point numbers for each address, multiply the address number by 10 for the base number, and then use numbers 1 through 8 in the ones place for the point numbers. For examples, refer to Section 8.
Valid B208 addresses
Corresponding point numbers
51 - 58, 61 - 68, 71 - 78, 81 - 88, 91 - 98, 101 - 108, 111 - 118, 121 - 128, 131 - 138, 141 - 148, 151 - 158, 161 - 168, 171 - 178, 181 - 188, 191 - 198, 201 - 208, 211 - 218, 221 - 228, 231 - 238, 241 - 248, 251 - 258, 261 - 268, 271 - 278, 281 - 288, 291 - 298, 301 - 308, 311 - 318, 321 - 328, 331 - 338, 341 - 348, 351 - 358, 361 - 368, 371 - 378, 381 - 388, 391 - 398, 401 - 408, 411 - 418, 421 - 428, 431 - 438, 441 - 448, 451 - 458, 461 - 468, 471 - 478, 481 - 488, 491 - 498, 501 - 508, 511 - 518, 521 - 528, 531 - 538, 541 - 548, 551 - 558, 561 - 568, 571 - 578, 581 - 588, 591 - 598
51 - 58, 61 - 68, 71 - 78, 81 - 88, 91 - 98
51 - 58, 61 - 68, 71 - 78, 81 - 88, 91 - 98, 101 - 108, 111 - 118, 121 - 127, 131 - 138, 141 - 148, 151 - 158, 161 - 168, 171 - 178, 181 - 188, 191 - 198, 201 - 208, 211 - 218, 221 - 228, 231 - 238, 241 - 247
51 - 58, 61 - 68, 71 - 75
3.1 | Mount the module in the enclosure
Mount the module into the enclosure’s 3-hole mounting pattern using the supplied mounting screws and mounting bracket. Refer to Figure 3.1.
Figure 3.1: Mounting the module in the enclosure
Callout ― Description
1 ― Module with mounting bracket installed
2 ― Enclosure
3 ― Mounting screws (3)
3.2 | Mount and wire the tamper switch
You can connect an optional enclosure door tamper switch for one module in an enclosure. Installing the optional tamper switch:
1. Mount the ICP-EZTS Tamper Switch (P/N: F01U009269) into the enclosure’s tamper switch mounting location. For complete instructions, refer to EZTS Cover and Wall Tamper Switch Installation Guide (P/N: F01U003734).
2. Plug the tamper switch wire onto the module’s tamper switch connector. Refer to Figure 1.1.
3.3 | Wire to the control panel
When you wire the module to a control panel, you can use either the module’s terminal strip labeled with PWR, A, B, and COM, or the module’s interconnect wiring connectors (wire included). Interconnect wiring parallels the PWR, A, B, and COM terminals on the terminal strip. Figure 1.1 indicates the location of both the terminal strip and the interconnect connectors on the module.
Refer to Figures 3.2, 3.3, and 3.4.
NOTICE!
Use either the terminal strip wiring or interconnect wiring connector to the control panel. Do not use both. When connecting multiple modules, you can combine terminal strip and interconnect wiring connectors in series.
Figure 3.2: Using terminal strip or interconnect cable wiring
D9412GV4 shown)
Callout ― Description
1 ― Terminal strip wiring (SDI2)
2 ― Interconnect cable (P/N: F01U079745) (included)
Figure 3.3: Installing multiple modules using the SDI2 terminal
strip (D9412GV4 shown)
Callout ― Description
1 ― Bosch control panel
2 ― B208 modules
Figure 3.4: Installing multiple modules using the SDI2 interconnect wiring connector (D9412GV4 shown)
Callout ― Description
1 ― Bosch control panel
2 ― B208 modules
3.4 | Sensor loop wiring
Wire resistance on each sensor loop must be less than 100 Ω with the detection devices connected. The terminal strip supports 12 to 22 AWG (0.65 to 2 mm) wires. The B208 detects open, short, normal, and ground fault circuit conditions on its sensor loops and transmits the conditions to the control panel. Each sensor loop is assigned a point number and transmits to the control panel individually. from the premises telephone and AC wiring.
Run wires away
For the dual EOL resistor circuit style order ICP-1K22AWG-10, a package of 10 1.0 kΩ EOL resistors.
NC
Point
COM
1
Point
COM
1.0 k:
2
NC
1.0 k:
1.0 k:
NO
5
3
4
Figure 3.5: Sensor loop wiring single (upper) and dual (lower)
Callout ― Description
1 ― Point sensor loop terminals
2 ― Normally closed device (contact)
3 ― 1 kΩ resistor at device
4 ― 1 kΩ resistor at end-of-line (EOL)
5 ― Normally open device (contact)
Dual EOL requires B208 fi rmware v1.05.001 or higher. Dual EOL meets the requirement of double protection for medium to high risk ULC installations.
4 | LED descriptions
The module includes one blue heartbeat LED to indicate that the module has power and to indicate the module’s current state. Refer to Table 4.1.
Flash Pattern Function
Flashes once every 1 sec
3 quick fl ashes every 1 sec
ON Steady LED trouble state: Module is not
OFF Steady
Table 4.1: LED descriptions
Normal state: Indicates normal operation state.
Communication error state: Indicates (the module is in a “no communication state”) resulting in an SDI2 communication error.
powered (for OFF Steady only), or some other trouble condition prohibits the module from controlling the heartbeat LED.
5 | Show the fi rmware version
To show the fi rmware version using an LED fl ash pattern:
- If the optional tamper switch is installed: With the enclosure door open, activate the tamper switch (push and release the switch).
- If the optional tamper switch is NOT installed: Momentarily short the tamper pins.
Refer to Figure 5.1 for an example of fl ash pattern
s.
Figure 5.1: Firmware LED fl ash patterns
When the tamper switch is activated, the heartbeat LED stays OFF for 3 seconds before indicating the fi rmware version. The LED pulses the major, minor, and micro digits of the fi rmware version, with a 1 second pause after each digit.
In the following example, the version 1.4.3 shows as LED fl ashes: [3 second pause] *___****___*** [3 second pause, then normal operation].
6 | Certifi cations
Region
USA UL 365 - Police Station Connected Burglar Alarm
Units and Systems
UL 609 - Local Burglar Alarm Units and Systems
UL 636 - Holdup Alarm Units and Systems
UL 864 - Control Units and Accessories for Fire Alarm Systems (Commercial Fire)
UL 985 - Household Fire Warning System Units
UL 1023 - Household Burglar Alarm System Units
UL 1076 - Proprietary Burglar Alarm Units and Systems
UL 1610 - Central Station Burglar Alarm Units
CSFM - California Offi ce of The State Fire Mar­shall
FCC Part 15 Class B
FDNY - Fire Department of New York
FM 3010 - Fire Alarm Signaling Systems
Canada CAN/ULC S303 - Local Burglar Alarm Units and
Systems
CAN/ULC S304 - Signal Receiving Centre and Premise
ICES-003 - Information Technology Equipment (ITE)
ULC-ORD C1023 - Household Burglar Alarm System Units
ULC-ORD C1076 - Proprietary Burglar Alarm Units and System
7 | Specifi cations
Dimensions 2.5 in x 3.8 in x 0.60 in
(63.75 mm x 96 mm x 15.25 mm)
Voltage
12 V nominal
(operating)
Current
35 mA
(maximum)
Operating
+32°F to +122°F (0°C to +50°C)
temperature
Relative humidity
5% to 93% at +90°F (+32°C) non­condensing
Loop inputs Up to eight inputs. Input contacts may be
Normally Open (NO) or Normally Closed (NC). NOTICE! Normally Closed (NC) is not permitted in Fire installations.
Loop End-of­Line (EOL) resistance
Loop wiring
Loops can be confi gured for single or dual EOL resistor circuit style using 1k Ω resistors.
100 Ω maximum
resistance
Loop states (Single EOL resistor
Short: 0 - 1.1 VDC Normal: 1.25 - 1.9 VDC Open: 2.25 - 5 VDC
circuit style)
Terminal
12 AWG to 22 AWG (2 mm to 0.65 mm)
wire size
SDI2 wiring Maximum distance - Wire size (Unshielded
wire only): 1000 ft (305 m) - 22 AWG (0.65 mm) 1000 ft (305 m) - 18 AWG (1.02 mm)
Compatibility B9512G/B9512G-E
B8512G/B8512G-E B5512/B5512E B4512/B4512E D9412GV4 D7412GV4 D7212GV4 (Refer to the control panel installation document for number of supported devices.)
8 | Point number examples
For B208 address 01 the point numbers for the input devices are 11 through 18:
Terminal no 12345 678
Input no 11 12 13 14 15 16 17 18
For B208 address 11 the point numbers for the input devices are 111 through 118:
Terminal no 12345 678
Input no 111 112 113 114 115 116 117 118
Octo-input Module
B208
en Installation Guide
Bosch Security Systems, Inc.
130 Perinton Parkway Fairport, NY 14450 USA
www.boschsecurity.com
Bosch Sicherheitssysteme GmbH
Robert-Bosch-Ring 5 85630 Grasbrunn Germany
Copyright
This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved.
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Bosch Security Systems, Inc. product manufacturing dates
Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at http://www.boschsecurity.com/datecodes/.
© 2015 Bosch Security Systems, Inc. F.01U.265.456 | 05 | 2015.06
Loading...