Bosch B520 Specsheet

Intrusion Alarm Systems | B520 Auxiliary Power Supply Module
B520 Auxiliary Power Supply Module
www.boschsecurity.com
u Provides up to 2A of 12V standby current for Fire or
Burglar Applications (4A of Burglary alarm current)
u Supervises up to two 12v 7-18Ah batteries
The B520 Auxiliary Power Supply Module is a fully supervised, addressable SDI2 bus device that provides an integrated auxiliary power supply solution for Bosch control panels.
System overview
The B520 Auxiliary Power Supply Module is an auxiliary power supply expansion device that connects to compatible control panels through the SDI2 bus. This module is supervised and communicates back to the control panel all status changes. Industrial, commercial, and institutional facilities are typical installations for the B520 module. The B520 rotary switches allow for ease of use in device addressing. The SDI2 Out terminals provide auxiliary power for SDI2 expansion devices such as keypads. The AUX PWR terminals provides added auxiliary power capabilities for additional devices such as PIR’s.
Functions
Supervision Monitoring
The module monitors and communicates status information over the SDI2 bus for the following:
• Operation (Heartbeat)
• Battery 1 (BATT 1)
• Battery 2 (BATT 2)
• AC input power (AC)
u Provides up to 80 hours of standby time
u Uses the Bosch standard TR1850 plug-in
transformer
u Easy to read rotary switch addressing
• Battery OK
• Low Battery
• Missing Battery
Indicators
• Heartbeat [icon]: Blue LED flashing On and Off when system is operating normally. A steady On or Off LED indicates a system error. Triple flash indicates communication failure.
• BATT 1 LED: Green steady On LED indicates the battery status of BATT 1 is operating normally. Flashing indicates low battery. Triple flash indicates battery charger failure. Off LED indicates a missing battery.
• BATT 2 LED: Green steady On LED indicates the battery status of BATT 2 is operating normally. Flashing indicates low battery. Triple flash indicates battery charger failure. Off LED indicates a missing battery.
• AC LED: Green steady On LED indicates the AC power is operational. A pulsating LED (3 pulses per sec.) occurs when a battery test is being performed. Flashing indicates low or failed AC.
Battery Charging
Fully charged batteries, connected to the battery terminals, sustain power to the B520 in the event that the AC power fails.
2 | B520 Auxiliary Power Supply Module
If AC power fails (is absent, or low) on the B520, the B520 automatically switches from primary power (AC) to secondary power (battery). When AC power is present, the B520 performs periodic battery tests to ensure battery life and usability.
Certifications and approvals
Region
US UL 365 Police Station Connected Burglar
Alarm Units and Systems
UL 609 Local Burglar Alarm Units and Systems
UL 636 Holdup Alarm Units and Systems
UL 864 Control Units and Accessories for Fire Alarm Systems
UL 985 Household Fire Warning System Units
UL 1023 Household Burglar Alarm System Units
UL 1076 Proprietary Burglar Alarm Units and Systems
UL 1610 Central Station Burglar Alarm Units
FCC Part 15 Class B
Canada CAN/ULC S303 Local Burglar Alarm Units
and Systems
CAN/ULC S304 Signal Receiving Centre and Premise Alarm Control Units
ULC-ORD C1023 Household Burglar Alarm System Units
ULC-ORD C1076 Propriety Burglar Alarm Units and Systems
ICES-003 Digital Apparatus
Region Certification
USA UL 20121010-S5579
CSFM see our website
Installation/configuration notes
Mounting Considerations
You can mount the B520 Auxiliary Power Supply Module in a variety of enclosures for optimal situations. Mounting in the D8103 requires the addition on the B12 Mounting plate. The D8103 enclosure supports up to two 12V, 18Ah batteries. The B10 supports either one 12V, 18Ah or up to two 12V, 7Ah batteries.
Wiring Considerations
The B520 connects to a control panel using the SDI2 IN connections (PWR, A, B, COM). Use 12 AWG to 22 AWG (1.5 mm to 0.6 mm) wires from the power supply to the control panel. The B520 provides auxiliary power to expansion modules via the SDI2 OUT (PWR, A, B, COM), or AUX Power (AUX PWR) connections using the screw terminal strip, or by using the interconnect wiring connection. Use 12 AWG to 22 AWG (1.5 mm to
0.6 mm) wires from the module to the SDI2 expansion module(s).
Parts included
Quantity Component
1 B520 Auxiliary Power Supply module
1 Hardware pack
1 Literature pack
B520 Kit, B10 Enclosure
Kit contents include:
• B520 Aux Power Supply
• TR1850 transformer
• B10 white enclosure
Order number: B520-B
B520 Kit, D8103 Enclosure
Kit contents include:
• B520 Aux Power Supply
• TR1850 transformer
• B12 mounting plate
• D8103 gray, steel enclosure
Order number: B520-C
Technical specifications
Properties
Board Dimensions 11.43 cm x 17.62 cm x 2.9 cm
Maximum Distance – Wire Size
Compatibility GV4 Series control panels (Up to 8
(4.5 in x 6.94 in x 1.15 in)
305 m (1000 ft) - 0.65 mm (22 AWG) 305 m (1000 ft) – 2 mm (18 AWG) Unshielded wire only
B520 Auxiliary Power Supply Modules per control panel) D8103 Enclosure B10 Large Control Panel Enclosure B12 Mounting Plate for the D8103 Enclosure D8108A Attack Enclosure D2203 Enclosure BATB-40 Enclosure AE1, AE2 Enclosures D8004 Transformer Enclosure*
B501-10 Interconnect cables (10 per pack)