BFT SP 4000 User Manual

Page 1
8
0 2 7 9 0 8 1 1 4 3 4 1
AUTOMAZIONE PER CANCELLI SCORREVOLI A CREMAGLIERA
GB
AUTOMATION FOR RAK SLIDING GATES
F
AUTOMATIONS POUR PORTAILS COULISSANTS Á CREMAILLÉRE
D
AUTOMATIONENE FÜR SCHIEBEGITTERTORE MIT ZAHNSTANGE
E
AUTOMATIZACIONES PARA PORTONES CORREDIZOS CON CREMALLERA
P
ACCIONADOR PARA PORTÖES DE CORRER A CREMALLERA
SP4000 - SP4000 FAST
D811229 ver.05 11-10-07
ISTRUZIONI D’USO E DI INSTALLAZIONE
INSTALLATION AND USER’S MANUAL
INSTRUCTIONS D’UTILISATION ET D’INSTALLATION
INSTALLATIONS-UND GEBRAUCHSANLEITUNG
INSTRUCCIONES DE USO Y DE INSTALACION
INSTRUÇÕES DE USO E DE INSTALAÇÃO
Via Lago di Vico 44 36015 Schio (VI) - Italy Tel. +39 0445 69 65 11 Fax. +39 0445 69 65 22 www.bft.it e-mail: info@bft.it
Page 2
ENGLISH
Fig. 2
Fig. 1
C
C
V
4 - SP4000 - SP4000 FAST - Ver. 05
D811229_05
USER’S MANUAL
Thank you for buying this product, our company is sure that you will be more than satisfied with the product’s performance. The product is supplied with a “Warnings” leaflet and an “Instruction booklet”. These should both be read carefully as they provide important information about safety, installa­tion, operation and maintenance. This product complies with the recognised technical standards and safety regulations. We declare that this product is in conformity with the following European Directives: 89/336/EEC, 73/23/EEC and 98/37/EEC (and subsequent amendments).
1) GENERAL OUTLINE
The SP4000 - SP4000 FAST controller consists of a strong gearmotor. The motor/reduction gear is an hydrodynamic coupling tipe that allows the gate leaf to start and stop smoothly, in order to avoid high structural stress. The self-braking motor allows the leaf to stop rapidly avoiding uncontrollable inertial sliding movements. The gearmotor is joined to the gate by means of a rack. The control panel is incorporated and comprises: protection fuses, three-phase overload cutout and control unit. The function logic allows various configurations to be set in order to bet­ter adapt the automation to the customer’s needs (e.g.: automatic closing, photocells activated on closing, etc.). To change any settings, contact a qualified technician (installer). The irreversible type gearmotor keeps the leaf locked on closing. This way it does not need an electric lock. A manual release system allows the leaf to be opened manually in case of power supply disconnection or inefficiency. The installation must be provided with all the devices needed to guarantee safety of persons, animals and things, according to the provisions set out by the current standards.
2) SAFETY
If correctly installed and used, this automation device satisfies the required safety standards. However, it is advisable to observe some practical rules in order to avoid accidental problems. Before using the automation device, carefully read the operation instructions and keep them for future reference.
• Keep children, persons and things outside the automation working area, particularly during operation.
• Keep radio control or other control devices out of children’s reach, in order to avoid any unintentional automation activation.
• Do not intentionally oppose the leaf movement.
• Do not attempt to open the gate manually before to have released the motor by mean of the appropriate key.
• Do not modify the automation components.
• In case of malfunction, disconnect the power supply, activate the emer­gency release in order to be able to open the gate manually and request the assistance of a qualified technician.
Before proceeding to any outside cleaning operation, disconnect the mains powers supply.
• Keep the sliding guide of the gate, photocell optical components and light signal devices clean. Check that the safety devices (photocells) are not obscured by branches or shrubs.
• Check the rack lubrication periodically.
For any direct assistance to the automation system, request the help of a qualified technician (installer).
• Have qualified personnel checking the automation system once a year.
3) EMERGENCY MANOEUVRE
When the electric supply is disconnected or the automation is faulty, the leaf must be opened manually.
3.1) Activation
• Open the front actuator door using the key provided (fig.1).
• At the time of opening, a safety microswitch stops the actuator from operating electrically.
• Take out the release key (fig.2 ref. “C”) located inside the box and insert it in the release screw (fig.2 ref. “V”) .
• Turn the key (fig.2 ref. “C”) anticlockwise until the pinion drive system becomes completely loosen.
• This way, the pinion is released and the gate can be operated manually.
WARNING - Considering the leaf weight, it is recommended to guide the leaf manually along the entire run, and absolutely avoid to push it in an uncontrolled way.
3.2) Re-activation
• Open the actuator door with the appropriate key.
• Insert the release key (fig.2 ref. “C”) in the release screw (fig.2 ref. “V”) and turn it clockwise until it is completely tightened.
• Put release key “C” back in its place, close the actuator door and check that the automation operates electrically.
• Put the actuator door key away in a safe place known to the operators.
4) MAINTENANCE AND DEMOLITION
The maintenance of the system should only be carried out by qualified personnel regularly. The materials making up the set and its packing must
be disposed of according to the regulations in force.
Batteries must be properly disposed of.
WARNINGS Correct controller operation is only ensured when the data contained in the present manual are observed. The company is not to be held responsible for any damage resulting from failure to observe the installation standards and the instructions contained in the present manual.
The descriptions and illustrations contained in the present manual are not binding. The Company reserves the right to make any alterations deemed appropriate for the technical, manufacturing and commercial improvement of the product, while leaving the essential product fea­tures unchanged, at any time and without undertaking to update the present publication.
Page 3
ENGLISH
14 - SP4000 - SP4000 FAST - Ver. 05
D811229_05
INSTALLATION MANUAL
Thank you for buying this product, our company is sure that you will be more than satisfied with the product’s performance. The product is supplied with a “Warnings” leaflet and an “Instruction booklet”. These should both be read carefully as they provide important information about safety, installa­tion, operation and maintenance. This product complies with the recognised technical standards and safety regulations. We declare that this product is in conformity with the following European Directives: 89/336/EEC and 73/23/EEC, 98/37/EEC (and subsequent amendments).
1) GENERAL SAFETY WARNING! An incorrect installation or improper use of the product can
cause damage to persons, animals or things.
The “Warnings” leaflet and all “Instruction booklets” supplied with this
product should be read carefully as they provide important information about safety, installation, operation and maintenance.
Scrap packing materials (plastic, cardboard, polystyrene etc) according
to the provisions set out by current standards. Keep nylon or polystyrene bags out of children’s reach.
Keep the instructions together with the technical brochure for future
reference.
This product was exclusively designed and manufactured for the use
specified in the present documentation. Uses not specified in this docu­mentation could damage the product and be dangerous.
The Company declines all responsibility for any consequences result-
ing from improper use of the product, or use which is different from that expected and specified in the present documentation.
Do not install the product in explosive atmosphere.
The construction elements must comply with the Current Standards.
The Company declines all responsibility for any consequences result-
ing from failure to observe good technical practice when constructing closing structures (door, gates etc.), as well as from any deformation which might occur during use.
The installation must comply with the provisions set out by the Current
Standards and always respect good technical practice.
Disconnect the electrical power supply before carrying out any
operations on the installation. Also disconnect any buffer batteries, if fitted.
Fit an omnipolar circuit breaker or thermal magnetic circuit breaker on
the mains power supply, having a contact opening distance equal to or greater than 3 mm.
Check that a differential switch with a 0.03A threshold is fitted just before
the power supply mains.
Check that earthing is carried out correctly: connect all metal parts for
closure (doors, gates etc.) and all system components provided with an earth terminal.
Fit all the safety devices (photocells, electric edges etc.) which are needed
to protect the area from any danger caused by squashing, conveying and shearing.
Place at least one light signal device (blinker), and fix a Warning sign
to the structure where it can be easily seen.
The Company declines all responsibility with respect to the automation safety
and correct operation when other manufacturers’ components are used.
Only use original parts for any maintenance or repair operation.
Do not modify the automation components, unless explicitly authorised
by the company.
Instruct the product user about the control systems provided and the
manual opening operation in case of emergency.
Do not allow persons or children to remain in the automation operation
area.
Keep radio control or other control devices out of children’s reach, in
order to avoid unintentional automation activation.
The user must avoid any attempt to carry out work or repair on the
automation system, and always request the assistance of qualified personnel.
Anything which is not expressly provided for in the present instructions,
is not allowed.
• Installation must be carried out using the safety devices and controls prescribed by the EN 12978 Standard.
2) GENERAL OUTLINE
The SP4000 - SP4000 FAST controller consists of a strong gearmotor. The motor/reduction gear is an hydrodynamic coupling tipe that allows the gate leaf to start and stop smoothly, in order to avoid high structural stress. The self-braking motor allows the leaf to stop rapidly avoiding uncontrollable inertial sliding movements. The gearmotor is joined to the gate by means of a rack. The control panel is incorporated and comprises: protection fuses, three-phase overload cutout and control unit.
The function logic allows various configurations to be set in order to bet­ter adapt the automation to the customer’s needs (e.g.: automatic closing, photocells activated on closing, etc.). To change any settings, contact a qualified technician (installer). The irreversible type gearmotor keeps the leaf locked on closing. This way it does not need an electric lock. A manual release system allows the leaf to be opened manually in case of power supply disconnection or inefficiency. The installation must be provided with all the devices needed to guarantee safety of persons, animals and things, according to the provisions set out by the current standards. The gearmotor (fig.1) comprises :
MF) Motor with electric brake G) Hydrodynamic motor/reduction gear coupling R) Reduction gear in oil bath with worm screw/wheel MS) Opening door safety microswitch S) Electromechanical end-of-stroke unit P) Pinion Q) Control panel SB) Emergency release C) Box with lockable door.
3) TECHNICAL SPECIFICATIONS
3.1) SP4000 - SP4000 FAST
Power supply ...... : three-phase+N 400V three-phase 230V ±10% 50Hz (*)
Motor revolutions ................................................... ....: 1400min
.........................................................................2800 min
-1
-1
(SP 4000)
(SP 4000 FAST)
Absorbed power .............................................................................: 1500W
Max absorbed power ....................................... : 2.6A (400V); 4.84A (230V)
Protection .............................................: overload cutout wired in the panel
Insulation class ........................................................................................ : F
Reduction ratio ....................................................................................: 1/46
Output revolutions .......................................................... : 30min
............................................................................. 60 min
-1
(SP 4000)
-1
(SP 4000 FAST)
Pinion pitch .................................................................: m=6mm z=18 teeth
Max leaf weight ............................................ : 40000N (~4000kg) (SP 4000)
.......................................................... : 10000N (1000kg) (SP 4000 FAST)
Leaf speed ................................................................: 10.1m/min (SP 4000)
...................................................................... : 20.2 m/min (SP 4000 FAST)
Impact reaction .....................................................: stop (with electric edge)
Reduction gear lubrication ......................................................................: oil
Manual manoeuvre ...............................: multi-disk mechanical key release
No. manoeuvres in 24 hours .........................................: continuous service
Control unit ......................................................... : SIRIO TEL with interface
Environmental conditions ..........................................: from -15°C to +50°C
Degree of protection ...........................: IP X4(Electrical components:IP 54)
Dimensions ..................................................................................: See fig. 2
Controller weight ...................................................................: 850N (~86kg)
(*) 230V three-phase power supply available
3.2) SIRIO TEL
Power supply (*):....................400 vac three-phase + /230 vac three-phase
Mains - low voltage insulation:........................................ > 2MOhm 500Vdc
Mains - low voltage dielectric strength: .......................................3750Vac 1'
Power supply to accessories: ....................................................24Vac/0,5A
Gate-open warning light:....................................................................24/3W
Blinker: .........................................................................................230V/40W
4) PRELIMINARY CHECKS
Check that the gate structure is conform to whatever is prescribed by the current standards, and in particular that:
• the gate sliding track is linear and horizontal, and the wheels are suitable for supporting the gate weight;
• the gate manual operation can be carried out smoothly along its entire run, and there is no excessive side slipping;
• a correct play is provided between the upper guide and the gate to ensure regular noiseless movement;
• the gate stops on opening and closing are or can be positioned;
• the established position for gearmotor fixing allows the emergency manoeuvre to be carried out smoothly and safely.
In the case where the elements checked do not meet the above requirements,
proceed to carrying out the necessary corrective actions or replacements.
WARNING: Remember that control devices are intended to facilitate gate use, but can not solve problems due to any defects or deficiency resulting from failure to carry out gate maintenance.
Take the product out of its packing and inspect it for damage. Should it be damaged, contact your dealer. Remember to dispose of its components (card­board, polystyrene, nylon, etc.) according to the current prescriptions.
Page 4
INSTALLATION MANUAL
ENGLISH
5) BASE PLATE ANCHORING
D811229_05
1) Identify a suitable position, and check that there are no underground cables or pipes.
2) Arrange for a pit or column near the fixing plate for the various con nections, in order to have a single raceway with a 60-80mm diameter reaching the actuator.
3) The anchoring base, which is already assembled (fig. 3), must be posi­tioned with the gear label facing the gate.
4) Dig a hole having the size specified in fig. 3, where to cement the base plate log bolts to fix the actuator with. If the sliding track is already there, digging must be partly carried out in the track foundation casting. This way, should the track sag, the gearmotor base would also lower, thus maintaining the play between pinion and rack (approximately 4-5mm). In order to keep the base plate correct position during installation, it may be useful to weld two iron rods under the track, and then weld the log bolts onto them (fig. 3).
5) Position the base plate according to the mesurement specified in fig. 4. The pinion symbol printed on the base plate must be visible and directed towards the gate. This also ensures the correct positioning of the pipe or the cable channel for electrical connections.
6) Let the single pipe or cable channel provided for electric cables protrude from the base plate.
7) Proceed to casting the concrete.
8) Accurately check that:
- The positioning dimensions (fig. 4) are correct,
- The base plate to be levelled in both directions,
- The 4 stud threads and the base are free from cement.
- Let the casting harden.
Note: The actuator must be fixed to the foundation base which comprises a steel plate treated against corrosion and the log bolts to anchor the plate to the ground.
WARNING: Do not loosen the nuts securing the log bolts. After cement­ing, use a dynamometric wrench to check that these are tightened with a 70Nm torque.
Fig. 5 shows dimensions and holes to be drilled in the actuator base.
6) GEARMOTOR FIXING
When the casting has hardened, make all the mains and accessory con­nection cables go through, letting them protrude from the foundation plate by approximately 1 metre. Observe fig. 6 and proceed as follows:
1) Open the door and unscrew the 4 screws which fix the protective cover to the base (fig. 1 ref. ”C”) using a suitable key.
2) Position the actuator over the plate, and insert all the cables or pipes in the appropriate hole (fig. 6), and the tie rods in the fixing slots.
3) Thread a flat spacer washer, a spring washer and an M12 nut on each one of the four base tie rods. Leave the nuts loose for correct positioning.
4) Fit the four levelling dowels (fig. 7 ref. “G”) and adjust them so as to level (fig. 7 ref. “L”) the actuator, which should be raised by approximately 8­10mm with respect to the foundation base.
5) Slide the actuator in the appropriate slots, find its final position respect­ing the measurements specified in fig. 4, and fix the four nuts (fig. 7 ref. “T”) which secure the actuator to the foundation plate and the levelling dowel lock nuts.
Note: the rack teeth should mesh with the pinion along their entire width.
7) ARRANGEMENT FOR RACK FITTING
A steel rack having a pitch of m=6mm teeth and cross section of at least 30x30mm must be fixed to the gate. It is usually supplied in 2-metre ele­ments. As far as length is concerned, this must take into account the passage space, the pinion meshing section and also the space for fixing the runners controlling the end-of-stroke. Rack fixing must be suitable for the type of gate used. As an example, this paragraph describes the rack fixing method by means of welded angle bars (fig. 8). WARNING – Welding is to be carried out by a skilled operator wearing all personal protective equipment prescribed by the current safety standards. During welding operations, use suitable screens to protect the actuator from any welding spits.
7.1) Fitting
1) Prepare some rack fixing angle bars using adequately-sized “L” shaped sections. They must be fixed or welded at a distance of approximately 80-100cm.
2) Bring the gate to a fully closed position (or open, if more practical) by hand.
3) Activate the emergency release (See paragraph on “EMERGENCY MANOEUVRE”).
4) Rest the end of one rack element on the control pinion, keeping it levelled (parallel to the track).
5) Rest one angle bar on the rack and secure it with a suitable clamp; while
-
keeping the rack level and lined up with the pinion profile, spot weld the angle bar to the gate and then the rack to the angle bar (fig. 8).
6) Push the leaf by hand as far as the other end of the rack, centre the rack into the pinion teeth, rest one angle bar on the rack, secure it with a suitable clamp, spot weld it to the gate and then weld the rack to the angle bar.
7) While sliding the leaf by hand, position and lightly spot weld the inter mediate angle bars (one every 80-100cm).
8) Slide the rack element out of the pinion, and strongly weld the angle bars and the rack.
WARNING: Do not weld the joints of the rack elements together.
9) Position another rack element next to the one welded previously. Couple the joints of the two elements by opposing a piece of rack (fig. 9) to keep the correct pitch, and secure everything using suitable clamps.
10) Proceed to welding and positioning all the elements by repeating the procedure described above.
8) Pinion adjustment
Having finished fixing the rack, the rack-pinion play must be adjusted as follows, with reference to fig. 10.
1) Slacken the four “G” dowels at the base of the actuator by approximately 4 mm.
2) Check levelling by means of a level.
3) Check that the rack meshes with the pinion all along its width and the leaf stroke.
4) Fix the 4 log-bolts nuts (fig. 10 ref. “T”) which fasten the actuator to the ground.
5) Fix the 4 levelling dowel lock nuts (fig. 10 ref. “G”).
6) Check the slack between pinion and rack along the whole rack length; if necessary, adjust the play between pinion and rack.
WARNING – Remember that the life of the rack and pinion largely de-
pends on the mesh.
9) FITTING OF END-OF-STROKE RUNNERS
These are used to control the opening/closing limit microswitches. They can be directly welded on the rack or fixed by means of screws. When fixed by screws, the runner position can be re-adjusted later.
WARNING - The automation must not be electrically operated without the end-of-stroke runners.
This operation is to be carried out with the emergency release activated and mains power supply disconnected.
1) If the mains power is already connected, ensure that the automation switch is down.
2) Activate the emergency release as described in the respective para­graph.
3) Push the leaf fully open by hand, and stop it approximately 4-5cm before the required stop point.
4) Connect an ohmmeter to the control unit terminals related to the opening limit switch (SWO) by consulting the paragraph on “Terminal connec- tions”. Check the instrument reading by pushing the end-of-stroke control lever by hand towards the opening direction (the instrument must show interruption of continuity).
5) Position the end-of-stroke runner on the rack and push it against the end­of-stroke lever (fig. 11 ref. “P”) until the instrument signals microswitch intervention.
6) After identifying the runner position, fix it by spot welding. In the case of screw fixing, mark the identified position and proceed accordingly.
7) Connect the instrument to the control unit terminals related to the clos­ing limit switch (SWC). Check the instrument reading by pushing the end-of-stroke control lever by hand towards the opening direction (the instrument must show interruption of continuity).
8) Push the leaf fully closed by hand. Stop the leaf by approximately 4­5cm from the required closing point. If necessary, take into account any clearance (fig.12) or impact device (fig.13 - ref. “CS”) needed, according to the provisions set out by current national standards.
9) Position the end-of-stroke runner on the rack and push it against the end­of-stroke lever until the instrument signals microswitch intervention.
10) After identifying the runner position, fix it by spot welding. In the case of screw fixing, mark the position and proceed accordingly.
11) Disconnect the instrument, restore motorised operation (see paragraph on “Emergency release”). Correct electrical limit switch intervention is to be checked after carrying out electrical connections and checking the “DIRECTION OF ROTATION” (see relevant paragraph). If the position is correct, secure the welded runners with sturdy welding, or check that the fixing screws to be well tightened (depending on the chosen fixing way).
SP4000 - SP4000 FAST - Ver. 05 - 15
-
Page 5
ENGLISH
16 - SP4000 - SP4000 FAST - Ver. 05
D811229_05
INSTALLATION MANUAL
IMPORTANT: In the case where the leaf keeps sliding after the stop command,
the moulded end section of the runner (fig. 11 ref. “A”) can be lengthened so as to stop the runner from going past the end-of-stroke point. WARNING! To avoid inefficiency, or damage to the automation, keep always a space of 4-5cm before the required opening/closing end positions (fig. 12).
10) GATE BACKSTOPS DANGER - The gate must be provided with mechanical backstops both on
closing and opening (fig. 12 ref. “F”) in order prevent it from coming out of the upper guide. The mechanical stops must be sturdily secured to the ground, a few centi­metres beyond the electric stop point.
11) ELECTRICAL INSTALLATION SET-UP
Lay out the electrical installation as shown in fig. 13, with reference to the CEI 64-8 and IEC 364 provisions complying with the HD 384 and other national standards in force for electrical installation. WARNING – Check the actuator rating. For the 400V three-phase version, connect the mains using a multipolar R-S-T-N+EARTH cable having a minimum cross section of 2.5 sq mm and complying with the current national standards (e.g.: H07RN-F type). For the 230V three-phase version, connect the mains using a multipolar R-S-T+EARTH cable having a minimum cross section of 2.5 sq mm and complying with the current national standards (e.g.: H07RN-F type). Connect the control and safety devices in compliance with the previously mentioned technical installation standards.
The mains power supply connections must be kept totally separate from the auxiliary connections.
Fig. 13 shows the number of connections and the cross section for approximate lengths of 100 metres; in case of greater lengths, calculate the cross section for the true automation load: The main automation components are (fig. 13): I Type-approved omnipolar circuit breaker with adequate capacity
and at least 3 mm contact opening, provided with protection against overloads and short circuits, suitable for cutting out automation from the mains. If not already installed, place a type-approved differential switch with a 0.03A threshold before the automation system
QR Control panel and incorporated receiver S Key selector AL Blinker with tuned antenna M Actuator E Electric lock P Control buttons CS Electric edge CC Edge control Fte, Fre Pair of external photocells Fti, Fri Pair of internal photocells CF Posts T 1-2-4 channel transmitter.
WARNING! Operator without torque limiter: install the actuator with appropriate safety systems (eg. device type E item 5.5.1 of
EN12453:2000 standard)
12) CONTROL PANEL CONNECTIONS
After the appropriate electric cables have been passed through the raceways and fixed to the various automation components in the chosen points, these must be connected according to the indications and diagrams shown in the relevant instruction manuals. Connect the phase, neutral (230V three-phase excluded), and earth (compul­sory) cables. The protection (earth) wire, having a yellow/green insulating sheath, must be connected to the appropriately marked terminals provided . The automation device is to be operated after all the safety devices have been connected and checked. Fig. 14-15 shows the wiring diagram of the panel fitted to the actuator. Here follows a description of the terminals to be connected to the control panel (fig.14-15) including the SIRIO TEL mod. unit (fig. 16).
Panel N-R-S-T+ EARTH 400Vac ±10%, 50Hz, three-phase panel power supply R-S-T+ EARTH 230Vac ±10%, 50Hz, three-phase panel power supply
SIRIO TEL control unit terminal board (fig.16) N.B.:
The board is supplied with a series of previously bridged terminals. The jumpers refer to the following terminals: 26-29, 26-30, 26-31, 26-35. If these terminals are not used, leave them bridged.
JP1 - THREE-PHASE 400V
1-2-3-4 Three-phase power supply+neutral 400V (1N - 2R - 3S - 4T). 8-9 230Vac output for blinker 40W max.
JP1 - THREE-PHASE 230V
2-3-4 Three-phase power supply 230V (2R - 3S - 4T). 8-9 230Vac output for blinker 40W max.
JP2
10-11 24Vac (3W) output for gate-open warning light. 11-12 24Vac power supply to accessories and safety devices which are
12-13 24VTx power supply only for safety device transmitters which are
14 LOOP1 input for safety device check ring (see fig.5). 15 LOOP2 input for safety device check ring (see fig.5). 16-17 Second radio channel output for two-channel receiver board
18-19 Antenna input for radio receiver board (18 signal, 19 braid).
JP7
20-21-22 23-24-25 Outputs for the connection of safety devices which are to be che-
JP4
26-27 START button (n.o.). 26-28 Block button (n.c.). Additional buttons to be connected in series
26-29 Photocell contact input (n.c.). If not used, leave on. If used while
26-30 Opening limit switch (n.c.). If not used, leave bridged. 26-31 Closing limit switch (n.c.). If not used, leave bridged. 26-32 Pedestrian access button (n.o.). 26-33 Open button (n.o.). 26-34 Close button (n.o.). 26-35 IR edge contact input (n.c.). If not used, leave bridged.
JP6 1-2 channel radio receiver board connector.
12.1) Check of direction
WARNING! Before supplying the system with power, it is compulsory to check the “DIRECTION OF ROTATION” as described below.
1) Activate the release as described in the paragraph on “
2) Bring the leaf to the fully closed position by hand (limit microswitch
3) When the system is supplied with power (control unit door and box open),
If the LED are on, the SWO and SWO limit switch connections must be
4) Bring the leaf to the half-way position by hand.
5) Restore motorised operation (“EMERGENCY MANOEUVRE”) and
6) Disconnect the mains power supply temporarily to reset the control
7) At the first start command, the control unit always carries out the opening
a)if the gate moves along the opening direction, the direction of rotation
b)if the gate moves along the closing direction, disconnect the mains
8) Connect the mains power supply and carry out a complete checking cy
13) CONNECTION TO SAFETY DEVICES
• In case of standard devices with 4 terminals and without self-diagnostic
• In case of devices featuring internal self-diagnostic function, refer to point
• The standard devices with 5 terminals and without self-diagnostic function can
13.1) Safety devices WITHOUT SELF-DIAGNOSIS
Connections must be carried out as shown in fig. 18. Keep the Dip-switches 9 and 10 in the ON position (standard setting). The tripping contacts of a group of devices of the same type, must be connected in series with one another.
13.2) Safety devices WITH INTERNAL SELF-DIAGNOSIS
Connections must be carried out as shown in fig.18. Keep the Dip-switches 9 and 10 in the ON position (standard setting). The tripping contacts of several devices of the same type, must be connected in series.
not checked.
checked.
(n.o.).
cked (see fig.5).
with one another.
checking, observe wiring diagram in fig.5.
EMERGENCY
MANOEUVRE”.
pressed).
the SWC LED must be off.
reversed in the control unit.
reposition the box door to close the respective safety contact.
unit.
manoeuvre; check the following:
of the actuator is correct;
power supply and invert two phases in the control unit power supply terminal board.
cle.
function, the connection can be carried out without verification as indicated in point 13.1.
13.2.
be included in the control and self-diagnostic cycle observing the instructions given in point 13.3.
-
Page 6
INSTALLATION MANUAL
ENGLISH
13.3) Safety devices WITHOUT SELF-DIAGNOSIS but with voltage-free
D811229_05
EX-CHANGE CONTACTS.
We conventionally make reference to a receiving device (RCS- fig.5) with 5 terminals which have the following functions: terminals 1 and 2 are for 24Vac power supply, terminal 3 is a common terminal, terminal 4 is a normally closed contact not in use, terminal 5 is a normally open contact not in use.
Fig. 19 “A” shows the wiring diagram for connecting the power supply to
A)
those receivers and transmitters for which a self-diagnosis is required.
B) Fig. 19 “B”. Connection of one or more receivers (photocell) of the same
type up to a maximum of four (Dip 9 OFF/Dip 10 ON, photocells only, leave jumped 35-26). For example, if there are two photocells, connect F1 and F2, then interrupt the connection chain by connecting the terminal 4 of F2 to LOOP1 and the terminal 5 of F2 to COM. If only one receiver has to be connected, connection must be made as shown in fig.19 ref.1. If the receivers to be connected are less than four, it is necessary to interrupt the connection chain by performing the connections as shown in fig.19 ref. 2 or 3. If rubber edges instead of photocells have to be connected, use terminal 35-BAR of the control unit.
If the devices concerned are rubber edges instead of photocells, use terminal
35-BAR in the control unit (Dip 9 ON/Dip 10 OFF, leave jumped 29-26).
C) Connection of one photocell and one rubber edge.(Dip 9 OFF/Dip 10
OFF)
D) Connection of two photocells and one rubber edge.(Dip 9 OFF/Dip 10
OFF)
When connecting two rubber edges and one photocell, F1 and F2 in fig.19
“D” become 2 rubber edges, and C1 one photocell; invert the connections PHOT and BAR of the control unit with one another.(Dip 9 OFF/Dip 10 OFF)
E) Connection of three photocells and one rubber edge. When connecting
three rubber edges and one photocell, F1, F2 and F3 (fig.19 “E”) become 3 rubber edges and C1 one photocell; invert the connections PHOT and BAR of the control unit with one another.(Dip 9 OFF/Dip 10 OFF)
F) Connection of three photocells and two rubber edges When connecting
three rubber edges and two photocells, F1, F2 and F3 (fig.19 “F”) become three rubber edges, C1 and C2 two photocells; invert the connections PHOT and BAR of the control unit with one another.(Dip 9 OFF/Dip 10 OFF)
G) Connection of four photocells and one rubber edge. When connecting four
rubber edges and one photocell, F1, F2 , F3 and F4 (fig.19 “G”) become four rubber edges and C1 one photocell; invert the connections PHOT and BAR of the control unit with one another.(Dip 9 OFF/Dip 10 OFF)
14) OPERATION LOGIC
14.1) Dip-switch
Dip 1 and 2 ......................................................................Photocells (FCH)
ON - Excludes photocell operation during gate opening, and immediately rever-
ses movement during the closing phase when the photocell is obscured. OFF - In the case where the photocell is obscured by an obstacle during the closing manoeuvre, the gate is stopped; when the obstacle is removed, the gate reopens. In the case where the photocell is obscured by an obstacle during the opening manoeuvre, the gate is stopped; when the obstacle is removed, the gate continues to open.
Dip 3 ....................................................................... Impulse blocking (IBL)
ON - The Start / Start pedestrian impulse has no effect during the opening
phase. OFF - The Start / Start pedestrian impulse during the opening phase causes the gate to stop.
Dip 4 ................................................................... Automatic closing (TCA)
ON - Automatically closes the gate after a dwell time set by the TCA trimmer.
The automatic closing manoeuvre is activated after the gate has reached the opening end-of-stroke position, after the gate opening time has ended, or after the gate has stopped in the opening phase due to a Start impulse. OFF - Excludes automatic closing. Dip 5 2 or 4 step logic (2P/4P) ON - A Start impulse given during the closing phase reverses the direction of movement, during the opening phase it stops the gate. (Dip-switch OFF). OFF - A Start impulse given while the gate is moving, causes it to stop; the following impulse reverses the running direction. (4-step logic). N.B.: The Start impulse in the opening phase has no effect when Dip-switch 3 is ON.
Dip 6 .......................................................................... Pre-alarm (PREALL)
ON - The blinker comes on about 3 seconds before the motor starts. OFF - The blinker comes on at the same time as the motor starts.
Dip 7 .............................................................Open/Close command (U.P.)
Activates the signals connected to terminals 33-34. ON - Hold-to-run operation: the manoeuvre continues as long as pressure is maintained on the command button. OFF - Separate automatic Open/Close operation: by means of an impulse, it opens the gate if closed and vice versa.
Dip 8 .............................Reduced or normal operation time range (S.TW)
ON - TW operation time ranging between 1-90 seconds (TW.PED pedes-trian
operation time from 1 to 20 seconds). OFF - TW operation time ranging between 3÷210 seconds (TW.PED pede­strian operation time from 5 to 60 seconds).
Dip 9 ............................................................. Unchecked photocells (FNV)
Activates the photocell control logic. ON - The photocells are excluded from the safety check cycle which is carried out before each manoeuvre; however their logic state is analysed (for connection, refer to the typical method of connecting photocells with continuously active beams). This is used to connect photocells which have not been checked or have internal self-diagnosing systems, and always provide a voltage-free output contact. OFF - The photocells are included in the Ok safety check cycle which is carried out before each manoeuvre. For connection, refer to the enclosed diagrams.
Dip 10 ................................................................... Unchecked edge (BAR)
Activates the rubber edge device control logic. ON - The edge devices are excluded from the safety check cycle which is carried out before each manoeuvre; however their logic state is analysed (for connection, refer to the typical method of connecting infrared edges with continuously active beams). This is used to connect IR edges which have not been checked or have internal self-diagnosing system, and always provide a voltage-free output contact. OFF - The IR edge devices are included in the Ok safety check cycle which is carried out before each manoeuvre. For connection, refer to the enclosed diagrams.
14.2) Trimmer-set functions
TW.PED Sets the partial operation time of a sliding gate which is being used
for both vehicles and pedestrians.
TW Sets the operation time during both the opening and closing phases
(adjustable from 3 to 210 seconds).
TCA Sets the dwell time, after which the gate closes automatically (from
1 to 120 seconds).
14.3) LED functions
The SIRIOTEL control unit is provided with leds which are useful in identifying any anomalies in the system. (DL1) Stays on when supplied with mains power and with F1 fuse in-
tact.
(DL2) Comes on when the motor is activated during closing. (DL3) Comes on when the motor is activated during opening. (DL4) Comes on following the Start command or the activation of the first
radio-receiver channel.
(DL5) Goes off when the block command is activated. (DL6) Goes off when photocells are not aligned, i.e. when obstacles are
present. When Dip-switch 9 is OFF, the photocells and related leds are only activated during manoeuvring.
(DL7) Goes off when the gate is in the completely open position, if pro-
vided with end-of-stroke device.
(DL8) Goes off when the gate is in the completely closed position, if
provided with end-of-stroke device.
(DL9) Comes on at the Start command for pedestrian gate. (DL10) Comes on with manual opening command. (DL11) Comes on with manual closing command. (DL12) Goes off when the pneumatic edge is activated. When Dip-
switch 10 is OFF, the edge and its related LED are only activated during manoeuvring.
(DL13) Comes on when the safety ring is closed. (DL14) Comes on when the safety micro has stepped in.
15) EMERGENCY MANOEUVRE
When the electric supply is disconnected or the automation is faulty, the leaf must be opened manually.
15.1) Activation
• Open the front actuator door using the key provided (fig.23).
At the time of opening, a safety microswitch stops the actuator (fig.23
- ref. “S”) from operating electrically.
• Take out the release key (fig.23 ref. “C”) located inside the box and insert it in the release screw (fig.24 ref. “V”) .
• Turn key “C” anticlockwise until the pinion drive system becomes com­pletely loose.
This way, the pinion is released and the gate can be operated manu-
ally.
WARNING - Considering the leaf weight, it is recommended to guide the leaf manually along the entire run, and absolutely avoid pushing it in an uncontrolled way.
SP4000 - SP4000 FAST - Ver. 05 - 17
Page 7
ENGLISH
18 - SP4000 - SP4000 FAST - Ver. 05
D811229_05
INSTALLATION MANUAL
15.2) Re-activation
• Open the actuator door with the appropriate key.
• Insert the release key in the release screw (fig.24 - ref. “V”) and turn it clockwise until it is completely tightened.
• Put the release key back in its place, close the actuator door and check that the automation operates electrically.
• Put the actuator door key away in a safe place known to the operators.
16) AUTOMATION TESTING
Before the installation is made fully operational, carry out the following checks.
• Check that the overload cutout (fig.22 – ref. “SM”) is set for the rated current absorbed by the motor (400V / 2.8A) -(230V / 4.84A).
• Check that all safety devices (limit microswitches, photocells, electric edges, etc.) operate correctly.
• Check the tightening torque of the pinion release (emergency re­lease).
• Check that the leaf stops within the time and limits provided for by current prescriptions.
• Check that the rack-pinion mesh is correct (4mm minimum play).
• Check that the opening and closing end-of-stroke runners are correctly positioned and secured.
• Check the start and stop operation in case of manual control.
• Check the start and stop operation in case of remote radio control.
• Check the normal or customised function logic.
• Check that all components are tightly secured.
• Apply the danger warning label (fig. 23).
17) CONTROL
The use of this control device allows the gate to be opened and closed au­tomatically. There are different types of controls (manual, remote, magnetic badge access control, etc.) depending on the installation requirements and characteristics. For the various control systems, refer to the applicable instructions.
Explain the correct operation of the automation device to the end users.
18) Maintenance
WARNING! Any maintenance operation must be carried out by qualified
personnel (see paragraph 2).
• Check the play between the pinion and rack (4mm c.a.). Moderately clean
and grease the rack.
• Always keep the sliding track clean and free from debris.
• Occasionally clean the photocell optical elements.
• Check the correct tightening torque of the pinion release screw.
• When any operational malfunction is found, and not solved, disconnect
the mains power supply. When automation is out of order, activate the emergency release (see paragraph “EMERGENCY RELEASE”) so as to put the pinion in neutral and allow the gate to be opened or closed manually.
4) Check that the photocells or electric edges are neither dirty nor engaged nor misaligned. Otherwise proceed accordingly.
5) Check that the electronic equipment is correctly supplied with power. Check that the fuses are not damaged.
6) By means of the control unit diagnosing LEDs (see respective instructions), check that the functions are correct. If not, identify the cause of any fault. If the LEDs show a persistent unwanted start command, check that there are no radio controls, start buttons or other control devices keeping the start contact activated (closed).
7) If the control units does not work, replace it.
22.2) The gate does not open. The motor turns but there is no move-
ment.
1) The manual release was left activated. Restore motorised operation.
2) Check whether the gate is well housed in the mechanical end-of-stroke stops.
Release the gate manually, move it from its position and restore motorised
operation. Check and correct the position of the end-of-stroke runners to anticipate microswitch intervention. If after electric stoppage there is excessive leaf sliding, check the electric brake air gap, as specified in the motor instruction manual supplied with the product.
3) Check that the gate does not show mechanical defects, as for example wheels blocked, pinion/rack misaligned, etc.
4) If the motor turns, but the leaf is not strong enough to move, check that there are no oil leaks in the coupling, and check the oil level in the hydrodynamic coupling, as explained in the instruction manual for the coupling.
5) Any abundant oil leak may indicate that the hydrodynamic coupling thermal protection has been triggered. Find the hidrodynamic coupling oil plug, the appropriate type of oil and proceed as follows:
Disconnect the mains power supply. Remove the box. Remove the actuator from its fixing base and lay it down tilted to the
right with the motor in a horizontal position.
Rotate the hydrodynamic coupling by hand until it shows the green
thermal plug (fig.24 ref. TV) to be replaced.
For maintenance and repair, carefully read the hydrodynamic coupling
instruction manual supplied with the product, and follow the relevant instructions.
Reposition the actuator in the base plate, align and secure it. Refit the box, the doors and then recheck operation.
The descriptions and illustrations contained in the present manual are not binding. The Company reserves the right to make any alterations deemed appropriate for the technical, manufacturing and commercial improvement of the product, while leaving the essential product features unchanged, at any time and without undertaking to update the present publication.
19) NOISE
The aerial noise produced by the gearmotor under normal operating condi­tions is constant and does not exceed 70dB(A).
20) SCRAPPING
Materials must be disposed of in conformity with the current regulations. In case of scrapping, the automation devices do not entail any particular risks or danger. In case of materials to be recovered, these should be sorted out by type (electrical components, copper, aluminium, plastic etc.).
21) DISMANTLING
When the automation system is disassembled to be reassembled on another site, proceed as follows:
• Disconnect the power supply and the entire electrical installation.
• Remove the gearmotor from its fixing base.
• Disassemble the control panel, if separate, and all installation compo­nents.
• In the case where some of the components cannot be removed or are damaged, they must be replaced.
22) MALFUNCTION: CAUSES AND REMEDIES.
22.1) The gate does not open. The motor does not turn.
1) Check that the system is supplied with power (see main switch).
2) Check that the door safety microswitch operates correctly.
3) Check that the overload cutout located inside the control panel has not been activated; if necessary, restore operation using the appropriate button and check current absorption by means of amperometric pliers.
Page 8
Fig. 1
Fig. 3Fig. 2
Fig. 5Fig. 4
MF
R
SB
S
G
P
Q
C
MS
524
288
297
81.5 327 133.5
60
M12
Ø6
0
245
236
Øp108-Z18 M6
542
305
16
52
293
69945
1870 7 54
160
56.5 45 115 45 43.5
185 120
40
49
30
Lato uscita pignone
Pinion exit side
Côté sortie de pignon
Seite des zahnrades
Lato salita piñón
65
Min. 10
187 194
93
Piano superiore
Top level
Oberseite
Dessus supérieur
Superficie superior
350
400
550
D811229_05
SP4000 - SP4000 FAST - Ver. 05 - 39
Page 9
Fig. 6 Fig. 7
Fig. 8 Fig. 9
Fig. 10 Fig. 11
8
8 10
G
T
L
L
45mm
T
G
L
26 30 31
SWO
SWO SWC
COM
26 30 31
COM
SWC
P
A
40 - SP4000 - SP4000 FAST - Ver. 05
D811229_05
Page 10
Fig. 12
Fig. 13
3x1mm
2
Fte
Fre
T
S
P
C
M
Qr
CF
Fti
I
Al
CS
CS
CC
CC
Fri
CF
2x1.5mm
2
3x1mm
2
2x1mm
2
2x1mm
2
4x1mm
2
4x1mm
2
RG58
*
*
*
400V 3~ 5x2.5mm
2
*
230V 3~ 4x2.5mm
2
min. 50m
m
min. 50m
m
20m
m
F
D811229_05
SP4000 - SP4000 FAST - Ver. 05 - 41
Page 11
Fig.14
SIRIOTEL
400
52 53
N R S T
50 51
48 49
45 46
47
42 43 44
40 39 38 37
K0 K0
K3 K2 A1
A2
A1
A2
A1 K1
26 27 28 29 30 31
20 21 22 23 24 25
32 33 34 35 36
10 11 12 13 14 15 16 17 18 19
400V
*
5*
4*
1*
2*3*
-
~~
+
M
3~
R
N
S T
400V ~
*
7 x 1,5 mm
2
42 - SP4000 - SP4000 FAST - Ver. 05
D811229_05
Page 12
Fig.15
SIRIOTEL
230
52 53
N R S T
50 51
48 49
45 46
47
42 43 44
41 40 39 38 37
K0 K0
K3 K2 A1
A2
A1
A2
A1 K1
26 27 28 29 30 31
20 21 22 23 24 25
32 33 34 35 36
10 11 12 13 14 15 16 17 18 19
M
3~
~
-
~
+
230V
5*
*
4*
1*
2*3*
R S T 230V ~
*
7 x 1,5 mm
2
D811229_05
SP4000 - SP4000 FAST - Ver. 05 - 43
Page 13
Fig. 16
1 2
N L
3 4 5 6 7 8 9
N R S T BLINK
10 11 12 13 14 15 16 17 18 19
SCA 24VAC TX L1 L2 IICAN ANT SHLD
20 21 22 23 24 25
NAR NCB CFB NAA NCA CFA
26
U8
K10
R5
JP6
JP1 JP2
JP7
JP5
RV1
F1
T1
U3
U2
U1
0.2AT
RICEV
DL2
DL14
DL3 DL4 DL5 DL6 DL7 DL8 DL9 DL10 DL11 DL12 DL13
DL2
U6
U5
U10
D20
D19
D18
D14
D15
D26
D13
D16 D17
U7
27 28 29 30 31 32 33 34 35 36
COM START STOP PHOT SWO SWC PED
OPEN CLOSE
BAR
MICRO
4
42
43
44
50
51
52
53
45
46
47
48
49
1 40 39 38 37
230V S 400V Safety
SIRIOTEL
DIP function 1 FCH 2 FCH 3 IBL 4 TCA 5 2P/4P 6 PREALL 7 U.P. 8 S.TW 9 FNV 10 BAR
1 2
TWPED
- ++- TCA + - TW
R31
C37
C8
C11
U4
2AT
F2
R1
C1
C2
C3
C7
C4
IC1
Y1
K8
K9
F3
F2A
R105
K7
K4
R8
R6
R7
R104
R32 R33
+
+
+
+
3 4 5 6 7 8 9 10
ON
Fig. 17 Fig. 18
SIRIOTEL
Rx FL Rx RI
Tx FL Tx RI
35
BAR
Dip 9 ON
29
PHOT
26
COM
11
12
13
24VAC
1 2 3 4 5
1 2 1 2
Dip 10 ON
1 2 3 4 5
JP2
JP1 SIRIO TEL 230
JP1 SIRIO TEL 400
JP7
fig.19
10 1911 12 13 14 15 16 17 18
1 2 3 4 8 9
20 21 22 23 24 25
JP4
26 36
27 28 29 30 31 32 33 34 35
24V
3W
ANT.
CH2
24V Tx
LOOP1
LOOP2
24Vac
NO
NCNCNC
NC
NONONO
COM
START
STOP
PED
APRE
CHIUDE
PHOT
BAR
SWO
SWC
1 2 3 4 8 9
S
230V
40W
230V
40W
R S T
230V ~
RN S T
400V ~
44 - SP4000 - SP4000 FAST - Ver. 05
D811229_05
Page 14
Fig. 19
SIRIO TEL
SIRIO TEL
F4 F3
4-14 LOOP1 / 5-26 COM
F2 F1
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
22
14-LOOP1
26-COM
252120
24
23
26-COM
29-PHOT
35-BAR
4-14 LOOP1 / 5-26 COM 3-26 COM / 4-14 LOOP1
3 2 1
SIRIO TEL
C1 F1
1 2 3 4 5 1 2 3 4 5
24
35-BAR
15-LOOP2
26-COM
29-PHOT
SIRIO TEL
C3 F2
1 2 3 4 5 1 2 3 4 5
35-BAR
F1
1 2 3 4 5
15-LOOP2
26
26-COM
29-PHOT
RX
24Vac
A
24VTx
TX
5
4
2
1
3
2
1
13
12
12
11
SIRIO TEL
F3 F2
1 2 3 4 5 1 2 3 4 5
26-COM
F1
1 2 3 4 5
25
C1
1 2 3 4 5
35-BAR
15-LOOP2
24
23
26-COM
29-PHOT
SIRIO TEL
F3 F2
1 2 3 4 5 1 2 3 4 5
26-COM
F1
1 2 3 4 5
25
C2
1 2 3 4 5
26-COM
22
24
23
26-COM
29-PHOT
C1
1 2 3 4 5
20
21
15-LOOP2
SIRIO TEL
F3 F2
1 2 3 4 5 1 2 3 4 5
20
F1
1 2 3 4 5
25
21
F4
1 2 3 4 5
26-COM
22
24
23
26-COM
29-PHOT
C1
1 2 3 4 5
35-BAR
15-LOOP2
B C
D E
F
G
Legenda
RX: ricevente fotocellule o coste infrarossi. TX: trasmittente fotocellule o coste infrarossi. F1 - F2 - F3 - F4: dispositivi riceventi fotocellule. C1 - C2 - C3 - C4: dispositivi riceventi coste sensibili.
Key
RX: photocell receiver or infrared rubber edges. TX: photocell transmitter or infrared rubber edges. F1 - F2 - F3 - F4: photocell receiving devices. C1 - C2 - C3 - C4: rubber edge receiving devices.
Légende
RX: récepteur cellules photoélectriques ou barres palpeuses à infrarouges. TX: émetteur cellules photoélectriques ou barres palpeuses à infrarouges. F1 - F2 - F3 - F4: dispositifs récepteurs cellules photoélectriques. C1 - C2 - C3 - C4: dispositifs récepteurs barres palpeuses.
Zeichenerklärung
RX: Empfangsteil der Photozellen oder Infrarotleisten. TX: Sendeeinheit der Phototellen oder Infrarotleisten. F1 - F2 - F3 - F4: Empfangsvorrichtungen der Photozellen. C1 - C2 - C3 - C4: Empfangsvorrichtungen der Sicherheitsleisten.
Leyenda
RX: receptor fotocélulas o barras de infrarrojos. TX: receptor fotocélulas o barras de infrarrojos. F1 - F2 - F3 - F4: dispositivos receptores fotocélulas. C1 - C2 - C3 - C4: dispositivos receptores barras sensibles.
Legenda
RX: ricevente fotocellule o coste infrarossi. TX: trasmittente fotocellule o coste infrarossi F1 - F2 - F3 - F4: dispositivi riceventi fotocellule. C1 - C2 - C3 - C4: dispositivi riceventi coste sensibili.
Fig. 21Fig. 20
C
S
C
V
D811229_05
SP4000 - SP4000 FAST - Ver. 05 - 45
Page 15
Fig. 22
400V 3~
230V 3~
2.7
3.
2
2
.2
6,3
4
5,2
Fig. 24
Fig. 23
TV
46 - SP4000 - SP4000 FAST - Ver. 05
D811229_05
Loading...