BFT PHOBOS BT User Manual

PHOBOS BT
ELECTROMECHANICAL
LOW-VOLTAGE
AUTOMATION FOR
SWING GATES
D811316 10-11-01 Vers. 02
156
Thank you for buying this product, our company is sure that you will be more than satisfied with the products performance. The product is supplied with a Warnings leaflet and an Instruction booklet. These should both be read carefully as they provide important information about safety, installation, operation and maintenance. This product complies with the recognised technical standards and safety regulations. We declare that this product is in conformity with the following European Directives: 89/336/EEC and 73/ 23/EEC (and subsequent amendments).
1) GENERAL SAFETY WARNING! An incorrect installation or improper use of the product can cause damage to persons, animals or things.
The Warnings leaflet and Instruction booklet supplied with this product should be read carefully as they provide important information about safety, installation, use and maintenance.
Scrap packing materials (plastic, cardboard, polystyrene etc) according to the provisions set out by current standards. Keep nylon or polystyrene bags out of childrens reach.
Keep the instructions together with the technical brochure for future reference.
This product was exclusively designed and manufactured for the use specified in the present documentation. Any other use not specified in this documentation could damage the product and be dangerous.
The Company declines all responsibility for any consequences resulting from improper use of the product, or use which is different from that expected and specified in the present documentation.
Do not install the product in explosive atmosphere.
The construction components of this product must comply with the
following European Directives: 89/336/CEE, 73/23/EEC, 98/37/EEC and subsequent amendments. As for all non-EEC countries, the above­mentioned standards as well as the current national standards should be respected in order to achieve a good safety level.
The Company declines all responsibility for any consequences resulting from failure to observe Good Technical Practice when constructing closing structures (door, gates etc.), as well as from any deformation which might occur during use.
The installation must comply with the provisions set out by the following European Directives: 89/336/CEE, 73/23/EEC, 98/37/EEC and subsequent amendments.
Disconnect the electrical power supply before carrying out any work on the installation. Also disconnect any buffer batteries, if fitted.
Fit an omnipolar or magnetothermal switch on the mains power supply, having a contact opening distance equal to or greater than 3mm.
Check that a differential switch with a 0.03A threshold is fitted just before the power supply mains.
Check that earthing is carried out correctly: connect all metal parts for closure (doors, gates etc.) and all system components provided with an earth terminal.
Fit all the safety devices (photocells, electric edges etc.) which are needed to protect the area from any danger caused by squashing, conveying and shearing.
Position at least one luminous signal indication device (blinker) where it can be easily seen, and fix a Warning sign to the structure.
The Company declines all responsibility with respect to the automation safety and correct operation when other manufacturers components are used.
Only use original parts for any maintenance or repair operation.
Do not modify the automation components, unless explicitly authorised
by the company.
Instruct the product user about the control systems provided and the manual opening operation in case of emergency.
Do not allow persons or children to remain in the automation operation area.
Keep radio control or other control devices out of childrens reach, in order to avoid unintentional automation activation.
The user must avoid any attempt to carry out work or repair on the automation system, and always request the assistance of qualified personnel.
Anything which is not expressly provided for in the present instructions, is not allow
2) GENERAL OUTLINE
Electromechanical piston designed to automatically operate residential gates. The irreversible gearmotor keeps the gate locked both in the closing and opening positions, making the use of the electric lock redundant. The actuator is supplied with an electronic torque limiter. The unit is controlled by means of an electronic control board with torque adjustment. End-of-stroke operation is controlled by two magnetic limiting devices.
The actuator features an obstacle detection system in compliance with EN12453 and EN 12445 Standards.
The following optional accessories are available on request:
- Buffer battery kit mod. PHOBOS-BT BAT
Allows operation of the automation even when there is no mains power supply for a short period of time.
3) TECHNICAL SPECIFICATIONS
3.1) PHOBOS BT
Power supply : ................................................................24V single-phase
Motor revolutions : .................................................................... 3800 min
-1
Absorbed power : ............................................................................... 40 W
Absorbed current : ............................................................................. 1.5 A
Motion transmission : ........................................................... push and pull
Push and pull force :....................................................... 2000 N (~200 kg)
Working stroke :............................................................................. 280 mm
Stem speed : ................................................................... 14 mm/s approx.
Impact reaction : ...................... Torque limiter aboard Libra control board
End-of-stroke limitino devices: .............. Magnetic, built-in and adjustable
Manual manoeuvre : ........................................................ CLS release key
No. of manoeuvres in 24hours: ......................................... 60 manoeuvres
Max. leaf length : ......................................................................... 1800 mm
Max. leaf weight : ...........................................................2500 N (~250 kg)
Environmental conditions: .......................................from -20 °C to +80 °C
Protection level : ................................................................................ IP 44
Dimensions : .................................................................................See fig.1
Controller weight : .................................................................... 50N (~5kg)
Lubrication : .................................................................. permanent grease
3.2) BATTERY KIT PHOBOS-BT BAT
Charging voltage: .......................................................................... 27.2Vdc
Charging current: ............................................................................ 130mA
Outside temperature when values were measured: .......................... 25°C
Battery capacity: .................................................................2x (12V 1.2Ah)
Flat battery protection threshold: .................................................. 20.4Vdc
Battery charging time: ................................................................. 12/14 hrs
4) INSTALLATION OF THE ACTUATOR
4.1) Preliminary checks
Check that:
The gate structure is sufficiently sturdy.
Also make sure that the actuator pushes against the leaf reinforced
section.
The leaves move manually and without effort all along their stroke.
The door stop plates are fitted at the end of both closing and opening
strokes.
If the gate has not been recently installed, check the wear condition of all components.
Repair or replace faulty or worn parts. The automation reliability and safety are directly influenced by the state of the gate structure.
The diagram in fig. 2 should be used as a reference for installation and consult the table for the distances in mounting the gate post. The diagram in fig. 2 uses the following legend: P Gate post rear fastening bracket F Front leaf fastening fork a-b “P” bracket installation value C Distance between fixing points (C = 993 mm) D Gate length X Distance from gate axis to the edge of the post Z Always over 45 mm (b - X) kg max. weight of leaf α° leaf opening in degrees
4.2) How to read the installation distance tables
Select “a” and “b” according to the angle in degrees α° that the gate has to open. The table shows the ideal value for “a” and “b” for an opening of α° = 90° at constant speed. If there is too large a difference between “a” and “b”, the leaf will not travel smoothly and the pushing or pulling force will fluctuate during its stroke. To respect the opening speed and ensure the controller operates correctly, it is best to keep the difference between “a” and “b” as low as possible. When “a” and “b” are at their maximum, the piston develops the maximum force.
AUTOMATION FOR SWING GATES
AUTOMATION FOR SWING GATES
D811316_02
157
D811316_02
4.3) Off-standard installations.
Fig. 3 shows an installation with a recess when there is not sufficient space between the leaf and perimeter wall. When the leafs position does not allow for an “a” value listed in the table, the leafs hinge pivot can be shifted (fig. 4), or a recess can be made cut out of the actual gate-post (fig. 5).
4.4) Mounting the brackets to the gate-post and to the gate.
Fix the bracket “P” (fig. 6) to the gate-post with a good welding. The fork “F” should be welded in the same way to the gate taking care that the actuator can then be mounted perfectly horizontal to the line of travel of the gate fig. 7. If the gate operates on a slope (opening inwards with an uphill driveway), fig. 7 gives the maximum oscillations of the piston with respect to its horizontal.
If the gate-post is in brick, the plate PF must be set soundly into the post using adequately sized cramps “Z” welded to the back of the plate (fig.
8).
If the gate-port is in stone and the gate is small, the plate PF can be mounted with four metal expansion plugs “T” (fig. 9). If a larger gate is being installed it would be better to use a corner plate PF (fig. 10).
5) GROUND GATE STOPS
For the controller to operate correctly the gate stop “B” must be used both in opening and closing, as shown in fig. 11.
6) THE ELECTRICAL PLANT SET-UP (fig. 12).
Lay out the electrical installation (fig. 16) with reference to the CEI 64-8 and IEC 364 provisions, complying with the HD 384 and other national standards in force for electrical installation. The mains power supply connections must be kept totally separate from the service connections (photocells, electric edges, control devices etc.).
WARNING! For connection to the mains, use a multipolar cable with a minimum of 3x1.5mm2 cross section and complying with the previously mentioned regulations. For example, if the cable is out side (in the open), it has to be at least equal to H07RN-F, but if it is on the inside (or outside but placed in a plastic cable cannel) it has to be or at least egual to H05VV-F with section 3x1.5mm2.
Connect the control and safety devices in compliance with the previously mentioned electrical installation standards. Fig.12 shows the number of connections and the cross section for power supply cables having a length of approximately 100 metres; in case of longer cables, calculate the cross section for the true automation load. When the auxiliary connections exceed 50-metre lengths or go through critical disturbance areas, it is recommended to decouple the control and safety devices by means of suitable relays.
The main automation components are (fig.12): I Type-approved omnipolar circuit breaker with at least 3mm contact
opening, provided with protection against overloads and short circuits, suitable for cutting out automation from the mains. If not already installed, place a type-approved differential switch with a 0.03A threshold in the circuit just before the automation system.
Qr Control panel and incorporated receiver. SPL Heater board for operation at temperatures below 10°C (optional) S Key selector AL Blinker tuned in with antenna M Controller Fte Pair of outside photocells (transmitters) Fre Pair of outside photocells (receivers) Fti Pair of inside photocells with column (transmitters) Fri Pair of inside photocells with column (receivers) T 1-2-4 channel transmitter RG58 Antenna cable
For the connection from the controller to the control board, three cables have been provided having the following functions:
red motor +
black motor -
white end-of-stroke control
Fig. 16 shows the wiring diagram of the LIBRA control unit. Should the opening or closing direction be incorrect, it is possible to invert the connections of motor + and motor - (red/black) on the control board. The first command after an interruption of the power supply should be an opening manoeuvre.
The cable sections and numbering are indicated in the diagram (fig. 12). For distances of over 100 meters, the cable section must be increased. All metal masses in the housings of equipment and automation must be earthed.
7) ADJUSTING THE PUSHING FORCE
WARNING: Check that the impact force value measured at the
points established by the EN 12445 standard is lower than that specified in the EN 12453 standard.
The pushing force is calibrated by means of the torque regulator in the control unit. The optimum torque must allow a complete opening or closing cycle with the minimum force necessary. An excessive torque can reduce the anti-crush safety. In the other case, an insufficient torque can impede the manoeuvres. Consult the control units instruction manual.
8) ADJUSTMENT OF THE LIMITING DEVICES
The correct adjustment of the limiting devices is obtained by positioning the end-of-stroke magnets correctly (FC1 and FC2 in Fig.1) with respect to the axis of the front bracket. Loosen the fastening screws of the magnets as described in the following paragraphs so that they can slide inside the end­of-stroke track “B” (Fig.1).
8.1) Adjustment of the closing limiting devices (Fig.13):
Move the leaf to the desired closing point, loosen the two screws A and B of the closing limiting device (FC1 in Fig.1) and move it so that the distance between the screw B and the axis of the front racket is 376 mm approximately (as shown in fig. 13). Perform a closing manoeuvre to make sure that the end-of-stroke limiting device operates correctly; if the leaf stops too far before the desired closing point, slightly move the limiting device towards the end of the stem; if, on the contrary, the leaf hits the ground closing stopping device and the actuator reverses its moving direction, move the end-of-stroke limiting device slightly towards the actuator body. After identifying the correct position of the limiting device , fix it using the two screws A and B.
8.2) Adjustment of the opening limiting devices (Fig.14):
Move the leaf to the desired opening position, loosen the two screws C and D of the opening limiting device (FC2 in Fig.1) and move it so that the distance between the screw D and the axis of the front bracket is 376 mm approximately (as shown in fig. 13). Perform an opening manoeuvre to make sure that the end-of-stroke limiting device operates correctly; if the leaf stops too far before the desired opening point, slightly move the limiting device towards the actuator body; if, on the contrary, the leaf hits the ground closing stopping device and the actuator reverses its moving direction, move the end-of-stroke limiting device slightly towards the end of the stem. After identifying the correct position of the limiting device , fix it using the two screws C and D.
N.B. When using the LIBRA control board, remember to slightly anticipate the intervention of the limiting devices because the stem, after intercepting the limiting devices, continues to move for a further 1-2 cm. (100 ms). In this way a perfect strike of the leaves against the ground supports is guaranteed.
9) MANUAL OPENING
All controllers feature a key release mechanism. After lifting the lock cover (fig.15), insert the release key supplied and turn it clockwise by 90°. Push the leaf manually to open the gate. To reset the motorised operation, turn the key in the opposite direction and refit the cover.
10) COVERS
An optional stem cover (mod.CPH) is available on request in order to protect the stem and to improve the appearance of the actuator. The actuator equipped with the stem cover mod. CPH looks like in fig.17. The stem cover is mounted on the right or left actuator by simply inverting the position of the cover and making sure that the water drain outlet is directed downwards.
11) CHECKING THE AUTOMATION
Before considering the automation completely operational, the following checks must be made with great care:
Check that all the components are firmly anchored.
Control all the safeties work properly (i.e. photocells, pneumatic skirt,
etc.).
Check the emergency manoeuvre control.
AUTOMATION FOR SWING GATES
AUTOMATION FOR SWING GATES
Loading...
+ 6 hidden pages