The APC by Schneider Electric Switched Rack Power Distribution Unit (PDU) may be used as a standalone, network-manageable power distribution device or up to 4 devices can be connected together with
one network connection. The Rack PDU provides real-time remote monitoring of connected loads. Userdefined alarms warn of potential circuit overloads. The Rack PDU provides full control over outlets
through remote commands and user interface settings.
Your unit comes with one terminator installed. It is not needed for stand-alone operation of this unit. To
use Network Port Sharing between up to four units, a terminator must be installed in the In port at one
end of the group and another on the Out port at the other end of the group.
You can manage a Rack PDU through its Web interface, its command line interface (CLI), StruxureW are
Data Center Expert, or Simple Network Management Protocol (SNMP). (T o use the PowerNet MIB with
an SNMP browser, see the PowerNet SNMP Management Information Base (MIB) Reference Guide,
available at www.apc.com.) Rack PDUs have these additional features:
• Peak load, and power and energy monitoring for all connected loads.
• Voltage, current, and power monitoring for phases.
• Current monitoring for outlet banks.
• Configurable alarm thresholds that provide network and visual alarms to help avoid overloaded
circuits.
• Four levels of user access accounts: Administrator , Device User, Read-Only User, and Outlet User
• Independent outlet control.
• Configurable power delays.
• Up to twenty-four independent outlet user accounts.
• Event and data logging. The event log is accessible by Telnet, Secure CoPy (SCP), File Transfer
Protocol (FTP), serial connection, or Web browser (using HTTPS access with SSL, or using
HTTP access). The data log is accessible by Web browser, SCP, or FTP.
• E-mail notifications for Rack PDU and system events.
• SNMP traps, Syslog messages, and e-mail notifications based on the severity level or category of
the Rack PDU and system events.
• Security protocols for authentication and encryption.
• Network Port Sharing: Up to four Rack PDUs can be connected using the In and Out ports so that
only one network connection is necessary.
Note: The Rack PDU does not provide power surge protection. To ensure that the device is protected
from power failure or power surges, connect the Rack PDU to an APC Uninterruptible Power Supply
(UPS).
Switched Rack PDU User Guide1
Access Priorities for Logging on
Only one user at a time can log on to the Rack PDU. The priority for access, beginning with the highest
priority, is as follows:
• Local access to the command line interface from a computer with a direct serial connection to the
Rack PDU
• Telnet or Secure SHell (SSH) access to the command line interface from a remote computer
• Web access, either directly or through StruxureWare Data Center Expert
Note: See “SNMP” on page 87 for information about how SNMP access to the Rack PDU is
controlled.
Types of User Accounts
The Rack PDU has four levels of access (Administrator, Device User , Read-Only User , and Outlet User),
which are protected by user name and password requirements.
• An Administrator can use all of the menus in the Web interface and all of the commands in the
command line interface. The default user name and password are both apc.
• A Device User can access only the following:
– In the Web interface, the menus on the Device Manager tab, the Environment tab, and the
event and data logs, accessible under the Events and Data headings on the left navigation
menu of the Logs tab. The event and data logs display no button to clear the log.
– In the command line interface, the equivalent features and options.
The default user name is device, and the default password is apc.
• A Read-Only User has the following restricted access:
– Access through the Web interface only.
– Access to the same tabs and menus as a Device User, but without the capability to change
configurations, control devices, delete data, or use file transfer options. Links to configuration
options are visible but disabled. The event and data logs display no button to clear the log.
The default user name is readonly, and the default password is apc. To set User Name and Password values for the three account types above, see “Setting user access” on page 77.
• An Outlet User has the following restricted access:
– Access through the Web interface and command line interface.
– Access to the same menus as a Device User, but with limited capability to change
configurations, control devices, delete data, or use file transfer options. Links to configuration
options are visible but are disabled. The Outlet User has access to the Outlet Control menu
option that allows the user to control the outlets assigned by the Administrator. Outlet Users
cannot clear the event or data logs.
The user name and password are defined by the Administrator during the process of adding a
new Outlet User.
2Switched Rack PDU User Guide
Watchdog Features
Overview
To detect internal problems and recover from unanticipated inputs, the Rack PDU uses internal, systemwide watchdog mechanisms. When it restarts to recover from an internal problem, a System: Warmstart event is recorded in the event log.
Network interface watchdog mechanism
The Rack PDU implements internal watchdog mechanisms to protect itself from becoming inaccessible
over the network. For example, if the Rack PDU does not receive any network traffic for 9.5 minutes
(either direct traffic, such as SNMP, or broadcast traffic, such as an Address Resolution Protocol [ARP]
request), it assumes that there is a problem with its network interface and restarts.
Resetting the network timer
To ensure that the Rack PDU does not restart if the network is quiet for 9.5 minutes, the Rack PDU
attempts to contact the default gateway every 4.5 minutes. If the gateway is present, it responds to the
Rack PDU, and the response restarts the 9.5-minute timer. If your application does not require or have a
gateway, specify the IP address of a computer that is running on the network and is on the subnet. The
network traffic of that computer will restart the 9.5-minute time frequently enough to prevent the Rack
PDU from restarting.
Network Port Sharing
About the Network Port Sharing Feature
You can use the Network Port Sharing feature to view the status of and configure and manage up to four
Rack PDUs using only one network connection. This is made possible by connecting the Rack PDUs via
the "In" and "Out" ports on the Rack PDU front panel.
Note: All Rack PDUs in the group must be using the same Rack PDU firmware revision, 5.1.5 or later
(excluding v6.0.5 EnergyWise), in order to support the Network Port Sharing Feature.
Display ID
The display ID is a number, 1 to 4, used to uniquely identify the Rack PDUs in a group. After two or
more Rack PDUs are connected to one another in a group, they can be identified on the various
interfaces by the use of this "Display ID". This Display ID is viewable on the LCD by selecting the
Display Settings > Display ID > Show option on the LCD keypad.
Installation Instructions
Connect up to four Rack PDUs. Insert an RJ45 terminator (included) in the unused "In"/"Out" ports on
each end of the chain.
Note: Failure to use terminators may cause a loss of communication on the Rack PDUs.
Note: To reduce the possibility of communication issues, the maximum total length of cabling
connecting Rack PDUs in a group should not exceed 10 meters. All Rack PDUs in a Network Port
Sharing group should reside in the same rack enclosure.
Connect the "Network" port of one of the grouped Rack PDUs to a network hub or switch. This unit
will be the "Host" for the Rack PDU group. A Host is defined as a Rack PDU that is connected to the
network and is part of a Rack PDU group. Set up network functionality for this Host Rack PDU as
specified in the Establish Network Settings section. The Host will automatically discover any "Guest"
PDUs connected via In/Out ports. The Rack PDU group is now available via the Host's IP address.
Switched Rack PDU User Guide3
Specific assignment of Display IDs. Follow the instructions below before powering up any of the
Rack PDUs in the group.
If it is desired to have a specific assignment of Display IDs, this can be achieved by powering up the
units for the first time in the desired order, 1 to 4. For example, before powering up any of the Rack
PDUs connected in a group, determine the Display ID order that you would like. Then, first power up
the unit that you would like to have Display ID 1. After that unit has initialized and the LCD has started
displaying its screens, power on the unit that you would like to have Display ID 2. Continue in the same
way for units 3 and 4, if applicable for your setup.
Note: The Display ID can be configured from the web interface via the "Device Manager > Load
Management > device load > Display ID" field.
Getting Started
To start using the Rack PDU:
1. Install the Rack PDU using the Rack Power Distribution Unit Installation Instructions that were
shipped with your Rack PDU.
2. Apply power and connect to your network. Follow the directions in the Rack Power Distribution
Unit Installation Instructions.
3. Establish network settings. (See “Establish Network Settings” on page 5.)
4. Begin using the Rack PDU by way of one of the following:
– “Web Interface” on page 52
– “Command Line Interface” on page 14
– “Rack PDU Front Panel” on page 9
4Switched Rack PDU User Guide
Establish Network Settings
Note: Disregard the procedures described in this section if you have StruxureWare Data Center Expert
as part of your system. See the documentation for your StruxureWare Data Center Expert for more
information.
You must configure the following TCP/IP settings before the Rack PDU can operate on a network:
• IP address of the Rack PDU
• Subnet mask
• Default gateway
Note: If a default gateway is unavailable, use the IP address of a computer that is located on the
same subnet as the Rack PDU and that is usually running. The Rack PDU uses the default
gateway to test the network when traffic is very light.
Note: Do not use the loopback address (127.0.0.1) as the default gateway address for the Rack
PDU. It disables the card and requires you to reset TCP/IP settings to their defaults using a local
serial login.
See “Watchdog Features” on page 3 for more information about the watchdog role of the default
gateway.
TCP/IP configuration methods
Use one of the following methods to define the TCP/IP settings needed by the Rack PDU:
• “Device IP Configuration Wizard” on page 102
• “DHCP and BOOTP configuration” on page 5
• “Command Line Interface” on page 7
INI file utility
You can use the INI file export utility to export INI file settings from configured Rack PDUs to one or
more unconfigured Rack PDUs. For more information, see “Use an .ini File” on page 99.
DHCP and BOOTP configuration
The default TCP/IP configuration setting, DHCP, assumes that a properly configured DHCP server is
available to provide TCP/IP settings to Rack PDU. You can also configure the setting for BOOTP.
A user configuration (INI) file can function as a BOOTP or DHCP boot file. For more information, see
“Use an .ini File” on page 99.
If neither of these servers is available, see “Device IP Configuration Wizard” on page 102 or “Command
Line Interface” on page 7.
BOOTP. For the Rack PDU to use a BOOTP server to configure its TCP/IP settings, it must find a
properly configured RFC951-compliant BOOTP server.
In the BOOTPTAB file of the BOOTP server, enter the Rack PDU’s MAC address, IP address, subnet
mask, and default gateway , and, optionally, a bootup file name. Look for the MAC address on the bottom
of the Rack PDU or on the Quality Assurance slip included in the package.
Switched Rack PDU User Guide5
When the Rack PDU reboots, the BOOTP server provides it with the TCP/IP settings.
• If you specified a bootup file name, the Rack PDU attempts to transfer that file from the BOOTP
server using TFTP or FTP. The Rack PDU assumes all settings specified in the bootup file.
• If you did not specify a bootup file name, you can configure the other settings of the Rack PDU
remotely through its “Web Interface” on page 52 or “Command Line Interface” on page 7; the
user name and password are both apc, by default. To create a bootup file, see your BOOTP server
documentation.
DHCP. Y ou can use an RFC2131/RFC2132-compliant DHCP server to configure the TCP/IP settings for
the Rack PDU.
This section summarizes the Rack PDU’s communication with a DHCP server. For more detail about
how a DHCP server can configure the network settings for a Rack PDU, see “DHCP response options”
on page 82.
1. The Rack PDU sends out a DHCP request that uses the following to identify itself:
– A Vendor Class Identifier (APC by default)
– A Client Identifier (by default, the MAC address of the Rack PDU)
– A User Class Identifier (by default, the identification of the application firmware installed on
the Rack PDU)
– A Host Name (by default, apcXXYYZZ with XXYYZZ being the last six digits of the PDU).
This is known as DHCP Option 12.
2. A properly configured DHCP server responds with a DHCP offer that includes all the settings
that the Rack PDU needs for network communication. The DHCP offer also includes the Vendor
Specific Information option (DHCP option 43). The Rack PDU can be configured to ignore
DHCP offers that do not encapsulate the APC cookie in DHCP option 43 using the following
hexadecimal format. (The Rack PDU does not require this cookie by default.)
Option 43 = 01 04 31 41 50 43
Where:
– The first byte (
– The second byte (
– The remaining bytes (
01) is the code.
04) is the length.
31 41 50 43) are the APC cookie.
See your DHCP server documentation to add code to the Vendor Specific Information option.
Note: By selecting the Require vendor specific cookie to accept DHCP Addr ess check box
in the Web interface, you can require the DHCP server to provide an “APC” cookie, which
supplies information to the Rack PDU: Administration > Network>TCP/IP>ipv4 settings.
6Switched Rack PDU User Guide
Command Line Interface
1. Log on to the command line interface. See “Log on to the Command Line Interface” on page 14.
2. Contact your network administrator to obtain the IP address, subnet mask, and default gateway
for the Rack PDU.
3. Use these three commands to configure network settings. (Text in italics indicates a variable.)
tcpip -i yourIPaddress
a.
tcpip -s yourSubnetMask
b.
tcpip -g yourDefaultGateway
c.
For each variable, type a numeric value that has the format xxx.xxx.xxx.xxx.
For example, to set a system IP address of 156.205.14.141, type the following command
and press E
tcpip -i 156.205.14.141
4. Type exit. The Rack PDU restarts to apply the changes.
NTER:
Switched Rack PDU User Guide7
Recovering from a Lost Password
You can use a local computer (a computer that connects to the Rack PDU or other device through the
serial port) to access the command line interface.
1. Select a serial port at the local computer, and disable any service that uses that port.
2. Connect the serial cable (APC part number 940-0144A) to the selected port on the computer and
to the Serial port at the Rack PDU.
®
3. Run a terminal program (such as HyperTerminal
8 data bits, no parity, 1 stop bit, and no flow control.
) and configure the selected port for 9600 bps,
4. Press
ENTER, repeatedly if necessary, to display the User Name prompt. If you are unable to
display the User Name prompt, verify the following:
– The serial port is not in use by another application.
– The terminal settings are correct as specified in step 3.
– The correct cable is being used as specified in step 2.
5. Press the Reset button. The Status LED will flash alternately orange and green. Press the Reset
button a second time immediately while the LED is flashing to reset the user name and password
to their defaults temporarily.
6. Press
ENTER, repeatedly if necessary, to display the User Name prompt again, then use the
default, apc, for the user name and password. (If you take longer than 30 seconds to log on after
the User Name prompt is re-displayed, you must repeat step 5 and log on again.)
7. At the command line interface, use the following commands to change the User Name and
Password settings, both of which are now apc:
user -an yourAdministratorName
user -ap yourAdministratorPassword
For example, to change the Administrator user name to Admin, type:
user -an Admin
8. Type quit or exit to log off, reconnect any serial cable you disconnected, and restart any service
you disabled.
8Switched Rack PDU User Guide
Rack PDU Front Panel
Note: Your APC product is configured so the display backlight turns off after 10 minutes of inactivity.
The backlight can be turned on by depressing any button below the display.
ItemFunction
DisplayShows information about the Rack PDU. In normal operation,
input voltage, current, and power refreshes every five seconds. To
reverse the text, press and hold simultaneously for five seconds
the Main Menu (), Scroll (), and Select () buttons.
Main Menu buttonPress to view the Rack PDU electrical input.
Scroll buttonPress once to display the menu. Press
additional times to highlight the desired
menu option.
Select buttonWith a menu option highlighted, press the
Select button to display Rack PDU
information. Network information is shown.
Switched Rack PDU User Guide9
ItemFunction
OK, Warning, Overload LEDIndicates the status of the Rack PDU load. See “Load indicator
LED” on page 13.
T emp/Humidity portPort for connecting an APC Temperature Sensor (AP9335T) or an
APC Temperature/Humidity Sensor (AP9335TH).
In and Out portsFor use with the Network Port Sharing feature.
USB port(For use with a flash drive for firmware upgrades - 5V @ 100ma.)
Outlet status LEDIlluminates green when the outlet is energized. (Each outlet has an
outlet LED.)
RJ-12 Serial PortPort for connecting the Rack PDU to a terminal emulator program
for local access to the command line interface. Use the supplied
serial cable (APC part number 940-0144A).
10/100 Base-T ConnectorConnects the Rack PDU to the network.
Network status LEDSee “Network Status LED” on page 13.
10/100 LEDSee “10/100 LED” on page 13.
Reset buttonResets the Rack PDU without affecting the outlet status.
!
10Switched Rack PDU User Guide
Display Tree Example 1
Switched Rack PDU User Guide11
Display Tree Example 2
12Switched Rack PDU User Guide
Network Status LED
ConditionDescription
OffOne of the following situations exists:
• The Rack PDU is not receiving input power.
• The Rack PDU is not operating properly. It may need to be repaired or
replaced. Contact APC Customer Support.
Solid GreenThe Rack PDU has valid TCP/IP settings.
Solid OrangeA hardware failure has been detected in the Rack PDU. Contact APC
Customer Support.
Flashing GreenThe Rack PDU does not have valid TCP/IP settings.
Flashing OrangeThe Rack PDU is making BOOTP requests.
Alternately flashing green and
orange
1. If you do not use a BOOTP or DHCP server, see “Establish Network Settings” on page 5 to configure the
TCP/IP settings of the Rack PDU.
2. To use a DHCP server, see “TCP/IP and Communication Settings” on page 81.
If the LED is flashing slowly, the Rack PDU is making DHCP2 requests1.
If the LED is flashing rapidly, the Rack PDU is starting up.
10/100 LED
ConditionDescription
OffOne or more of the following situations exists:
• The Rack PDU is not receiving input power.
• The cable that connects the Rack PDU to the network is disconnected or
defective
• The device that connects the Rack PDU to the network is turned off.
• The Rack PDU itself is not operating properly. It may need to be repaired or
replaced. Contact APC Customer Support.
Solid greenThe Rack PDU is connected to a network operating at 10 Megabits per second
(Mbps).
Solid orangeThe Rack PDU is connected to a network operating at 100 Mbps.
Flashing greenThe Rack PDU is receiving or transmitting data packets at 10 Mbps.
Flashing orangeThe Rack PDU is receiving or transmitting data packets at 100 Mbps.
Load indicator LED
The load indicator LED identifies overload and warning conditions for the Rack PDU.
ConditionDescription
Solid GreenOK. No load alarms (warning or critical) are present.
Solid YellowWarning. At least one load warning alarm is present, but no critical alarms are
present.
Flashing RedOverload. At least one load critical alarm is present.
Switched Rack PDU User Guide13
Command Line Interface
About the Command Line Interface
You can use the command line interface to view the status of and configure and manage the Rack PDU
(and any connected Rack PDUs if using the Network Port Sharing Feature). In addition, the command
line interface enables you to create scripts for automated operation. An Administrator has full access to
the command line interface, a Device user and Outlet User have limited access, and a Read-Only user is
completely restricted.
You can configure all parameters of a Rack PDU (including those for which there are not specific CLI
commands) by using the CLI to transfer an INI file to the Rack PDU. The CLI uses XMODEM to
perform the transfer. However, you cannot read the current INI file through XMODEM.
Log on to the Command Line Interface
To access the command line interface, you can use either a local (serial) connection or a remote (Telnet
or SSH) connection with a computer on the same network as the Rack PDU.
Remote access to the command line interface
You can access the command line interface through T elnet or SSH. Telnet is enabled by default. Enabling
SSH disables Telnet.
To enable or disable these access methods, use the Web interface. On the Administration tab, select
Network on the top menu bar, and then the access option under Console on the left navigation menu.
Telnet for basic access. Telnet provides the basic security of authentication byuser name and
password, but not the high security benifits of encryption.
To use Telnet to access the command line interface:
1. From a computer that has access to the network on which the Rack PDU is installed, at a
command prompt, type
139.225.6.133, when the Rack PDU uses the default Telnet port of 23), and press ENTER.
If the Rack PDU uses a non-default port number (from 5000 to 32768), you must include a colon
or a space, depending on your Telnet cliet, between the IP address (or DNS name) and the port
number. (These are commands for general usage. Some clients do not allow you to specify the
port as an argument and some types of Linux might want extra commands).
2. Enter the user name and password (by default, apc and apc for an Administrator, or device and
apc for a Device User).
If you cannot remember your user name or password, see “Recovering from a Lost Password” on
page 8.
telnet and the IP address for the Rack PDU (for example, telnet
SSH for high-security access. If you use the high security of SSL for the Web interface, use SSH for
access to the command line interface. SSH encrypts user names, passwords, and transmitted data. The
interface, user accounts, and user access rights are the same whether you access the command line
interface through SSH or Telnet, but to use SSH, you must first configure SSH and have an SSH client
program installed on your computer.
14Switched Rack PDU User Guide
Local access to the command line interface
For local access, use a computer that connects to the Rack PDU through the serial port to access the
command line interface:
1. Select a serial port at the computer and disable any service that uses that port.
2. Connect the serial cable (APC part number 940-0144A) from the selected serial port on the
computer to the Serial port on the Rack PDU.
3. Run a terminal program (e.g., HyperTerminal) and configure the selected port for 9600 bps, 8
data bits, no parity, 1 stop bit, and no flow control.
4. Press
ENTER. At the prompts, enter your user name and password.
About the Main Screen
Following is an example of the main screen, which is displayed when you log on to the command
line interface of a Rack PDU.
American Power Conversion Network Management Card AOS vx.x.x
(c)Copyright 2012 All Rights Reserved RPDU 2g PPPP vx.x.x
-------------------------------------------------------------------------Name : Test Lab Date : 10/30/2012
Contact : Don Adams Time : 5:58:30
Location : Building 3 User : Administrator
Up Time : 0 Days, 21 Hours, 21 Minutes Stat : P+ N4+ N6+ A+
APC>
• Two fields identify the APC operating system (AOS) and application (APP) firmware versions.
The application firmware name identifies the type of device that connects to the network. In the
example above, the application firmware for the Rack PDU is displayed.
Network Management Card AOSvx.x.x
RPDU 2g vx.x.x
• Three fields identify the system name, contact person, and location of the Rack PDU.
Name: Test Lab
Contact : Don Adams
Location : Building 3
• An Up Time field reports how long the Rack PDU has been running since it was last turned on or
reset.
Up Time : 0 Days, 21 Hours, 21 Minutes
• Two fields identify when you logged in, by date and time.
Date : 10/30/2012
Time : 5:58:30
• The User field identifies whether you logged in through the Administrator or Device Manager
account. (The Read Only User account cannot access the command line interface.)
User : Administrator
Switched Rack PDU User Guide15
• A Stat field reports the Rack PDU status.
Stat : P+ N4+ N6+ A+
P+ The APC operating system (AOS) is functioning properly.
IPv4
only
N+ N+N4+ N6+The network is functioning properly.
N? N6? N4? N6?A BOOTP request cycle is in progress.
N– N6- N4- N6-The Rack PDU failed to connect to the network.
N! N6! N4! N6!Another device is using the Rack PDU IP address.
* The N4 and N6 values can be different from one another: you could, for example, have
N4- N6+.
A+The application is functioning properly.
A–The application has a bad checksum.
A?The application is initializing.
A!The application is not compatible with the AOS.
IPv6
only
IPv4 and
IPv6*
Description
Note: If P+ is not displayed, contact APC support staff.
Using the Command Line Interface
At the command line interface, use commands to configure the Rack PDU. To use a command, type the
command and press
ENTER. Commands and arguments are valid in lowercase, uppercase, or mixed case.
Options are case-sensitive.
While using the command line interface, you can also do the following:
• Type
? and press ENTER to view a list of available commands, based on your account type.
• To obtain information about the purpose and syntax of a specified command, type the command, a
space, and
radius ?
? or the word help. For example, to view RADIUS configuration options, type:
or
radius help
• Press the UP arrow key to view the command that was entered most recently in the session. Use
the
UP and DOWN arrow keys to scroll through a list of up to ten previous commands.
• Type at least one letter of a command and press the
TAB key to scroll through a list of valid
commands that match the text you typed in the command line.
• Type
exit or quit to close the connection to the command line interface.
16Switched Rack PDU User Guide
Command Syntax
ItemDescription
-Options are preceded by a hyphen.
< >Definitions of options are enclosed in angle brackets. For example:
-dp <device password>
[ ]If a command accepts multiple options or an option accepts mutually exclusive
arguments, the values may be enclosed in brackets.
|A vertical line between items enclosed in brackets or angle brackets indicates that
the items are mutually exclusive. You must use one of the items.
Example of a command that supports multiple options:
user [-an <admin name>] [-ap <admin password>]
In this example, the user command accepts the option -an, which defines the Administrator user name,
and the option
and password to XYZ:
-ap, which defines the Administrator password. To change the Administrator user name
1. Type the user command, one option, and the argument
user -ap XYZ
XYZ:
2. After the first command succeeds, type the user command, the second option, and the argument
XYZ:
user -an XYZ
Example of a command that accepts mutually exclusive arguments for an option:
alarmcount -p [all | warning | critical]
In this example, the option -p accepts only three arguments: all, warning, or critical. For example, to
view the number of active critical alarms, type:
alarmcount -p critical
The command will fail if you type an argument that is not specified.
Switched Rack PDU User Guide17
Command Response Codes
The command response codes enable scripted operations to detect error conditions reliably without
having to match error message text:
The CLI reports all command operations with the following format:
E [0-9] [0-9] [0-9] : Error message
CodeMessage
E000Success
E001Successfully Issued
E002Reboot required for change to
take effect
E100Command failed
E101Command not found
E102Parameter Error
E103Command Line Error
E104User Level Denial
E105Command Prefill
E106Data Not Available
E107Serial communication with the
Rack PDU has been lost
18Switched Rack PDU User Guide
Network Management Card Command Descriptions
Access: Administrator, Device User, Outlet User
Description: View a list of all the CLI commands available to your account type. To view help text for
a specific command, type the command followed by a question mark.
Example: To view a list of options that are accepted by the alarmcount command, type:
alarmcount ?
about
Access: Administrator, Device User, Outlet User
Description: View hardware and firmware information. This information is useful in troubleshooting
and enables you to determine if updated firmware is available at the APC Web site.
alarmcount
Access: Administrator, Device User, Outlet User
Description:
OptionArgumentsDescription
-pallView the number of active alarms reported by the Rack PDU. Information
about the alarms is provided in the event log.
warningView the number of active warning alarms.
criticalView the number of active critical alarms.
Example:
alarmcount -p warning
To view all active warning alarms, type:
appcli
Access: Administrator, Device User, Outlet User
Description: Access the Rack PDU Command Line Interface.
Switched Rack PDU User Guide19
boot
Access: Administrator only
Description: Define how the Rack PDU will obtain its network settings, including the IP address,
subnet mask, and default gateway. Then configure the BOOTP or DHCP server settings.
OptionArgumentDescription
-b
<boot
mode>
-cenable | disabledhcp and dhcpBootp boot modes only. Enable or disable the requirement
The default values for these three settings generally do not need to be changed:
-v <vendor class>: APC
-i <client id>: The MAC address of the Rack PDU, which uniquely identifies it on the network
-u <user class>: The name of the application firmware module
dhcp | bootp | manual Define how the TCP/IP settings will be configured when the Rack PDU turns
on, resets, or restarts. See “TCP/IP and Communication Settings” on page 81
for information about each boot mode setting.
that the DHCP server provide the APC cookie.
Example: To use a DHCP server to obtain network settings:
1. Type
boot -b dhcp
2. Enable the requirement that the DHCP server provide the APC cookie:
boot -c enable
cd
Access: Administrator, Device User, Outlet User
Description: Navigate to a folder in the directory structure of the Rack PDU.
Example 1: To change to the ssh folder and confirm that an SSH security certificate was uploaded to
the Rack PDU:
1. Type
2. Type
cd ssh and press ENTER.
dir and press ENTER to list the files stored in the SSH folder.
Example 2: To return to the main directory folder, type:
cd ..
clrrst
Access: Administrator, Device User, Outlet User
Description: Clear reset reason.
20Switched Rack PDU User Guide
console
Access: Administrator only
Description: Define whether users can access the command line interface using Telnet, which is
enabled by default, or Secure SHell (SSH), which provides protection by transmitting user names,
passwords, and data in encrypted form. You can change the Telnet or SSH port setting for additional
security. Alternately, disable network access to the command line interface.
OptionArgumentDescription
-Sdisable | telnet | sshConfigure access to the command line interface, or use the disable
command to prevent access. Enabling SSH enables SCP and disables Telnet.
-pt<telnet port n>Define the Telnet port used to communicate with the Rack PDU (23 by
default).
-ps<SSH port n>Define the SSH port used to communicate with the Rack PDU (22 by
default).
-b2400 | 9600 | 19200 |
38400
Configure the speed of the serial port connection (9600 bps by default).
Example 1: To enable SSH access to the command line interface, type:
console -S ssh
Example 2: To change the Telnet port to 5000, type:
console -pt 5000
Switched Rack PDU User Guide21