AEG PROTECT A. 500 User Manual

UPS OPERATING INSTRUCTIONS
PROTECT
A.
500
A.
PROTECT A.700
2
Thank you for deciding to purchase the PROTECT A. UPS from AEG Power Solutions.
The following safety instructions are an important part of the operating instructions are will protect you against problems from operating errors and possible dangers. Please read these instructions carefully prior to commissioning!
3
1 Notes on these Operating
Instructions
Duty to provide information
These operating instructions will help you to install and operate the U PROTECT A. 500 or PROTECT A. 700 - referred to as PROTECT A. in this document - safely and properly, and for its intended purpose. These operating instructions contain important information for avoiding dangers.
Please read these instructions carefully prior to commissioning!
These operating instructions are a composite part of PROTECT A.
The owner of this unit is obliged to communicate the full content of these operating instructions to all personnel transporting or starting the PROTECT A. or performing maintenance or any other work on the unit, without the information having to be requested.
Validity
These operating instructions comply with the current technical specifications of PROTECT A. at the time of publication. The contents do not constitute subject matter of the contract, but serve for information purposes only.
ninterruptible Power Supply (UPS),
Warranty and liability
We reserve the right to alter any specifications given in these operating instructions, especially with regard to technical data and operation, prior to start-up or as a result of service work.
Claims in connection with supplied goods must be submitted within one week of receipt, along with the packing slip. Subsequent claims cannot be considered.
The warranty does not apply for damage caused by non­compliance with these instructions (such damage also includes damage to the warranty seal). AEG will accept no liability for consequential damage. AEG will rescind all
4
obligations such as warranty agreements, service contracts, etc. entered into by AEG or its representatives without prior notice in the event of maintenance and repair work being carried out with anything other than original AEG parts or spare parts purchased from AEG.
Handling
PROTECT A. is designed and constructed so that all necessary steps for start-up and operation can be performed without any internal manipulation of the unit. Maintenance and repair work may only be performed by trained and qualified personnel.
Illustrations are provided to clarify and facilitate certain steps. If danger to personnel and the unit cannot be ruled out in the
case of certain work, it is highlighted accordingly by pictographs explained in the safety regulations of chapter 3.
Hotline
If you still have questions after having read these operating instructions, please contact your dealer or our hotline:
Tel.: +49 (0) 1805 234 787 Fax: +49 (0) 1805 234 789 Internet: www.AEGpartnerNet.com
Copyright
No part of these operating instructions may be transmitted, reproduced and/or copied by any electronic or mechanical means without the express prior written permission of AEG.
© Copyright AEG 2008. All rights reserved.
5
Table of Contents
1 Notes on these Operating Instructions ................................4
2 System Overview ................................................................7
2.1 Brief Overview.....................................................................7
2.2 Principle of Operation..........................................................8
3 Safety................................................................................10
3.1 General Safety Instructions...............................................10
3.2 Safety Instructions for PROTECT A. .................................10
3.3 CE Certificate....................................................................14
3.4 Technical Data ..................................................................15
4 Set-up................................................................................17
4.1 Unpacking and Inspection.................................................17
4.2 Installation Site..................................................................18
4.3 Connections, Operating and Display Elements.................19
5 Installation and Operation..................................................20
5.1 Check................................................................................20
5.2 Installation.........................................................................20
5.3 Charging............................................................................21
5.4 Connecting the Load (e.g. computer)................................21
5.5 Modem/Phone Connection (data line protection)......................22
5.6 Communication Connection, Connection with USB
or Serial Cable...................................................................22
5.7 Operation...........................................................................23
5.7.1 Normal Operation.......................................................23
5.7.2 Battery Operation / Autonomous Operation...............24
5.7.3 System Diagnosis / Fault Test ...................................24
5.7.4 Shutdown and UPS Management Software...............25
6 Displays and Troubleshooting...........................................26
6.1 Warning Sounds................................................................26
6.2 General Troubleshooting and Fault Rectification...............26
7 Maintenance......................................................................28
7.1 Battery Replacement.........................................................29
8 Storage and Disposal........................................................30
9 List of Terms......................................................................31
9.1 Technical Terminology ......................................................31
6
2 System Overview
PROTECTA. is an uninterruptible power supply (UPS) for essential loads such as PCs, work-
i
The PROTECT A. series is a compact, interactively operating UPS available with nominal power output ratings 500, 700, 1000 and 1400 VA.
This document describes both types, PROTECT A. 500 and PROTECT A.700.
2.1 Brief Overview
LED display and a pushbutton switch are located on the front of the UPS for straightforward monitoring and operation. The display unit with traffic light function clearly signals the particular operating condition: normal operation, battery discharge, fault.
The connections for the mains and the loads are located on the rear of the PROTECT A., as are the communication interfaces and connections for telephone lines. Important UPS data is monitored permanently and transferred to the computer via USB or the RS232 interface and using the CompuWatch software.
stations, relatively small-scale telecommunication equipment and similar devices.
Features of the PROTECT A.:
VI (line – interactive) protection technologyAutomatic voltage regulation against mains voltage
deviations (AVR)
Microprocessor control for high reliabilityModern battery management with integrated protection
against exhaust. discharge and overloading
User-friendly display
with optimum legibility
Intelligent monitoring system
with USB and RS232 interfaces
7
Overvoltage protection (RJ11)
for fax, modem and phone
CompuWatch software for shutdown, status messages
and measurement values for all major operating systems (incl. Windows, Mac, Linux)
Compact design / without fan
2.2 Principle of Operation
The UPS is connected to a shockproof socket between the public utility’s mains and the loads to be protected.
Under normal operating conditions, i.e. if PROTECT A. is supplied with mains voltage, the battery charger will ensure that the battery is always completely charged.
During this operating status, the loads connected to PROTECT A. are supplied with voltage via mains filters which provide effective protection against mains voltage peaks and high-frequency faults.
In case of sustained mains undervoltage or overvoltage within defined ranges, the automatic voltage regulator (AVR) further stabilises the load voltage. As a result, voltage fluctuations in the public utility’s mains are reduced to a level which is acceptable for the loads. This is performed without recourse to the internal energy storage, something which in turn has a positive effect on battery availability.
Mains
Line filter
Rectifier
UPS Block diagram PROTECTA.
A. V. R.
Load
switch
Static bypass
Inverter
Battery
8
The static bypass switch is activated in the event of a mains failure. The inverter then takes over the voltage supply of the connected loads, in order to prevent the risk of data loss or damage to the loads. PROTECT A. supplies voltage until the battery is discharged or your IT system has been shut down and switched off properly.
The standby time mainly depends on the connected loads. If the mains power supply is back to normal values, the UPS will switch back the loads to mains supply. The battery charger will then recharge the battery.
For safety reasons (as required by German standards, VDE), the mains input in the unit will be disconnected by a two-pole switch in the event of a mains failure. Energy backfeed to the mains and voltage supply to the pins of the mains connector are thus reliably avoided.
Furthermore, additional measures ensure effective protection for the data/network interface.
9
3 Safety
Useful and important information for operating
3.1 General Safety Instructions
Read these operating instructions carefully prior to commissioning of the PROTECT A. UPS and observe the safety instructions!
Only use the unit if it is in a technically perfect condition and always in accordance with its intended purpose, while being aware of safety and danger aspects, and in accordance with the operating instructions! Immediately eliminate any faults that could be detrimental to safety.
The following pictograms are used in these operating instructions to identify dangers and important information:
Danger!
Identifies risk of fatal injury to the operator.
Attention!
Identifies risk of injury and risk of damage to the device and parts of the device.
Information!
i
the UPS.
3.2 Safety Instructions for PROTECT A.
This chapter contains important instructions for the PROTECT A. UPS. These must be followed during assembly, operation and maintenance of the uninterruptible power supply and the batteries.
The UPS is live, and the voltage can be dangerous. The unit may only be opened by trained and qualified personnel. Repairs may only be carried out by qualified customer service staff!
10
The output may be live, even if the UPS is not connected to the mains supply, as the UPS has its own internal power supply (battery)!
For health and safety reasons, the unit must be earthed correctly!
PROTECT A. may only be operated with or connected to a 220 / 230 / 240 VAC mains with protective grounding using a mains connection cable with PE conductor (included in the delivery) that has been tested in accordance with German standards (VDE).
Risk of burning!
The battery has powerful short-circuit currents. Incorrect connection or isolation faults can lead to melting of the plug connections, sparking potential and severe burns!
The unit has a warning signal that sounds when the battery voltage of PROTECT A. is exhausted or when the UPS is not working in its normal mode.
Observe the following safety instructions to ensure permanent operational safety of and safe work with the UPS:
Do not dismantle the UPS!(The UPS does not contain any parts that require
regular maintenance. Bear in mind that the warranty will be invalidated if the unit is opened!)
Do not install the unit in direct sunshine or in close
proximity of heaters!
The unit is designed to be installed inside in heated
rooms. Never install the UPS in the vicinity of water or in an excessively damp environment!
11
Condensation may occur if the UPS is brought from a
cold environment into the room where it is to be installed. The UPS must be absolutely dry prior to start­up. As a result, leave it to acclimatise for at least two hours.
Never connect the mains input and the UPS output!Ensure that no fluids or foreign bodies can penetrate
the UPS!
Do not block the air vents of the unit! Make sure, for
example, that children do not insert any objects in the ventilation openings!
Do not connect household appliances such as
hairdryers to the UPS!
The mains connection should be near the unit and
easily accessible to facilitate disconnecting the AC input or pulling out the plug!
During operation, do not disconnect the mains
connection cable from the UPS or from the socket outlet in the building (shockproof socket), otherwise the protective grounding of the UPS and all the loads connected to it will be cancelled.
Danger! Electric shocks!
Even after the mains voltage has been disconnected, the components within the UPS remain connected to the battery and can thus cause electric shocks. It is therefore imperative to disconnect the battery circuit before carrying out any maintenance or repair work!
If it is necessary to replace the battery or carry out maintenance work, this must be done by or under the supervision of a specialist familiar with batteries and the necessary safety precautions!
Only authorised persons are allowed in the vicinity of the batteries!
12
When replacing the battery, the following must be observed: Only ever use an identical, maintenance-free sealed lead battery with the same data as the original battery.
Danger! Explosive!
Never throw batteries into open fire. Never open or damage batteries. (Electrolyte may leak out and damage skin and eyes. It may be toxic!)
Batteries can cause electric shocks and high short-circuit currents.
Therefore, take the following safety precautions when working with batteries:
Take off watches, rings and other metallic objects!Only use tools with insulated handles!
For personal safety reasons, never switch on the main switch when the mains connector of PROTECT A. is disconnected!
13
3.3 CE Certificate
14
3.4 Technical Data
Type rating
PROTECT A.500 500 VA / 300 W PROTECT A.700 700 VA / 420 W
UPS input
Nominal connection voltage 220 / 230 / 240 Vac Voltage range without battery 170 Vac to 280 Vac Frequency (automatic detection) 50 / 60 Hz
Connection Non-heating appliance
UPS output
Rated output voltage / 230 Vac AVR technology
Rated output voltage in ±10% battery operation
Frequency in battery operation 50 Hz / 60 Hz ±1Hz Nominal output current 2.2 A (PROTECT A.500)
Changeover time in the event of a mains failure 2-6 ms (typical)
Type of voltage approximated sine Connection 4 non-heating appliance
Protection against over- yes temperature and short circuit
connector IEC320 C14
3.0 A (PROTECT A.700)
connectors IEC320 C13 with overvoltage protection,
3 with UPS back-up
Battery
Autonomy time at nominal load 2 min Exhaustive discharge protection/ yes
protection against excess load
15
Charging time (to 90 % of rated capacity) 8 h
Type Sealed, maintenance-free PROTECT A.500 Block battery 12 V / 7 Ah
e.g. CSB, type GP1272F2 3-5 years acc. to EUROBAT
Yuasa, type NP7-12D Connection plug 6.3 mm Panasonic, type LC-R127R2P (Faston 250)
PROTECT A.700 Block battery 12 V / 9 Ah
e.g. CSB, type HR1234WF2 3-5 years acc. to EUROBAT
Yuasa, type NPW7-12D Connection plug 6.3 mm Panasonic, type UP-RW1245P1 (Faston 250)
Communication
Interfaces USB and RS232 Shutdown software on CD For all common operating
systems, e.g. Windows, Linux, Mac, Unix, FreeBSD, Novell, Sun
General data
Inherent noise (1 m distance) < 40 dB(A) Operating temperature range 0 °C - 40 °C Humidity 0 to 90 %
(without condensation)
Installation height Up to 1000 m
at nominal output Housing colour Silver/black Dimensions W x H x D [mm] 100 x 140 x 330 Weight [kg] 6 kg (PROTECTA.500)
6.5 kg (PROTECT A. 700)
Cooling type Increased natural air cooling Storage temperature range -15° C to +50° C
(UPS electronics) UPS with integrated battery 0 °C to +40 °C
Conformity CE
16
Directives
Claims for damage during transport must always
The PROTECT A. meets the product standard EN 50091. The CE mark on the unit confirms compliance with the EC
outline directives for 73/23 EEC – Low voltage and for 89/336 EEC – Electromagnetic compatibility if the installation instructions described in the operating instructions are observed.
For 73/23 EEC low-voltage directive Reference number EN 62040-1-1 : 2003
For 89/336 EMC directive Reference number EN 50091-2 : 1995
4 Set-up
4.1 Unpacking and Inspection
The unit has been completely checked and inspected. Although the device has been packed and shipped with the usual degree of care, damage during transport cannot be ruled out completely.
EN 61000-3-2 : 1995
EN 61000-3-3 : 1995
be made with the transport company!
i
Check the shipping container for damage on arrival. If necessary, ask the transport company to check the goods and make a record of the damage in the presence of the transport company employee and report the damage to the AEG representative or dealer within eight days of delivery.
17
Check the content is complete:
PROTECT A. with 500 or 700 VAMains connection cable with shockproof plug
acc. to CEE 7/7 Second mains connection cable with UK plug acc. to BS 1363
Two device connecting cablesUSB / RS232 communication cableManagement software “CompuWatch” on CDOperating instructions
Please contact our hotline (see page 5) in case of any discrepancy.
The original packaging provides effective protection against mechanical shocks and should be retained so the unit can be transported safely later on.
Please keep the plastic packaging bags away from babies and children in order to safeguard against suffocation accidents.
4.2 Installation Site
PROTECT A. is designed to be installed in a protected environment. When installing the unit, pay attention to such factors as sufficient ventilation and suitable ambient conditions.
PROTECT A. is air-cooled. Do not obstruct the air vents!
The UPS should preferably be operated at room temperature (between 15° C and 25° C).
Install the UPS in a room that is dry, relatively dust-free and free of chemical vapours.
Make sure that no magnetic storage media are stored and/or operated close to PROTECT A.
Check the nameplate to make sure the voltage and frequency data correspond to the values applicable to your loads.
18
4.3 Connections, Operating and Display Elements
Front
1 Main switch of the UPS
(mains switch)
2 LED displays:
Green LED: Mains/normal operation Yellow LED: Battery operation Red LED: Warning/fault,
battery renewal indication
Rear
1 Load connections with
overvoltage protection and UPS backup
2 Mains connection (UPS input)
with input fuse and integrated back-up fuse
3 Data interface for modem/ fax/
phone (RJ11)
4 RS232 communication interface
(SUB-D 9-pin socket)
5 USB connection 6 Load connection with direct mains
supply (with overvoltage protection) –
without UPS back-up!
19
5 Installation and Operation
5.1 Check
Remove the UPS from its transport packaging and check that it has not been damaged in transit. If you find any damage, pack the unit up again and send it back to where you purchased it.
5.2 Installation
Install the UPS unit in a protected location where there is an adequate air supply and where it will be largely free from dust build-up, corrosive vapours and electrically conductive contamination.
Do not operate your UPS where it is exposed to high ambient temperatures or atmospheric humidity. Set up the UPS at least 20 cm away from the monitor in order to avoid interference.
20
5.3 Charging
The battery is charged irrespective of the setting
8 hours
The PROTECT A. is supplied with its battery fully charged. Nevertheless, energy may have been lost during transport, so the battery should be fully recharged before it is used for the first time.
Connect the input of the UPS (no. 2 in the figure in chapter 4.3 on page 19) to the mains connection cable provided and plug the mains connector into a suitable shockproof socket. Allow the UPS to charge up for about 8 hours without any load (i.e. without any devices such as computers, monitors, etc. connected to it).
i
of the main switch on the front of the UPS.
5.4 Connecting the Load (e.g. computer)
Connect your loads to the individual UPS backed-up output sockets on the rear of the UPS (chapter 4.3 / no. 1 / pg.19).
21
i
Note that the additional output socket identified
in white has a special property (chapter 4.3 / no.
outputs. It is not backed up by the UPS, nor can
it be switched off using the main switch of the
UPS. It is intended for loads that should be
protected against overvoltage but do not
necessarily need a continued power supply
mains failure.
6 / pg.19). This is always live irrespective of the other
(emergency power) in case of a Limit the power to max. 500 W.
5.5 Modem/Phone Connection (data line protection)
Connect the incoming phone line into the “IN” connection on the back of the PROTECT A.
Connect the data terminal unit (phone, fax, modem) to the “OUT” socket.
The data line protection has been designed for RJ11 and does not support network cables
i
(RJ45); these should be protected by external measures if necessary.
Data lines are not supplied with the UPS.
5.6 Communication Connection, Connection with USB or Serial Cable
In order to allow unsupervised shutdown of the operating system, connect the RS232 or USB cable as shown in the drawing.
The USB connection is automatically detected.
22
The interfaces are mutually exclusive. There is no
provision for simultaneous
operation of RS232
i
and USB.
5.7 Operation
Once you have connected the UPS to a suitable mains connection, you can start operation using the UPS main switch.
Switching ON and OFF:
Normally, the UPS operates continuously. The UPS now supplies the output with voltage, this being signalled by the green “Normal” LED which lights up permanently (chapter 4.3 / no. 2 / pg. 19).
5.7.1 Normal Operation
During normal operation, i.e. when mains voltage is available, the built-in battery charger keeps the battery fully charged and the mains voltage monitoring system switches the inverter to standby mode.
To switch on, press the main
switch on the front of the UPS (chapter 4.3 / no. 1 / pg.19). You must be able to feel this engage in its 2nd position.
Press the main switch again
to switch off the UPS.
23
The connected loads are powered using the monitored and filtered mains voltage, which is additionally stabilised by the integrated A.V.R. control unit. The green “Normal” LED shows that the unit is active.
5.7.2 Battery Operation / Autonomous Operation
When there is a mains failure or if the input voltage moves outside the tolerance range, the inverter automatically switches over to autonomous mode and supplies the loads with voltage from the battery. This drains the capacity of the battery and it is discharged. This status is signalled by the green “Battery” LED flashing as well as an intermittent acoustic signal (chapter 4.3 / no. 2 / pg. 19).
If the UPS does not automatically return to normal operation after a few minutes, close all your work as usual and switch off the loads (e.g. PC) before the battery is fully discharged. This lengthens the service life of the battery! Switch OFF the UPS by pressing the main switch.
During the discharge process as the battery capacity consistently drops, the “Battery” LED flashes, accompanied by an intermittent acoustic signal (once every 10 seconds). The electronics of the UPS switch off the voltage supply of the loads shortly after the battery undervoltage limit is reached (“Battery” LED flashes every second; acoustic signal sounds every second).
Never store the unit in this condition! The discharged battery system should be recharged within a week at the latest.
When the mains voltage comes back, the UPS must be switched on again using the main switch (only applies if it was previously switched off manually), in order to recharge the battery and thus store sufficient battery capacity for any possible future mains failures.
The battery is automatically charged when the mains is present. The battery charging time (to 90% of rated capacity) is about 8 hours after being previously fully discharged.
5.7.3 System Diagnosis / Fault Test
If the monitoring electronics detect an irregularity, the red “Fault” LED is triggered at the same time as an acoustic fault
24
signal. This might occur because the battery undervoltage limit has been reached, if the temperature has risen too high, or it might indicate that the internal battery system needs to be renewed.
Faults detected and signalled during diagnosis must be rectified, otherwise there is a risk of load voltage loss if a mains failure occurs!
5.7.4 Shutdown and UPS Management Software
The “CompuWatch” software specially developed for these purposes by AEG continuously checks the mains supply and the UPS status.
In conjunction with the “intelligent” UPS, this ensures that the availability of IT components and data security are guaranteed.
The “CompuWatch” shutdown software supports different operating systems, e.g. Windows Linux, Unix, Mac OS X, etc.
Refer to the manual on the CD for details about installing the software on the various operating systems. Other tips and information as well as updates are available from our website at www.AEGpartnerNet.com PRODUCTS >> Software >> CompuWatch.
25
>>
6 Displays and Troubleshooting
6.1 Warning Sounds
Warning sound
Sounds every 10 seconds
Sounds every second
Sounds every two seconds
Sounds twice every second
Sounds every 2 seconds; continuous warning sound after 50 min
Sustained warning sound
Meaning
UPS is operating in battery mode.
UPS is running in battery mode and will shortly shut down (battery system has reached the battery undervoltage limit).
Battery system faulty, it may have to be renewed (battery diagnosis negative).
UPS output is overloaded.
Overload of the step-up/down converter due to UPS overload.
UPS faulty.
6.2 General Troubleshooting and Fault Rectification
Fault Cause Solution
No LED display on the front cover plate
Alarm buzzer sounds continuously with normal AC supply
Battery missing Insert the battery and first
Battery fault Renew the battery with a
On/off switch not pressed UPS overload Check whether the load
charge it up for at least 8 hours
battery of the same type Press the switch again
matches the UPS capacity indicated in the technical data
26
Data backup time is
into the
Check the software settings.
only very short on power failure
Mains normal, but “Battery” LED flashes
Communication between UPS and computer interrupted
UPS overload Remove loads that are less
Battery voltage is too low Charge the battery for at
Battery fault die to high temperature in the operating environment or incorrect treatment of the battery;
advanced battery ageing Fuse blown De-energise the unit; insert
Mains cable loose Insert the plug firmly
Software is not installed correctly
Cable not connected properly
important
least 8 hours Renew the battery with a
battery of the same type
a replacement fuse.
non-heating appliance socket of the UPS.
Support is available at www.AEGpartnerNet.com
Check that the RS232/USB cable is firmly connected to the COM or USB port of the computer and confirm the settings again
If you cannot solve the problem that has occurred, stop the entire procedure, switch off the UPS and disconnect the connector from the socket. Please contact our hotline in this case (see page 5).
Please have the serial number of the unit as well as the purchase date at hand. The hotline will provide you with technical support and can inform you about further procedures once you have described the problem.
27
7 Maintenance
The PROTECT A. consists of state-of-the-art, non-wearing components. We do, however, recommend regular visual checks of the unit to maintain its continuous availability and operational reliability. Check whether:
there is any mechanical damage or foreign bodies can
be found in the system,
any conductive dirt or dust has accumulated in the unit,accumulation of dust affects heat supply and
dissipation.
CAUTION:
The PROTECT A. must be disconnected from the power supply prior to carrying out the following work.
If large quantities of dust have accumulated, the unit should, as a precaution, be cleaned with dry compressed air, in order to ensure adequate heat dissipation.
The intervals at which visual checks should be performed are primarily determined by the site conditions.
Checking the battery
Progressive ageing of the battery system can be detected by regular capacity checks. Every 12 months, perform measurements to compare the achievable standby times, e.g. by simulating a mains failure. In this case, the load should always have approximately the same capacity demand. Have the battery system renewed if the time drops drastically compared to the previous measurement.
28
7.1 Battery Replacement
The following precautions should be taken
If you are not qualified to renew the battery, do
not try to open the battery cover. Leave this
ATTENTION:
A battery can cause an electric shock, and represents a considerable hazard if handled incorrectly.
before the battery is renewed.
Switch off the UPS and disconnect the mains cable
from the socket.
Remove any rings, wristwatch and other metallic
objects you may be wearing.
If the replacement battery kit is damaged in any way or
shows any signs of leaking, please contact your dealer immediately.
Recycle or dispose of the used battery appropriately.
Never dispose of batteries by burning. The batteries might explode.
Note:
i
work to qualified personnel.
29
8 Storage and Disposal
Long storage times without charging or
e battery at regular intervals may
Storage
discharging th lead to permanent damage of the battery.
If the battery is stored at room temperature (20° C to 30° C) it will automatically discharge at a rate of 3-6% per month due to internal reactions. Storing the battery at temperatures above room temperature should be avoided. A high storage temperature also means a higher rate of battery degradation.
Batteries that are stored at room temperature should be recharged every six months to maintain their full capacity and service life.
Connect PROTECT A. to the mains before putting it into storage, in order to make sure
i
Disposal
In the interest of environmental protection and recycling, please dispose of the individual system components in accordance with the regulations and legal guidelines when permanently taking the system out of operation.
that the battery is fully charged. The charging time should be at least 8 hours.
30
9 List of Terms
9.1 Technical Terminology
AVR Automatic Voltage Regulation
DC/DC booster Circuit technology for increasing a DC voltage
EPO E
PFC P
Appliance protection Term from overvoltage technology
Class D See appliance protection LED L
SNMP S
VFD Output V
VI Output V
VFI Output Voltage and Frequency Independent
Automatic voltage regulation against mains voltage deviations
to a higher voltage level
mergency Power Off
Device for emergency shutdown
ower Factor Correction Circuit technology for minimising system disturbances (particularly important when connecting non-linear loads)
Classic mains overvoltage protection consists of a lightning surge arrester (Class B), overvoltage protection (Class C) and, finally, what is referred to as appliance protection (Class D) – see also http://www.phoenixcontact.de (“TRABTECH” topic) for example
ight Emitting Diode Electronic semi-conductor component, commonly referred to as an LED, used for optic signalling.
imple Network Management Protocol A protocol encountered frequently in networks for managing / handling components
from mains supply The UPS output is dependent on mains voltage and frequency fluctuations. Earlier designation: OFFLINE
supply The UPS output is dependent on mains frequency fluctuations, but the mains voltage is prepared by electronic / passive voltage control units. Earlier designation: LINE­INTERACTIVE
from mains supply The UPS output is independent from mains voltage and frequency fluctuations. Earlier designation: ONLINE
oltage and Frequency Dependent
oltage Independent from mains
31
Guarantee Certificate
Type: …….……………….…......................................................
Unit
number:…….……………….…...................................................
Date of
purchase:…….……………….…................................................
Dealer stamp / signature
Errors and changes excepted.
AEG Power Solutions GmbH
Emil-Siepmann-Straße 32
59581 Warstein-Belecke
Germany
Operating instructions
BAL 8000024070 EN
32
Loading...