Hot Surface Ignition Control

 

INSTALLATION INSTRUCTIONS

 

 

Operator: Save these instructions for future use!

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.

DESCRIPTION

The White Rodgers 50E47 is an automatic gas interrupted ignition control employing a microprocessor to continually monitor, analyze, and control the proper operation of the gas burner.

Signals interpreted during continual surveillance of the thermostat and flame sensing element initiate automatic ignition of the burner, sensing of the flame and system shut-off during normal operation.

System fault analysis, which quickly shuts off the gas flow, coupled with automatic re-ignition upon sensing a fault correction, highlight the control’s capabilities.

PRECAUTIONS

! GENERAL PRECAUTION

Application of this type of control may cause flame rollout on initial startup and could cause personal injury and/or property damage.

Replace only with exact model number, including dash number. Failure to use exact replacement control could cause personal injury and/or property damage.

If in doubt about whether your wiring is millivolt, line, or low voltage, have it inspected by a qualified heating and air conditioning contractor or licensed electrician.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical

! CAUTION

To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

This control is not intended for use in locations where it may come in contact with water. Suitable protection must be provided to shield the control from exposure to water (dripping, spraying, rain, etc.).

codes and ordinances.

This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.

CONTENTS

 

Description .........................................................

1

Precautions ........................................................

1

Specifications .....................................................

2

Installation ..........................................................

3

Mounting & Wiring

 

Operation ............................................................

4

!WARNING

Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazard.

Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/or property damage.

 

 

 

 

 

 

WHITE-RODGERS DIVISION

 

PART NO. 37-4836B

 

 

 

 

 

 

EMERSON ELECTRIC CO.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9797 REAVIS ROAD

Printed in U.S.A.

Replaces 37-4836A

 

 

 

 

 

 

 

 

 

 

 

 

ST. LOUIS, MISSOURI 63123-5398

 

9541

 

 

 

 

 

 

 

 

 

 

 

 

 

R

SPECIFICATIONS

ELECTRICAL RATINGS:

Input Voltage: 25 VAC 50/60 Hz

Current: 0.2 amp

Relay Contact Ratings:

Valve Relay: 1.5 amp @ 25 VAC 50/60 Hz 0.6 pf Ignitor Relay: 6.0 amp @ 120 VAC 50/60 Hz-

resistive

Flame Current Requirements:

Minimum current to insure flame detection: 2 μa DC* Maximum current for non-detection: 0.2 μa DC* Maximum allowable leakage resistance: 100 M ohms

*Measured with a DC microammeter in the flame probe lead

HUMIDITY RANGE:

To 95% relative humidity (non-condensing)

MOUNTING:

Surface mount or 4" x 4" junction box

Timing Specs (see table below for variable timings): maximum

 

60 Hz

50 Hz

Flame Establishing Time

 

 

Standard

4.0 sec

4.8 sec

Optional

7.0 sec

8.4 sec

Flame failure Response time:

0.8 sec

0.96 sec

Recycle Time: Immediate, or equal to prepurge time on models with prepurge option.

OPERATING TEMPERATURE RANGE:

 

Gases Approved: Natural, Manufactured, Mixed,

 

-40° to 175°F (-40° to 80°C)

 

 

 

 

 

 

Liquid Petroleum, and LP Gas Air Mixtures are all

 

 

 

 

 

 

 

 

 

 

 

 

approved for use.

 

 

 

 

 

 

 

TIMING SPECIFICATIONS

 

 

 

 

 

 

 

(all times in seconds unles otherwise noted)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ignitor

Trial for

Ignition

 

 

Valve

 

 

 

 

 

 

Warmup

Ignition

Activation

 

Sequence

 

Lockout

 

 

Dash Number

Pre-purge

Period

Period

Period

 

Retries

Period

Interpurge

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-1 thru -9

0

17

4

1

 

0

4

0

21

 

 

-10 thur -19

0

45

4

1

 

0

4

0

49

 

 

-20 thru -29

30

17

4

1

 

0

4

0

51

 

 

-30 thru -39

30

45

4

1

 

0

4

0

79

 

 

-40 thru -49

30

17

4

1

 

2

12

90

293

 

 

-50 thru -59

30

45

4

1

 

2

12

90

377

 

 

-60thru -69

0

17

4

1

 

2

12

60

203

 

 

-70 thru -79

0

45

4

1

 

2

12

60

287

 

 

-101 thru -109

0

17

7

4

 

0

7

0

24

 

 

-110 thru -119

0

45

7

4

 

0

7

0

52

 

 

-120 thru -129

30

17

7

4

 

0

7

0

54

 

 

-130 thru -139

30

45

7

4

 

0

7

0

82

 

 

-140 thru -149

30

17

7

4

 

2

21

90

302

 

 

-150 thru -159

30

45

7

4

 

2

21

90

386

 

 

-160 thru -169

0

17

7

4

 

2

21

60

212

 

 

-170 thru -179

0

45

7

4

 

2

21

60

296

 

 

-201 thru -209

0

17

4

1

 

0

4

0

21

 

 

-210 thru -219

0

45

4

1

 

0

4

0

49

 

 

-220 thru -229

30

17

4

1

 

0

4

0

51

 

 

-230 thru -239

30

45

4

1

 

0

4

0

79

 

 

-240 thru -249

30

17

4

1

 

2

12

90

293

 

 

-250 thru -259

30

45

4

1

 

2

12

90

377

 

 

-260 thru -269

0

17

4

1

 

2

12

60

203

 

 

-270 thru -279

0

45

4

1

 

2

12

60

287

 

 

-301 thru -309

0

17

7

4

 

0

7

0

24

 

 

-310 thru -319

0

45

7

4

 

0

7

0

52

 

 

-320 thru -329

30

17

7

4

 

0

7

0

54

 

 

-330 thru -339

30

45

7

4

 

0

7

0

82

 

 

-340 thru -349

30

17

7

4

 

2

21

90

302

 

 

-350 thru -359

30

45

7

4

 

2

21

90

386

 

 

-360 thru -369

0

17

7

4

 

2

21

60

212

 

 

-370 thru -379

0

45

7

4

 

2

21

60

296

 

NOTE: All times are in nominal seconds at 60 Hz. Multiply all timings by 120% at 50 Hz.