To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or
transmitted, in any form or by any means, mechanical, electronic, photocopying, recording, or otherwise,
without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the
information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality
products, the information contained in this manual is subject to change without notice. Every precaution has
been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or omissions.
Neither is any liability assumed for damages resulting from the use of the information contained in this
publication.
YAS KAWA ELE CTR IC TOBP C730600 42D 1000-Series Option SI-P3 Installation Manual3
Page 4
1 Preface and Safety
1Preface and Safety
Yaskawa manufactures products used as components in a wide variety of industrial systems
and equipment. The selection and application of Yaskawa products remain the responsibility
of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its
products are incorporated into the final system design. Under no circumstances should any
Yaskawa product be incorporated into any product or design as the exclusive or sole safety
control. Without exception, all controls should be designed to detect faults dynamically and
fail safely under all circumstances. All systems or equipment designed to incorporate a
product manufactured by Yaskawa must be supplied to the end user with appropriate
warnings and instructions as to the safe use and operation of that part. Any warnings
provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express
warranty only as to the quality of its products in conforming to standards and specifications
published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS
OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses,
or claims arising from misapplication of its products.
◆
Applicable Documentation
The following manuals are available for the option:
Read this manual first.
The installation manual is packaged with the option
and contains information required to install the option
and set up related drive parameters.
The technical manual contains detailed information
about the option. Access the following sites to obtain
the technical manual:
U.S.: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://www.e-mechatronics.com
Other areas: Contact a Yaskawa representative.
Yaskawa Drive
The drive manuals cover basic installation, wiring,
YASKAWA AC Drive
1000-Series Quick Start Guide
YASKAWA AC Drive
1000-Series Technical Manual
4YASKAWA ELECTRIC TOBP C730600 42D 1000-Series Option SI-P3 Installation Manual
operation procedures, functions, troubleshooting, and
maintenance information.
The manuals also include important information about
parameter settings and drive tuning.
Access these sites to obtain Yaskawa instruction manuals:
U.S.: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://www.e-mechatronics.com
Page 5
1 Preface and Safety
DANGER
W ARNING
◆
Terms and Abbreviations
Note:Indicates a supplement or precaution that does not cause drive damage.
Drive: YASKAWA AC Drive 1000-Series
Option: YASKAWA AC Drive 1000-Series Option PROFIBUS-DP SI-P3
V/f: V/f Control
CLV: Closed Loop Vector Control
OLV/PM: Open Loop Vector Control for PM
AOLV/PM: Advanced Open Loop Vector Control for PM
CLV/PM: Closed Loop Vector Control for PM
◆
Registered Trademarks
• PROFIBUS-DP is a registered trademark of PROFIBUS and PROFINET International.
• Trademarks are the property of their respective owners.
◆
Supplemental Safety Information
Read and understand this manual before installing, operating, or servicing this option. Install
the option according to this manual and local codes.
The following conventions indicate safety messages in this manual. Failure to heed these
messages could cause fatal injury or damage products and related equipment and systems.
Indicates a hazardous situation, which, if not avoided, will result in death or serious
injury.
Indicates a hazardous situation, which, if not avoided, could result in death or
serious injury.
Indicates a hazardous situation, which, if not avoided, could result in minor or
moderate injury.
Indicates an equipment damage message.
■General Safety
General Precautions
• The diagrams in this book may include options and drives without covers or safety shields to
illustrate details. Be sure to reinstall covers or shields before operating any devices. Use the option
according to the instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and
may not apply to all products to which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the
manual may be changed without notice to improve the product and/or the manual.
• When ordering new copies of the manual, contact a Yaskawa representative or the nearest Yaskawa
sales office and provide the manual number shown on the front cover.
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting
from failure to heed the warnings in this manual.
The SI-P3 PROFIBUS-DP Option is an open digital communication system supporting a
wide range of fast, time-critical applications.
PROFIBUS Decentralized Periphery (PROFIBUS-DP) is one of the three PROFIBUS
variants. DP is dedicated to fast data communication between systems and peripherals at a
field level. This option connects a Yaskawa drive to a field network using the PROFIBUSDP protocol.
PROFIBUS-DP is included into the European Fieldbus Standard EN 50170.
The network is primarily used in process and factory automation.
Installing the option to a Yaskawa drive allows a PROFIBUS-DP master device to:
• operate the drive
• monitor the operation status of the drive
• change parameter settings.
◆
Applicable Models
The option can be used with the models in Table 1.
Table 1 Applicable Models
Drive SeriesDrive Model Number
A1000All models
U1000All models
U1000LAll models
Z1000UAll models
8YASKAWA ELECTRIC TOBP C730600 42D 1000-Series Option SI-P3 Installation Manual
Page 9
3 Receiving
MANUAL
3Receiving
Please perform the following tasks upon receiving the option:
• Inspect the option for damage. Contact the shipper immediately if the option appears
damaged upon receipt.
• Verify receipt of the correct model by checking the model number printed on the option
nameplate (Refer to Figure 1 on page 10).
• Contact your supplier if you have received the wrong model or the option does not
function properly.
◆
Contents and Packaging
Table 2 Contents of Package
Description:Option
Quantity:113 11
◆
Tools Required for Installation
Ground
Wire
• A Phillips screwdriver (M3 metric / #1, #2 U.S. standard size) is required to install the
option.
• A pair of diagonal cutting pliers.
• A small file or medium-grit sandpaper.
Note: Tools required to prepare option cables for wiring are not listed in this manual.
A – Connector (CN5)F – LED (ERR)
B – Installation holeG – Ground terminal and installation hole <2>
C – LED (RUN) <1>H – Communication cable connector
D–LED (COMM)
E – LED (BF)
<1> Refer to Option LED Display on page 11 for details on the LEDs.
<2> The ground wire provided in the option shipping package must be connected during installation.
10YASKAWA ELECTRIC TOBP C730600 42D 1000-Series Option SI-P3 Installation Manual
<1>I – Model number
<1>
Figure 1 PROFIBUS-DP Option Components
<1>
Page 11
4 Option Components
1
5
6
9
7
8
2
3
4
◆
Communication Connector
The option has a 9-pin D-sub connector to connect to a PROFIBUS network.
Table 3 Communication Connector (9-pin D-sub)
ConnectorPinSignalDescription
1ShieldConnected to the metal-shell (no direct FG-connection)
2––
3RxD/TxD-P Receive/Transmit data; line B (red)
4CNTR-PControl signal for repeaters (direction control)
5DGNDData ground (reference voltage to VP)
6VPPower supply output for bus termination (for termination resistor)
7––
8RxD/TxD-N Receive/Transmit data; line A (green)
9––
◆
Option LED Display
The option has four bicolor, red/green LEDs to relay information about power,
communication status, and errors.
The operational states of the LEDs after completion of the power-up diagnostic process are
described in Table 5. Wait at least 2 seconds for the power-up diagnostic process to complete
before verifying the states of the LEDs.
Table 4 Option LED States
LED
RUN
(Power)
ERR
(Option Error)
Display
Color Status
Green
OFF
Flashing
Red
OFF
Operating
Status
Power supply ONPower is supplied to the option, and the option hardware
ON
Power supply
OFF
ONOption errorSelf-diagnostics error occurred in the option.
Drive connection
error
Normal
operation
self-diagnostics check is complete.
• The drive has no power supply.
• Option and drive are not connected properly and/or no
power is supplied to the option.
• An internal, self-diagnostic error occurred in the option.
Connection error between option and drive. This includes
node address setting errors to parameter F6-30 on the drive
side.
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Disconnect all power to the drive and wait at least the amount of time specified on the
drive front cover safety label. After all indicators are off, measure the DC bus voltage to
confirm safe level, and check for unsafe voltages before servicing. The internal capacitor
remains charged after the power supply is turned off.
Electrical Shock Hazard
Do not remove the front covers of the drive while the power is on.
Failure to comply could result in death or serious injury.
The diagrams in this section may include options and drives without covers or safety
shields to show details. Be sure to reinstall covers or shields before operating any devices.
Use the option according to the instructions described in this manual.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized
personnel familiar with installation, adjustment, and maintenance of this product.
Do not touch circuit boards while the power to the drive is on.
Failure to comply could result in death or serious injury.
14YASKAWA ELECTRIC TOBP C730600 42D 1000-Series Option SI-P3 Installation Manual
Page 15
5 Installation Procedure
NOTICE
W ARNING
Do not use damaged wires, stress the wiring, or damage the wire insulation.
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to
overheating of electrical connections.
Damage to Equipment
Observe proper electrostatic discharge (ESD) procedures when handling the option,
drive, and circuit boards.
Failure to comply may result in ESD damage to circuitry.
Never shut the power off while the drive is running or outputting voltage.
Failure to comply may cause the application to operate incorrectly or damage the drive.
Do not operate damaged equipment.
Failure to comply may cause further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Tighten all terminal screws to the specified tightening torque.
Failure to comply could result in damage to the terminal block.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance.
Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive.
Note: Refer to the instruction manual of a specific drive for details.
Prior to installing the option, wire the drive, make the necessary connections to the drive
terminals, and verify that the drive functions normally. Refer to the Quick Start Guide
packaged with the drive for information on wiring and connecting the drive.
Figure 2 shows an exploded view of the drive with the option and related components for
reference.
Figure 2
A – Insertion point for CN5H – Included screws
B – Option cardI – Ground wire
C – Front coverJ – Drive grounding terminal (FE)
D – Digital operatorK – Connector CN5-A
E – LED labelL – Connector CN5-B
F – Terminal coverM – Connector CN5-C
G – Removable tabs for wire routing
Figure 2 Drive Components with Option (CIMR-A2A)
Refer to the instructions below to install the option.
Note: Refer to the instruction manual of a specific drive for information on removing and installing the
operators and the covers.
DANGER! Electrical Shock Hazard. Disconnect all power to the drive and wait at least the amount of time
specified on the drive front cover safety label. After all indicators are off, measure the DC bus voltage to
confirm safe level, and check for unsafe voltages before servicing to prevent electric shock. The internal
capacitor remains charged even after the power supply is turned off.
1.
Shut off power to the drive, wait the appropriate amount of time for voltage to
dissipate, then remove the digital operator (D), front cover (C), and terminal cover
(F). Refer to the Quick Start Guide packaged with the drive for directions on
removing the front covers. Cover removal varies depending on drive size.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling
the option, drive, and circuit boards. Failure to comply may result in ESD damage to circuitry.
Figure 3
Figure 3 Remove the Front Cover, Terminal Cover, and Digital Operator
Connect the ground wire (I) to the ground terminal (J) using one of the remaining
provided screws (H). Connect the other end of the ground wire (I) to the remaining
ground terminal and installation hole on the option using the last remaining provided
Figure 6
screw (H).
Figure 6 Connect the Ground Wire
Note: There are two screw holes on the drive for use as ground terminals. When connecting three
options, two ground wires will need to share the same drive ground terminal.
5.
Confirm proper option wiring.
Depending on the drive model, some drives may require routing the wiring through
the side of the front cover to the outside. In these cases, use diagonal cutters to cut
out the perforated openings in the left side of the drive front cover as shown in
Figure 7-A and leave no sharp edges to damage wiring.
Route the wiring inside the enclosure as shown in Figure 7-B for drives that do not
require routing through the front cover. Refer to the Peripheral Devices & Options
section of the drive Technical Manual for more information.
<1> The drive will not meet NEMA Type 1 requirements if wiring is exposed outside the enclosure.
6.
Select proper PROFIBUS-DP cables.
<1>
Figure 7 Wire Routing Examples
B – Use the open space provided
inside the drive to route option
wiring.
Communication Cable Specifications
To ensure proper performance, Yaskawa recommends using PROFIBUS-DPdedicated cables. Refer to the PROFIBUS-DP website at www.profibus.com for
more information on cables.
Yaskawa recommends using PROFIBUS-DP cables suitable for the conditions
listed in Tabl e 6 and Table 7.
Table 6 Communication Cable Requirements
ConditionSpecifications
Impedance135 to 165 Ω at a frequency of (3 to 20 MHz)
Turn on the termination resistor
switch for the last node on the bus.
SI-P3
RTS
DGND
VP
A-line
B-line
1B
1A
3
8
4
6
5
2B
2A
CN5-A
FE
<1>
PROFIBUS cable
PROFIBUS cable connector
(Red)
(Green)
(Red)
(Green)
(Shell)
To PROFIBUS-DP
master
To the next slave
(Shell)
390 Ω220 Ω390 Ω
Table 7 Communication Cable Length
Communication Speed (kbps)Distance per Segment
9.61200 m (3937 ft.)
19.21200 m (3937 ft.)
45.451200 m (3937 ft.)
93.751200 m (3937 ft.)
187.51000 m (3280 ft.)
500400 m (1312 ft.)
1500200 m (656 ft.)
3000100 m (328 ft.)
6000100 m (328 ft.)
12000100 m (328 ft.)
Figure 8
Connection Diagram
Figure 8 Option Connection Diagram
<1> The ground wire provided in the option shipping package must be connected
during installation.
PROFIBUS-DP Termination
The option does not have a built-in termination resistor. The termination resistance
must be set on the final drive in the network using a switch on the 9-pin D-sub
connector. Make sure that only the connector for the final drive in the network has a
termination resistor; communication problems may arise if any other network drive
has a termination resistor.
Use only the input side cable entry as shown in Figure 9 when connecting both
ends of the network. Most 9-pin D-sub connectors have a function for disconnecting
the output side of the cable. Communication will not be possible between devices if
the connector is reversed. Most connectors have arrows indicating the input and
output sides.
Figure 9 PROFIBUS Cable Connection with Termination Resistors
Bus termination ON = incoming and outgoing cables not connected.
Bus termination OFF = incoming and outgoing cables connected.
Termination resistors without inductors as shown in Figure 10 can only be used for
baud rates below 1.5 Mbps. Baud rates 1.5 Mbps and higher require termination
with resistors and inductors as shown in Figure 8.
VP (pin 6)
390 Ω
B - Data line
RxD/TxD-P (pin 3)
220 Ω
A - Data line
RxD/TxD-N (pin 8)
390 Ω
DGND (pin 5)
Figure 10 Cable Termination of the Option Cable to EN50170
The following parameters are used to set up the drive for operation with the option.
Confirm proper setting of all parameters in Tab le 8 before starting network communications.
Table 8 Related Parameters
No.
(Addr. Hex)
b1-01
(180)
<1>
b1-02
(181)
<1>
F6-01
(3A2)
F6-02
(3A3)
F6-03
(3A4)
F6-06
(3A7)
<5>
F6-07
(3A8)
NameDescriptionValue s
Selects the frequency reference input source.
Frequency Reference
Selection 1
Run Command Selection 1
Communications Error
Operation Selection
External Fault from Comm.
Option Detection Selection
External Fault from Comm.
Option Operation Selection
Torque Reference/Torque
Limit Selection from Comm.
Option
Multi-Step Speed Enable/
Disable Selection when
NefRef/ComRef is Selected
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option
4: Pulse Input (Terminal RP)
Selects the run command input source.
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S
2: MEMOBUS/Modbus communications
3: Option
Determines drive response when a bUS error is
detected during communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
4: Alarm and Run at d1-04 <2> <3> <4>
5: Alarm and Ramp to stop <3> <4>
Sets the condition for external fault detection (EF0).
0: Always detected
1: Detected only during operation
Determines drive response for external fault input
(EF0) detection during PROFIBUS communication.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0: Torque reference/torque limit via network
communications are disabled.
1: Torque reference/torque limit via network
communications are enabled.
Determines which F6- and F7- parameters
are reset to default values when initializing the drive
using A1-03.
0: Do not reset parameters
1: Reset parameters
Note: Setting this parameter does not affect
communication-related parameters. Setting this
parameter only determines if communication-related
parameters
(F6- and F7-) are also reset when initializing
with A1-03.
Enables or disables the bUS Error Auto Reset.
0: Disabled
1: Enabled
Sets the node address.
Selects the action to take when a “Clear Mode”
command is received.
0: Resets to 0
1: Maintains the previous value
Sets the time-out value for communication loss
detection in tenths of a second. A value of 0 disables
the connection time-out.
Example: An entered value of 100 represents 10.0
seconds.
Sets MEMOBUS/Modbus address for PZD1 Write
(PPO Write).
The value of 0 to 2 enables the PZD1 Write as STW.
Sets MEMOBUS/Modbus address for PZD2 Write
(PPO Write).
The value of 0 to 2 enables the PZD2 Write as HSW.
Sets MEMOBUS/Modbus address for PZD3 Write
(PPO Write).
The value of 0 to 2 disables the PZD3 Write.
Sets MEMOBUS/Modbus address for PZD4 Write
(PPO Write).
The value of 0 to 2 disables the PZD4 Write.
<1> Set b1-02 to 3 to start and stop the drive through the PROFIBUS-DP network. Set b1-01 to 3 to control the
frequency reference of the drive via the PROFIBUS-DP network.
<2> Take proper safety measures, such as installing an emergency stop switch, when setting F6-03 to 3 or 4, as the
drive will continue operation when detecting a fault.
<3> Available in the A1000 software versions PRG: 1021 and later.
<4> Refer to the instruction manual of a specific drive to determine if settings 4 and 5 are available in the drive.
<5> Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7). When enabled, d5-01 determines
whether the value is read as the torque limit value (d5-01 = 0) or as the torque reference value (d5-01 = 1). In
CLV/PM, this value is read as the torque limit.
<6> Default setting specifies that the torque reference or torque limit is to be provided via network communications
(F6-06 = 1). The motor may not rotate if no torque reference or torque limit is supplied from the PLC.
<7> Available in the option software versions PRG: 2103 and later.
<8> All node addresses must be unique. Node addresses 0, 1, and 2 are typically reserved for control, maintenance,
and diagnostic equipment. The “Err” LED will illuminate when a value of 0 or a value greater than 125 is entered.
<9> Cycle power for setting changes to take effect.
<10> Requires also setting bit 0 to 1 to issue Run command. Refer to the option Technical Manual for more
information.
<11> When writing this parameter to the drive through the PROFIBUS-DP network, the parameter is validated by
automatically executing the Enter command.
PZD9 Read
PZD10 Read
NameDescriptionValu es
Sets MEMOBUS/Modbus address for PZD9 Read
(PPO Read).
The value of 0 to 2 disables the PZD9 Read.
Sets MEMOBUS/Modbus address for PZD10 Read
(PPO Read).
The value of 0 to 2 disables the PZD10 Read.
The PROFIBUS-DP master configuration tool sets the I/O data length of the option from
Extended Data 1 (32 bytes), Extended Data 2 (12 bytes), and Basic Data (6 bytes).
Conventional formats have two message types: High-speed I/O Data and MEMOBUS/
Modbus message. Set parameter F6-32 to 1 to use conventional formats.
■High-Speed I/O Data
High-speed I/O data is directly transferred between the drive and controller or PLC. When
the drive is set for PROFIBUS-DP communications, the drive Run/Stop and Frequency
Reference commands are transferred within 2 ms after being received by the option.
■MEMOBUS/Modbus Message
MEMOBUS/Modbus message data is transferred between the drive and controller or PLC
using MEMOBUS/Modbus messages. All drive parameters and data can be accessed
through MEMOBUS/Modbus. The data in this message type is transferred to the drive after
being received and edited by the option and more time is required to return the data to the
master. The master must synchronize the timing of sending and receiving the data by a
process called handshaking.
◆
Memory Maps
The following register maps show the I/O data bytes.
■Basic and Extended Register Maps
Table 9 Number of Bytes in Basic and Extended Data Messages
Basic Data
(6 bytes)
High-speed I/O DataBytes 0 to 5Bytes 0 to 15Bytes 0 to 3
MEMOBUS/Modbus Data–Bytes 16 to 31Bytes 4 to 11
Extended Data 1
(32 bytes)
Extended Data 2
(12 bytes)
Table 10 Basic Data Register Map Detail
Output (Master Device to Drive)Input (Drive to Master Device)
ByteDescriptionByteDescription
0Operation Command High Byte 0Drive Status High Byte
1Operation Command Low Byte1Drive Status Low Byte
2Frequency Reference High Byte2Motor Speed High Byte
4Torque Reference/Torque Limit High Byte <1> <2>4Output Current High Byte <4>
5Torque Reference/Torque Limit Low Byte <1> <2>5Output Current High Byte <4>
<1> Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7).
<2> Set when network communication is designated as the source of the torque limit and torque reference
(F6-06 = 1). When enabled, d5-01 determines whether the value is read as the torque limit value (d5-01 = 0) or as
the torque reference value (d5-01 = 1). In CLV/PM, this value is read as the torque limit.
<3> Unit depends on the setting of o1-03 (Digital Operator Display Scaling). When the drive is operating in V/f
Control or OLV/PM, the drive output frequency becomes the input data.
<4> Data is displayed in units of 0.01 A for drives 7.5 kW and smaller, and in units of 0.1 A for drives 11 kW and
larger. The number of decimal places in the parameter value depends on the drive model and the ND/HD selection
in parameter C6-01. For delails, refer to the 1.3 Model Number and Nameplate Check of the drive Technical
Manual.
Table 11 Extended Data 1 Register Map
Output (Master Device to Drive)Input (Drive to Master Device)
ByteDescriptionByteDescription
0Operation Command High Byte0Drive Status High Byte
1Operation Command Low Byte1Drive Status Low Byte
2Frequency Reference High Byte2Motor Speed High Byte
Output (Master Device to Drive)Input (Drive to Master Device)
ByteDescriptionByteDescription
20MEMOBUS/Modbus Data 1 High Byte20MEMOBUS/Modbus Data 1 High Byte
21MEMOBUS/Modbus Data 1 Low Byte21MEMOBUS/Modbus Data 1 Low Byte
22MEMOBUS/Modbus Data 2 High Byte22MEMOBUS/Modbus Data 2 High Byte
23MEMOBUS/Modbus Data 2 Low Byte23MEMOBUS/Modbus Data 2 Low Byte
24MEMOBUS/Modbus Data 3 High Byte24MEMOBUS/Modbus Data 3 High Byte
25MEMOBUS/Modbus Data 3 Low Byte25MEMOBUS/Modbus Data 3 Low Byte
26MEMOBUS/Modbus Data 4 High Byte26MEMOBUS/Modbus Data 4 High Byte
27MEMOBUS/Modbus Data 4 Low Byte27MEMOBUS/Modbus Data 4 Low Byte
28 to 30 Reserved28 to 30 Reserved
31Handshaking Register31Handshaking Register
<1> Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7).
<2> Set when network communication is designated as the source of the torque limit and torque reference
(F6-06 = 1).When enabled, d5-01 determines whether the value is read as the torque limit value (d5-01 = 0) or
read as the torque reference value (d5-01 = 1). In CLV/PM, this value is read as the torque limit.
<3> To select drive analog output channel for communications, set H4-01 (Multi-Function Analog Output Terminal
FM) and H4-04 (Multi-Function Analog Output Terminal AM) to 000 (through-mode).
<4> Drive digital output ON/OFF during communications, set H2-01 (Terminal M1, M2 and MC Function Selection
(relay)), H2-02 (Terminal P1-PC Function Selection (open-collector)), and H2-03 (Terminal P2-PC Function
Selection (open-collector)) to F (through-mode).
<5> Unit depends on the setting of o1-03 (Digital Operator Display Scaling). Input data is 0 when the drive is set for
V/f Control or OLV/PM.
<6> Not possible when using V/f control, V/f with PG, or OLV/PM (A1-02 = 0, 1, or 5).
<7> Data is displayed in units of 0.01 A for drives 7.5 kW and smaller, and in units of 0.1 A for drives 11 kW and
larger. The number of decimal places in the parameter value depends on the drive model and the ND/HD selection
in parameter C6-01. For delails, refer to the 1.3 Model Number and Nameplate Check of the drive Technical
Manual.
Table 12 Extended Data 2 Register Map
Output (Master Device to Drive)Input (Drive to Master Device)
ByteDescriptionByteDescription
0Operation Command High Byte0Drive Status High Byte
1Operation Command Low Byte1Drive Status Low Byte
2Frequency Reference High Byte2Motor Speed High Byte
Output (Master Device to Drive)Input (Drive to Master Device)
ByteDescriptionByteDescription
9MEMOBUS/Modbus Data 1 Low Byte9MEMOBUS/Modbus Data 1 Low Byte
10Reserved10Reserved
11Handshaking Register11Handshaking Register
<1> Unit depends on the setting of o1-03 (Digital Operator Display Scaling). When the drive is operating in V/f
Control or OLV/PM, the drive output frequency becomes the input data.
◆
Supported Parameter Process Data Object (PPO) Type Formats
Set drive parameter F6-32 to 0 to use PPO type formats. The PPO is defined for cyclic data
transfer, allowing the master and the slave to exchange process data (PZD) and parameters.
Refer to the PROFIBUS specification for more information on PPO types 1~5.
The option supports five possible PPO type formats:
• PPO type 1 (8 octets PKW + 4 octets PZD)
• PPO type 2 (8 octets PKW + 12 octets PZD)
• PPO type 3 (4 octets PZD)
• PPO type 4 (12 octets PZD)
• PPO type 5 (8 octets PKW + 20 octets PZD)
All PPO Types have the registers STW, ZSW, HSW, and HIW. These registers are not
mapped directly to drive registers.
Ta bl e 1 3 lists the various fault codes related to the option. Further details on various faults
can be found in the drive Technical Manual.
■Faults
Both bUS (Option Communication Error) and EF0 (External Fault Input from the option)
can appear as either an alarm or as a fault. When a fault occurs, the digital operator ALM
LED remains lit. When an alarm occurs, the digital operator ALM LED flashes.
Check the following items first when an error code occurs on the drive:
• Communication cable connections
• Make sure the option is properly installed to the drive
• Operation status of the controller program and controller CPU
• Did a momentary power loss interrupt communications?
Table 13 Fault Displays, Causes, and Possible Solutions
Digital Operator DisplayFault Name
Option Communication Error
bUS
CausePossible Solution
Master controller (PLC) has
stopped communicating.
Communication cable is not
connected properly.
A data error occurred due to
noise.
Option is damaged. If there are no wiring problems and the error continues to occur, replace the option.
Digital Operator DisplayFault Name
EF0
CausePossible Solution
An external fault is being sent
from the main controller (PLC).
Problem with the PLC program.
The connection was lost after establishing initial communication.
Only detected when the run command frequency reference is assigned to the option
(bl-01 = 3 or bl-02 = 3).
Check for faulty wiring.
Correct any wiring problems.
• Counteract noise in control circuit wiring, main circuit lines, and ground wiring.
• If a magnetic contactor is the noise source, install a surge absorber to the
contactor coil.
• Use cables recommended by Yaskawa or another type of shielded line. Ground
the shield on the controller side and on the option side.
External Fault Input from the option
The alarm function for an external device has been triggered.
• Remove the cause of the external fault.
• Reset the external fault input from the PLC device.
Check the program used by the PLC and make the appropriate corrections.
Options AI-A3 or D1-A3
connected to the CN5-C port
while an option was connected
to CN5-A.
Option Fault (CN5-C)
Two of the same options are connected simultaneously.
Only one of these options, AI-A3, DI-A3 or SI- option can be connected to the
drive at the same time. The SI-N3 must be connected to CN5-A.
■Minor Faults and Alarms
Digital Operator DisplayMinor Fault Name
bb
CausePossible Solution
The drive output is disabled.
“bb” is displayed on the operator
when the drive is set for control by
PROFIBUS-DP, and a conventional
data format is used,
and the operation command bit F is
set to 1, or a PPO type data format is
used, and the control word (STW)
bit 3 is set to 0.
Digital Operator DisplayMinor Fault Name
CALL
CausePossible Solution
Communication wiring or terminal
resistor connection is faulty. There is
a short circuit, or an option
component is not connected
properly.
Master-side programming error.
Damaged communication circuitry.
Baseblock
Data format and setting contents do not match.
Set either of the bits depending on the data format used. No output
Serial Communication Transmission Error
Communication has not yet been established.
Check for wiring errors and correct the wiring.
Remove any ground shorts and reconnect loose wires.
Check communications at start-up and correct
programming errors.
Perform a self-diagnostics check and replace the drive
if the fault continues to occur.
The CE mark indicates compliance with European safety and environmental regulations. It
is required for engaging in business and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low
Voltage Directive for electronics manufacturers, and the EMC guidelines for controlling
noise.
This option displays the CE mark based on the EMC guidelines.
EMC Guidelines: 2004/108/EC
Drives used in combination with this option and devices used in combination with the drive
must also be CE certified and display the CE mark. When using drives displaying the CE
mark in combination with other devices, it is ultimately the responsibility of the user to
ensure compliance with CE standards. After setting up the device, verify that conditions
meet European standards.
◆
EMC Guidelines Compliance
This option is tested according to European standards EN61800-3:2004/A1:2012 and
complies with EMC guidelines. We declared the CE marking based on the harmonized
standards.
■Installation Method
Verify the following installation conditions to ensure that other devices and machinery used
in combination with this option and drives also comply with EMC guidelines.
1.
Use dedicated shield cable for the option and external device (encoder, I/O device,
master), or run the wiring through a metal conduit.
2.
Keep wiring as short as possible. Ground the shield according to Figure 14.
3.
Ground the largest possible surface area of the shield to the metal panel when
using dedicated shield cable.
36YASKAWA ELECTRIC TOBP C730600 42D 1000-Series Option SI-P3 Installation Manual
Room 1011, Tower W3 Oriental Plaza, No. 1, East Chang An Ave.,
Dong Cheng District, Beijing, 100738, China
Phone: +86-10-8518-4086
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei, 104, Taiwan
Phone: +886-2-2502-5003
http://www.yaskawa.com.tw
YASKAWA INDIA PRIVATE LIMITED
#17/A, Electronics City, Hosur Road, Bangalore, 560 100 (Karnataka), India
Phone: +91-80-4244-1900
http://www.yaskawaindia.in
Fax: +55-11-3585-1187
Fax: +82-2-784-8495
Fax: +65-6289-3003
Fax: +86-10-8518-4082
Fax: +886-2-2505-1280
Fax: +91-80-4244-1901
In the event that the end user of this product is to be the military and said product is to be
employed in any weapons systems or the manufacture thereof, the expor t will fall under the
relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations.
Therefore, be sure to follow all procedures and submit all relevant documentation according
to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and
improvements.