Xylem CPC User Manual

Steps for setting up 2 (or more) communicating Aquavar CPC drives:
1
Connect 3 Wires to terminals 29,
30 & 31 on both
drives
2
On the Keypad of the first drive Go To:
Menu
Parameters
Group 11
Parameter 1102
(Application macro)
Change to: Multicontrol
4
Now on the 2nd Drive, Exit out to Groups
Go to Group 22
Parameter 2207
(Pump Address)
Change value to 2
3
Repeat step 2 on the 2nd drive
Repeat steps 3 and 4 for (up to 2) additional drives as needed
These simple instructions are in addition to the basic wiring and programming used for setting up individual drives.
For expanded detail of Aquavar CPC setup and capabilities, refer to IM167, Aquavar CPC Instruction and Operation manual.
(Recommend 22AWG 3 or 4 wire shielded cable)
Notes:
February 2011