Xylem BrazedPlate Heat Exchangers User Manual

Heat Transfer
BrazedPlate Heat Exchangers
Installation, Operation and Maintenance Manual
Installation
FIGURE 1
FIGURE 2
T
Mb
Mv
Evaporators
Refrig. In: ......... F4
Refrig. Out: ...... F1
Liquid In:............ F2
Liquid Out: ......... F3
STEAM TO LIQUID
Condensers
Steam In: ......... F1
Condensate Out: F4
Liquid In:............ F3
Liquid Out: ......... F2
Condensers
REFRIGERATION:
Refrig. In: ......... F1
Refrig. Out: ...... F4
Liquid In:............ F3
Liquid Out: ......... F2
TABLE 4
TABLE 1
of ITT Brazed Plate Heat Exchangers
Upon receipt of the exchanger, inspect for shipping
1.
2.
3.
damage, especially to the connections. If damage is extensive, notify the carrier immediately. Finally, check the heat exchanger against proper drawings and spec sheets to make sure everything is as expected.
Before piping up, inspect all openings in the
heat exchanger for foreign material. Remove all plugs and shipping covers immediately prior to installing. Make sure it is thoroughly cleaned to remove all preservation materials, if any were used, unless the material is soluble in the system fluid.
For single phase fluids, the heat exchanger can be
mounted in any orientation that is convenient and should be piped in a counter current, parallel flow arrangement. For two phase fluids, the heat exchanger should be mounted vertically and piped as shown in Figure 1 and Table 1. Connections may be either on the front or back of the exchanger.
Provide air vent valves for the heat exchanger so that it
4.
5.
6.
7.
can be purged to prevent or relieve vapor or gas binding.
Install proper relief valves and temperature alarms to make sure the heat exchanger is not subject to
conditions beyond the intended design.
Do not weld or braze brackets or attachments directly to body of heat exchanger.
For soldering type connections, braze with minimum
45% silver solder and at maximum 1200° F. For welded type connections use TIG or MIG welding. Avoid overheating. A wet cloth or rag should be placed around the base of the connection. A Nitrogen purge should be used to avoid internal oxidation. Braze or weld with exchanger in the vertical position.
CAUTION:
Many Heat exchangers circulate fluids which are irritating or dangerous to the human system.
These fluids could cause problems if bolted or threaded joints are not maintained in a leak tight
condition at operating pressures, temperatures, and no flow, ambient conditions.
Even if fluids are not irritating or dangerous, a leak could cause a slippery situation on the floor below.
Since one fluid in the heat exchanger is at a higher temperature, any leaks may cause burns.
FIGURE 2
T
Mb
Mv
F
Liquid Hot Liquid Cold
Gas Hot Liquid Cold
Condensing Gas Hot Liquid Cold
Liquid or Gas Hot Vaporizing Liquid Cold
Start both fluids gradually at the same time.
Start cold fluid first then hot fluid.
Start hot fluid first then slowly start cold fluid. Avoid temperature shock.
Start hot fluid first then cold fluid.
Shut down both fluids gradually at the same time.
Shut down hot fluid gradually then cold fluid.
Shut down cold fluid first then hot fluid.
Shut down cold fluid first then hot fluid.
Type of Fluid Relative Type of Fluid Relative Start-Up Shut-Down
Temperature Temperature Procedure Procedure
TABLE 4
Condensers
REFRIGERATION: STEAM TO LIQUID
Refrig. In: F1
Refrig. Out: F4
Liquid In: F3
Liquid Out: F2
Evaporators
Refrig. In: F4
Refrig. Out: F1
Liquid In: F2
Liquid Out: F3
Evaporators
Refrig. In: ......... F4
Refrig. Out: ...... F1
Liquid In:............ F2
Liquid Out: ......... F3
Condensers
Steam In: F1
Condensate Out: F4
Liquid In: F3
Liquid Out: F2
STEAM TO LIQUID
Condensers
Steam In: ......... F1
Condensate Out: F4
Liquid In:............ F3
Liquid Out: ......... F2
Model T (lbs) F (lbs) Mb (in-lbs) Mv (in-lbs)
400 3327 1798.4 (-1348.8) 327.5 1504.6 410 411 5552.6 1798.4 (-1348.8) 540 1504.6 412
415 5552.6 2158.1 (-1663.5) 540 3407.5
422 24952.8 6069.6 (-4720.8) 6550 8912.7
433 Consult Factory Consult Factory
Start both fluids gradually at the same time.
Start cold fluid first then hot fluid.
Start hot fluid first then slowly start cold fluid. Avoid temperature shock.
Start hot fluid first then cold fluid.
Shut down both fluids gradually at the same time.
Shut down hot fluid gradually then cold fluid.
Shut down cold fluid first then hot fluid.
Shut down cold fluid first then hot fluid.
Temperature Temperature Procedure Procedure
Condensers
REFRIGERATION:
Refrig. In: ......... F1
Refrig. Out: ...... F4
Liquid In:............ F3
Liquid Out: ......... F2
TABLE 2
TABLE 4
435 psig Standard Design
Condensers
REFRIGERATION: STEAM TO LIQUID
Refrig. In: F1
Refrig. Out: F4
Liquid In: F3
Liquid Out: F2
Evaporators
Refrig. In: F4
Refrig. Out: F1
Liquid In: F2
Liquid Out: F3
Evaporators
Refrig. In: ......... F4
Refrig. Out: ...... F1
Liquid In:............ F2
Liquid Out: ......... F3
Condensers
Steam In: F1
Condensate Out: F4
Liquid In: F3
Liquid Out: F2
STEAM TO LIQUID
Condensers
Steam In: ......... F1
Condensate Out: F4
Liquid In:............ F3
Liquid Out: ......... F2
Model T (lbs) F (lbs) Mb (in-lbs) Mv (in-lbs)
400 3327 1798.4 (-1348.8) 327.5 1504.6 410 411 5552.6 1798.4 (-1348.8) 540 1504.6 412
415 5552.6 2158.1 (-1663.5) 540 3407.5
422 24952.8 6069.6 (-4720.8) 6550 8912.7
433 Consult Factory Consult Factory
Model T (lbs) F (lbs) Mb (in-lbs) Mv (in-lbs)
400 200 100 20 200 410 411 280 130 27 300 412
Start both fluids gradually at the same time.
Start cold fluid first then hot fluid.
Start hot fluid first then slowly start cold fluid. Avoid temperature shock.
Start hot fluid first then cold fluid.
Shut down both fluids gradually at the same time.
Shut down hot fluid gradually then cold fluid.
Shut down cold fluid first then hot fluid.
Shut down cold fluid first then hot fluid.
Temperature Temperature Procedure Procedure
Condensers
REFRIGERATION:
Refrig. In: ......... F1
Refrig. Out: ...... F4
Liquid In:............ F3
Liquid Out: ......... F2
TABLE 2
TABLE 4
TABLE 3
The nozzle connections are designed
8.
for normal torque force and damage may occur if over tightened. The use of pipe sealant materials compatible with the system fluids is recommended for threaded type connections. Connection load limits should be observed and are shown in Figure 2, Table 2, and Table 3.
150 psig Pressure Design
Operation
Be sure the entire system is clean
1.
vent plugging of passages with debris. The use of strainers or settling tanks in pipelines leading to the heat exchanger is recommended. The recommended strainer size is 20-24 mesh.
before starting operation to pre-
2. 3.
Start operating gradually. See
Table 4 for suggested start-up and shut-down procedures for most applications. If in doubt, consult the nearest ITT Heat Transfer representative for specific instructions.
CAUTION:
A heat exchanger is a pressure vessel designed for operation at certain specific limits of pressure and temperature. The cooling or process system,
which includes the heat exchanger, must be safeguarded with safety valves and controls so that these heat exchanger design conditions are not
exceeded. All operating personnel should be made aware of these specific design pressures and temperatures.
conditions in excess of the specified design limits shown on the nameplate attached to the heat exchanger.
4.
corroding.
Do not operate the heat exchanger under pressure and/or temperature
Drain all fluids when shutting down to eliminate possible freezing and
Maintenance
Clean exchangers subject to
1.
fouling (scale, sludge deposits, etc.) periodically, depending on specific conditions. A sludge or scale coating on the plates can reduce effectiveness. A marked increase in pressure drop and/or reduction in performance usually indicates cleaning is necessary.
Some suggested methods of
3.
cleaning either side of the heat
exchanger are listed below:
n Back flush with a high pressure stream
of hot water to remove loose deposits.
n Circulating hot wash oil or light
distillate will usually effectively remove sludge or similar soft deposits.
n A 5% solution of Phosphoric Acid or
Ox al ic Acid may be effective in removing more stubborn deposits. For optimum results, the solution should be in a back flush type flow pattern. Rinse heat exchanger with cl ean fresh water after use . It is recommended that the refrigerant circuit not be chemically cleaned.
A s s u g g e s t e d u n de r
2.
strainer is recommended if the fluid quality is poor (extensive dirt, debris, and contaminants). If the fluids are relatively clean, there should be little problem with fouling so periodic cleaning is adequate.
4.
be cleaned by commercial cleaning methods, then replacement of the unit is suggested.
“Operation”, the use of a
If the h ea t e xc hange r i s excessively fouled and it cannot
NO TE : Use in accordance with
the manufacturer’s instructions and check that cleaning compounds are compatible with the materials of the heat exchanger. Since there are a wide variety of cleaning compounds av ai la bl e w hi ch are c ompatible with certain metals and alloys, it is recommended that you contact a representative of the above commercial cleaning products to determine which particular cleaning fluid they would suggest for your type of scaling problem.
CAUTION:
When the heat exchanger is cleaned, it is
important that full characteristics of the fouling
material and the cleaning agent be known and
care exercised in handling them according to
instructions. Use eye protection to prevent
damage to your eyes. Wear a respirator when
required.
CAUTION:
Do not exceed design conditions of heat
exchanger during operation or maintenance.
CAUTION:
Brazed plate heat exchangers have exposed
sharp metal surfaces. Protective gloves are
recommended during handling.
Warranty
Seller warrants only that it will furnish by freight a replacement for, or at its option repair, any product of its manufacture or part or portion thereof, proved to its satisfaction to be defective in material or workmanship under normal use and service within one (1) year from the date all other equipment or part thereof is first placed in use, or two (2) years from the date of shipment, whichever shall be less. See ITT terms and conditions of sale for details.
For m or e in fo rm at io n, pl ea se c on ta ct :
175 Standard Parkway Cheektowaga, NY 14227
800/447-7700 Fax: 716/897-1777 www.itt.com
Lit# 104-65 (4/07)
© 2007 ITT
Heat Transfer
Loading...