Xantrex Technology RS2000 User Manual

RS2000 Sine Wave Inverter/Charger
RS2000
Operation Guide
RS2000 Sine Wave Inverter/Charger
Operation Guide
About Xantrex
Xantrex Technology Inc. is a world-leading supplier of advanced power electronics and controls with products from 50 watt mobile units to one MW utility-scale systems for wind, solar, batteries, fuel cells, microturbines, and backup power applications in both grid-connected and stand-alone systems. Xantrex products inclu de inverters, batt ery chargers, programmable power supplies, and variable speed drives that convert, supply, control, clean, and distribute electrical power.
Trademarks
RS2000 Sine Wave Inverter/Charger is a trademark of Xantrex International. Xantrex and Xanbus are registered trademarks of Xantrex International.
Other trademarks, registered trademarks, and product names are the property of their respective owners and are used herein for identification purposes only.
Notice of Copyright
RS2000 Sine W a ve Inverter/Charger Operation Guide © June 2004 Xantrex International. All rights reserved.
Disclaimer
UNLESS SPECIFICALLY AGREED TO IN WRITING, XANTREX TECHNOLOGY INC. (“XANTREX”) (a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY
TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION. (b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT,
INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.
Date and Revision
June 2004 Rev A
Part Number
975-0125-01-01
Contact Information
Telephone: 1 800 670 0707 (toll free North America)
1 360 925 5097 (direct)
Fax: 1 800 994 7828 (toll free North America)
1 360 925 5143 (direct) Email: customerservice@xantrex.com Web: www.xantrex.com
About This Guide
Purpose
The RS2000 Sine Wave Inverter/Charger Operation Guide provides explanations and procedures for operating, configuring, and troubleshooting the RS2000 Sine Wave Inverter/Charger (RS2000).
Scope
The guide provides safety guidelines and information about operating, configuring, and troubleshooting the unit. It does not include information for installing the inverter/charger. Refer to the RS2000 Sine Wave
Inverter/Charger Installation Guide.
The guide also provides general guidelines on batteries; it does not provide details about particular brands of batteries. You need to consult individual battery manufacturers for this information.
Audience
The guide is intended for users who need to configure and operate the RS2000 Sine Wave Inverter/Charger.
Organization
This guide is organized into four chapters and three appendixes. Chapter 1, “Introduction”, outlines the main performance and safety
features of the RS2000 Sine Wave Inverter/Charger. Reading this chapter will give you a clear understanding of the inverter/charger’s capabilities.
Chapter 2, “Operation”, provides information about operating the RS2000. Details are provided on how to read the front panel indicators to monitor the RS2000.
Chapter 3, “Configuration”, explains how to configure the RS2000 from the control panel.
975-0125-01-01 iii
About This Guide
Chapter 4, “Troubleshooting”, explains how to identify and solve problems that can occur with the RS2000.
Appendix A, “Specifications” provides electrical, physical, and performance specifications for the inverter/charger.
Appendix B, “Battery Charging Reference” provides information on three-stage charging, two-stage charging, and charging times.
Appendix C, “Terminology” provides a glossary and a listing of commonly used abbrevations and acronyms.
“Warran ty and Product Information” contains the product warranty, explains how to return a product for service, and describes what to prepare for a call to Xantrex Customer Service.
Conventions Used
The following conventions are used in this guide.
WARNING
Warnings identify conditions or practices that could result in personal injury or loss of life.
CAUTION
Cautions identify conditions or practices that could result in damage to the RS2000 or other equipment.
Important:
you must pay attention to.
iv 975-0125-01-01
These notes describe an important action item or an item that
Symbols Used
About This Guide
The following symbols are used on the product labels or in this guide.
In this guide: Important information, warnings or cautions.
!
On the product: Important information, warnings or cautions with further explanation in the product guides.
AC – Alternating current
"
#
Related Information
For related materials on this product and its available accessories, see also:
RS2000 Sine Wave Inverter/Charger Installation Guide (975-0126-01-01) System Control Panel Owner’s Guide (975-0083-01-01) Automatic Generator Start Owner’s Guide (975-0082-01-01) Xanbus System Installation Guide (975-0136-01-01)
More information about Xantrex Technology Inc. as well as its products and services, including a complete list of Xanbus-enabled devices, is available at www.xantrex.com
Contact Information
Telephone: 1 800 670 0707 (toll free North America)
DC – Direct current
1 360 925 5097 (direct)
Fax: 1 800 994 7828 (toll free North America)
1 360 925 5143 (direct) Email: customerservice@xantrex.com Web: www.xantrex.com
975-0125-01-01 v
vi
Important Safety Instructions
READ AND SAVE THESE INSTRUCTIONS
The RS2000 Sine Wave Inverter/Charger Operation Guide contains important safety instructions.
Before you install and use your RS2000 Sine Wave Inverter/Charger, be sure to read, understand and save these safety instructions and those in the other product guides.
Read all instructions and cautionary markings on the inverter/char ger, the batteries and all appropriate sections of this guide.
WARNING: Risk of injury or loss of life
The RS2000 Sine W ave Inverter/Charger shall not be used in connection with life support systems or other medical equipment or devices.
WARNING
The following warnings identify conditions or practices that could result in personal injury or loss of life.
1. Use of accessories not recommended or sold by Xantrex T echnology, Inc. may result in a risk of fire, electric shock, or injury to persons.
2. The inverter/charger is designed to be permanently connected to your AC and DC electrical systems. Xantrex recommends that all wiring be done by a certified technician or electrician to ensure adherence to the local and national electrical codes applicable in your application.
3. To avoid a risk of fire and electr ic shock, make sure that existing wiring is in good condition and that wire is not undersized. Do not operate the inverter/charger with damaged or substandard wiring.
4. To reduce risk of damage and injury, charge only rechargeable lead-acid batteries (flooded, gel, or absorbed glass mat (AGM) types). Other types of batteries may burst causing personal injury and damage.
975-0125-01-01 vii
Safety
5. Do not operate the inverter/charger if it has received a sharp blow, been dropped, or otherwise damaged in any way. If the unit is damaged, see the “Warranty and Product Information” section in the
RS2000 Sine Wave Inverter/Charger Operation Guide.
6. Do not disassemble the inverter/charger; it does not contain user serviceable parts. T ake it to a qualified service person when service or repair is required. Incorrect reassembly may result in a risk of electrical shock or fire. Internal capacitors remain charged after all power is disconnected. For instructions on obtaining service, see the “W arranty and Produ ct Information” section in the
Inverter/Charger Operation Guide
.
RS2000 Sine Wave
7. Do not expose the inverter/charger to rain, snow, or water.
8. T o reduce risk of electric shock, disconnect all sources of AC and DC power from the inverter/charger attempting any maintenance or cleaning. Turning off controls will not reduce this risk.
9. The inverter/charger must be provided with equipment grounding conductors connected to the AC input ground and chassis ground terminals.
CAUTION
Cautions identify conditions or practices that could result in damage to the unit or other equipment.
T o reduce the risk of overheating, keep the ventilation openings clear and do not install the inverter/charger in a compartment with limited airflow or inadequate clearances around the unit. Refer to the
Inverter/Charger Installation Guide
for required clearance.
RS2000 Sine Wave
viii 975-0125-01-01
Explosive Gas Precautions
WARNING: Risk of explosive gases
Working in vicinity of a lead-acid battery is dangerous. Batteries generate explosive gases during normal battery operation. For this reason, it is of utmost importance that you must read this guide and follow its instructions closely each time before you service equipment in the vicinity of the battery.
1. To reduce risk of battery explosion, follow these instructions and those published by the battery manufacturer and manufacturer of any equipment you intend to use in vicinity of battery. Review cautionary markings on these products and on the engine.
2. This equipment contains components which tend to produce arcs or spark. To prevent fire or explosion, do not install the inverter/charger in compartments containing batteries or flammable materials or in locations that require ignition-protected equipment. This includes any space containing gasoline-power machinery, fuel tanks, as well as joints, fittings, or other connections between components of the fuel system.
Safety
Personal Precautions When Working With Batteries
1. Someone should be within range of your voice or close enough to come to your aid when you work near a lead-acid battery.
2. Have plenty of fresh water and soap nearby in case battery acid contacts your skin, clothing, or eyes.
3. Wear complete eye protection and clothing protection. Avoid touching your eyes while working near batteries.
4. If battery acid contacts your skin or clothing, wash immediately with soap and water. If acid enters your eye, immediately flood the eye with running cold water for at least ten minutes and get medical attention immediately.
5. Never smoke or allow a spark or flame in vicinity of battery or engine.
6. Be extra cautious to reduce risk of dropping a metal tool onto battery . It might spark or short-circuit battery or other electrical part that may cause explosion.
975-0125-01-01 ix
Safety
7. Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a lead-acid battery. A lead- acid battery can produce a short-circuit current high enough to weld a ring or the like to metal, causing a severe burn.
8. Never charge a frozen battery.
9. If necessary to remove the battery, always remove the grounded terminal from the battery first. Make sure all accessories are off, so as not to cause an arc.
10. Be sure area around battery is well ventilated.
11. Clean battery terminals. Be careful to keep corrosion from coming in contact with your eyes.
12. Study all battery manufacturer ’s specific precautions such as removing or not removing cell caps while charging and recommended rates of charge.
13. For refillable (flooded) batteries, add distilled water in each cell until the battery acid reaches the level specified by the battery manufacturer. This helps to purge excessive gas from cells. Do not overfill. Carefully follow manufacturer’s recharging instructions.
FCC Information to the User
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a residential environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction guide, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equ ipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and the receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
x 975-0125-01-01
Contents
Important Safety Instructions
Explosive Gas Precautions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -ix Personal Precautions When Working With Batteries - - - - - - - - - - - - - - - - - - - - - - - - - - - ix FCC Information to the User - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - x
1
Introduction
About the RS2000 Sine Wave Inverter/Charger - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–2
Premium Power and Ease of Use - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–2 How RS2000 Works - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–3
Inverting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–3
Charging - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–3 Xanbus System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–5 Xanbus Enabled - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–5
Comprehensive Electronic Protection- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–6 RS2000 Features- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–7
Front Panel Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–7 Side Panel Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–9 DC Terminal Covers and Battery Temperature Sensor - - - - - - - - - - - - - - - - - - - - -1–11
DC Terminal Covers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–11
Battery Temperature Sensor - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–11
System Accessories and Network Components - - - - - - - - - - - - - - - - - - - - - - - - - - - -1–12
2
Operation
Operating the RS2000 with the System Control Panel- - - - - - - - - - - - - - - - - - - - - - - - -2–2 Using the System Control Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–3 On Start Up - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–4 System Start-up Check- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–5 System Modes - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–6
Operate Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–7 Power Save Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–7 Safe Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–8
Putting the System into Safe Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–9 Hibernate mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–11
Operation in Invert Mode- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–12
Load Sense Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–12 Operating Limits for Inverter Operation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–13
Power Output - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2–13
975-0125-01-01 xi
Contents
Operating in Charger Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–14
Charger Operation with Battery Temperature Sensor - - - - - - - - - - - - - - - - - - - - - 2–15
Operating in Equalization Mode- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–16
Equalizing Batteries - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–17 Terminating the Equalization Process - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–20 Operating Limits for Charger Operation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–20
Power Share - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–20 Monitoring the RS2000 Indicator Lights - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–21 Faults and Warnings- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–22 Monitoring Status Messages on the System Control Panel - - - - - - - - - - - - - - - - - - - - 2–22
3
Configuration
General Configuration Information- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2
System Control - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2 System Menu Map - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3
Viewing the System Screen - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4
Viewing the Select Device Menu - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4
Selecting the RS2000 Basic Menu - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–5
Selecting and Adjusting the Configurable settings - - - - - - - - - - - - - - - - - - - - - - - - 3–6 RS2000 Configuration Menus - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–7 RS2000 Device Menu- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–9
Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–9
Battery - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–10
AC Input - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–10
AC Out - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–10 RS2000 Menu (Basic)- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–11
Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–11
Charger - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–12
Power Share - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–13
Equalize - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–13
Batt Type - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–16
Batt Size - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–17
Clear Faults - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–17 RS2000 Menu (Advanced) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–18
Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–18
Charger - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–18
Power Share - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–18
Configure Inv/Chg (Configure Inverter/Charger) - - - - - - - - - - - - - - - - - - - - - - - - 3–18
Max Chg Rate - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–19
Load Sense - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–19
xii 975-0125-01-01
Contents
Equalize - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–20 Clear Faults - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–20 View Device Info - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–20 Basic Menu - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–20 Selecting the RS2000 Advanced Menu - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–21 Returning to RS2000 Basic Menu - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–22
Sub-Menus - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–23
Configure Inv/Chg Menu (Configure Inverter/Charger Menu) - - - - - - - - - - - - - - -3–23
Lo DC Volt - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–23 Batt Type - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–23 Batt Size - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–23 Sense Below - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–23 Sense Interval - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–24 Cfg AC Limits (Configure AC Limits) - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–24 # Chg Stages - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–24 Eqz Volts - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–25 Force Charge - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–25
Cfg AC Limits (Configure AC Limits) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–26
Lo AC Volt - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–26 Lo AC Freq - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–26 Hi AC Volt - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–27 Hi AC Freq - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–27
View Device Info Menu (Device Information Menu) - - - - - - - - - - - - - - - - - - - - - 3–28
View Fault Log - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–28 View Warning Log - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–28 View Event Log - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–28 Restore Defaults - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3–29
4
Troubleshooting
Faults and Warnings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–2
Fault Types - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–2
Warning Types - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–3 Troubleshooting Reference- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–4 General Troubleshooting Guidelines - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–5 Warning Messages - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–7 Fault Messages- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–11 Inverter Applications- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–17
Resistive Loads - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–17
Motor Loads - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–17
Problem Loads - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4–17
975-0125-01-01 xiii
Contents
Very small loads - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–17 Fluorescent Lights & Power Supplies - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–18 Clocks - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–18 Searching - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–18
A
Specifications
Inverter Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -A–2 Charger Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -A–3 Transfer and General Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -A–4 Environmental Specifications- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -A–4 Physical Specifications with Projections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -A–5 Regulatory Approvals- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -A–5 Fan Operation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -A–5 Invert Power Derating vs Ambient Temperature - - - - - - - - - - - - - - - - - - - - - - - - - - - -A–6 Charger Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -A–6
B
Battery Charging Reference
Charging Algorithms (Formulas) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–2
Battery Type - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–2
Charge Algorithm Stages - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–2
Three-stage charging - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–2
Bulk Charge - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–3 Absorption Charge - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–3 Float Charge - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–4 Equalization Charge - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–4
Two-Stage Charging - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–5 Charge Algorithm Graph- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–6 Charge Algorithm Definitions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–6 AC Reconnect Summary- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–7
C
Terminology
Glossary- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -C–2 Abbreviations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -C–5
xiv 975-0125-01-01
Contents
Warranty and Product Information
Warranty- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -WA–1 Return Procedure - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -WA–3 Out of Warranty Service - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -WA–4 Information About Your System - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -WA–4
Index
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -IX–1
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - -WA–1
975-0125-01-01 xv
xvi
Figures
Figure 1-1 Typical Xanbus System Diagram- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–5 Figure 1-2 Front Panel of the RS2000 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–7 Figure 1-3 Front Panel Lights and Buttons - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–8 Figure 1-4 Completed Connections on Side Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–9 Figure 1-5 Battery Terminal Covers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–11 Figure 1-6 Battery Temperature Sensor - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–11 Figure 2-1 System Control Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–3 Figure 2-2 System Control Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–6 Figure 2-3 Operate Mode- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–7 Figure 2-4 Power Save Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–8 Figure 2-5 Select Device Menu- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–9 Figure 2-6 System Settings Menu - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10 Figure 2-7 Safe Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10 Figure 2-8 Battery Temperature Sensor - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–15 Figure 2-9 Equalize On - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–17 Figure 2-10 Equalize Confirmation Warning - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–18 Figure 2-11 Equalization Home Screen - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–18 Figure 2-12 Equalize Cancellation Warning - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–19 Figure 3-1 System Menu Map - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–3 Figure 3-2 RS2000 Float System Screen (Example)- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4 Figure 3-3 Select Device Menu- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4 Figure 3-4 RS2000 Basic Menu in Invert Mode- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–5 Figure 3-5 RS2000 Menu - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–7 Figure 3-6 RS2000 Menu Structure — Overview - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–8 Figure 3-7 Invert Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–9 Figure 3-8 Equalize On - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–14 Figure 3-9 Equalize Confirmation Warning - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–14 Figure 3-10 Equalization System Home Screen- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–15 Figure 3-11 Equalize Cancellation Warning - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–15 Figure 3-12 Highlighting System on the Select Device Menu - - - - - - - - - - - - - - - - - - - - - - - - - - 3–21 Figure 3-13 Highlighting Global Menus - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–21 Figure 3-14 Restore Defaults Warning- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–29 Figure A-1 Inverter Output Power vs Ambient Temperature - - - - - - - - - - - - - - - - - - - - - - - - - - -A–6 Figure B-1 Three-stage Charging Profile - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -B–6
975-0125-01-01 xvii
xviii
1
Introduction
Congratulations on your purchase of the RS2000 Sine Wave Inverter/Charger.
The RS2000 has been designed to give you premium power, ease of use, and outstanding reliability.
Please read this chapter to familiarize yourself with the main performance and protection features of the RS2000.
Introduction

About the RS2000 Sine Wave Inverter/Charger

The RS2000 Sine Wave Inverter/Charger is a convenient combination of an inverter, multistage battery charger, and transfer switch in one electronic device.
As an inverter, the RS2000 provides sine wave power for your microwave, entertainment system, computer, and other loads. This power is identical to the AC source provided from the utility grid (power company).
Some of the benefits of sine wave power include consistent cooking in your microwave, handling of sensitive loads such as your TV set, dimmer switches, and appliances with speed controls.
As a 100 amp charger, the RS2000 quickly and completely recharges your batteries.
The built-in transfer switch automatically transfers between inverter power and incoming qualified AC power.

Premium Power and Ease of Use

For managing your onboard power system, the RS2000 provides superi or features and rugged durability combined with ease of use:
2000 watt inverter/charger with 5000 watt surge for 5 seconds
Three-stage charge with 100 amps of output and charge formulas for flooded, gel, and AGM deep cycle batteries plus equalization for flooded batteries
Sine wave output powers sensitive entertainment electronics
Built-in 30 amp transfer switch provides automatic transfer between AC input and inverter power
Easy-to-read indicator lights on the front panel
Automatic cooling fans
Power sharing reduces charging current to prevent tripping of AC input breaker
1–2 975-0125-01-01

How RS2000 Works

The RS2000 is designed to:
•invert
•charge With AC input available from the utility grid or a generator, power is
passed through the RS2000 Sine Wave Inverter/Charger to operate connected AC loads. The remaining AC power not used by loads is converted to DC power and used to charge batteries.
If AC input power becomes disconnected, fails, or falls out of specification and is no longer qualified as good AC, a quick transfer takes place and the RS2000 begins converting DC power from the batteries into AC power, with no interruption in power supplied to the AC loads.

Inverting

The RS2000’s inverting function:
produces 120 volts AC from your batteries
delivers 2000 watts of power on a continuous basis and 5000 watts of
Introduction
surge power to start loads like pumps and refrigerators.

Charging

To prevent power being drawn needlessly from the batteries, Xantrex® has included the load sensing feature.
Load Sense Mode To reduce battery draw, you can turn on Load Sense
Mode with the System Control Panel. In Load Sense Mode, the inverter/ charger periodically sends out a search pulse to see whether a load is present. If it finds a load, the inverter/charger will turn on. You can adjust the interval between load sense pulses, and you can also adjust the load power at which the inverter will turn on. If no load is found, then the inverter will continue in load sense mode, which reduces the inverter draw from the battery to a minimum.
In Load Sense mode, there’s a short delay—up to the interval you’ve set—between the time you turn on a load and the time the inverter/charger delivers power. Load Sense mode can be disabled at any time if you find the delay to be inconvenient.
The RS2000’s charging function:
produces 100 amps to charge your batteries
equalizes flooded, lead acid batteries
975-0125-01-01 1–3
Introduction
Built-in Charge Formulas For the inverter to perform at the highest
level, the batteries must be charged correctly. The RS2000 has optimized algorithms for flooded, gel, and AGM batteries.
Battery Temperature Sensor Since battery temperature is a key factor
in correct charging, the charging formula must be adjusted (automatically and in real time) according to the actual battery temperature to ensure that batteries are fully charged, but not overcharged. For this reason, Xantrex has included a battery temperature sensor with your RS2000 Sine Wave Inverter/Charger and has temperature compensated the charge formula.
Manual Equalization Over a period of time, the cells in a flooded
battery can develop uneven chemical states. This can result in a weak (undercharged) cell which, in turn, can reduce the overall capacity of the battery. To improve the life and performance of a non-sealed, flooded battery, the RS2000’s multi-stage charging cycle includes a manual equalize mode that can be used, if recommended by the battery manufacturer
.
Dead Battery Charging
Another feature that the RS2000 includes is dead battery charging. The RS2000—unlike many chargers— has the ability to recharge batteries even if the battery voltage is very low.
Load Management The RS2000 has a built-in transfer relay that
connects AC input from the utility grid, generator, or inverter output to your loads. Because the usual AC pow er sources such as campground outlets or small generators often have limited current availability, having the capability to manage your AC loads is extremely valuable. The RS2000 provides a number of features to facilitate this:
The charger is power factor corrected to use AC current as efficiently
as possible and only requires 15 amps to provide rated charger output. Minimizing the AC current used by th e charge r means more current is available for your AC loads.
RS2000 uses a power share feature which monitors the AC load on
the system. It reduces the charge current and gives priority to the AC load to avoid nuisance tripping of the breaker.
Occasionally, AC input sources have low voltage. To avoid loading
these weak sources any further, the charger automatically reduces its AC current draw as the AC voltage approaches the minimum acceptable level.
1–4 975-0125-01-01

Xanbus System

Introduction
The RS2000 is the device in a Xanbus® system that typically provides network power—800 mA at 15 volts DC. All of the Xanbus-enabled devices, such as the RS2000, the System Control Panel (SCP), and the Automatic Generator Start (AGS) are able to communicate their settings and activity to each other. See Figure 1-1.
AC Out
AC In
Figure 1-1
Typical Xanbus System Diagram

Xanbus Enabled

The Xanbus-enabled designation means that this product works on a Xanbus network. Xanbus-enabled products are:
Easy to use. The Xanbus network simplifies operation and automates routine tasks.
Reliable. Software control eliminates errors due to analog signalling.
Accurate. Digital information is less susceptible to interference and line loss.
Upgradeable. Software upgrades mean your purchase will remain up to date.
For detailed instructions and a complete list of Xanbus-enabled devices, visit
www.xantrex.com
975-0125-01-01 1–5
Introduction

Comprehensive Electronic Protection

RS2000 is approved to meet a number of safety standards including UL 458, 4th edition, and CSA C22.2 No. 107.1. See “Regulatory Approvals” on page A–5 for more information.
RS2000 is equipped with numerous protection features to ensure safe operation.
Protection feature This feature…
Battery over-voltage protection
Battery under-voltage protection
Over-temperature protection
Automatic over load protection
Short circuit protection Detects short circuits and protects the unit by
Keeps the battery voltage from getting too high in charge mode. Shuts the inverter off in invert mode.
Prevents inverter from discharging your batteries too low. The inverter doesn’ t run if battery voltage is too low.
Protects the unit from overheating by either derating (charge mode) or by shutting down (invert mode). See “Invert Power Derating vs Ambient Temperature” on page A–6.
Protects the unit from excessive loads. The unit will provide 5000 watts (2.5 times of the rated load) for up to 5 seconds, and then protect itself by shutting down. See Specifications on page A–2 for more information.
shutting it down.
1–6 975-0125-01-01

RS2000 Features

Front Panel Features

Before you begin to operate the RS2000, review the front panel features shown in Figure 1-2 and described in Table 1-1. A detailed view of the lights and buttons on the front panel is shown in Figure 1 -3 and d escribed in Table 1-2.
Introduction
4
2
3
Figure 1-2 Table 1-1
Feature Description
1 AC wiring compartment access panel provides access to the terminal block for
wiring the AC input and AC output.
2 AC knockouts provide access for AC input and AC output wiring. A total of four
knockouts are provided on the unit: two on the front and one on each side (not shown).
3 Mounting flanges are used for mounting the unit. A total of six flanges are
provided on the unit.
4 Fans are located on the top of the unit and the bottom of the unit.
• Top external fan is an intake fan that activates when the internal temperature of the inverter/charger increases. The fan speed varies with the internal temperature and turns off when the inverter/charger cools down. (This internal temperature may be caused by heat in the inverter/charger or by high ambient temperature.)
• Bottom internal fan (no t shown) is an exhaust fan and runs continuously if the unit is inverting or charging.
2
Front Panel of the RS2000
Front Panel Features
1
2
2
3
975-0125-01-01 1–7
Introduction
5
4
3
2
1
10
7
6
8
9
11
12
13
Figure 1-3 Table 1-2
Feature Description
1 External AC light illuminates when you are connected to an AC source like the utility grid or
2 Inverter ON light illuminates when the RS2000 is operating in invert mode. 3 Low Battery light illuminates when the battery voltage is low. 4 Network light illuminates when there is activity on the network. 5 Fault light illuminates if a fault condition occurs. 6 Charger ON light illuminates when the RS2000 is in charge mode and is producing DC output
7 Bulk light illuminates when the charger is in the bulk stage of battery charging. 8 Absorption light illuminates when the charger is in the absorption stage of battery charging. 9 Float light illuminates when the charger is in the float stage of battery charging. 10 Equalize light illuminates when the unit is equalizing the batteries. 11 Charger Enable button toggles between enable (On) and disable (Off). When the charger is
12 Inverter Enable button toggles between enable (On) and disable (Off). When the inverter is
13 Reset button is used for several functions: to reset after a fault, to perform a power on reset, to
Front Panel Lights and Buttons
Description of Front Panel Lights and Buttons
a generator and the AC is qualified.
to charge your batteries.
enabled, it can produce DC output to charge your batteries. When the charger is disabled, it does not produce DC output to charge your batteries, but still passes AC input through to AC loads (if present).
enabled, it can produce AC output to run your AC loads. When the inverter is disabled, it does not produce AC output to run your loads; however, if qualified AC is present, the unit passes AC through to AC loads.
wake the RS2000 from Power Save mode or Hibernate mode. See “System Modes” on page 2– 6 for a description of the different modes.
1–8 975-0125-01-01

Side Panel Features

CAUTION: Equipment Damage
Connect only to other Xanbus compatible devices.
Although the cabling and connectors used in this network system are the same as Ethernet connectors, this network is not an Ethernet system. Equipment damage may result from attempting to connect two different systems.
For your reference, the side panel features with all connections completed is shown in Figure 1-4.
Introduction
1
3
2
Figure 1-4 Table 1-3
Feature Description
1 AC knockout provides access for AC input and AC output wiring (shown with strain-relief
2, 5, 9 Mounting flanges are used for mounting the unit. A total of six flanges are on the unit. 3 Battery temperature sensor jack provides connection for the battery temperature sensor.
975-0125-01-01 1–9
Completed Connections on Side Panel
Description of Side Panel Features
clamp installed). There are four knockouts on the unit: two on the front and two on the side.
4
4
5
5
7
6
8
8
9
Introduction
Table 1-3
Feature Description
4 Dual network jacks provide connection for network-enabled devices. (The number of
6 Chassis ground point connects the chassis of the RS2000 to your system’s chassis grounding
7 & 8 DC terminals – negative (black) (7) and positive (red) (8) —shown here with DC covers on.
Description of Side Panel Features
connections depends on your layout. Your connections may not be the same as shown here.)
point.
1–10 975-0125-01-01

DC Terminal Covers and Battery Temperature Sensor

DC Terminal Covers

Two covers are supplied to prevent accidental contact with the cabling connectors after installation. The red cover is for the positive cabling terminal, and the black cover is for the negative cabling terminal.
Introduction
Figure 1-5

Battery Temperature Sensor

The battery temperature sensor continuously measures the temperature of the battery and adjusts the charger output for a more accurate, temperature-compensated charge.
3
Figure 1-6
Battery Terminal Covers
2
1
Battery Temperature Sensor
Table 1-4
Feature Description
1 Sensor can be mounted on the side of the battery case or on the
2 Sensor cable is 25 feet (7.6 meters). 3 Connector plugs into the Battery Temp. jack (battery
975-0125-01-01 1–11
Description of Battery Temperature Sensor Features
negative battery terminal.
temperature sensor) on the RS2000.
Introduction

System Accessories and Network Components

System accessories can be used with the RS2000 in a Xanbus system. The System Control Panel (SCP) provides configuration and monitoring capability for Xanbus-enabled devices such as the RS2000. Automatic Generator Start (AGS) automatically starts and stops your generator. It continuously monitors your battery system and thermostats and starts the generator if the battery state of charge or the voltage reaches preset limits, or the air conditioner or heater needs to be run.
Table 1-5 provides the part numbers for the system accessories.
Table 1-5
Accessory Part number
System Control Panel (SCP) 809-0910 Automatic Generator Start (AGS) 809-0915
System Accessories
Consult with your local system designer to determine what network components will be needed for your specific installation. Table 1-6 provides a list of network components and part numbers. Pre-made cables are available in standard lengths ranging from 3 feet to 75 feet.
Table 1-6
Network Component Part Number
Network termination — Male (2 per pack) 809-0901 3-way network connector 809-0903 Network termination — Female (2 per pack) 809-0905 Network cable 3 ft. (0.9 m) 809-0935 Network cable 5 feet (1.5 m) 809-0936 Network cable 7 feet (2.0 m) 809-0937 Network cable 10 feet (3.0 m) 809-0938 Network cable 14 feet (4.3 m) 809-0939 Network cable 25 feet (7.6 m) 809-0940 Network cable 50 feet (15.2 m) 809-0941 Network cable 75 feet (22.9 m) 809-0942
Network Components and Part Numbers
These accessories and network components are available from any authorized Xantrex dealer or at on planning and installing your network is available in the
Installation Guide.
This guide is available for downloading at
www.xantrex.com. Detailed information
Xanbus System
www.xantrex.com
1–12 975-0125-01-01
2
Operation
Chapter 2, “Operation” contains information and procedures for using your RS2000. This chapter begins with a system startup check that you carry out after installation and configuration to verify that the RS2000 is operating correctly.
If you’re using the System Control Panel to operate or monitor the status of the unit, also refer to the System Control Panel Owner’s Guide.
WARNING: Restrictions on use
RS2000 Sine Wave Inverter/Charger shall not be used in connection with life support systems or other medical equipment or devices.
CAUTION
Read this chapter before operating the RS2000 Sine Wave Inverter/Charger.
Operation

Operating the RS2000 with the System Control Panel

The System Control Panel (SCP) provides operating, configuration, and monitoring capability for your Xanbus system.
The System Control Panel:
Monitors activity throughout your onboard power system
Displays the latest information about your inverter/charger, battery charge level, battery charge output, and generator start and stop activity.
Displays the settings for each Xanbus-enabled device in the system
Enables you to adjust the settings for each Xanbus-enabled device in the system.
Preserves all of its settings in non-volatile memory if system power is interrupted. After power is restored, you don’t have to reconfigure the SCP or any of the Xanbus-enabled devices connected to it.
This section provides information on operating the RS2000 with the System Control Panel. Please refer to the
for complete information on using the System Control Panel.
Guide
System Control Panel Owner’s
Important:
be saved if the unit is shut down by selecting Power Save mode, Safe mode or Hibernate mode. See “System Modes” on page 2–6 for more information about the different types of modes.
Any RS2000 setting changed from the System Control Panel will
2–2 975-0125-01-01
Operation

Using the System Control Panel

The System Control Panel has important features which you’ll want to be familiar with, as shown in Figure 2-1.
Display screen System information is shown on the display screen with an adjustable
backlight.
Indicator lights Four indicator lights on the front pan el indicate the operating stat us of the
Xanbus system.
Push buttons Four push buttons allow you to select device menus and change or display
settings. The red System button toggles the System Control Panel and Xanbus-enabled devices between Operate mode and Power Save mode. For more information on the different system modes, see “System Modes” on page 2–6.
9
1
1 2
3
4
10
6
5
Figure 2-1 Table 2-1
Feature Description
1 AC In/Charge light indicates that qualified AC is present at
2 Inverter On light illuminates when the RS2000 is enabled
3 Low Battery light illuminates when the battery voltage on the
975-0125-01-01 2–3
System Control Panel
System Control Panel Features and Buttons
the input of an inverter/charger. When the RS2000 is connected to a qualified AC source like the utility grid or a generator, this light on the System Control Panel illuminates.
(turned on).
RS2000 is low.
8
7
Operation
Table 2-1
Feature Description
4 Fault light indicates a condition that requires user attention
5 Enter button
6 Up arrow button
7 Down arrow button
8 Exit button
9 System button:
10 Screen displays menus, settings, and system information.
System Control Panel Features and Buttons
and intervention. The Fault light illuminates when any Xanbus-enabled device connected to the network is in fault. See “Faults and W arnings” on page 4–2 for the definitions of a fault and warning.
• Confirms selection of a menu item.
• Moves you to th e next screen.
• Scrolls up one line of text.
• Increases a selected value.
• Scrolls down one line of text.
• Decreases a selected value.
• Cancels selection of a menu item.
• Returns yo u to the previo us screen.
• Toggles all Xanbus-enabled devices on the system between Operate mode and Power Save mode. See “System Modes” on page 2–6.

On Start Up

When the RS2000 is powered up or comes out of a reset state, all of the front panel lights illuminate and remain on for a minimum of five seconds. After five seconds, the lights remain illuminated until the front panel has status information for all the lights.
The RS2000 is disabled every time the unit is powered up. The inverter must then be enabled. When a function is disabled, it is not allowed to occur and if it is occurring, it is terminated. Regardless of other conditions, the function will not be activated. For example, even if AC power is present, if the charger is disabled, the unit will not charge.
When a function is enabled, it is allowed to occur but other conditions may have to be met before the function is activated or turned on. For example, the charger function on the RS2000 may be enabled, but it will not charge unless qualified AC power is present.
2–4 975-0125-01-01

System Start-up Check

WARNING
Review the “Important Safety Instructions” on page vii before operating the inverter/charger.
To test the charging and inverting functions from the RS2000 front panel:
1. Disconnect AC power from inverter input by opening the breaker or disconnect. Press the Inverter Enable button on the RS2000. The Inverter On light illuminates.
2. Place a load on the inverter. For example, plug a 100 watt light bulb into an outlet that the inverter is powering and make sure it works. The inverter should run the load using battery power.
3. To test the charger, reconnect the AC input power to allow AC to the AC input. The Charger On light should illuminate after a brief delay. Any AC loads previously powered by the inverter will also work at this time.
4. Remove the AC input power. The inverter/charger should tran sf er to invert mode immediately. (The transfer relay will make a clicking sound and the Inverter On light will illuminate.) Loads should continue to operate uninterrupted.
To test the transfer switch:
Operation
1. Press the Inverter Enable button on the unit to disable. The Inverter On light is not illuminated.
2. Apply qualified AC power to the RS2000 input. After a brief delay, the External AC light should illuminate and AC loads on the output should operate.
If any part of this procedure fails, determine the cause before using the inverter/charger. Consult the “Troubleshooting” chapter starting on page 4–1.
975-0125-01-01 2–5
Operation

System Modes

This section provides an overview of the four different system modes. The system modes described in this section affect the performance and
behavior of the RS2000 and all other Xanbus-enabled devices on the Xanbus system. You’ll have to change the system mode when travelling, putting your vehicle in storage, or when installing a Xanbus-enabled device.
You can change system modes using the System Settings menu on the System Control Panel.
You can also use the red System button on the System Control Panel to put the System Control Panel and all other Xanbus-enabled devices into Power Save mode only.
System button
Figure 2-2
System modes are changed using the System Settings menu. The four system modes are:
•Operate
Power Save
•Safe
Hibernate Please read the section about each system mode to find out which mode is
appropriate for different conditions or situations.
2–6 975-0125-01-01
System Control Panel
Operation

Operate Mode

Characteristics In Operate mode, all communications are enabled on the Xanbus system.
All power conversion functions are enabled. Each Xanbus-enabled device is monitoring and communicating its input.
The basic state of the System Control Panel is Operate mode. In Operate mode, the System Control Panel communicates with other Xanbus­enabled devices and displays all the network information which it is configured to display.
Whenever the System Control Panel or any other device on the Xanbus system is powered on or reset, it will be in Operate mode.
Figure 2-3
Operate Mode

Power Save Mode

Characteristics Power Save mode minimizes power draw by the System Control Panel
and other Xanbus-enabled devices on the Xanbus system. Power Save mode stops all communication on the network, and disables the power conversion functions of Xanbus devices. For example, in Power Save mode, the inverter/charger will not invert and an Automatic Generator Start will not start a generator.
When to use Use Power Save mode during periods when your power needs are
minimal—while you are driving, for example. Putting the system in Power Save mode will help preserve the charge in your batteries during periods of minimal power usage.
Entering and exiting Power Save mode also serves as a “reset” command for the system.
If there are active faults in the system, you cannot put the system into Power Save mode. Clear any active fault, correct the condition that caused the fault, then put the system into Power Save mode.
975-0125-01-01 2–7
Operation
To enter or exit Power Save mode:
Press and hold the System button on the System Control Panel for one second.
After you release the System button, the System Control Panel screen and indicator lights will turn off.
You can also enter or exit Power Save mode on the System Settings menu by selecting Desired Mode and scrolling to PowerSave as shown in Figure 2-4.
Operate
[Advanced]
Returning to Operate mode
Figure 2-4
If an inverter/charger supplies power to the network, applying AC input with utility power or generator power automatically returns the system to Operate mode.
Power Save Mode

Safe Mode

CAUTION: Unexpected behavior
Before installing or removing a device on the network, put the network into Safe mode. This prevents unexpected behaviour.
Characteristics Selecting Safe mode stops the generator (if it is running) and puts the
System Control Panel (and all Xanbus-enabled devices) into Safe mode. While in Safe mode, the System Control Panel remains powered, “listening” to and reporting its status to the network. However, the ouptut power of all Xanbus-enabled devices is disabled and all inverting, charging, and generator starting activity stops. In Safe mode, the RS2000 will not pass AC.
2–8 975-0125-01-01
Operation
In Safe mode, the RS2000 continues to communicate, but the inverting and charging functions are disabled.
When to use Use Safe mode when you are adding or removing devices from the
network. Authorized service personnel must also put the System Control Panel in Safe mode before performing software upgrades and diagnostics with the Xantrex Diagnostic Tool.
If the System Control Panel is powered off while in Safe mode, it will be in Safe mode when it is powered up again.
To return to Operate mode:
On the System Settings menu, under Desired Mode, select “Operate.”

Putting the System into Safe Mode

When you are installing or removing devices from the Xanbus system, putting the system into Safe mode prevents unexpected behavior.
To enter Safe mode:
1. On the Select Device menu, use the down arrow button to highlight System.
The cursor on the right of the screen indicates where you are in the menu.
Figure 2-5
Select Device Menu
2. Press Enter. The System Settings menu appears.
975-0125-01-01 2–9
Operation
Figure 2-6
System Settings Menu
3. On the System Settings menu, with Desired Mode highlighted, press Enter.
4. Use the down arrow button to scroll through the other modes to select Safe mode.
For more information on the different system modes: Operate, Power Save, and Hibernate see “System Modes” on page 2–6.
Figure 2-7
Safe Mode
5. Press Enter. You are now in Safe mode.
6. Press Exit twice to return to the System Home Screen.
To exit Safe mode and return to Operate mode:
1. On the System Settings menu, under Desired Mode, select “Operate.”
2. Press Enter.
2–10 975-0125-01-01
Operation

Hibernate mode

Characteristics Hibernate mode removes network power from the System Control Panel
and all Xanbus-enabled devices on the Xanbus system. The System Control Panel suspends all operations (including starting and stopping the generator) until power is restored to the network. All Xanbus-enabled devices other than the RS2000 have no network power.
When to use Use Hibernate mode when the Xanbus system is left unattended for long-
periods of time to prevent any unattended system activity and to prevent battery drain during long periods of inactivity.
The system will automatically enter Hibernate mode if it is in Power Save mode for more than two hours.
Important:
Hibernate mode from the System Control Panel before putting your RV or boat into storage.
To prevent any unattended system activity, put the system into
If there are active faults in the system, you cannot force the system into Hibernate mode. Clear any active faults, correct the condition that caused the fault, then put the system into Hibernate mode. The RS2000 can enter hibernate mode with an active fault.
Restoring power Once in Hibernate mode, the System Control Panel cannot return the
System to Operate mode. You must restore power to the network by pressing the Reset button on the RS2000 front panel for several seconds.
If an inverter/charger supplies power to the network, you can bring the system out of Hibernate mode either by pressing the reset button on the inverter/charger front panel or by applying AC input with utility power or generator power.
975-0125-01-01 2–11
Operation

Operation in Invert Mode

WARNING
Review the “Important Safety Instructions” on page vii before operating the inverter/charger.
Once the inverter/charger is installed, you can operate it in invert mode.
To operate in invert mode from the front panel:
1. Press the Inverter Enable button on the RS2000.
2. If external AC is present, the External AC light illuminates. If AC is present and you want to run the inverter, remove AC so the inverter turns on.
Once the Inverter On light is on, the RS2000 inverter is ready to deliver AC power to the loads.
To operate the inverter with the System Control Panel, refer to
Chapter 3, “Configuration”.

Load Sense Mode

Important:
“Inverter Applications” on page 4–17.
The load sense mode of the RS2000 reduces battery power consumption in order to conserve battery capacity.
When the inverter is enabled, the inverter/charger can be configured to search for an acceptable AC load. (It does this when you enable (turn on) “Load Sense” on the RS2000 Advanced Menu on the System Control Panel and set the load sense power threshold “Sense Below.”)
The inverter output turns off if the unit doesn’t detect a load that meets the load sense parameters. When the load sense featu r e is disa ble d (turn ed off), the inverter is continuously on. When an acceptable load is detected, the inverter output is turned on and provide full output power.
The unit will “sleep” if it doesn’t detect a load that meets the load sense parameters. If a load exceeds the “Sense Below” threshold set in the RS2000 advanced menu, the RS2000 will “wake up” and deliver full power to the load.”
If you are having problems with any of your loads, refer to
2–12 975-0125-01-01
Operation

Operating Limits for Inverter Operation

Power Output

Temperature The continuous output rating for the RS2000 is 2000 watts or 17 amps at
120 volts AC. The RS2000 can deliver this power in an ambient (surrounding) temperature up to 122 °F (50 °C). Above this temperature, you must reduce the power demand or the unit may shut down to protect itself against overheating.
As with all inverters, the amount of continuous power that the RS2000 can deliver without overheating is limited by the ambient air temperature. The RS2000 will operate and deliver its continuous power rating at higher temperatures, but the ambient temperature as well as the input voltage from the battery will limit the extent to which it can run continuously. Operating the inverter/charger in conditions outside of power and temperature limits will result in thermal shutdown and/or significantly decreased performance. In addition, operation in this range is outside the
Difficulty on starting loads
ratings covered by the regulatory approvals of the product. See
Power Derating vs Ambient Temperature” on page A–6.
The inverter/charger should be able to operate all AC loads rated at or below its power rating. Some high horsepower induction motors used in pumps and other motor-operated equipment require very high surge currents to start, and the inverter/charger may have difficulty starting these loads. See “Inverter Applications” on page 4–17.
If you have problems starting certain loads, ensure that:
“Invert
the battery connections are tight and clean
the DC cabling is no longer than the recommended length. Refer to
RS2000 Sine Wave Inverter/Charger Installation Guide for this
the information.
the AC wiring is of recommended size. Refer to the
Wave Inverter/Charger Installation Guide
the battery is of sufficient capacity and is fully charged.
975-0125-01-01 2–13
for this information.
RS2000 Sine
Operation

Operating in Charger Mode

WARNING: Explosive Gases
Review the “Important Safety Instructions” on page vii before operating the inverter/charger. During charging, batteries may generate explosive gases. Thoroughly ventilate the areas around the batteries and ensure that there are no sources of flames or spark in the vicinity.
Study all battery manufacturer’s precautions such as removing or not removing cell caps while charging and the recommended rates of charge.
Important:
distilled water in each cell. The battery acid should be at the level specified by the battery manufacturer. This helps prevent over-heating and purges excessive gases from the cells. Do not overfill. For a battery without cell caps, follow the manufacturer’s recharging instructions carefully.
If you are charging a non-sealed battery, ensure there is sufficient
To operate the RS2000 in charger mode from the front panel:
1. Connect AC input power. The charger automatically starts up when qualified AC power is
connected if the charger is enabled, or the charger is disabled but the Force Charge enable override is On. See “Force Charge” on page 3–
25.
The batteries are charged according to the two-stage or three-
stage formula you have selected on the System Control Panel. (See “Battery Charging Reference” on page B–1 for more information on two-stage or three-stage charging.)
You can interrupt the charge cycle any time you desire by
disabling the charger from the System Control Panel or by pressing the Charger Enable button (on the front panel of the RS2000) so it is no longer illuminated.
To maintain optimal performance in flooded batteries, an
occasional equalize cycle may be required. See “Operating in Equalization Mode” on page 2–16.
While the batteries are being charged, you can monitor which
stage they are in from the front panel of the RS2000 or from the System Control Panel.
To operate the charger with the System Control Panel, refer to
Chapter 3, “Configuration”.
2–14 975-0125-01-01

Charger Operation with Battery Temperature Sensor

Since battery temperature is a key factor in correct char ging, the char ging formula must be adjusted (automatically and in real time) according to the actual battery temperature to ensure that batteries are fully charged, but not overcharged. For this reason, Xantrex has included a battery temperature sensor (see Figure 2-8) with your RS2000 Sine Wave Inverter/Charger and has temperature compensated the charge formula.
The battery temperature sensor continuously measures the temperature of the battery and adjusts charger output for a more accurate, temperature­compensated charge.
When batteries are cold, their chemical reaction is sluggish, meaning they don’t absorb charge as easily. Thus a charge level optimized for room temperature will not charge the batteries sufficiently if they are cold. The charger must compensate by increasing its voltage to achieve the compensated equivalent of a room temperature charge. If the batteries are hot, the chemical reaction is hyperactive and they absorb energy too easily; thus a standard room-temperature charge would tend to overcharge a hot battery. Therefore, the charger compensates by reducing its voltage.
The battery temperature sensor automatically, and in real time, makes adjustments to the charger’s voltage setpoints to properly charge your batteries. The actual charge compensation formula can be found on page A–3.
Operation
Important:
setpoint when charging if the battery case temperature is above or below 77 °F (25 °C)
It is normal to see a voltage that is different than the specified
If a battery temperature sensor is not present, the RS2000 uses the cold, warm, and hot settings. Charging may not be effective at extreme temperatures. See “Charger Specifications” on page A–3.
Figure 2-8
975-0125-01-01 2–15
Battery Temperature Sensor
Operation

Operating in Equalization Mode

WARNING: Explosive gases
Equalization generates explosive gases. Ensure adequate ventilation.
CAUTION: Batteries may be damaged
Sealed lead-acid batteries and gel batteries must NEVER be equalized or premature battery failure will result. Equalize mode is disabled if you have selected “Gel” and “AGM” as the battery type.
Only flooded (wet) lead-acid batteries should be equalized. As a general rule, do not equalize a battery unless there are provisions to add water to it and the manufacturer recommends equalization.
CAUTION: Batteries may be damaged
If carried out too frequently or done improperly, equalization can damage your batteries. Never equalize a battery more than necessary . Always check electrolyte level before AND after equalization. Fill with distilled water per the battery manufacturer’s recommendation.
CAUTION: Risk of damage to DC load equipment
Equalization voltage may be as high as 15.8 volts DC. Disconnect sensitive loads from the battery before equalizing.
Follow the battery manufacturer’s recommendations for equalizing your batteries. As a guide, a heavily used flooded battery may need to be equalized once a month, and a battery in light service may only need to be equalized every two to four months.
Measure the specific gravity (S.G.) of each cell using a hydrometer. For fully charged lead-acid batteries, the reading should be approximately
1.265. Low specific gravity after charging or a 0.25 difference from cell
to cell indicates the need for equalization.
2–16 975-0125-01-01

Equalizing Batteries

Operation
Important:
Equalization only runs for 60 minutes and may need to be restarted if the specific gravity is still uneven.
To equalize your batteries:
1. Turn off or disconnect all loads on the battery. The voltage applied to the battery during equalization may damage
your electronic equipment. As well, equalization won’t proceed correctly if loads are drawing current from the battery.
2. Check electrolyte level. Fill with distilled water if the electrolyte level is low.
3. To request the equalization charge, ensure the Charger switch is enabled, and then scroll to the Equalize setting on the System Control Panel.
4. In the RS2000 home menu, highlight Equalize, as shown in Figure 2-9.
Equalization will be carried out after an absorption charge.
[Enabled]
[10.0A]
[On]
[Flooded]
Figure 2-9
When you select On, the equalization confirmation warning appears, as shown in Figure 2-10.
975-0125-01-01 2–17
Equalize On
Operation
Yes
Figure 2-10
Selecting Yes by pressing the Enter button takes you to the equalization system home screen, as shown in Figure 2-11.
OR Selecting No by pressing the Exit button on Figure 2-10 takes you to the
RS2000 device screen.
Equalize Confirmation Warning
No
Yes
n/a
13.0V
Menu
Figure 2-11
Equalization Home Screen
Cancel
See Table 2-2 for an explanation of the equalize home screen content.
Table 2-2
Equalization Home Screen content Explanation of items displayed
Precharging • “Yes”—precharging occurs if batteries are not
2–18 975-0125-01-01
Equalization Home Screen Content
fully charged before equalization. Batteries must be fully charged before equalization.
• “Done”—indicates the precharge is complete or if it was not required.
Operation
Table 2-2
Equalization Home Screen content Explanation of items displayed
Time Remaining Indicates the time left for equalization. Equalizatio n
Battery Voltage Displays a range of 13.0 V to 18.0 with increments of
Menu Pressing Menu returns you to Select Device screen. Cancel Pressing Cancel will display a confirmation screen, as
Equalization Home Screen Content
runs for 60 minutes; time is counted down in 1 minutes increments until the Time Remaining display 0 min. (During a precharge, the Time Remaining displays “n/a”— not applicable.)
0.1V.
shown in Figure 2-12, asking you to confirm that you want to cancel equalization.
Yes
Figure 2-12
Equalize Cancellation Warning
No
If you choose Yes, the equalization process is cancelled and you are returned to the RS2000 home menu.
0R If you choose No and continue with equalization, the equalization home
screen, as shown in Figure 2-11, appears.
5. When equalization is finished, check the battery electrolyte level. T op up as necessary with distilled water only and recheck the specific gravity as specified by the battery manufacturer.
975-0125-01-01 2–19
Operation

Terminating the Equalization Process

The equalization process can be terminated in three ways:
user cancellation from the System Control Panel as shown in Figure 2-12
inverter/charger cancellation if AC is removed or the charger is disabled
successful completion of the equalization process

Operating Limits for Charger Operation

The maximum output current for the RS2000 is 100 amps. You can reduce the total output if you change the “Charge Rate” setting on the RS2000 Advanced Menu or the maximum Power Share setting on the RS2000 Basic Menu
The charger can ope rate over an AC i nput range of 90– 135 volts AC. This is the default setting and can be adjusted to 85–145 volts AC as a maximum range and to 110–120 volts AC as a minimum range.This wide range allows the RS2000 to charge your batteries even when incoming AC voltage is less than ideal.
.

Power Share

The RS2000 charger shares incoming power with AC loads. The AC loads have priority, which means that the charger will reduce its output with large AC loads and increase the output again when the AC load decreases. The regulatory maximum for continuous AC loads is 80% of the breaker rating that the loads are connected to.
The RS2000 senses pass-through current going to the AC load. The difference between the pass-through (load) and 80% of the Power Share setting is the current that is available for charging the batteries.
For example, if the AC input of the RS2000 is from an AC panel with a 30A breaker, the Power Share setting on the System Control P anel should be selected as 30A. Based on this, the charger will control the charge current so that the total current draw is equal to or less than 24A in this case. Should the load current be more than 24A, the charger output will reduce to 0A, but the RS2000 will continue to supply the loads. The RS2000 will continue to pass-through power to the loads, even if the load current exceeds the Power Share setting. In this case, it will be up to the user to remove/disconnect loads if tripping the AC input breaker supplying the RS2000 is to be avoided.
2–20 975-0125-01-01

Monitoring the RS2000 Indicator Lights

The ten indicator lights on the front panel show you the operating status of the RS2000. A description of the lights is provided in Table 2-3.
If none of the front panel lights are on, see “Troubleshooting Reference” on page 4–4.
t
Table 2-3
Light Illuminated Color Status Action or Status Item
Front Panel Lights
Operation
External AC Green When the RS2000 is connected to a
qualified AC source or a generator, the External AC light illuminates.
Inverter ON Green When the RS2000 is enabled (on)
and producing AC or load sensing, the Inverter ON light illuminates. This light is not illuminated if the unit is charging.
Low Battery Yellow When the Low Battery light
illuminates, the battery level is low.
Network Green Indicates that there is activity on the
network.
Fault Red A fault has occurred on the
network.
Charger ON Green When the RS2000 is in charge
mode, the Charger ON light is illuminated. In three-stage charging, charging occurs in 3 stages: bulk, absorption, and float. One of these 3 lights will be illuminated at the same time the Charger ON light is illuminated. If the Charger ON light is off, the RS2000 is not in any charge mode.
You can run your appliances from an AC source like the utility grid or a generator.
You can run your appliances from the inverter.
Y ou can run your appliances but your battery level is low. Charge your battery or connect to an AC source or turn off the inverter.
Communication on the network
Investigate and clear the fault condition.
The charger is active and charging your batteries. The Charger ON light is always illuminated if charging, whether the unit is putting out current or not.
975-0125-01-01 2–21
Operation
Table 2-3
Light Illuminated Color Status Action or Status Item
Bulk Green RS2000 is in bulk m ode of battery
Absorption Green RS2000 is in absorption mode of
Float Green RS2000 is in float mode of battery
Equalize Yellow RS2000 is in equalize mode of
Front Panel Lights
charging.
battery charging.
charging. The Float light illuminates in three-stage charging.
battery charging.
These lights indicate which state of charge the RS2000 is in.

Faults and Warnings

A fault affects the operation of the unit. A manual fault requires user intervention by clearing the condition and then pressing the Reset button on the inverter/charger’s front panel. See the
Owner’s Guide
for information on clearing faults from the System
Control Panel. A warning alerts you to a condition that could possibly affect operation of
the unit. See “Faults and Warnings” on page 4–2 for more explanation on the
difference between faults and warnings.
System Control Panel

Monitoring Status Messages on the System Control Panel

Refer to “System Menu Map” on page 3–3 of the Configuration chapter.
2–22 975-0125-01-01
3
Configuration
Chapter 3, “Configuration” contains information about all configurable settings and procedures for the RS2000.
Configuration

General Configuration Information

System Control

All changes to the configuration of the RS2000 are made with the System Control Panel (SCP). The System Control Panel provides configuration and monitoring capability for all Xanbus-enabled devices on the network.
The front panel of the RS2000 provides limited control, including reset; charger enable and disable; and inverter enable and disable. When a function is disabled, it is not allowed to occur and if it is occurring, it is terminated. Regardless of other conditions, the function will not be activated. For example, even if AC power is present, if the charger is disabled, the unit will not charge.
When a function is enabled, it is allowed to occur but other conditions may have to be met before the function is activated or turned on. For example, the charger function on the RS2000 may be enabled, but it will not charge unless qualified AC power is present.
These functions can also be controlled from the System Control Panel.
3–2 975-0125-01-01

System Menu Map

Figure 3-1 provides a map of how the menus are organized. The order of devices appearing on the System Control Panel will vary, depending on the order in which they’ve been connected to the network.
Power Up
Startup screen
Startup screen
Standby ChargingInverting Load SenseAC Bypass Equalize
Select Device
Select Device
Enter
menu
menu
Enter
Exit
Exit
Inverter/Charger
Inverter/Charger
menu
System screen
System screen
menu
Configuration
Device menus
Figure 3-1
Auto Gen Start menu
Auto Gen Start menu
System Panel menu
System Panel menu
Clock menu
Clock menu
System Settings
System Settings
menu
menu
System Menu Map
Optional device. This menu will
=
appear if this device is installed.
975-0125-01-01 3–3
Configuration

Viewing the System Screen

The System screen, as shown in Figure 3-2, is used to monitor system activity. You cannot select or change any of the information on the System screen. If you would like to view more detailed information, press menu to go to the Select Device menu.
menu
Figure 3-2
RS2000 Float System Screen (Example)

Viewing the Select Device Menu

The Select Device menu is where you can view a list of all the Xanbus­enabled devices in your power system. The number of items appearing on the Select Device menu depends on how many devices are installed as part of your system.
To view the Select Device menu:
On the System screen, press Enter.
The Select Device menu appears with RS2000 highlighted.
Figure 3-3
3–4 975-0125-01-01
Select Device Menu

Selecting the RS2000 Basic Menu

To select the RS2000 from the Select Device menu:
1. On the Select Device menu, RS2000 appears highlighted.
2. Press Enter. The RS2000 basic menu appears.
Configuration
Invert
[*Enabled]
Figure 3-4
RS2000 Basic Menu in Invert Mode
975-0125-01-01 3–5
Configuration

Selecting and Adjusting the Configurable settings

You can view RS2000 settings or change RS2000 settings from the RS2000 menu. Display settings show status items and cannot be changed. Configurable settings are indicated by square brackets [ ] and can be adjusted, as shown in Figure 3-4.
Follow these steps to change any RS2000 setting.
1. On the RS2000 menu, use the up arrow or down arrow button to highlight the setting you want to change.
2. Press Enter to highlight the value of that Configurable setting, indicated by square brackets [ ].
The previously set value appears with an asterisk beside it, as shown in Figure 3-4.
3. Use the up arrow or down arrow button to change the value. Holding down a button lets you scroll through values quickly.
4. Press Enter to select the value.
5. If you have another setting to change, return to step 1. Or If you have no more settings to change, press Exit to return to the
Select Device menu.
3–6 975-0125-01-01

RS2000 Configuration Menus

The System Control Panel displays the RS2000 configuration menu in two formats: basic and advanced.
RS2000 basic menu list status information and settings you may have to adjust on a routine basis. It provides access to basic control of the inverter/charger.
RS2000 advanced menu settings require that you understand and plan for the changes you make. You may not have to adjust these settings as part of regular operation. Advanced Menu can be enabled or disabled through the System Control Panel. See “Selecting the RS2000 Advanced Menu” on page 3–21.
To access the RS2000 configurations menus, select the RS2000 menu, as shown in Figure 3-5.
Configuration
Invert
[Enabled]
Figure 3-5
975-0125-01-01 3–7
RS2000 Menu
Configuration
The RS2000 menu structure is shown in Figure 3-6. The first four lines appearing in both menus: Mode, Battery, AC Input or AC Out, are status items only and are not configurable.
Figure 3-6
3–8 975-0125-01-01
RS2000 Menu Structure — Overview

RS2000 Device Menu

The RS2000 device menu displays status information on the different modes of the inverter/charger. The first three lines of the device screen displays dynamic content that changes, depending on what operation mode that the RS2000 is in. Status information is not configurable; configurable items are indicated by square brackets [ ]. An asterisk indicates the value that was previously set.
For example, in Figure 3-7, the RS2000 is in invert mode with AC current going out.
Configuration
Invert
[*Enabled]

Mode

Figure 3-7
The first line indicates which mode that the RS2000 is in. Table 3-1 defines the different modes.
Table 3-1
Mode Description
Bulk Charge The first stage of three-stage battery charging. Current
Absorption Charge The second stage of three-stage battery charging.
Invert Mode
Modes
is supplied to the batteries at a constant rate while voltage gradually rises.
Voltage remains constant and current reduces as the battery becomes charged. This ensures complete charging.
975-0125-01-01 3–9
Configuration
Table 3-1
Mode Description
Float Charge The third stage of three-stage battery charging. After
Invert The RS2000 is converting DC power to AC power. AC Bypass AC input from an AC source like the utility grid or
Equalize To improve the life and performance of a non-sealed,
Load Sense In order to minimize power draw from the battery, the
Modes
batteries reach full charge, charging voltage is reduced to a lower level to prevent gassing and to prolong battery life. This stage is often referred to as a maintenance charge. Rather than charging a battery, it keeps an already-charged battery from discharging while providing load current.
from a generator is allowed to pass through the unit to operate connected AC loads. The charger is not enabled but AC is qualified and passed through the unit.
flooded (or wet) battery, the RS2000’s multi-stage charging cycle includes a manual equalize mode that can be used if recommended by the battery manufacturer.
inverter will periodically check if a load is connected when the inverter is enabled.

Battery

The second line of the device screen indicates the status of the battery. This line displays the volts (V), current (A) as either (+) positive amps (indicating that the battery is charging) or (–) negative amps (indicating the battery is discharging because you’re inverting) and battery temperature in either
°F or °C.

AC Input

When the RS2000 is in charge mode, this line indicates whether you have AC input from the utility grid or from a generator. This line shows the values for current (A), the frequency (Hz), and the AC voltage in (V).

AC Out

This line is displayed when the RS2000 is in invert mode or in AC bypass mode. This line indicates the AC output and shows the values for current (A), the frequency (Hz), and the AC voltage in (V).
3–10 975-0125-01-01
Configuration

RS2000 Menu (Basic)

The RS2000 basic menu indicates the status of items and lists settings that you may have to adjust on a routine basis.
If advanced menu is enabled, scroll through the RS2000 advanced menu items until Basic Menu is highlighted and press enter.
This section describes each display item and configurable item in detail with an example of the line item. Each item is described in terms of its purpose, whether it is a display or configurable setting, when to use, and the outcome of changing a setting.

Inverter

Configurable setting This setting lets you enable or disable the inverter. In the example shown,
the inverter is enabled. For an explanation of enable and disable, see “Terminology” on page C–1.
Inverter [Enabled]
Value Default
Enabled Disabled Disabled
When to use Enable the inverter when you would like to have AC power from the
inverter.
Outcome The inverter is enabled. The inverter provides power from the batteries
unless qualified AC input power is present.
975-0125-01-01 3–11
Configuration

Charger

Configurable setting This setting lets you enable or disable the operation of the char ger. When
the charger is enabled, and AC is connected to the input, your batteries will be charged. The charger can be disabled, if desired, anytime during the charge cycle.
If the charger is enabled and the AC is not qualified as good, then the charger will not operate until AC qualifies as good.
The charger can be enabled or disabled from the front panel of the RS2000 or from the System Control Panel (SCP). In the example shown, the charger is enabled.
Charger [Enabled]
Value Default
Enabled Enabled Disabled
Outcome Use the default Enabled setting to ensure batteries are always being
charged when connected to an AC source. Disabling the charger will turn off the charge function. Then the next time qualified AC power is connected, the charger is automatically enabled and charging will begin, if Force Charge is enabled. If Force Charge is not enabled, charging will not occur until the Charger setting is changed from disabled to enabled.
See “Force Charge” on page 3–25 for more information on this feature.
3–12 975-0125-01-01
Configuration

Power Share

Configurable setting Power Share is a configurable setting that you set to match to the breaker
rating on the AC input. This setting is used to ensure that the charger limits its output to try to prevent nuisance tripping of the AC input breaker due to the total current drawn by the charger and your other AC loads. See also
Power Share [10A]
Range of values Increment Default
5 to 50 amps 5 amp increments 30 amps
When to use Set the Power Share setting to match the AC input breaker. Use this
setting when connecting to an AC source. If using multiple AC sources via an AC transfer switch, adjust this setting to the smaller AC breaker size.
Outcome Setting the value higher than the AC source’s external breaker could
cause the external breaker to trip.
“Power Share” on page 2–20.

Equalize

Configurable setting This setting lets you enable or disable charger equalization, if the battery
type is flooded (or wet). Equalization can be turned on (enabled) or off (disabled).
Equalize [Off]
Value Default
On Off Off
When to use Review the section, “Operating in Equalization Mode” on page 2–16
before adjusting this setting. This menu item is displayed if the battery type allows equalization.
975-0125-01-01 3–13
Configuration
In the RS2000 home menu, highlight Equalize, as shown in Figure 3-8.
[Enabled]
[10.0A]
[On]
[Flooded]
Figure 3-8
When you select On, the equalization confirmation warning appears, as shown in Figure 3-9.
Figure 3-9
Selecting Yes takes you to the equalization system home screen, as shown in Figure 3-10.
Equalize On
Yes
Equalize Confirmation Warning
No
3–14 975-0125-01-01
Yes n/a
13.0V
Configuration
Menu
Figure 3-10
Batteries must be fully charged before equalization. If they are not fully charged, a precharge occurs. During precharge, the Time Remaining appears as “n/a”—not applicable. When the equalization process begins, Time Remaining appears as a value between 60 min and 1 min.
You can cancel the equalization process by selecting Cancel, in which case Figure 3-11 appears, asking if you want to cancel equalization.
Equalization System Home Screen
Yes
Cancel
No
Figure 3-11
If you choose Yes, the equalization process is cancelled and you are returned to the RS2000 home menu.
If you choose No, the equalization home screen as shown in Figure 3-10 appears.
975-0125-01-01 3–15
Equalize Cancellation Warning
Configuration

Batt Type

Full name Battery Type Configurable setting Select the type of battery from flooded, AGM, gel or custom. If a battery
temperature sensor is not present, the RS2000 uses cold, warm or hot settings with the hot setting as the default.
Batt Type [Flooded]
Value Default Battery Type
Flooded Flooded Custom AGM Gel
When to use This setting is adjusted for the type of battery you have. It is important
during installation to choose the correct setting (battery type) to optimize the charge algorithm for your battery and to properly enable or disable equalization. See information.
The custom setting is selected to get the battery settings programmed by the dealer.
“Battery Charging Reference” on page B–1 for more
3–16 975-0125-01-01
Configuration

Batt Size

Full name Battery size Configurable setting This features let you select the size of the battery bank being charged.
Batt Size [440 Ah]
Range of values Increment Default
50 Ah to 2000 Ah 10 Ah 440 Ah
When to use Adjust this setting to your actual battery bank size. Outcome Reduces the maximum charger current to protect against charging smaller
batteries too aggressively. This setting charges batteries appropriately based on capacity. See “Battery Charging Reference” on page B–1 for more information.

Clear Faults

Purpose Clear RS2000 faults is a command which clears all active faults in the
RS2000. When faults are cleared, the device will resume normal operation. If the fault condition still exists, the fault will reoccur.
Clear Faults
Value Effect
Yes Faults are cleared No No action
975-0125-01-01 3–17
Configuration

RS2000 Menu (Advanced)

The RS2000 advanced menu lists settings that provide you with additional control over RS2000. However , you may not have to adjust these settings as part of regular operation. For a listing of advanced menu items, see “RS2000 Menu Structure — Overview” on page 3–8.
These settings are only visible if Advanced Menu is selected. T o select the RS2000 Advanced Menu, see “Selecting the RS2000 Advanced Menu” on page 3–21.
In addition to several items from the basic menu, the RS2000 advanced menu contains the following sub-menus and commands:
Configure Inv/Chg (Configure Inverter/Charger)
Cfg AC Limits (Configure AC Limits)
Dev Info (Device Info)
When you select a sub-menu and press Enter, a list of menu items appears.
This section describes each display item and configurable item in detail. Each item is described as a display or configurable setting, when to use the setting, and the outcome of changing a setting.

Inverter

See a description of this feature on page 3–11.

Charger

See a description of this feature on page 3–12.

Power Share

See a description of this feature on page 3–13.

Configure Inv/Chg (Configure Inverter/Charger)

Cfg Inv/Chg is a sub menu command. If you select this item, you’ll access a list of sub-menu items. See “Configure Inv/Chg Menu (Configure Inverter/Charger Menu)” on page 3–23.
3–18 975-0125-01-01
Configuration

Max Chg Rate

Full name Maximum charge rate Configurable setting The actual battery charge rate is determined by two things. First, the
RS2000 uses the bank size setting (C) divided by 5 (C÷5). This value is then regulated by the charge rate setting. For example, if the battery bank size is set to 300 Ah and the charge rate was set at 100%, the calculation would be: 300 ÷ 5 or 60 amps × 100% which is a 60 amp charge rate. If the charge rate is adjusted to 50%, the resulting charge rate would be 30 amps (60 amps × 50%).
The RS2000 has a maximum charge rate of 100 amps. Even though you can set a bank size of 2000 Ah, where C÷5 is 400 amps, the RS2000 would still charge at 100 amp maximum.
Max Chg Rate [100%]
Range of values Increment Default
10% to 100% 10 100%
When to use Displayed only if in charger mode when you wish to control the
maximum charge rate to your batteries.

Load Sense

Configurable setting This setting lets you enable or disable the load sensing function.
Load sense [On]
Value Default
On Off Off
When to use Enable this setting if you want the inverter to conserve battery power
when there are small loads or no loads applied.
Outcome A small load like a clock display on a microwave may not get power.
When loads are below the load sense threshold, the inverter will turn off the output to save battery power.
975-0125-01-01 3–19
Configuration

Equalize

See a description of this feature on page 3–13.

Clear Faults

See a description of this feature on page 3–17.

View Device In fo

For more information on this sub menu, Device Information, see “View Device Info Menu (Device Information Menu)” on page 3–28.

Basic Menu

Purpose Selecting Basic Menu takes you back to the basic menu of the RS2000
only. Advanced menu items will no longer be visible on the System Control Panel.
When to use Use this setting when you want to return to the basic menu of the RS2000.
3–20 975-0125-01-01

Selecting the RS2000 Advanced Menu

The System Control Panel shows the RS2000 basic menu by default. If you would like to view the advanced menu, you must go to the System Settings menu and select Global Menus.
Configuration
Important:
Control Panel will display the advanced menus for all devices.T o return to viewing the basic menu for any Xanbus-enabled devices, select Basic Menu from the advanced menu for that device.
To select the RS2000 Advanced Menu:
1. On the Select Device menu with System highlighted, press Enter.
When you select Advanced on the Global Menu, the System
System
Figure 3-12
2. Scroll with the down arrow button to highlight Global Menus.
Highlighting System on the Select Device Menu
Figure 3-13
3. Press Enter.
975-0125-01-01 3–21
Highlighting Global Menus
Configuration
4. Select Advanced and press Enter.
5. Press Exit to return to Select Device menu.

Returning to RS2000 Basic Menu

You can return to viewing the RS2000 basic menu by selecting Basic Menu from the RS2000 advanced menu. See “Basic Menu” on page 3–
20.
3–22 975-0125-01-01
Configuration

Sub-Menus

Configure Inv/Chg Menu (Configure Inverter/Charger Menu)

Cfg/Inv Chg is a sub-menu. If selected, a list of sub-menu items appears.

Lo DC Volt

Full name Low DC input voltage shutdown Configurable setting This setting lets you set the low voltage shutdown level for the inverter.
Lo DC Volt [10.0V]
Range Increment Default
10 to 13 volts 0.1 volt 10 volts
When to use This setting limits the depth of discharge on your battery.

Batt Type

See a description of this feature on page 3–16.

Batt Size

See a description of this feature on page 3–23.

Sense Below

Configurable setting This setting lets you set the threshold for load sense power. This setting
saves battery consumption by keeping the inverter disabled (turned off) except when load demand is present.
Sense Below [50W]
Range of values Increment Default
40 watts to 150 watts 10 watts 10 watts
When to use Adjust this setting to control the inverter based on the load. Outcome Sets the load threshold at a power level where you want the inverter to
stay on, for example, when a sufficient load is applied.
975-0125-01-01 3–23
Configuration

Sense Interval

Configurable setting This setting lets you adjust the interval of load sensing. The longer the
interval, the more power you will save. However, the longer intervals may cause delays in the inverter power up and starting your loads.
Sense Interval [1s]
Range of values Increment Default
1 second to 25 seconds
1 second 1 second

Cfg AC Limits (Configure AC Limits)

Cfg AC Limits is a sub-menu. If selected, a list of sub-menu items appear. For more information on this sub menu, Configure AC Limits, see page 3–26.

# Chg Stages

Full name Number of charge stages Configurable setting These settings let you adjust your charger stages to either two-stage
charging or three-stage charging.
page B–1
# Chg Stages [3Stage]
Value Default
2Stage 3Stage 3Stage
for an explanation of two-stage and three-stage charging.
See “Battery Charging Reference” on
3–24 975-0125-01-01
Configuration

Eqz Volts

Full name Equalization voltage Configurable setting This setting lets you set the desired equalization voltage. This menu is
displayed only if charger equalization is enabled. Select a setting based on the battery manufacturer’s recommendation. For more information, see “Battery Charging Reference” on page B–1.
Eqz Volts [15.8V]
Range of values Increment Default
13.5 to 15.8 VDC 0.1 volt s 15.8 VDC

Force Charge

Full name Force Charge Configurable setting This setting forces the charger to be enabled (On) whenever you have
qualified AC or reacquired qualified AC. If Force Enabled is not on, you must turn it to On using the System Control Panel.
Force Charge [On]
Values Default
On On Off
When to use If you want the charger to automatically start when you connect to
qualified AC input.
Outcome The charger starts whenever qualified AC input appears.
975-0125-01-01 3–25
Configuration

Cfg AC Limits (Configure AC Limits)

CAUTION: Risk of damage to equipment
The following configuration settings adjust the quality of the AC input source that the inverter/charger will qualify and pass through to your AC loads. Voltage or frequency that is too high or too low for a particular piece of load equipment may cause damage to that load. Before adjusting these settings, refer to the electrical rating of connected load equipment. Most equipment that is marked with a single voltage (120 VAC, for example) rather than a range (110–125 VAC) can be expected to run properly over the range of 108 VAC to 125 VAC, since this is the normal operating range of electrical utilities.

Lo AC Volt

Full name Low AC Transfer voltage (AC under voltage level) Configurable setting Low AC Transfer voltage is the voltage below which the inverter/charger
no longer qualifies AC as “good”, opens the relay , and attempts to transfer to Invert mode if Invert is enabled.
Lo AC Volt [90.0V]
Range of values Increment Default
85 to 110 VAC 1 volt 90 VAC
When to use This setting lets you adjust the AC parameters when AC supply is outside
of the lower voltage range required for electrical equipment.
Outcome The lower level of voltage that will be accepted as “good” by the inverter/
charger can be varied.

Lo AC Freq

Full name Low AC transfer frequency (AC under frequency level) Configurable setting This setting lets you adjust the frequency at which the inverter/charger no
longer qualifies AC as “good” and attempts to transfer to invert mode.
Lo AC Freq [55Hz]
Range of values Increment Default
55 to 58 Hz 1 Hz 55 Hz
3–26 975-0125-01-01
Configuration
When to use This setting lets you adjust the AC parameters when the AC supply is
outside the lower frequency range required for electrical equipment.
Outcome The lower frequency of voltage that will be qualified as “good” by the
inverter/charger can be varied.

Hi AC Volt

Full name Hi AC transfer voltage (AC over voltage level) Configurable setting This setting lets you adjust the voltage above which the inverter/charger
no longer qualifies AC as “good” and attempts to transfer to Invert.
Hi AC Volt [135V]
Range of values Increment Default
120 to 145 VAC 1 volt 135 VAC
When to use This setting lets you adjust the AC parameters when AC supply is outside
the upper voltage range required for electrical equipment.
Outcome The upper level of voltage that will be qualified as “good” by the inverter/
charger can be varied.

Hi AC Freq

Full name Hi AC transfer frequency (AC over frequency level) Configurable setting This setting lets you adjust the frequency at which the RS2000 no longer
qualifies AC as “good” and attempts to transfer to Invert.
Hi AC Freq [65Hz]
Range of values Increment Default
62 to 70 Hz 1 Hz 65 Hz
When to use This setting lets you adjust the AC parameters when the AC supply is
outside the higher frequency range required for electrical equipment.
Outcome The higher frequency of voltage that will be qualified as “good” by the
inverter/charger can be varied.
975-0125-01-01 3–27
Configuration

View Device Info Menu (Device Information Menu)

The View Device Info menu allows you to view the Fault, Warning and Event logs. On the View Device Info menu, you can also restore the default setting for the RS2000.
For a definition of faults and warnings, see “Faults and Warnings” on page 4–2. An event is an indicator of the system modes that the unit has been in.

View Fault Log

Display setting The Fault log displays the 20 most recent faults for your reference.

View Warning Log

Display setting The Warnin g log displays the 10 most recent warnings.

View Event Log

Display setting The Event log displays the 10 most recent events. Events can include:
Changing the system mode
Enabling or disabling the charger
When to use The list provides useful information to a technical user about events on
the system, including an event ID, number ID, and the date and time of the event.
3–28 975-0125-01-01
Configuration

Restore Defaults

Configurable setting The Restore Default command restores the default settings for each
device.
Restore Defaults
When to use Adjust this setting when you wish to restore your settings to defaults.
Important:
Restoring to defaults will overwrite all of the stored values.
When you select Restore Defaults, a warning message appears, as shown in Figure 3-14:
continue cancel
Figure 3-14
If you select continue, your settings will be restored to default. If you select cancel, your existing settings will be retained and the Device
Info menu appears.
Defaults If your dealer has created a set of defaults tailored to your unit, those will
automatically be used in place of the factory defaults. The user cannot select between these two sets of defaults.
Restore Defaults Warning
975-0125-01-01 3–29
3–30
4
Troubleshooting
WARNING: Electrical shock and fire hazard
Do not disassemble the RS2000. It does not contain any user serviceable parts. Attempting to service the unit yourself could result in electrical shock or fire.
The RS2000 is designed for high reliability of operation and has a number of protection features to provide trouble free operation. If, however, you have any problems operating your inverter/charger read this troubleshooting chapter.
If you cannot resolve the problem, record the necessary information on the form, “Information About Your System” on page WA–4. This information will help your dealer or Xantrex Customer Service to assist you better when you contact them.
Troubleshooting

Faults and Warnings

When a fault or warning message appears, you can acknowledg e the message to clear the screen. To acknowledge a fault or warning message, press the Enter button on the System Control Panel. This action does not clear the fault or warning condition, so you should consult Table 4-3 and Table 4-4 for suggested actions after you have acknowledged the message. Refer to the information on faults and warnings.

Fault Types

There are three types of fault messages: automatic faults, manual faults, and escalating automatic faults. Table 4-1 describes how they differ in their behavior and how you can respond to them when they appear on the System Control Panel.
System Control Panel Owner’s Guide for more
Table 4-1
Fault type Behaviour
Automatic faults Clear automatically if the fault condition that
Manual faults Require you to clear them by:
Escalating automatic faults
Faults Types and Behaviors
generated the message goes away. You can also acknowledge automatic faults without waiting for them to clear automatically.
• selectin g Clear Faults on th e RS2000 or on the device that generated the fault (if the fault condition still exists, the fault message reappears)
• correctin g the condition that caused the fault
Clear automatically if the fault condition goes away, just like an automatic fault. However, if an escalating automatic fault occurs several times within a defined time period, the escalating automatic fault becomes a manual fault, requiring user intervention. For example, three faults occur in one minute. It will no longer clear itself but becomes a manual fault. Then you must identify the problem, correct the fault condition, and clear the fault or reset the device.
4–2 975-0125-01-01

Warning Types

Troubleshooting
There are two types of warnings: automatic and manual. When the RS2000 detects a warning condition, it displays a warning message on the System Control Panel.
Table 4-2 describes how they differ in their behavior and in how you can respond to them when they appear on the System Control Panel.
Table 4-2
Warning type Behaviour
Automatic warning Clear automatically if the fault condition that
Manual warning Require you to acknowledge them before you can
Warning Types and Behavior
generated the message goes away. You can also acknowledge automatic warnings without waiting for them to clear automatically.
proceed with configuring or operating the RS2000. Manual warnings are usually in the form of a Yes/ No question that you may acknowledge by pressing the Enter button on the System Control Panel for Yes and the Exit button for No. Refer to the System Control Panel Owner’s Guide for more information.
975-0125-01-01 4–3
Troubleshooting

Troubleshooting Reference

This chapter provides you with troubleshooting tips to identify and solve most problems that can occur with the RS2000.
This chapter is divided into the following four sections:
Section Page Number
General Troubleshooting Guidelines See page 4–5. Warni ng Messag es See page 4–7. Fault Messages See page 4–11. Inverter Applications (Loads) See page 4–17.
4–4 975-0125-01-01

General Troubleshooting Guidelines

This section will help you narrow down the source of any problem you may encounter. Please read the following troubleshooting steps:
1. Check for a Warning or Fault message on the System Control Panel. See “Warning Messages” on page 4–7 and “Fault Messages” on page 4–11 for descriptions of these messages and the specific action s to take. If a message is displayed, record it before doing anything further.
2. As soon as possible, record on the form, “Information About Your System” on page WA–4, the conditions at the time the problem occurred. These details should include the following as well as any other information asked for on page page WA–4:
Loads the RS2000 was running or attempting to run
Battery condition at the time of failure (voltage, state of charge,
for example), if known
Recent sequence of events (for example, charging had just
finished, we disconnected shore power as were preparing to leave the RV park, but the inverter didn’t come on)
Any known unusual AC input factors such as low voltage or
unstable generator output
Extreme conditions which may have existed at the time
(temperature, vibrations, moisture, for example).
3. Attempt the solution indicated in Table 4-3 or Table 4-4.
Troubleshooting
4. If your RS2000 or System Control Panel is not displaying a Fault light, check the following list to make sure that the present state of the installation allows proper operation of the unit:
Is the inverter/charger located in a clean, dry, adequately ventilated
place?
Are the battery cables adequately sized and short enough?Is the battery in good condition and are all DC connections tight?Are the AC input and output connections and wiring in good
condition?
Are the configuration settings correct for your particular installation?Are the display panel and the communications cable properly
connected and undamaged?
Is the battery temperature sensor and its cable properly connected and
undamaged?
975-0125-01-01 4–5
Troubleshooting
5. Contact Xantrex Customer Service for further assistance. Please be prepared to describe details of your system installation and provide the model and serial number of the unit. See “Contact Information” on page v for contact information.
4–6 975-0125-01-01

Warning Messages

Warning messages appear on the System Control Panel to alert you to an impending system change. You can retrieve and view the last ten warning messages using the control panel. The warnings have been recorded with a time stamp to let you know the date and time that the warning appeared. See “Warning Types” on page 4–3 for an explanation of automatic and manual warnings.
You can view the most recent fault messages of the RS2000 (up to 20) by selecting Fault Log from the Device Info menu in the RS2000 Advanced Menu.
If several warning messages occur before you can acknowledge or clear them, they are displayed together on a warning list. This list contains messages from every Xanbus-enabled device, not just the RS2000. You can select a message and view its details from warning list.
To view a message from a warning list:
1. On the list, use the up arrow or down arrow button to highlight the message you want to view.
2. Press Enter. The complete message appears.
After viewing the message, you can return to the warning list by pressing Exit or continue to the menu for the device that caused the fault by pressing Enter. Each time you return to the list after viewing a complete message, the viewed message is removed from the list.
Troubleshooting
If you have left the warning list, you can view them at any time from the System Settings menu.
To view a fault list:
1. On the Select Device menu, highlight System and press Enter.
2. On the System Settings menu, highlight View Warning List.
3. Press Enter.
975-0125-01-01 4–7
Troubleshooting
Table 4-3 provides a detailed description of the warning messages and solutions.
Table 4-3
Warning Number Message
W0 FET1 over-temp.
W1 FET2 over-temp.
W2 Bulk cap. over-temp.
W3 Transf’r over-temp.
W4 Battery over-temp.
Warning Messages
Check airflow around it.
Check airflow around it.
Check airflow around it.
Check airflow around it.
Check battery settings.
Warning Type Cause Solution
Automatic FET1 Over
Temperature Warning
Automatic FET2 Over
Temperature Warning
Automatic DC Bulk Capacitor
Over Temperature Warning
Automatic Transformer Over
Temperature Warning
Automatic Battery Over
Temperature Warning
Ensure adequate ventilation around the RS2000. Reduce the AC loads.
Ensure adequate ventilation around the RS2000. Reduce the AC loads.
Ensure adequate ventilation around the RS2000. Reduce the AC loads.
Ensure adequate ventilation around the RS2000. Reduce the AC loads.
Check battery voltage and battery cable connections. Stop charging, if necessary. Check for excessive ambient temperature and adequate ventilation in the battery compartment
W5 Over-temperature.
Check airflow around it.
W6 Too many AC loads.
Turn some off.
W7 Yo u hav e e nabled
system restart after faults.
W8 Yo u hav e e nabled
battery equalization. See manual.
4–8 975-0125-01-01
Automatic Ambient Over
Temperature Warning
Automatic AC Overload Warning
(AC OUPUT)
Automatic Auto Restart After
Fault Feature Enabled. (This parameter is not accessible through the System Control Panel. In the future, this feature may be configurable with advanced panels.)
Automatic Equalization Enabled
Warning
Ensure adequate ventilation around the RS2000. Reduce charge rate or AC load.
Turn off some AC loads.
If in invert mode, the unit may start up unexpectedly.
Make sure voltage sensitive loads are disconnected from batteries.
Table 4-3
Troubleshooting
Warning Messages
Warning Number Message
W9 Battery temp sensor
not detected. Check connections.
W10 Battery temp sensor
failure.
W11 Batt voltage too high.
Check DC wiring to inverter/charger.
W12 Battery voltage is
getting low. Recharge battery.
W13 Line 1 AC voltage
too high. System may shut down
W14 Line 1 AC voltage
too low. System may shut down.
W15 Line 2 AC voltage
too high. System may shut down.
Warning Type Cause Solution
Automatic Battery Temperature
Sensor Not Present
Automatic Battery Temperature
Sensor Shorted
Automatic DC Over Voltage
Warning
Automatic DC Under Voltage
Warning
Automatic AC Over Voltage
Warning (AC Line 1 input)
Automatic AC Under Voltage
Warning (AC Line 1 input)
Automatic AC Over Voltage
Warning (AC Line 2 input)
Install a battery temperature sensor (BTS). This warning will continue to display as long as no BTS is connected.
Replace battery temperature sensor.
Turn off or check additional charging sources to batteries. Check battery cables.
Recharge batteries and check battery cables from inverter to batteries for loose connections.
Check AC input voltage. Check high AC input voltage setting.
Check AC input voltage. Check low AC input voltage setting.
Not applicable to RS2000.
W16 Line 2 AC voltage
too low. System may shut down.
W18 Cannot Equalize Manual Cannot equalize Wrong battery type. Change
W19 Equalization
terminated abnormally
W500 Lost network
connection
975-0125-01-01 4–9
Automatic AC Under Voltage
Warning (AC Line 2 input)
Manual Equalization
terminated abnormally
Automatic Lost network
connection
Not applicable to RS2000.
battery type only if the battery type setting is not the same as actual battery type. Cannot equalize a gel or AGM battery.
Investigate cause of problem.
Check network cables or terminators.
Troubleshooting
Table 4-3
Warning Number Message
W501 Inv/Chg is trying to
Warning Messages
fix a memory problem
Warning Type Cause Solution
Manual Non-volatile memory
warning
Normal operation may return or may go to fault. Push Reset button if normal operation does not resume.
4–10 975-0125-01-01

Fault Messages

Troubleshooting
When the RS2000 detects a fault condition, the fault is displayed on the System Control Panel and also is indicated by the illuminated red Fault light on the RS2000 front panel. A fault affects the operation of the unit. See “Fault Types” on page 4–2 for an explanation of the different fault types.
You can view the 20 most recent fault messages of the RS2000 by selecting Fault Log from the Device Info menu in the RS2000 Advanced Menu.
If several faults occur before you can acknowledge or clear them, they are displayed together on a warning list. This list contains messages from every Xanbus-enabled device, not just the RS2000. You can select a message and view its details from the fault list.
To view a message from a fault list:
1. On the list, use the up arrow or down arrow button to highlight the message you want to view.
2. Press Enter. The complete message appears.
After viewing the message, you can return to the fault list by pressing Exit or continue to the menu for the device that caused the fault by pressing Enter. Each time you return to the list after viewing a complete message, the viewed message is removed from the list.
If you have left the fault list, you can view them at any time from the System Settings menu.
To view a fault list:
1. On the Select Device menu, highlight System and press Enter.
2. On the System Settings menu, highlight View Fault List.
3. Press Enter.
975-0125-01-01 4–11
Troubleshooting
Table 4-4 provides a detailed description of the fault messages and solutions. If you are unable to resolve the problem after referring to this table, contact your dealer or Customer Service.
Table 4-4
Fault Number Message
F0 is too hot and has
F2 is too hot and has
F3 is too hot and has
F4 Battery over-temp.
Fault Messages
shut down. See guide.
shut down. See guide.
shut down. See guide.
Inv/Chg has shut down. See guide.
Fault Type Cause Solution
Automatic FET1 Over
T emperature Shutdown
Automatic FET2 Over
T emperature Shutdown
Automatic Transformer Over
T emperature Shutdown
Automatic Battery Over
T emperature Shutdown
Clear the fault and attempt restart. Ensure adequate ventilation around the RS2000. Reduce AC loads.
Clear the fault and attempt restart. Ensure adequate ventilation around the RS2000. Reduce AC loads.
Clear the fault and attempt restart. Ensure adequate ventilation around the RS2000. Reduce AC loads.
Clear the fault and attempt restart. Stop charging, check battery voltage and temperature. Check for excessive ambient temperature and adequate ventilation in the battery compartment.
F5 is too hot and has
shut down. See guide.
F6 Too man y AC load s.
Turn some off, clear fault, try again.
4–12 975-0125-01-01
Automatic Ambient Over
T emperature Shutdown
Escalating Auto Fault. Must occur 3 times in 30 seconds before becoming a manual fault.
AC Overload Shutdown (AC OUTPUT)
Clear the fault and attempt restart. Ensure adequate ventilation around RS2000. Reduce AC loads.
Clear the fault and attempt restart. Reduce AC loads.
Table 4-4
Troubleshooting
Fault Messages
Fault Number Message
F7 Too many AC loads.
Turn some off, clear fault, try again.
F8 has lost input neutral
connection. See guide.
F9 Battery voltage is too
high. See guide.
Fault Type Cause Solution
Escalating Auto Fault. Must occur 3 times in 30 seconds before becoming a manual fault.
Manual Neutral loss shutdown Clear the fault and attempt
Automatic DC Over Voltage
AC Overload (PEAK CURRENT) Shutdown (AC OUTPUT)
Shutdown
Clear the fault and attempt restart. Reduce AC loads.
restart. Check AC input wiring for presence of a proper neutral connection and ground connection. Check the AC input source to make sure the neutral is bonded to ground.
Clear the fault and attempt restart. Ensure battery voltage is 10–16 VDC at RS2000 terminals. Check all other charging source outputs, battery cables.
F10 Battery is too low,
can’t invert. Recharge battery.
F11 Battery is too low,
can’t invert. Recharge battery.
F12 Input AC too high.
Check source, clear fault, try again.
F13 Input AC too low.
Check source, clear fault, try again.
975-0125-01-01 4–13
Automatic DC Under Voltage
Shutdown (Immediate) occurs if DC voltage is below 8 volts DC
Automatic DC Under Voltage
Shutdown occurs if DC voltage is below 10 volts DC.
Automatic AC Over Voltage
Shutdown (AC Line 1 input)
Automatic AC Under Voltage
Shutdown (AC Line 1 input)
Clear the fault and attempt restart. Recharge batteries. Check battery cable connections.
Clear the fault and attempt restart. Recharge batteries. Check battery cable connections.
Clear the fault and attempt restart. Check AC input voltage. Check and adjust AC input high voltage settings.
Clear the fault and attempt restart. Check AC input voltage. Check and adjust AC input low voltage setting.
Troubleshooting
Table 4-4
Fault Number Message
F14 Input AC too high.
F15 Input AC too low.
F16 AC input frequency
F17 AC input frequency
F18 AC input frequency
Fault Messages
Check source, clear fault, try again.
Check source, clear fault, try again.
problem. Check gen for overspeed.
problem. Check gen for underspeed.
problem. Check gen for overspeed.
Fault Type Cause Solution
Automatic AC Over Voltage
Shutdown (AC Line 2 input)
Automatic AC Under Voltage
Shutdown (AC Line 2 input)
Automatic AC Over Frequency
Shutdown (AC Line 1 input)
Automatic AC Under Frequency
Shutdown (AC Line 1 input)
Automatic AC Over Frequency
Shutdown (AC Line 2 input)
Not applicable for RS2000
Not applicable to RS2000.
Clear the fault and attempt restart. Check AC input frequency. Check and adjust AC input high frequency setting.
Clear the fault and attempt restart. Check AC input frequency. Check and adjust AC input low frequency setting.
Not applicable to RS2000.
F19 AC input frequency
problem. Check gen for underspeed.
F23 Reset the RS2000. If
problem persists, call customer service.
4–14 975-0125-01-01
Automatic AC Under Frequency
Shutdown (AC Line 2 input)
Escalating Auto Fault. Must occur 3 times in 30 seconds before becoming a manual fault.
AC Over Voltage Shutdown (Inverter AC output)
Not applicable to RS2000.
Clear the fault and attempt restart. If problem persists, call customer service.
Table 4-4
Troubleshooting
Fault Messages
Fault Number Message
F24 Reset the RS2000. If
problem persists, call customer service.
F25 Reset the RS2000. If
problem persists, call customer service.
F26 Reset the RS2000. If
problem persists, call customer service.
Fault Type Cause Solution
Escalating Auto Fault. Must occur 3 times in 60 seconds before becoming a manual fault.
Escalating Auto Fault. Must occur 3 times in 30 seconds before becoming a manual fault.
Escalating Auto Fault. Must occur 3 times in 30 seconds before becoming a manual fault.
AC Under Voltage Shutdown (Inverter AC output)
Auxiliary Power Supply Over Voltage Shutdown
Auxiliary Power Supply Under Voltage Shutdown
Clear the fault and attempt restart. If problem persists, call customer service.
Clear the fault and attempt restart. If problem persists, call customer service.
Clear the fault and attempt restart. If problem persists, call customer service.
F29 Reset the RS2000. If
problem persists, call customer service.
F30 is too cold and has
shut down. See guide.
F40 Reset the RS2000. If
problem persists, call customer service.
975-0125-01-01 4–15
Manual AC Backfeed
Shutdown
Manual Battery Under
Temperature Fault
Manual No IPC
communication
Clear the fault and attempt restart. If problem persists, call customer service.
Clear the fault and attempt one restart. Try restart again when ambient temperature is warmer or gently warm the battery.
Service required.
Troubleshooting
Table 4-4
Fault Number Message
F41 Reset the RS2000. If
F500 Silicon Serial ID
F502 Watchdog reset error Manual Watchdog reset error Service required. F505 Controller fault Manual Controller fault S ervice required. F506 Wrong fault
F507 Wrong identifier Manual Wrong identifier Service required. F508 Invalid interrupt Manual Invalid interrupt Service required.
Fault Messages
problem persists, call customer service.
Failure
identifier
Fault Type Cause Solution
Manual Dead battery charger
timeout
Manual Silicon Serial ID
Failure
Manual Wrong fault identifier Service required.
Try restarting dead battery charging once. Then check the condition of the battery and replace if necessary.
Service required.
4–16 975-0125-01-01
Loading...