Whirlpool AMB 868, AMB 869/G, AMB 868/G INSTRUCTION FOR USE

Page 1
33933053GB.fm Page 130 Friday, January 21, 2005 2:39 PM
INSTRUCTIONS FOR USE
INVERTER SPLIT AIR CONDITIONER WITH ECO GAS
PREPARATION BEFORE USE SAFETY PRECAUTIONS IDENTIFICATION OF PARTS REMOTE CONTROL OPERATION INSTRUCTIONS MAINTENANCE TROUBLESHOOTING PROTECTION INSTALLATION INSTRUCTIONS ELECTRICAL CONNECTION
MODELS AVAILABLE 9K AND 12K BTU
This appliance is marked according to the European directive 2002/96/EC on Waste Electrical and Electronic Equipment (WEEE). This guideline is the frame of a European-wide validity of return and recycling on Waste Electrical and Electronic Equipment.
130
Page 2
33933053GB.fm Page 131 Friday, January 21, 2005 2:39 PM
PREPARATION BEFORE USE
Before using the air conditioner, be sure to check and preset the following.
• Remote Control presetting
The remote control is NOT preset as Cooling Only Air Conditioner or Heat Pump by manufacturer. Each time the remote control batteries are replaced, the Cooling indicator and Heating indicator will flash alternately on the remote control LCD. The user can preset the remote control depending on the air conditioner type purchased as follows: Pressing any button when flashes, Heat Pump is set. Pressing any button when flashes, Cooling Only is set. If you don’t press any button within 12 seconds, the remote control is preset as Heat Pump automatically.
Note: If the air conditioner you purchased is a Cooling Only one, but you preset the remote control as Heat Pump, it doesn’t matter. But if the air conditioner you purchased is a Heat Pump one, and you preset the remote control as Cooling Only, then you CANNOT preset the Heating operation with the remote
control.
• Back-light function (optional)
Pressing any button of the remote control for about 2 seconds, the back-light turns on. Once the button is released, it automatically turns off after 10 seconds.
Note: Back-light is an optional function.
• Auto Restart Presetting
The Auto restart function is not preset by the manufacturer. To set the auto restart function, press the Emergency button (ON/OFF) on the indoor unit for at least 5 seconds. A buzz sound will signal that the auto restart function is set and the air conditioner is in standby. To cancel the auto restart function, press the Emergency button (ON/OFF) on the indoor unit for at least 5 seconds. A buzz sound will signal that the auto restart function is cancelled and the air conditioner is in standby.
SAFETY PRECAUTIONS
Be sure not to do the following.
It is harmful to your health if the cool air reaches you for a long time. It is advisable to let the air flow be deflected to all the room.
Prevent the air flow from reaching the gas burners and stove.
Do not touch the operation buttons when your hands are wet.
Pay attention to such a situation.
Do not repair the appliance by yourself. If this is done incorrectly, it may cause an electric shock, etc.
Be sure to follow this instruction.
Do not put any objects on the outdoor unit.
Earthing is essential.
It is the user’s responsibility to have the appliance be earthed according to local laws by a qualified technician.
Warning: Incorrect handling could cause a serious hazard, such as death, serious injury, etc.
Use correct power supply in accordance with the rating plate requirement. Don't use any extension cord for power supply. Otherwise, serious faults or hazard may occur or a fire may break out.
Keep the power supply circuit breaker or plug from dirt. Connect the power supply cord to it firmly and correctly, lest an electric shock or a fire break out due to insufficient contact.
Do not use the power supply circuit breaker or pull off the plug to turn it off during operation. This may cause a fire due to spark, etc.
Do not twist, pull or press the power supply cord, lest the power supply cord be broken. An electric shock or fire is probably caused by a broken power supply cord.
Never insert a stick or similar obstacle in the unit. Since the fan rotates at high speed, this may cause an injury.
Turn off the appliance with remote control first before cutting off power supply if malfunction occurs.
131
Page 3
33933053GB.fm Page 132 Friday, January 21, 2005 2:39 PM
IDENTIFICATION OF PARTS
I
G
E
F
H
A
B
Indoor unit
P
C
D
L
Outdoor unit
M
N
O
Indoor unit A
- Air Intake
B
- Front Panel
C
- Operation Panel
D
- Display
E
- Air Outlet
F
- Vertical Adjustment Louver
G
- Horizontal Adjustment Louver
H
- Remote Control
I
- Air Filter
NOTE: The figure above is only a simple presentation of the unit, it may not match the external appearance of the unit you purchased.
Outdoor unit L
- Air Intake
M
- Pipes and Power Connection Cord
N
- Drain Hose
Note: The condensate water drains at COOLING or DRY operation.
O
- Air Outlet
P
- Rating plate (product technical data)
132
Page 4
33933053GB.fm Page 133 Friday, January 21, 2005 2:39 PM
ON/OFF
Operating and Display
1
2
RUN
TIMER
1.
Emergency button
Used to control the unit when the remote control is out of service.
2.
Run Indicator (Green)
It is on during operation. When SLEEP mode is set, it will flash for ten seconds, then it will light up.
4
5
3
3.
Timer Indicator (Yellow)
It lights up during the set time.
4.
Power Indicator (Red)
It displays energy requirement during operation and protection status.
5.
Signal Receptor
Receives signal from remote control.
133
Page 5
33933053GB.fm Page 134 Friday, January 21, 2005 2:39 PM
REMOTE CONTROL
The remote control transmits signals to the system.
OFF button
A. ON
/
will be stopped when it is in operation, if you press this button.
B. MODE button: C. FAN button:
or low.
D. ROOM TEMPERATURE SETTING buttons:
room temperature. Used to set time in TIMER mode and real time Clock.
E. SWING button:
swinging and set the desired up/down airflow direction.
F. 6th Sense button
regardless of the unit is on or off.
G. TIMER ON/OFF button: H. SLEEP button I. button
cooling mode or turbo heating in heating mode
J. button:
temperature signal to indoor unit every 10 minutes if you press this button.
K. Clock button:
The appliance will be started when it is energized or
:
Used to select the operation mode.
Used to select fan speed in sequence auto, high, medium
Used to stop or start vertical adjustment louver
Used to enter fuzzy logic operation directly,
:
Used to set or cancel the timer operation.
Used to set or cancel Sleep Mode operation.
:
TURBO
:
Remote controller automatically transmits room
mode, used to start
Used to enter the current time.
Used to select the
TURBO
cooling funtion in
D
I
G
C
K
A
F B E
H
J
Indication symbols on LCD:
Cooling indicator Dry indicator Fan only indicator *Heating indicator
NOTE: Each mode and relevant function will be further specified in following pages.
How to insert the batteries
Remove the battery cover in the direction of the arrow.
Insert new batteries making sure that the (+) and (-) of battery are matched correctly.
Refit the cover by sliding it back into position.
Note:
Use 2 LR03 AAA (1.5 V) batteries. Do not use rechargeable batteries. Replace batteries with new ones of the same type when the display becomes dim.
If the replacement is done within 1 minute, the remote control will keep original presetting. However, if you want to change the presetting from Heat Pump to Cool Only or Cool Only to Heat Pump, you should reload batteries 3 minutes after removing the old ones. (Please refer to page 131 for details.)
Storage and tips for using the remote control
The remote control can be stored in a holder mounted on the wall.
NOTE:
The remote control holder is an optional part.
How to use the remote control
To operate the room air conditioner, point the remote control at the signal receiver. The remote control will operate the air conditioner at a distance of up to 7 m when pointing at the signal receiver of the indoor unit.
Choose cooling only remote control or heat pump. Please refer to page 131 “Preparation before use“ for details.
Auto fan speed
High fan speed Medium fan speed Low fan speed
indicator SLEEP indicator indicator
JET TURBO indicator
Remote control holder
Signal transmit
Display set timer Display clock Display set temperature
134
Signal receiver
Page 6
33933053GB.fm Page 135 Friday, January 21, 2005 2:39 PM
OPERATION INSTRUCTIONS
Operating modes
1. Selecting mode
Each time sequence:
COOLING DRY FANONLY HEATING
IMPORTANT:
Heating mode is NOT available for cooling only air conditioner.
2. “FAN” mode
Each time the “FAN” button is pressed, the fan speed is changed in sequence:
AUTO HIGH MEDIUM LOW
IMPORTANT:
3. Setting temperature
Range of available set temperature: *HEATING, COOLING 18°C ~ 32°C DRY unable to set FAN ONLY unable to set
*NOTE: Heating mode is NOT available for cooling only models.
4. Turning on
Press button, when the appliance receives the signal, the RUN indicator of the indoor unit lights up.
SWING, 6th SENSE, TIMER ON, TIMER OFF, CLOCK, SLEEP, TURBO and ROUND U operation modes will be specified in the following pages.
IMPORTANT:
• Changing modes during operation, sometimes the unit does not response at once. Wait 3 minutes.
• During heating operation, air flow is not discharged at the beginning. After 2-5 minutes, the air flow will be discharged until temperature of indoor heat exchanger rises.
• Wait 3 minutes before restarting the appliance.
5. Airflow direction control
Vertical airflow is automatically adjusted to a certain angle in accordance with the operation mode after turning on the unit. The direction of airflow can also be adjusted to your own requirement by pressing the “SWING” button of the remote control.
*Heating mode is only available for heat pump models.
Vertical airflow control (using the remote control)
Use the remote control to set the flow angles.
Swinging airflow.
Pressing the “SWING” button once, the vertical adjustment louver will swing up and down automatically.
Desired airflow direction.
Press the “SWING” button again when the louvers swing to a suitable angle as desired.
MODE
button is pressed, the operation mode is changed in
In “FAN ONLY” mode, only “High”, ”Medium” and “Low” are available. In “DRY” mode, airflow is set at “Low” automatically, “FAN” button is ineffective in this case.
Press once to raise temperature setting by 1°C Press once to lower temperature setting by 1°C
operation mode direction of airflow
COOLING, DRY
*HEATING, FAN ONLY
horizontal downward
135
Page 7
33933053GB.fm Page 136 Friday, January 21, 2005 2:39 PM
Horizontal airflow control (with hands)
ù
Turn the control rods of the horizontal adjustment louvers to change horizontal air flow as shown.
Note: The shape of the unit may look different from that of the air conditioner you have selected.
Control rods of horizontal adjustment louvers
Important:
• Do not turn the vertical adjustment louvers manually, otherwise malfunction may occur. If that happens, first turn off the unit and cut off the power supply, then restore the power supply again.
• It is better not to let the vertical adjustment louver tilt downward for a long time at COOLING or DRY mode to prevent condensed water from dripping.
Clock button
You can adjust the real time by pressing CLOCK button, then using and buttons to get the correct time, press CLOCK button again the real time is set.
6th Sense mode
Pressing the 6th Sense button, the unit enters fuzzy logic operation directly regardless whether the unit is on or off. In this mode, temperature and fan speed are automatically set according to the actual room temperature.
Operation mode and temperature are determined by indoor temperature Heat pump models
Indoor temperature Operation mode Target temperature
21°C or below HEATING 22°C
21°C - 26°C DRY
Room temperature decreases 1.5°C after
operating for 3 minutes
Over 26 COOLING 26°C
Cooling only models
Indoor temperature Operation mode Target temperature
26°C or below DRY
Room temperature decreases 1.5°C after
operating for 3 minutes
Over 26 COOLING 26°C
Important: 6th sense button is ineffective in TURBO mode. Note: Temperature, airflow and direction are controlled automatically in 6th Sense mode. However, a decrease or rise of up to 2°C can be set with the remote control if you still feel uncomfortable.
What you can do in 6th SENSE MODE
Your feeling Button Adjustment procedure
Slightly warmer
A decrease up to 2°C can be set
Press once to lower the set temp by 1°C
Press twice to lower the set temp by 2°C
Slightly cooler
A rise up to 2°C can be set
Uncomfortable because of unsuitable air
flow volume.
Uncomfortable because of unsuitable flow
direction.
136
Press once to raise the set temp by 1°C
Press twice to raise the set temp by 2°C
Indoor fan speed alternates among High, Medium and Low each time this button is pressed.
Press it once, the vertical adjustment louver swings to change vertical airflow direction. Press it again, swings stops. For horizontal airflow direction, please refer to the previous page for details.
Page 8
33933053GB.fm Page 137 Friday, January 21, 2005 2:39 PM
Round U mode
When you press the Round U button the remote controller transmit signal of the actual room temperature around the remote controller to the indoor unit every 10 minutes. Therefore please keep the remote controller in a location form which it can transmit the signal to the indoor unit properly.
Press once to set and press again to cancel.
Timer mode
It is convenient to set the timer on with go out in the morning to achieve a comfortable room temperature at the time you get home. You can also set timer off at night to enjoy a good sleep.
How to set TIMER ON
•TIMER ON
wished in order to switch on the appliance at your desired time..
button can be used to set the timer programming as
TIMER ON/OFF
buttons when you
1
2
2
1.
2.
3.
TIMER ON
Press press the or buttons to select your desired time for appliance on.
Press the setting by 1 minute.
Press the decrease the time setting by 10 minute. Press the the time by 1 hour.
Note: If you don’t set the time in 10 seconds after you press TIMER
ON button, the remote controller will exit the TIMER ON mode automatically.
When your desired time is displayed on LCD, press the TIMER ON button and confirm it.
A “beep” can be heard. “ON” stops flashing. The TIMER indicator on the indoor unit lights up.
After the set timer displayed for 5 seconds the clock will be displayed on the LCD of the remote controller instead of set timer.
How to cancel TIMER ON
Press the TIMER ON button again, a "beep" can be heard and the indicator disappears, the TIMER ON mode has been cancelled.
Note: It is similar to set TIMER OFF, you can make the appliance
switch off automatically at your desired time.
button, “ON 12:00” flashes on the LCD, then you can
Increase
Decrease
TIMER ON
TIMER ON
TIMER ON
button once to increase or decrease the time
button one and a half seconds to increase or
button for a longer time to increase or decrease
137
Page 9
33933053GB.fm Page 138 Friday, January 21, 2005 2:39 PM
TURBO mode
Turbo Cooling Mode
TURBO mode is used to start or stop fast cooling. Fast cooling operates at high fan speed, changing the set temperature automatically to 18°C.
TURBO mode can be set when the appliance is in operation or energized.
In TURBO mode, you can set airflow direction and timer. If you want to quit from TURBO mode, press any-TURBO, MODE, FAN, ON/OFF or TEMPERATURE SETTING button, the display will return to the original mode.
Turbo Heating Mode
TURBO mode is used to start or stop fast heating. Fast heating operates at high fan speed, changing the set temperature automatically to 32°C.
TURBO mode can be set when the appliance is in operation or energized.
In TURBO mode, you can set airflow direction and timer. If you want to quit from TURBO mode, press any-TURBO, MODE, FAN, ON/OFF or TEMPERATURE SETTING button, the display will return to the original mode.
Note: SLEEP and 6th Sense buttons are not available in TURBO mode.
TURBO button is ineffective in Heating mode. The appliance will continue working in TURBO mode with set
temperature of 18°C or 32°C if you don't quit it by pressing any TURBO, MODE, FAN, ON/OFF or TEMPERATURE setting button.
Sleep mode
SLEEP mode can be set in COOLING or HEATING operation mode. This function gives you a more comfortable environment for sleep. In SLEEP mode,
The appliance will stop operation automatically after operating for 8 hours.
Fan speed is automatically set at low speed.
*The set temperature will rise by max. 1°C if the appliance operates in cooling mode for two hours, then it will remain constant.
The set temperature will decrease by max 3°C if the appliance operates in heating mode for 3 hours, then it will remain constant.
COOLING
8 hours timer
1 hour
1 hour
Rise by 0.5°C
SET
TEMP.
START
Rise by 0.5°C
**HEATING
8 hours timer
SET
TEMP.
START
1 hour
1 hour
Decrease by
1°C
1 hour
Decrease by
1°C
Decrease by
1°C
*: In cooling mode, if room temperature is 26°C or above, set
temperature will not change.
**: Heating is NOT available for cooling only air conditioner.
138
STOP
STOP
Page 10
33933053GB.fm Page 139 Friday, January 21, 2005 2:39 PM
MAINTENANCE
Appliance maintenance
Unplug from the power supply
Stop the appliance before unplugging.
To remove the front panel pull it outwards as shown in the figure (a)
Wipe with a soft, dry cloth
Use lukewarm water (below 40°C) to clean the appliance when it is very dirty.
Use a dry and soft cloth to clean it.
Never use volatile substances such as gasoline or polishing powder to clean the unit.
Never sprinkle water on the indoor unit
Danger! Electric shock!
Refit and close the front panel
Refit and close the front panel by pushing it downwards as shown in the figure (b).
Clean the air filter
It is advisable to clean the air filter after approx. 100 hours of operation.
Stop the appliance and remove the air filter
1.
Open the front panel.
2.
Press the air filter handle gently, the filter will spring out.
3.
Pull out the filter.
Replace the filter in its original position after cleaning
If the filter is very dirty, clean it with a solution of lukewarm water and neutral detergent, then dry it in the air.
Close the front panel. IMPORTANT: Clean the air filter every two weeks when the air conditioner is
operated in a dusty environment.
TROUBLESHOOTING
Trouble Analysis
Does not run
No cool or warm air
Ineffective control
Does not operate immediately
Peculiar smell
A sound of running-water
A “pixi” sound can be heard
Spray mist from the outlet
The compressor indicator (red) lights up
constantly, and the indoor fan stops.
Is the protection device or fuse blown?
Sometimes it stops working to protect the appliance.
Are the remote control batteries low?
Is the plug unplugged?
Is the air filter dirty?
Are the intakes and outlets of the air conditioner obstructed.
Is the temperature set properly.
If there is a strong interference (from excessive static electricity discharge, power supply voltage abnormality) presents, operation will be abnormal. In this case, unplug from the power supply and plug in after 2-3 seconds.
Changing mode in operation, there may be a delay of 3 minutes.
This odour may come from another source such as furniture or others.
Caused by the flow of refrigerant in the air conditioner, not a fault.
Caused by the expansion or contraction of the front panel because of temperature changing, not a fault.
Mist appears when the room air becomes very cold as during operation in “COOLING” or “DRY” mode.
The unit is shifting from heating mode to defrost. The indicator will turn off within ten minutes and return to heating mode.
139
Page 11
33933053GB.fm Page 140 Friday, January 21, 2005 2:39 PM
PROTECTION
Operating condition
The protective device may trip and stop the appliance in the cases listed below.
Outdoor air temperature is over 24°C
*HEATING
COOLING
DRY
*For Tropical (T3) Climate condition models, the temperature point is 52°C instead of 43°C.
If the air conditioner runs in “COOLING” or “DRY” mode with door and/or window open when relative humidity is higher than 80%, dew will drip down from the outlet.
Features of protection device
Outdoor air temperature is below -7°C Room temperature is over 27°C Outdoor air temperature is over* 43°C Room temperature is below 21°C Room temperature is below 18°C
• The protection device will trip in the following cases:
-
Restarting the unit at once after operation stops or changing mode during operation, you need to wait 3 minutes.
-
After connecting to power supply and turning on the appliance immediately, there may be a delay of 20 seconds before it starts to operate.
-
If all operation has stopped, press ON/OFF button again to restart, Timer should be set again if it has been cancelled.
Noise pollution
Install the air conditioner in a place that can bear its weight in order to operate more quietly.
Install the outdoor unit in a place where the air discharged and the operating noise do not annoy your neighbours.
Do not place an obstacle in front of the outlet of the outdoor unit as it may affect the air conditioner operation and increase the noise level.
Inspection
After a long time of operation, an inspection is necessary in the following cases:
Abnormal heating of the power supply cord and plug or even a smell.
Abnormal operating noise or vibration.
Water leakage from indoor unit.
Metal cabinet electrified.
IMPORTANT: Stop the air conditioner if any fault occurs. It is advisable to check the air conditioner carefully every five years even if none of the above faults occur the air conditioner.
HEATING mode features
Preheating
2-5 minutes are necessary to preheat the evaporator at the beginning of HEATING operation, so that cold air is not discharged.
Defrosting
In HEATING mode the appliance will defrost automatically to raise efficiency. This procedure usually takes 2-10 minutes. During defrosting, fans stop operation. After defrosting completes, it returns to HEATING mode automatically.
Note: Heating is NOT available for cooling only air conditioner models.
140
Page 12
33933053GB.fm Page 141 Friday, January 21, 2005 2:39 PM
INSTALLATION INSTRUCTIONS
Distance from ceiling should be over 50 mm
Distance from wall should be over 50 mm
Air intake distance from the wall should be over 250 mm
Installation diagram
Distance from the wall should be over 50 mm
Distance from floor should be over 2500 mm
Air intake distance from the wall should be over 250 mm
A
i
r
o
u
s
t
h
l
o
e
t
u
l
d
d
i
b
st
a
e
n
o
c
v
e
e
f
r
ro
5
m
0
0
t
h
m
e
m
w
a
l
l
NOTE: The figure above is only a simple presentation of the unit, it may not match the external appearance of the
unit you purchased. Installation must be performed in accordance with the national wiring standards by authorised personnel only.
Over 250 mm
141
Page 13
r
33933053GB.fm Page 142 Friday, January 21, 2005 2:39 PM
Select the best location
Location for Installing the Indoor Unit
Where there is no obstacle near the air outlet and air can easily be blown to every corner.
Where piping and wall hole can easily be arranged.
Observe the required distance from ceiling and wall according to the wiring diagram.
Where the air filter can easily be removed.
Keep the unit and remote control 1 m or more from the television, radio etc.
To prevent the effects of a fluorescent lamp, keep the unit as far as possible.
Do not put anything near the air inlet that could obstruct it.
In a place that can bear the weight and will not increase operating noise and vibrations.
Indoor unit
Height should
be less than 5 m
Pipe length max 15 m
Outdoor unit
Location for Installing the Outdoor Unit
Install in a convenient and well-ventilated place; avoid installing it where flammable gas could leak.
Observe the required distance from the wall.
Do not install the outdoor unit in a dirty or greasy place, near a vulcanization gas exit or highly salty seashore.
Avoid installing it at the roadside where it could be soiled with muddy water.
A fixed base where operating noise will not increase.
Where the air outlet is not obstructed.
Outdoor unit installation
1.
Install Drain Port and Drain Hose (for heat-pump model only)
The condensate drains from the outdoor unit when the unit operates in heating mode. In order not to disturb your neighbours and protect the environment, install a drain port and a drain hose to direct the condensate water. Just install the drain port and rubber washer on the chassis of the outdoor unit, then connect a drain hose to the port as shown in the figure on the right.
2.
Install and Fix Outdoor Unit
Fix with bolts and nuts tightly on a flat and strong floor. If installed on the wall or roof, make sure to fix the support well to prevent it from shaking due to serious vibrations or strong wind.
3.
Outdoor Unit Piping Connection
Remove the valve caps from the 2-way and 3-way valve. Connect the pipes to the 2-way and 3-way valves separately according to the required torque.
4.
Outdoor Unit Cable Connection (see page 146)
Pipe length max 15 m
Indoor unit
Drain port
Outdoor unit
Height should
be less than 5 m
Washe
Drain hose (prepare by user)
142
Page 14
33933053GB.fm Page 143 Friday, January 21, 2005 2:39 PM
Indoor unit installation
1.
Installing the Mounting Plate
Select a location to install the mounting plate according to the indoor unit location and piping direction.
Adjust the mounting plate horizontally with a horizontal ruler or plumb line.
Drill holes 32 mm deep on the wall to fix the plate.
Insert the plastic plugs in the hole, then fix the mounting plate with tapping screws.
Check that the mounting plate is well fixed. Then drill a hole for the piping.
NOTE: The shape of your mounting plate may be different from the one above, but installation method is similar.
2.
Drill a Hole for Piping
Decide the position of the hole for piping according to the location of the mounting plate.
Drill a hole on the wall. The hole should slightly be inclined downward toward outside.
Install a sleeve through the wall hole to keep the wall tidy and clean.
3.
Indoor Unit Piping Installation
Fit the piping (liquid and gas pipe) and cables through the wall hole from outside or fit them from inside after completing indoor piping and cables connections so as to connect to outdoor unit.
Decide whether to saw off the plastic part in accordance with the piping direction (as shown below).
NOTE: When fixing the pipe along directions 1, 2 or 4, saw the
corresponding plastic part off the indoor unit base.
After connecting the piping as required, install the drain hose. Then connect the power cords. After connecting, wrap the piping, cords and drain hose together with thermal insulating materials.
IMPORTANT: Piping Joints Thermal Insulation:
Wrap the piping joints with thermal insulating materials and then cover with vinyl tape.
Hook the line here
Mounting
plate
Indoor
Piping direction
trough
Plastic part
Saw off the plastic part along the trough
Thermal insulation
Line drops from here
Plumb line
Holes for fixing
Wall hole sleeve (hard polythene tube prepared by user)
Outdoor
5 mm (downward inclination)
wrapped with vinyl tape
143
Page 15
33933053GB.fm Page 144 Friday, January 21, 2005 2:39 PM
Thermal Insulation Piping:
Place the drain hose under the piping.
Insulating material: polythene foam over 6 mm in thickness.
NOTE: Drain hose is prepared by user.
Drain pipe should point downward for easy drain flow.
Do not twist the drain pipe, leave it sticking out or waving around, and do not immerse the end in water. If an extension drain hose is connected to the drain pipe, make sure it is thermally insulated when passing it through the indoor unit.
When the piping is directed to the right, piping, power cord and drain pipe should be thermally insulated and fixed at the rear of the unit with a piping fixer.
1. Insert the pipe fixer into the slot.
2. Press to hook the pipe fixer onto the base.
Piping Connection:
Connect the indoor unit pipes using two wrenches. Pay special attention to the torque allowed as shown below to prevent the pipes, connectors and flare nuts from being deformed and damaged.
At first finger-tighten them, then use the wrenches.
Model Pipe size Torque
Nut
width
7-9-12 K Liquid Side (ø 6 or ¼ inch) 1.8 Kg.m 17 mm
18-22-24 K Liquid Side (ø 10 or 3/8 inch) 3.5 Kg.m 22 mm
7-9 K Gas Side (ø 10 or 3/8 inch) 3.5 Kg.m 22 mm
12 K Gas Side (ø 12 or ½ inch) 5.5 Kg.m 24 mm
18-22-24 K Gas Side (ø 16 or 5/8 inch) 7.5 Kg.m 27 mm
Large pipe
Power cord
Defrost cable (for heat-pump)
Base
Base
Drain
hose
Insert here
Large
pipe
Small
pipe
Piping fixer
Thermally insulated
tube
Small pipe
Drain hose (prepared by user)
Piping fixer
Hook hereHook here
How to Purge Air Tubes
Unscrew and remove caps from 2 and 3-way valves.
Unscrew and remove cap from service valve.
Connect vacuum pump flexible hose to the service valve.
Start the vacuum pump for 10-15 minutes until it reaches an absolute vacuum of 10 mm Hg.
With the vacuum pump still running close the low pressure knob on the vacuum pump manifold. Then stop the vacuum pump.
Open the 2-way valve ¼ turn, then close it after 10 seconds. Check tightness of all joints using liquid soap or an electronic leak detector.
Turn the 2 and 3-way valves stem. Disconnect the vacuum pump flexible hose.
Replace and tighten all valve caps.
NOTES:
Please read this manual before installing and using the appliance.
Do not let air enter the refrigerating system or discharge refrigerant when moving the air conditioner.
When charging refrigerant into the system, make sure to charge in liquid state. Otherwise, chemical composition of refrigerant (R410A) inside the system may change and thus affect performance of the air conditioner.
Test run the air conditioner after finishing installation and record details of operation.
Type of fuse used on indoor unit control for 7 K, 9 K, 12 K is 50 T, with rating 2.5 A,T,250 V.
For 18 K, 22 K, 24 K models use 5 A, T, 250 V.
The fuse for the whole unit is to be provided by the user according to the current at maximum power input or use another over-current protective device instead.
Only the air conditioner can be connected to the power line.
The power connection for the air conditioner has to be done at the main power distribution which has to be of a low impedance.
In order to ensure the suitability of the equipment for connection, the user should consult with the supply authority, if necessary, that the service current capacity at the interface point is sufficient for the equipment.
Refer to the rating plate of the equipment for power consumption details.
If the supply cord is damaged, it must be replaced by the manufacturers After-Sales Service or a qualified tecnician in order to avoid a hazard.
Accessibility to the plug must be guaranteed even after the installation of the appliance to disconnect it if necessary. If this is not possible, connect the appliance to a double-pole switching device with contact distance of at least 3 mm placed in an accessible position even after installation.
Please pay more attention to the details of 2-way and 3-way valve. Service valve: 7/16 inch for R410A model; and 1/ 4 inch for R22 and R407C. Diameter of hexagon (inward): 4mm for R410A model; 5mm for R407C and R22.
144
Page 16
33933053GB.fm Page 145 Friday, January 21, 2005 2:39 PM
4.
Connecting the Cable
Indoor Unit
Connect the power cord to the indoor unit by connecting the wires to the terminals on the control board individually in accordance with the outdoor unit connection.
Front panel
Terminal (inside)
NOTE: (depending on the model)
It is necessary to remove the cabinet to perform connections with the indoor unit terminal.
Outdoor Unit
Remove the access door from the unit by loosening the screw.
-
Connect the wires to the terminals on the control board individually as follows. Secure the power connecting cord on the control board with a cable
-
clamp. Refit the access door in the original position and tighten the screw.
-
Use a recognized circuit breaker for 24 K model between the power
-
source and the unit. A disconnecting device to adequately disconnect all supply lines must be fitted.
CAUTION:
1. Use an individual power circuit specifically for the air
conditioner. As for the wiring method, refer to the circuit diagram on the inside of the access door.
2. Check that the cable thickness conforms to the power source
specification. (See the cable specification table below)
3. Check the wires and make sure that they are all tightly fastened
after cable connection.
4. Be sure to install an earth leakage circuit breaker in a wet or
moist area.
Cable Specifications
Power cord Power connecting cord
Capacity
(Btu/h)
7 K-9 K H05VV-F 1.0 mm2 X 3 H07RN-F 1.5 mm2 X 3 H07RN-F 0.75 mm2 X 2
22-24 K H07RN-F 2.5 mm2 X 3 H07RN-F
Type
12 K H05VV-F 1.5 mm2 X 3 H07RN-F 1.5 mm2 X 3 H07RN-F 0.75 mm2 X 2
18 K H05VV-F 2.0 mm2 X 3 H07RN-F 1.5 mm2 X 3 H07RN-F 0.75 mm2 X 2
Normal
cross
- section area
Type
Normal
cross
- section area
1.5 mm2 X 3 (heat pump)
1.5 mm2 X 4
(cool only)
Power connecting cord
(for heat pump)
Normal
Type
H07RN-F 0.75 mm2 X 3
cross
- section area
Indoor Unit
Outdoor Unit
Cabinet
Chassis
Access door Terminal (inside)
Attention: Accessibility to the plug must be guaranteed even after the installation of the appliance to disconnect it in case of need. If not possible, connect appliance to a double-pole switching device with contact separation of at least 3 mm placed in an accessible position
even after installation.
145
Page 17
HEAT PUMP COOLING ONLY
33933053GB.fm Page 146 Friday, January 21, 2005 2:39 PM
Wiring Diagram
Make sure that the colour of wires of the outdoor unit and the terminal number are the same as those of the indoor unit.
7 K,9 K,12 K,18 K Model
HEAT PUMP COOLING ONLY
Indoor unit Indoor unit
Terminal
Brown
Blue Blue
Power connecting cord I
Brown Brown
Outdoor unit
Terminal
Brown
Terminal Terminal
Brown Brown
Blue Blue
Outdoor unit
Blue
Power connecting cord
Blue
Yellow/GreenYellow/Green
Power connecting cord
Yellow/Green Yellow/Green
For above models, the power supply are connected form indoor unit, with a plug.
22-24 K Model
For 24 K model, the power supply is connected from the outdoor unit, with a circuit breaker. Other models from the indoor unit.
Indoor unit Indoor unit Outdoor unitOutdoor unit
Orange
Power connecting cord I
Violet Violet
low/Gre
l
Ye
e
Power connecting cord
n
Brown Brown
Y
e
llow/Green
Power supply
Orange
BlackBlack
BlueBlue
TerminalTerminal
Terminal Terminal
OrangeOrange
Brown Brown
Blue Blue
Terminal
Power connecting cord
Yellow/Green Yellow/Green
Power supply
Terminal
Defrost Cable (for heat pump air conditioner only)
Defrost wire (indoor) Defrost wire (outdoor)
Defrost cable (for heat-pump models only)
After connection, the defrost wire should be well wrapped with a wrapping tape and the connector should be put inside the unit.
146
Page 18
33933053GB.fm Page 147 Friday, January 21, 2005 2:39 PM
Air purging
Air containing moisture remaining in the refrigerant cycle may cause a malfunction of the compressor. After connecting the indoor and outdoor units, evacuate air and moisture from refrigerant cycle using a vacuum pump, as shown below.
Vacuum pump
Indoor unit
Service port
(2) Turn (8) Tighten
3-way valve diagram
Refrigerant flow direction
3-way valve
(7) Turn to fully open the valve
Valve cap
Connect to outdoor unit
Valve core
(1) Turn
2-way valve
(6) Open 1/4 turn
(7) Turn to fully open the valve
Valve cap
(1) Turn
(8) Tighten
(8) Tighten
Connect to indoor unit
Open position
Spindle
Needle
Service port cap
Note: Because the system pressure is high and also to protect the environment, be sure not to discharge the
refrigerant to the air directly.
147
Page 19
33933053GB.fm Page 148 Friday, January 21, 2005 2:39 PM
ELECTRICAL CONNECTION
1) For Great Britain only Warning - this appliance must be earthed Fuse replacement
If the mains lead of this appliance is fitted with a BS 1363A 13amp fused plug, to change a fuse in this type of plug use an A.S.T.A. approved fuse to BS 1362 type and proceed as follows:
1.
Remove the fuse cover (A) and fuse (B).
2.
Fit replacement 13A fuse into fuse cover.
3.
Refit both into plug.
Important:
The fuse cover must be refitted when changing a fuse and if the fuse cover is lost the plug must not be used until a correct replacement is fitted. Correct replacement are identified by the colour insert or the colour embossed in words on the base of the plug. Replacement fuse covers are available from your local electrical store.
2) For the Republic of Ireland only
The information given in respect of Great Britain will frequently apply, but a third type of plug and socket is also used, the 2-pin, side earth type.
3) Socket outlet / plug (valid for both countries)
If the fitted plug is not suitable for your socket outlet, please contact Whirlpool Service for further instruction. Please do not attempt to change plug yourself. This procedure needs to be carried out by a qualified Whirlpool technician in compliance with the manufactures instructions and current standard safety regulations.
148
Loading...