Viessmann BW 110, Vitocal 350, BW 113, BW 116, BW 212 Datasheet

...
VITOCAL 300 Typ e BW and WW
Up to 55 °C flow temperature Heat pump with electric drive for DHW and central heating
in mono or dual-mode heating systems
&
Brine/water heat pump
(typeBW)with6.4to32.6kW
&
(type WW = type BW plus conversion kit) with8.4to43.0kW
VITOCAL 350 Type BWH and WW H
Up to 65 °C flow temperature Heat pump with electric drive for DHW and central heating
in mono or dual-mode heating systems
&
Brine/water heat pump
(typeBWH)with11.0and17.1kW
&
(type WWH = type BWH plus conversion kit) with 14.1 and 20.0 kW
VIESMANN
Datasheet
Part numbers and prices: see pricelist
VITOCAL 300/350
Heat pump
Brine/Water – 6.4to32.6kW
Water/Water – 8.4to43.0kW
File in:
Vitotec folder, regi ster 11
5822 119-7 GB 4/2007
Brine/water heat pump (type BW/BWH) with g round probe
Typ e BW/B WH – heat from the ground:
The Vitocal 300/350 extracts heat from the ground with the help of ground collectors or ground probes. The groun d provides almost completely stable temperatures all the year round, enabling the Vitocal 300/350 to operate virtually independently of the outside temperature. It can cover the entire heat demand of a building, even on colder days.
Brine/water heat pump (type BW/BWH) with ground collector
Water/water heat pump (type WW/WWH) wi th supply and return wells
Type WW/WWH – heat fr om water:
The Vitocal 300/350 draws energy from groundwater, where the temperature is stable, and therefore achieves consistently high performance factors. This means that it is suitable for year round heating operation and DHW provision.
5822 119-7 GB
2 VIESMANN VITOCAL 300/350
Product d escription
&
Suitable for all operating modes: – Provides all DHW and central heating in mono-mode opera-
tion
– Can operate in dual-mode with a second heat source, e.g. in
modernisation projects
&
Achieves high performance factors: – up to 4.61 to DIN EN 255 with the Vitocal 300 BW
(brine: 0 °C, flow temperature: 35 °C)
– up to 5.9 to DIN EN 255 with the Vitocal 300 WW
(groundwater: 10 °C, flow temperature: 35 °C)
&
Can cover any heating requirement all the year round
&
High operational safety, reliability and quiet running through hermetically sealed Compliant scroll compressor with dual anti­vibration mounts
&
Especially s uitable for low heating system temperatures, e.g. underfloor heating
&
Vitocal 350 with 65 °C flow temperature for use in systems with radiators used in modernisation projects
&
Weather-compensated, digital heat pump control unit CD 60 with i ntegral cooling function. Menu-guided functions with plain text support and integral diagnostic system
Vitocal 300
A Evaporator
B Condenser
C Weather-compensated, digital heat pump control unit CD 60
D Hermetically sealed Compliant scroll compressor
E Additional heat exchanger
5822 119-7 GB
VITOCAL 300/350 VIESMANN 3
Benefits
Vitocal 300 brine/water heat pump (single stage)
Vitocal 300 (single stage) Type BW 106 BW 108 BW 110 BW 113 BW 116 Output data
*
1
Rated heating output kW 6.4 8.3 10.8 14.0 16.3 Refrigerating capacity kW 5.00 6.50 8.40 10.95 12.70 Power consumption kW 1.40 1.80 2.40 3.05 3.60 Coefficient of Performance (COP) 4.57 4.61 4.50 4.59 4.53 Brine (primary) Content litre 2.3 2.8 3.7 4.7 4.7 Min. throughput
*
2
l/h 1600 2100 2700 3600 3900 Pressure dro p mbar 90 90 90 90 105 Max. inlet temperature °C 25 25 25 25 25 Min. inl et temperature °C –5 – 5 –5 –5 –5 Heating water (secondary) Content litre 1.6 2.2 2.7 3.3 3.3 Min. throughput l/h 530 700 950 1200 1400 Pressure dro p mbar 40 40 40 40 60 Max. flow temperature °C 55 55 55 55 55
Electrical values
Heat pump Rated voltage 3/N/PE 400 V/50 Hz Rated current (max.) A 4.8 6.6 7.9 10.0 13.3 Starting current A 27 14
*
3
20
*
3
23
*
3
26
*
3
Starting current (with stalled armature)
A 31.0 43.5 51.0 59.5 70.5
Fuse(slow) A 3×10 3×16 3×16 3×16 3×20 Protection IP 20 Control circuit rated voltage 230 V/50 Hz Fuse (internal) 6.3 A H (slow)
Refrigerant circuit
Refrigerant R 407 C Fill volume kg 1.9 2.2 2.6 3.1 3.4 Compressor Type Hermetically sealed scroll compressor
Dimensions
Total length mm 650 650 650 650 650 Total width mm 600 600 600 600 600 Total height mm 945 945 945 945 945
Permissible operating pressure
Brine circuit (primary) bar 4 4 4 4 4 Heating water circuit (secondary) bar 4 4 4 4 4
Connections
Primary IN and OUT R 1" 1" 1¼" 1¼" 1¼" Heating flow and return R 1" 1" 1" 1" 1" Weight kg 110 120 140 160 165
5822 119-7 GB
4 VIESMANN VITOCAL 300/350
*1
At operati ng point B0/W35 to DIN EN 255: B0 = brine inlet t emperature 0 °C/W35 = heating water outlet temperature 35 °C. For furthe r operating points, see the output diagrams.
*2
Always safeguard the min. throughput.
*3
With starting current limiter.
Specification
Vitocal 300 brine/water heat pump (two-stage)
Vitocal 300 (two-stage) Type BW 212 BW 216 BW 220 BW 226 BW 232 Output data
*
1
Rated heating output kW 12.8 16.6 21.6 28.0 32.6 Refrigerating capacity kW 10.0 13.0 16.8 21.9 25.4 Power consumption kW 2.8 3.6 4.8 6.1 7.2 Coefficient of Performance (COP) 4.56 4.60 4.49 4.57 4.51 Brine (primary) Content litre 4.6 5.6 7.4 9.4 9.4 Min. throughput
*
2
l/h 3200 4200 5400 7200 7800 Pressure dro p mbar 100 100 100 100 120 Max. inlet temperature °C 25 25 25 25 25 Min. inl et temperature °C –5 – 5 –5 –5 –5 Heating water (secondary) Content litre 3.2 4.4 5.4 6.6 6.6 Min. throughput
*
2
l/h 1100 1400 1900 2400 2800 Pressure dro p mbar 100 100 100 100 130 Max. flow temperature °C 55 55 55 55 55
Electrical values
Heat pump Rated voltage 3/N/PE 400 V/50 Hz Rated current (max.) A 9.6 13.2 15.8 20.0 26.6 Starting current (per compressor) A 27 14
*
3
20
*
3
23
*
3
26
*
3
Starting current (per compressor) (with stalled armature)
A 31.0 43.5 51.0 59.5 70.5
Fuse(slow) A 3×16 3×20 3×20 3×35 3×35 Protection IP 20 Control circuit rated voltage 230 V/50 Hz Fuse (internal) 6.3 A H (slow)
Refrigerant circuit
Refrigerant R 407C Fillvolume kg 2×1.9 2×2.2 2×2.6 2×3.1 2×3.4 Compressor Type 2 hermetically sealed scroll compressors
Dimensions
Total length mm 650 650 650 650 650 Total width mm 780 780 780 780 780 Total height mm 1245 1245 1245 1245 1245
Permiss. operating pressure
Brine circuit (primary) bar 4 4 4 4 4 Heating water circuit (secondary) bar 4 4 4 4 4
Connections
Primary IN and OUT R 1" 1¼" 1¼" 1½" 1½" Heating flow and return R 1" 1" 1" 1" 1" Weight kg 250 270 280 300 310
5822 119-7 GB
VITOCAL 300/350 VIESMANN 5
*1
At operati ng point B0/W35 to DIN EN 255: B0 = brine inlet t emperature 0 °C/W35 = heating water outlet temperature 35 °C. For furthe r operating points, see the output diagrams.
*2
Always safeguard the min. throughput.
*3
With starting current limiter.
Specification (cont.)
Vitocal 300 water/water heat pump (single stage)
Vitocal 300 (single stage) Type WW 106 WW 108 WW 110 WW 113 WW 116 Output data
*
1
Rated heating output kW 8.4 10.9 14.2 18.3 21.5 Refrigerating capacity kW 6.90 9.00 11.70 15.20 17.80 Power consumption kW 1.50 1.90 2.50 3.10 3.70 Coefficient of Performance (COP) 5.60 5.74 5.68 5.90 5.81 Groundwater (primary) Content litre 2.3 2.8 3.7 4.7 4.7 Min. throughput
*
2
l/h 1600 2100 2700 3600 3900 Pressure dro p mbar 90 90 90 90 105 Max. inlet temperature °C 25 25 25 25 25 Min. inl et temperature
at min. throughput °C 7.5 7.5 7.5 7.5 7.5at min. throughput +40 °C 6.5 6.5 6.5 6.5 6.5
Heating water (secondary) Content litre 1.6 2.2 2.7 3.3 3.3 Min. throughput
*
2
l/h 580 730 1000 1250 1500 Pressure dro p mbar 45 45 45 40 60 Max. flow temperature °C 55 55 55 55 55
Electrical values
Heat pump Rated voltage 3/N/PE 400 V/50 Hz Rated current (max.) A 4.8 6.6 7.9 10.0 13.3 Starting current A 27 14
*
3
20
*
3
23
*
3
26
*
3
Starting current (with stalled armature)
A 31.0 43.5 51.0 59.5 70.5
Fuse(slow) A 3×10 3×16 3×16 3×16 3×20 Protection IP 20 Control circuit rated voltage 230 V/50 Hz Fuse (internal) 6.3 A H (slow)
Refrigerant circuit
Refrigerant R 407 C Fill volume kg 1.9 2.2 2.6 3.1 3.4 Compressor Type Hermetically sealed scroll compressor
Dimensions
Total length mm 650 650 650 650 650 Total width mm 600 600 600 600 600 Total height mm 945 945 945 945 945
Permissible operating pressure
Groundwater circuit (primary) bar 4 4 4 4 4 Heating water circuit (secondary) bar 4 4 4 4 4 Intermediate circuit for indirect operation bar 4 4 4 4 4
Connections
Primary IN and OUT R 1" 1" 1¼" 1¼" 1¼" Heating flow and return R 1" 1" 1" 1" 1" Weight kg 110 120 140 160 165
5822 119-7 GB
6 VIESMANN VITOCAL 300/350
*1
At operati ng point W10/W35 to DIN EN 255: W10 = groundwater inlet temperature 10 °C/W35 = heating water outlet temperature 35 ° C. For furthe r operating points, see the output diagrams.
*2
Always safeguard the min. throughput.
*3
With starting current limiter.
Specification (cont.)
Vitocal 300 water/water heat pump (two-stage)
Vitocal 300 (two-stage) Type WW 212 WW 216 WW 220 WW 226 WW 232
Output data
*
1
Rated heating output kW 16.8 21.8 28.4 36.6 43.0 Refrigerating capacity kW 13.80 18.00 23.40 30.40 35.60 Power consumption kW 3.00 3.80 5.00 6.20 7.40 Coefficient of Performance (COP) 5.58 5.72 5.66 5.87 5.79 Groundwater (primary) Content litre 4.6 5.6 7.4 9.4 9.4 Min. throughput
*
2
l/h 3200 4200 5400 7200 7800 Pressure dro p mbar 100 100 110 120 120 Max. inlet temperature °C 25 25 25 25 25 Min. inl et temperature
for min. throughput °C 7.5 7.5 7.5 7.5 7.5for min. throughput +40 °C 6.5 6.5 6.5 6.5 6.5
Heating water (secondary) Content litre 3.2 4.4 5.4 6.6 6.6 Min. throughput
*
2
l/h 1160 1460 2000 2500 3000 Pressure dro p mbar 105 105 105 110 110 Max. flow temperature °C 55 55 55 55 55
Electrical values
Heat pump Rated voltage 3/N/PE 400 V/50 Hz Rated current (max.) A 9.6 13.2 15.8 20.0 26.6 Starting current (per compressor) A 27 14
*
3
20
*
3
23
*
3
26
*
3
Starting current (per compressor) A 31.0 43.5 51.0 59.5 70.5 (with stalled armature) Fuse(slow) A 3×16 3×20 3×20 3×35 3×35 Protection IP 20 Control circuit rated voltage 230 V/50 Hz Fuse (internal) 6.3 A H (slow)
Refrigerant circuit
Refrigerant R 407 C Fill volume kg 2 × 1.9 2 × 2.2 2 × 2.6 2 × 3.1 2× 3.4 Compressor Type 2 hermetically sealed scroll compressors
Dimensions
Total length mm 650 650 650 650 650 Total width mm 780 780 780 780 780 Total height mm 1245 1245 1245 1245 1245
Permissible operating pressure
Groundwater circuit (primary) bar 4 4 4 4 4 Heating water circuit (secondary) bar 4 4 4 4 4 Intermediate circuit for indirect operation
bar 4 4 4 4 4
Connections
Primary IN and OUT R 1" 1¼" 1¼" 1½" 1½" Heating flow and return R 1" 1" 1" 1" 1" Weight kg 250 270 280 310 320
5822 119-7 GB
VITOCAL 300/350 VIESMANN 7
*1
At operati ng point W10/W35 to DIN EN 255: W10 = groundwater inlet temperature 10 °C/W35 = heating water outlet temperature 35 ° C. For furthe r operating points, see the output diagrams.
*2
Always safeguard the min. throughput.
*3
With starting current limiter.
Specification (cont.)
Vitocal 350 brine/water heat pump (single stage)
Vitocal 350 (single stage) Type BWH 110 BWH 113 Output data
At operati ng point
*
1
B0/W35 B2/W55 B2/W65 B0/W35 B2/W55 B2/W65 Rated output kW 11.0 13.2 13.2 16.2 17.7 17.7 Refrigerating capacity kW 8.45 9.00 8.10 12.45 12.00 10.60 Power consumption kW 2.55 4.20 5.10 3.75 5.70 7.10 Coefficient of Performance (COP) 4.31 3.14 2.59 4.32 3.11 2.49 Brine (primary) Content litre 3.7 4.7 Min. throughput
*
2
l/h 2700 3800 Pressure dro p mbar 90 100 Max. inlet temperature °C 20 20 Min. inl et temperature °C -5 -5 Heating water (secondary) Content litre 3.3 3.3 Min. throughput
*
2
l/h 1060 1350 Pressure dro p mbar 40 35 Max. flow temperature °C 65 65
Electrical values
Heat pump Rated voltage 3/N/PE 400 V/50 Hz Rated current (max.) A 9.1 14.0 Starting current A 23
*
3
26
*
3
Starting current A 59.5 70.5 (with stalled armature) Fuse (slow) A 3 × 20 3 × 20 Protection IP 20 Control circuit rated voltage 230 V/50 Hz Fuse (internal) 6.3 A H (slow)
Refrigerant circuit
Refrigerant R 407 C Fill volume kg 2.9 3.2 Compressor Type Hermetically sealed scroll compressor with injection
Dimensions
Total length mm 650 650 Total width mm 600 600 Total height mm 945 945
Permissible operating pressure
Brine circuit (primary) bar 4 4 Heating water circuit (secondary) bar 4 4
Connections
Primary IN and OUT R 1¼" 1¼" Heating flow and return R 1" 1" Weight kg 145 165
5822 119-7 GB
8 VIESMANN VITOCAL 300/350
*1
Operating point to DIN EN 255: B0 = brine inlet temperature 0 °C/W35 = heating water outlet temperature 35 °C. Operating point: B2 = brine inlet temperature 2 °C/W35 = heating water outlet temperature 55 °C. Operating point: B2 = brine inlet temperature 2 °C/W35 = heating water outlet temperature 65 °C. For furthe r operating points, see the output diagrams.
*2
Always safeguard the min. throughput.
*3
With starting current limiter.
Specification (cont.)