Tripp Lite BP240V10RT-3U User Manual

0 (0)

Warranty

 

todayTripp

 

Registration

 

a

 

 

 

 

 

for

Lite

 

-line

 

.com/warranty

 

 

FREE

 

 

Register

.tripplite

 

 

win

 

 

 

 

 

to

 

 

 

 

 

chance www

 

 

 

 

 

product!

 

 

 

 

 

 

Owner’s Manual

Single-Phase 5kVA, 6kVA & 10kVA

True On-Line UPS Systems (Rackmount/Tower)

For all UPS system modules (power module, transformer module and battery module). Select UPS system modules may include separate instruction or warning sheets which should be used

in conjunction with this manual.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Important Safety Warnings

2

 

 

 

 

 

 

 

 

 

 

 

 

Mounting

3

 

 

 

 

 

 

 

 

 

 

 

 

Features

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection

10

 

 

 

 

 

 

 

 

 

 

 

 

Optional Connection

17

 

 

 

 

 

 

 

 

 

 

 

 

Power ON/OFF

18

 

 

 

 

 

 

 

 

 

 

 

 

Manual Bypass Operation

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

21

 

 

 

 

 

 

 

 

 

 

 

 

Storage, Service, Warranty and Insurance

24

 

 

 

 

 

 

 

 

 

 

 

 

Specifications

25

 

 

 

 

 

 

 

 

 

 

 

 

Español/Français/Русский

26/51/76

 

 

 

 

 

 

 

 

 

 

1111 W. 35th Street • Chicago, IL 60609 USA

Customer Support: (773) 869-1234 • Application Services: (773) 869-1236 • www.tripplite.com

Copyright ©2005 Tripp Lite. All rights reserved.

Important Safety Warnings

SAVE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed during the installation and maintenance of all Tripp Lite SmartOnline Rackmount/Tower UPS Systems and their batteries.

UPS Location Warnings

Install your UPS indoors, away from excess moisture or heat, direct sunlight, dust and conductive contaminants.

Install your UPS in a structurally sound area. Your UPS is extremely heavy; take care when moving and lifting the unit.

Only operate your UPS at indoor temperatures between 32° F and 104° F (between 0° C and 40° C). For best results, keep indoor temperatures between 62° F and 84° F (between 17° C and 29° C).

Leave adequate space around all sides of the UPS for proper ventilation.

Do not install the UPS near magnetic storage media, as this may result in data corruption.

UPS Connection Warnings

• The power supply for this unit must be single-phase rated in accordance with the equipment nameplate. It also must be suitably grounded.

Equipment Connection Warnings

Do not use Tripp Lite UPS Systems in life support applications in which a malfunction or failure of a Tripp Lite UPS System could cause failure or significantly alter the performance of a life support device.

Connect your UPS power module’s and/or transformer module’s grounding terminal to a grounding electrode conductor.

The UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS is not connected to an AC supply.

Maintenance Warnings

Your UPS power module, transformer module and battery module(s) do not require routine maintenance. Do not open them for any reason. There are no user-serviceable parts inside.

Battery Warnings

Do not operate your UPS without connecting it to an external battery module.

Connect only Tripp Lite battery modules (of the correct type and voltage) to your UPS power module's external battery connector.

Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions. Do not dispose of the batteries in a fire. Do not open the UPS or batteries. Do not short or bridge the battery terminals with any object. Unplug and turn off the UPS before performing battery replacement. Use tools with insulated handles. There are no user-serviceable parts inside the UPS. Battery replacement should be performed only by authorized service personnel using the same number and type of batteries (sealed Lead-Acid). The batteries are recyclable. Refer to your local codes for disposal requirements or in the USA only call 1-800- SAV-LEAD or 1-800-8-BATTERY (1-800-822-8837) or visit www.rbrc.com for recycling information. Tripp Lite offers a complete line of UPS System Replacement Battery Cartridges (R.B.C.).Visit Tripp Lite on the Web at www.tripplite.com/support/battery/index.cfm to locate the specific replacement battery for your UPS.

Fuses should be replaced only by factory authorized personnel. Blown fuses should be replaced only with fuses of the same number and type.

Service and repair should be done only by trained personnel. Prior to any service work performed on hardwired power modules, they should be turned off or manually bypassed via the transformer. Prior to any service work performed on power modules that plug directly into wall outlets, they should be turned off and unplugged. Note that potentially lethal voltages exist within this unit as long as the battery supply is connected.

Do not connect or disconnect battery module(s) while the UPS is operating from the battery supply or when the transformer module is not in bypass mode (if your UPS system includes a transformer module with a bypass switch).

During "hot-swap" battery module replacement your UPS will be unable to provide battery backup in the event of a blackout.

2

Mounting (Rack)

Mount your equipment in either a 4-post or 2-post rack or rack enclosure.The user must determine the fitness of hardware and procedures before mounting. If hardware and procedures are not suitable for your application, contact the manufacturer of your rack or rack enclosure. The procedures described in this manual are for common rack and rack enclosure types and may not be appropriate for all applications.

WARNING!

All UPS System modules are extremely heavy! Use caution while lifting and mounting! User must properly stabilize the module while lifting and mounting!

4-Post Mounting

1Connect the two segments of each shelf A using the included attached screws and wing nuts B . Leave the screws slightly loose so that the shelves can be adjusted in the next step.

2Adjust each shelf to fit your rack, then mount them in the lowest available space of your rack with the screws, nuts and washers provided C . Note that the support ledges should face inward. Tighten the wingnuts that connect the shelf segments D .

3Attach mounting ears E to the front mounting holes of your equipment F using the screws provided G . The ears should face forward.

4Using an assistant, lift your equipment and slide it onto the mounting shelves. Attach your equipment to the rack by passing the screws, nuts and washers (user-provided) H through its mounting ears and into the rack rails.

2-Post (Telecom) Mounting

To mount your equipment in a 2-post rack, you must purchase a Tripp Lite 2-Post Rackmount Installation Kit (model: 2POSTRMKIT, sold separately) for each module installed. See the Installation Kit's owner's manual for complete mounting instructions.

 

B

 

1

A

B

 

 

 

C

 

2

D

 

F

 

3

E

G

 

H

 

4

 

 

3

Mounting (Tower)

All modules can be mounted in an upright, tower position when used with optional adjustable base stands, sold separately from Tripp Lite (model #: 2-9USTAND). When mounting modules on the adjustable base stands, make sure that the power module's control panel is towards the top. Also, if you are installing a transformer module, place it between the power module and its battery module.

WARNING!

All UPS System modules are extremely heavy! Use caution while lifting and mounting! User must properly stabilize the module while lifting and mounting!

Rotate the power module’s Control Panel to view it easier while the UPS is tower mounted. Insert a small screwdriver, or other tool, in the slots on either side of the Control Panel. Pop the panel out; rotate it; and pop the panel back into place.

4

Features

There are three separate UPS system modules available from Tripp Lite (a power module, a transformer module and a battery module) used in a variety of combinations. Familiarize yourself with the location and function of the features on each module before installing and operating your UPS system. The power module is the only module which includes front panel features.

Power Module Front Panel Controls

11 10 9 8

7 6

12

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

3

4

5

1.LCD DISPLAY: This backlit (16 × 2 character) dot matrix display indicates a wide range of UPS operating conditions and diagnostic data. It also displays UPS settings and options when the UPS is in setup mode.

2.ON/MUTE BUTTON: Press this button and hold it until you hear a beep to turn the UPS system’s inverter ON. If the UPS’s battery alarm is sounding, press this button to silence it.

3.SCROLL DOWN/EXIT SETUP BUTTON: This button allows you to browse through different options and power readings on the LCD display. Momentarily pressing it causes the LCD screen to display a different power reading (see “Operation”). Pressing it and the SCROLL UP Button together puts the UPS in setup mode, where this button is used to scroll through setup options and to exit setup mode.

4.SCROLL UP/SELECT BUTTON: This button allows you to browse through different options and power readings on the LCD display. Momentarily pressing it causes the LCD screen to display a different power reading (see “Operation”). Pressing it and the SCROLL DOWN Button together puts the UPS in setup mode, where this button is used to select setup options.

5.OFF BUTTON: Press this button until you hear a beep to turn the UPS system’s inverter OFF.

6.O/P (OUTPUT) LED: This green light will illuminate to indicate your UPS is supplying AC power to connected equipment.

7.DC/AC (INVERTER) LED: This green light will illuminate to indicate the UPS’s DC/AC inverter is activated.

8.BYPASS LED: This green light will illuminate when the UPS is providing filtered mains power without engaging its converter or inverter. If this LED is lit, connected equipment will not receive battery power in the event of a blackout.

9.AC/DC (Converter) LED: This green light will illuminate to indicate the UPS’s AC/DC converter is charging the connected battery pack(s).

10.BATTERY LED: This red light will illuminate when the UPS is discharging the battery to provide connected equipment with AC power. An alarm will sound which can be silenced by pressing the ON/MUTE Button. This LED will remain lit after the alarm is silenced.

11.I/P (INPUT) LED: This green light will illuminate to indicate an AC input supply is present.

12.ACCESS SLOTS: To rotate the controls, insert a flathead screwdriver into these slots and gently lever the panel out. Taking care not to excessively twist or yank the cables connecting the controls to the rest of the UPS, turn the controls to the desired orientation and reinsert them.

5

Tripp Lite BP240V10RT-3U User Manual

Features (Rear Panel) see page 9 for feature descriptions

5kVA Power Module

7

8

9

10

6

11

12

12

3

13

14

13

 

5kVA Transformer Module

25

 

25

19

 

26

24

25

24

5kVA Battery Module*

28

* The 5kVA Power Module is shipped with a Battery Module which is not expandable; however, the Power Module is fully compatible with Tripp Lite Battery Modules which are expandable (Tripp Lite model # BP240V10RT-3U, sold separately) if extended runtime is required.

6

Features (Rear Panel) see page 9 for feature descriptions

6kVA Power Module

5

 

 

4

 

1

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

8

9

10

6

3

6kVA Transformer Module

16

15

20

19

17

20

22

23

6kVA Battery Module*

* Expandable Battery Module (Tripp Lite model # BP240V10RT-3U) shown. Depending on the model ordered, the 6kVA Power Module may have been shipped with an expandable Battery Module (like the one shown above) or one which is not expandable. All 6kVA Power Modules, however, are fully compatible with BP240V10RT-3U Battery Modules (sold separately) if extended runtime is required.

28 27

7

Features (Rear Panel) see page 9 for feature descriptions

10kVA Power Module

6

5

4

3

 

 

 

 

 

7

 

 

 

 

8

9

10

1

2

10kVA Transformer Module

21

19

16

15

18

20

22

23

10kVA Battery Module

* Expandable Battery Module (Tripp Lite model # BP240V10RT-3U) shown. Depending on the model ordered, the 10kVA Power Module may have been shipped with an

expandable Battery Module (like the one shown above) or 28 27 one which is not expandable. All 10kVA Power Modules,

however, are fully compatible with BP240V10RT-3U Battery Modules (sold separately) if extended runtime is required.

8

Features (Rear Panel) continued

Power Module Feature Description

1.Output Terminal Block (6kVA and 10kVA models only): Use these terminals to connect your power module to your equipment or to the transformer module. Unscrew and remove the cover over the block for access.

2.Input Terminal Block (6kVA and 10kVA models only): Use these terminals to connect your power module to utility power or to the transformer module. Unscrew and remove the cover over the block for access.

3.External Battery Connector: Use this to connect one or more Tripp Lite battery modules to the power module. Remove the cover for access. The power module will not start without a connection to a charged battery module. Refer to the battery module owner’s manual for connection instructions and safety warnings.

4.AC Input Breaker (6kVA and 10kVA models only): One double-pole circuit breaker controls input power to the power module.

5.AC Output Breaker (6kVA and 10kVA models only): One double-pole circuit breaker controls output power from the power module.

6.Exhaust Fan: This cools and ventilates the inside of the power module.

7.Accessory Slot: Remove the small cover panel to install optional accessories to remotely control and monitor your UPS system. Visit Tripp Lite on the Web (www.tripplite.com) to learn about available SNMP, network management and connectivity products that may be installed in this slot.

8.EPO (Emergency Power Off) Port: The power module features an EPO port that may be used to connect the power module to a contact closure switch to enable emergency power off. See “Optional Connection” section for details.

9.RS-232 Communication Port: This female DB9 serial port may be used to connect your UPS to a workstation or server. It uses RS-232 protocol to communicate with a connected computer. It is used with Tripp Lite software and the included serial cable to monitor and manage the UPS remotely over a network and to automatically save open files and shut down equipment during a blackout. See “Optional Connection” for details.

10.Dry Contact Interface Port: This female DB9 port sends contact-closure signals to indicate line-fail and low-battery status. See “Optional Connection” for details.

11.AC Output 1 Breaker (5kVA models only): One double-pole circuit breaker controls output power from the 5kVA power module's AC receptacles labelled "Output 1."

12.AC Output 1 Receptacles (5kVA models only): Accepts direct plug-in connection of NEMA L6-20P equipment plugs.

13.AC Output 2 Receptacles (5kVA models only): Accepts direct plug-in connection of NEMA L6-30P equipment plugs. Either receptacle also accepts direct plug-in connection of transformer connector cable (if used).

14.AC Input Cord (5kVA models only): Connects directly to wall receptacle providing 200/208/220/230 or 240V AC utility power.

Transformer Module Feature Description (Transformer Module not included with hardwire (HV) models.)

15.Utility Input Terminal Block (6kVA and 10kVA models only): Use these terminals to connect your transformer module to utility power. Unscrew and remove the cover over the block for access.

16.Equipment Output Terminal Block (6kVA and 10kVA models only): Use these terminals to connect your equipment to the transformer module. Unscrew and remove the cover over the block for access.

17.Cable for Power Module Connection (6kVA models only): Connects the transformer module to the power module’s input/output after the power module’s terminal blocks have been removed. See “Connection” section for details.

18 Hardwire Terminal Block for Power Module Connection (10kVA models only): Use these terminals to connect the transformer module to the power module’s input and output terminal blocks. See “Connection” section for details.

19.Overtemperature Reset Breaker: This circuit breaker trips if the unit’s temperature climbs too high.

20.AC to UPS Breaker (6kVA and 10kVA models only): One double-pole circuit breaker controls the transformer module’s power output to the UPS.

21.Output Breaker (6kVA and 10kVA models only): One triple-pole circuit breaker controls the transformer module’s power output to connected equipment.

22.Manual Bypass Switch (6kVA and 10kVA models only): This red and yellow dial is used to circumvent the power module while still supporting connected equipment when performing power module maintenance. While this switch is on BYPASS, connected equipment will receive filtered AC mains power from the transformer module, but the equipment will not receive battery power in the event of a blackout. See “Manual Bypass Operation” section for complete bypass procedure.

WARNING! For qualified service personnel only. Failure to follow the bypass procedure completely will not adequately power down the UPS power module, resulting in the continued risk of death or injury from potential contact with high voltage.

9

Features (Rear Panel) continued

23.Input Voltage Select Switch (6kVA and 10kVA models only): Use this switch to set the transformer module's input voltage (either 200V AC, 208V AC or 240V AC). See “Connection” section for details.

24.AC Output Receptacles (5kVA models only): Accepts direct plug-in connection of NEMA 5-15P or NEMA 5-20P equipment plugs.

25.AC Output Breakers (5kVA models only): Push-button breakers control output power to transformer module's AC Output Receptacles which are directly adjacent.

26.Cable for Power Module Connection (5kVA models only): Plugs directly into either of the 5kVA power module's AC Output 2 Receptacles. NOTE: this cable should only be plugged into the 5kVA power module.

Battery Module Feature Description

27.Input Connector (select Battery Modules only): Use this connector to daisy chain additional battery modules onto the first. Remove the cover panel for access. Refer to the battery module owner’s manual for connection instructions and safety warnings.

28.Output Cable: Use this cable to connect the battery module to the power module or to another battery module. The power module will not start without a connection to a charged battery module. Refer to the battery module owner’s manual for connection instructions and safety warnings.

Connection

Hardwiring Cautions (6kVA & 10kVA models only)

Wiring must be done by a qualified electrician.

The UPS power module may be installed on its own or connected to an isolation transformer module. Both applications require the power module to be connected to a battery module.

When making wiring connections, observe the cable connection regulations appropriate to your area [e.g. National Electrical Code (NEC) in the U.S.] at all times. Be sure to install an easily accessible disconnect switch in your installation wiring so you may cut off the UPS’s AC input during fires and other emergencies. Ensure that cables are fitted with cable sleeves and are secured by connector clamps. Tighten connections with a torque of not less than 24-28 inch-pounds (2.7-3.2 NM).

Make sure that your equipment is properly grounded.

Using cables of improper size may damage your equipment and cause fire hazards. Choose appropriate cabling and protection circuits to make wiring connections (Ground conductors must be the same size and type as the power conductors used):

 

RATED INPUT CURRENT

RATED OUTPUT CURRENT

RATED OUTPUT CURRENT

OUTPUT PROTECTION

 

200 - 240 (1Ø, 2-Wire + PE)

200 - 240V (1Ø, 2-Wire + PE)

120V (1Ø, 2-Wire + PE)

CIRCUIT

6kVA Models

30A 8 AWG (10mm2)

30A 8 AWG (10mm2)

2 × 30A 8 AWG (10mm2)

30A

10kVA Models

50A 6 AWG (16mm2)

50A 6 AWG (16mm2)

2 × 50A 6 AWG (16mm2)

63A

Connecting Modules to Each Other and to Utility Power and Equipment

There are three separate UPS system modules available from Tripp Lite (a power module and a battery module, which are required in all applications, and a transformer module) used in a variety of combinations. Follow the connection procedure below which matches the combination of modules which you plan on installing.

10

Connection continued

Connection Combination #1:

Power Module (5kVA) + Battery Module

1 Plug your equipment into the power module.

Plug your equipment power cords A directly into the power module's AC Output Receptacles B .

2 Plug the power module into a wall receptacle.

Plug the power module's AC input cord C directly into a wall receptacle D providing 200/208/220/230 or 240V AC utility power.

3 Connect the battery module to the power module.

Consult the owner's manual that came with your battery module. Fully insert the connector on the end of the battery module's cable E into the connector on the rear panel of the power module F . Small sparks may occur; this is normal. NOTE: the power module does not contain internal batteries and will not start until a battery module is connected. The battery modules are fully charged prior to shipping. However, before expecting full backup capability (particularly if the battery module has been stored for an extended period) after the UPS system is connected to a utility power source, allow the battery module to recharge for 12 hours. Once the UPS system is in use, it will charge the batteries and maintain the charge level automatically. NOTE: The 5kVA Power Module is shipped with a Battery Module which is not expandable; however, the Power Module is fully compatible with Tripp Lite Battery Modules which are expandable (Tripp Lite model # BP240V10RT-3U, sold separately) if extended runtime is required.

5kVA Power Module Shown

B

A

1

C

D

2

F

E

3

11

Connection continued

Connection Combination #2:

Power Module (5kVA) + Transformer Module (5kVA) + Battery Module

1 Plug the transformer module into the power module.

Plug the transformer module's connector cable A directly into either of the 5kVA power module's AC Output 2 Receptacles B . NOTE: this cable should only be plugged into the 5kVA power module.

2 Plug your equipment into the power module and transfer module.

Plug your 200/208/220/230/240V AC equipment power cords C directly into the power module's AC Output Receptacles D . Plug your 120V AC equipment power cords E directly into the transformer module's AC output receptacles F .

3 Plug the power module into a wall receptacle.

Plug the power module's AC input cord G directly into a wall receptacle H providing 200/208/220/230 or 240V AC utility power.

4 Connect the battery module to the power module.

Consult the owner's manual that came with your battery module. Fully insert the connector on the end of the battery module's cable I into the connector on the rear panel of the power module J . Small sparks may occur; this is normal. NOTE: the power module does not contain internal batteries and will not start until a battery module is connected. The battery modules are fully charged prior to shipping. However, before expecting full backup capability (particularly if the battery module has been stored for an extended period) after the UPS system is connected to a utility power source, allow the battery module to recharge for 12 hours. Once the UPS system is in use, it will charge the batteries and maintain the charge level automatically. NOTE: The 5kVA Power Module is shipped with a Battery Module which is not expandable; however, the Power Module is fully compatible with Tripp Lite Battery Modules which are expandable (Tripp Lite model # BP240V10RT-3U, sold separately) if extended runtime is required.

5kVA Power Module Shown

B

1

A

 

 

C

E

D

 

2

F

 

 

H

3

G

 

 

J

I

4

12

Connection continued

 

Connection Combination #3:

 

Power Module (either 6kVA or 10kVA) + Battery Module(s)

6kVA Power Module Shown

 

1 Hardwire the power module to your equipment.

Using a screwdriver, remove the top of the box A covering the power module’s input and output terminals. Pass a user-supplied cable through the terminal box’s left knockout B and connect it to the power module’s output terminals. Connect the other end of the cable to your equipment.

2 Hardwire the power module to a utility power source.

Pass a user-supplied cable through the box’s right knockout C and connect it to the power module’s input terminals. Replace the top of the terminal box. Connect the other end of the cable to a utility power source.

3 Connect the battery module to the power module.

Consult the owner’s manual that came with your battery module. Fully insert the connector on the end of the battery module’s cable D into the connector on the rear panel of the power module E . Small sparks may occur; this is normal. NOTE: the power module does not contain internal batteries and will not start until a battery module is connected. The battery modules are fully charged prior to shipping. However, before expecting full backup capability (particularly if the battery module has been stored for an extended period) after the UPS system is connected to a utility power source, allow the battery module to recharge for 12 hours. Once the UPS system is in use, it will charge the batteries and maintain the charge level automatically. If needed, connect additional battery modules in a daisy-chain with each module’s cable inserted into the previous module’s connector F .

 

A

1

B

 

C

2

E

F

D

3

13

Connection continued

Connection Combination #4:

Power Module (6kVA) + Transformer Module (6kVA) + Battery Module(s)

1 Connect the power module to the transformer module.

Using a screwdriver, remove the entire box A covering the power module’s input and output terminals. Remove the screws on either side of the terminals. Grip the terminals B and slide them out until you can view the cable connector release tab C . Press the tab down and pull on the cables to release them from the internal connector D . Remove the terminals. Insert the connector cable from the transformer module E into the internal connectors in the power module’s terminal box until the release tab clicks in place. Replace the screws around the plate. Although they are not needed, retain the power module’s terminals and terminal box cover in case you plan to operate the power module without the transformer module at a future date.

2 Hardwire the transformer module to your equipment.

Using a screwdriver, remove the top of the box F covering the transformer

module’s input and output terminals. Pass a user-supplied cable through the box’s left knockout G and connect it to the transformer module’s output terminals. See the AC Output Voltage Diagram H to determine which terminal connections will provide voltage appropriate to your application. Connect the other end of the cable to your equipment.

A

 

D

B

C

1

 

 

 

NORMAL

 

BY

 

PASS

1

E

 

F

 

NORMAL

 

BY

 

PASS

 

G

2

 

 

AC OUTPUT VOLTAGE DIAGRAM

 

 

208V

 

 

240V

 

120V

120V

 

 

G

 

H

 

3 Hardwire the transformer module to a utility

 

 

power source.

 

 

Pass a user-supplied cable through the box’s right knockout I

and connect it to

 

the transformer module’s input terminals. Replace the top of the box covering

 

the transformer module’s terminals. Connect the other end of the cable to a utility

 

power source.

 

 

 

 

NORMAL

 

 

BY

 

 

PASS

Connection Combination #4 continued on next page

3

I

 

14

Connection continued

4 Select the transformer module’s input voltage.

Using a screwdriver, remove the panel covering the transformer module’s

Input Voltage Select Switch J . Set the switch to match your facility’s input voltage. Then, use the power module’s front panel switches to configure input voltage on the LCD Display (see “Configure your UPS’s input and output” in the “Power ON/OFF” section on page 14).

IMPORTANT NOTE: if your facility’s input voltage is 200VAC, set the transformer module’s switch to 240V AC, but configure the power module to 200V AC. If your facility’s input voltage is either 208V AC or 240V AC, the transformer module and power module settings must match. The factory default settings for both modules is 208V. See chart below.

NORMAL

240V AC

 

BY

 

 

PASS

 

 

208V

AC

 

 

J

4

 

 

 

Transformer Module

Power Module

Your Facility's

Input Voltage Setting

Input Voltage Setting

Input Voltage

(Rear Panel Switch)

(Front Panel Switches/LCD Display)

240V AC

240V AC

240V AC

208V AC

208V AC

208V AC

200V AC

240V AC

200V AC

5 Connect the battery module to the power module.

Consult the owner’s manual that came with your battery module. Fully insert the connector on the end of the battery module’s cable K into the connector on the rear panel of the power module L . Small sparks may occur; this is normal. NOTE: the power module does not contain internal batteries and will not start until a battery module is connected. The battery modules are fully charged prior to shipping. However, before expecting full backup capability (particularly if the battery module has been stored for an extended period) after the UPS system is connected to a utility power source, allow the battery module to recharge for 12 hours. Once the UPS system is in use, it will charge the batteries and maintain the charge level automatically. If needed, connect additional battery modules in a daisy-chain with each module’s cable inserted into the previous module’s connector M .

L

 

K

NORMAL

5

M

 

Connection Combination #5: Power Module (10kVA) + Transformer Module (10kVA) + Battery Module(s)

1 Hardwire the power module to the transformer module.

Using a screwdriver, remove the top of the box A covering the power module’s input and output terminals. Remove the top of the box B covering the transformer module’s terminals. With supplied cable, connect the power module’s input and output terminals to the corresponding terminals on the transformer module’s “Hardwire Terminal Block for Power Module Connection” in the box’s right knockout C .

2 Hardwire the transformer module to your equipment.

Pass a user-supplied cable through the box’s left knockout D and connect it to the transformer module’s output terminals. See the AC Output Voltage Diagram E to determine which terminal connections will provide voltage appropriate to your application. Connect the other end of the cable to your equipment.

 

A

 

 

B

 

 

 

NORMAL

1

C

BY

PASS

 

 

NORMAL

 

BY

 

PASS

2

D

AC OUTPUT VOLTAGE DIAGRAM

208V

240V

120V 120V

Connection Combination #5 continued on next page

G

15

E

 

Connection continued

3 Hardwire the transformer module to a utility power source.

Pass a user-supplied cable through the box’s middle knockout F and connect it to the transformer module’s input terminals. Connect the other end of the cable to a utility power source. Replace the top of the boxes covering the power module’s and transformer module’s terminals.

4 Select the transformer module’s input voltage.

Using a screwdriver, remove the panel covering the transformer module’s Input Voltage Select Switch G . Set the switch to match your facility’s input voltage. Then, use the power module’s front panel switches to configure input voltage on the LCD Display (see “Configure your UPS's input and output” in the “Power ON/OFF” section).

IMPORTANT NOTE: if your facility's input voltage is 200VAC, set the transformer module’s switch to 240V AC, but configure the power module to 200V AC. If your facility’s input voltage is either 208V AC or 240V AC, the transformer module and power module settings must match. The factory default settings for both modules is 208V. See chart below.

 

 

NORMAL

 

 

BY

 

 

PASS

3

F

 

 

 

NORMAL

240V AC

 

BY

 

 

PASS

 

 

208V

AC

 

 

 

 

G

4

 

 

 

Transformer Module

Power Module

Your Facility’s

Input Voltage Setting

Input Voltage Setting

Input Voltage

(Rear Panel Switch)

(Front Panel Switches/LCD Display)

240V AC

240V AC

240V AC

208V AC

208V AC

208V AC

200V AC

240V AC

200V AC

5 Connect the battery module to the power module.

Consult the owner’s manual that came with your battery module. Fully insert

the connector on the end of the battery module’s cable H into the connector on the rear panel of the power module I . Small sparks may occur; this is normal. NOTE: the power module does not contain internal batteries and will not supply power to connected equipment until a battery module is connected. The battery modules are fully charged prior to shipping. However, if the battery module has been stored for an extended period, after the UPS system is connected to a utility power source, allow the battery module to recharge for 12 hours. If needed, connect additional battery modules in a daisy-chain with each module’s cable inserted into the previous module’s connector J .

I

H

5 J

16

Optional Connection

The following connections are optional. Your UPS system will function properly without these connections.

RS-232 Serial Communication Connection

Use the included cable to connect the power module’s “RS-232” port to the communication port on your computer. This will allow full network monitoring and control of your UPS system. Install on your computer the Tripp Lite PowerAlert Software appropriate to your computer’s operating system.

Contact-Closure Communication Connection

Use a user-supplied contact-closure DB9 cable to connect the power module’s “DryContact” port to the communication port on your computer or other equipment. This will allow basic contact-closure signals to be sent to and from the UPS. Refer to the following diagram and table to determine the signals carried by this port. Install on your computer the Tripp Lite PowerAlert Software appropriate to your computer’s operating system.

DRY CONTACT INTERFACE DIAGRAM

 

 

 

 

 

 

 

lm in. > 3.3 mA

 

 

 

 

 

 

 

 

 

 

LOW BATTERY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BACK-UP

REMOTE SHUTDOWN SIGNAL

 

 

 

 

 

 

FROM EXTERNAL

NO

 

 

 

 

 

 

NO

 

COM NC

 

 

 

 

 

COM

NC

 

5

9 4

8

3

7 2

6

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIGNAL FROM COMPUTER

 

 

 

 

 

 

 

 

 

>2 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12 V

MAXIMUM CAPACITY OF DRY CONTACT: AC250V/3A • DC30V/3A

 

 

 

 

 

 

 

 

 

 

0

 

DRY CONTACT INTERFACE TABLE

 

 

 

 

 

 

 

 

 

 

 

UPS Operating

Pin 8,3

Pin 1,3

Pin 6,3

 

 

 

 

Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

OPEN

OPEN

*

 

 

 

 

 

 

 

 

 

Back Up

CLOSE

*

*

 

 

 

 

 

 

 

 

 

Low Battery

CLOSE

CLOSE

*

 

 

 

 

 

 

 

 

 

Fault

*

*

CLOSE

 

 

 

 

* Inactive: may be in either state

EPO Port Connection

This optional feature is only for those applications which require connection to a facility’s Emergency Power Off (EPO) circuit. When the power module is connected to this circuit, it enables emergency shutdown of the output. Using the included cable, connect the power module’s EPO port to a user-supplied remote switch. The pin assignments for the EPO port are shown in the following diagram. Note: if there is a short between pins 2 and 3, 2 and 5, 4 and 5, or 3 and 4, the UPS system will power off.

EPO PIN ASSIGNMENT

12V

 

X

1

 

 

2

 

3

 

4

1K

5

 

X

6

 

 

 

 

 

17

Power ON/OFF (5kVA models only)

1.Configure your UPS’s input and output: Put your UPS power module into setup mode by holding down both of its scroll buttons ( A and B ) at once. Scroll through the setup options (using A or B ) and select the appropriate setting for each of the following options using the “SELECT” button B .

Input & Output Voltage: Select 200, 208 or 240 VAC.

Output Frequency: Your UPS will autoselect 50 or 60 Hz to match the input.

Economy Mode: Your UPS can provide on-line operation with zero transfer time. It can also operate in a more energy-efficient line-interactive mode. Select Economy On to put the UPS in line-interactive mode. Select Economy Off to put the UPS in on-line mode.

After you have set these options, “exit” the setup mode with the scroll button A , then exit bypass mode by holding the ON button C down until you hear a beep.

2.Turn input to the UPS ON: Press and hold the power module's ON button C until you hear a beep to start your UPS in ON BATTERY mode. Note that some electronic equipment may draw more amps during startup; when starting from battery, consider reducing the initial load on the UPS. Your UPS will perform a brief self-test and show the results on the LCD Display D . See "Startup Self-Test" in the "Operation" section for the display sequence.

3.To turn the UPS power module and transformer module (if used) OFF: Press the power module's OFF button F until you hear a beep. Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display D will show BYPASS MODE. Turn the power module's Output Breaker E OFF. Unplug the power module's AC input cord from the wall outlet. If a transformer module is used, unplug its connector cable from the power module. Your load will no longer be energized, and the LCD Display D will be dark.

E

 

 

 

 

 

 

D

C

A

B

F

5kVA Models (Front Panel)

5kVA Models

18

Power ON/OFF (6kVA and 10kVA models only)

1.Configure your UPS’s input and output: Put your UPS power module into setup mode by holding down both of its scroll buttons ( A and B ) at once. Scroll through the setup options (using A or B ) and select the appropriate setting for each of the following options using the “SELECT” button B .

Input & Output Voltage: Select 200, 208 or 240 VAC.

Output Frequency: Your UPS will autoselect 50 or 60 Hz to match the input.

Economy Mode: Your UPS can provide on-line operation with zero transfer time. It can also operate in a more energy-efficient line-interactive mode. Select Economy On to put the UPS in line-interactive mode. Select Economy Off to put the UPS in on-line mode.

After you have set these options, “exit” the setup mode with the scroll button A , then exit bypass mode by holding the ON button C down until you hear a beep.

2.Turn input to the UPS ON: If the UPS power module is connected to a transformer module, turn the tranformer module’s AC-to-UPS and Output Circuit Breakers D on. Turn the UPS power module’s Input Circuit Breaker E on. Press the UPS power module’s ON button C until you hear a beep to begin inverter operation. If your AC input is not providing power normally, you may “cold start” your UPS

from battery. (Your battery must be at least partially charged for this operation to succeed.) Press and hold the ON C button until you hear a beep to start your UPS in ON BATTERY mode. Note that some electronic equipment may draw more amps during startup; when starting from battery, consider reducing the initial load on the UPS. Your UPS will perform a brief self-test and show the results on the LCD Display F . See “Startup Self-Test” in the “Operation” section for the display sequence.

3.Turn UPS output ON: Turn the UPS power module’s Output Circuit Breaker G ON. If the UPS is connected to a transformer module, turn the transformer module’s Manual Bypass Switch H from BYPASS to NORMAL and its Output Circuit Breaker ON. Your UPS will now provide power to connected equipment.

4.To turn the UPS power module and transformer module OFF: Press the UPS power module’s OFF button I until you hear a beep. Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display F will show BYPASS MODE. Turn the UPS power module’s Input and Output Circuit Breakers ( E and G ) OFF. If the UPS is connected to a transformer module, turn the transformer module’s power AC-to-UPS and Output Circuit Breakers D OFF. Your load will no longer be energized, and the LCD Display F will be dark.

G

E

 

G

D

D

 

E

 

 

 

H

H

6kVA Models

10kVA Models

 

 

 

F

C

A

B

I

6kVA & 10kVA Models (Front Panel)

19

Manual Bypass Operation (6kVA and 10kVA models

only) (for power module maintenance or replacement)

The following procedure only applies to UPS system configurations that include a 6kVA or 10kVA transformer module. The procedure details how to service or replace the power module while supplying equipment connected to the transformer module with utility power. NOTE: since the power module and battery module will be disconnected during the procedure, they will be unable to supply battery backup support to equipment connected to the transformer module in the event of a blackout.

WARNING! For qualified service personnel only. Failure to follow this procedure completely will not adequately power down the UPS power module, resulting in the continued risk of death or injury from potential contact with high voltage.

1.Disable PowerAlert Software and disconnect communication cable from the power module’s communication ports A .

2.Turn transformer module’s Bypass Switch B to “BYPASS”.

3.Press power module’s OFF Button C , if power module is powered, until a beep is heard and a “BYPASS MODE” message is displayed in the LCD panel D .

4.Turn off the transformer module's double-pole AC to UPS breaker E .

5.Turn off the power module’s double-pole input breaker F and double-pole output breaker G .

6.Disconnect battery module cable from the power module’s battery connector H .

7.FOR 10kVA POWER MODULES ONLY: Use a voltage meter to check the cable connecting the power module’s terminal blocks I to the transformer module’s terminal blocks J to ensure the power module is no longer powered. Once it is no longer powered, remove the cabling.

The power module is now safely powered down and maintenance/replacement can be performed.

G

 

G

F

A

F

A

E

NORMAL

H

I

B

H

J

E

B

6kVA Models (Rear Panel)

10kVA Models (Rear Panel)

D

C

6kVA & 10kVA Models (Front Panel)

20

Operation

Startup Self-Test

When you turn the UPS ON, it will enter Diagnostic Mode and perform a brief self-test lasting about 15 seconds. The results of the self-test are shown on the LCD screen in the sequence below.

STARTED WITH

AC INPUT

DIAGNOSTIC MODE

FREQ OUT = XXHz

DIAGNOSTIC MODE

INPUT AC OK

DIAGNOSTIC MODE

INPUT AC OK

DIAGNOSTIC MODE

BATTERY OK

DIAGNOSTIC MODE

CHARGER OK

DIAGNOSTIC MODE

AC/DC OK

DIAGNOSTIC MODE TESTING INVERTER

ONLINE MODE

LOAD = XXX% X.XXKW

COLD

START*

DIAGNOSTIC MODE

FREQ OUT = XXHz

DIAGNOSTIC MODE

INPUT AC BAD

DIAGNOSTIC MODE

INPUT AC BAD

DIAGNOSTIC MODE

BATTERY OK

DIAGNOSTIC MODE

AC/DC OK

DIAGNOSTIC MODE TESTING INVERTER

ON BATTERY MODE LOAD = XXX% X.XXKW

*Note: If the UPS is cold started, its BATTERY LED will be lit.

Failed Self-Test

If a problem is detected during the self-test, the LCD will display a error message. If your UPS displays any of the following messages in its LCD, call Tripp Lite Technical Support at (773) 869-1234 for service.

BAD BATTERY!

CALL FOR SERVICE

CHARGER FAILURE!

CALL FOR SERVICE

AC/DC FAILURE!

CALL FOR SERVICE

INVERTER FAILURE!

CALL FOR SERVICE

OUTPUT FAILURE!

CALL FOR SERVICE

FAN FAILURE!

CALL FOR SERVICE

21

Operation continued

Normal Operation

During normal operation, the first line of your LCD Display shows which operating mode your UPS is in: Online, Economy, On Battery, or Bypass.

Online mode: The UPS provides AC power while utility power is available and switches to On Battery mode instantly (zero transfer time) if AC power is interrupted.

Economy mode: The UPS provides AC power at high efficiency while utility power is available and switches to On Battery mode quickly if AC power is interrupted.

On Battery mode: The UPS provides AC power from battery backup so long as battery power lasts. It switches back to Online or Economy mode if utility power is available and shuts down if it runs out of battery power.

Bypass mode: The UPS provides AC power while utility power is available. The UPS shuts down if AC power is interrupted.

The second line of the LCD Display shows basic power conditions. Push the SCROLL buttons to browse through these basic power conditions in the sequence shown below.

XXXXMODE LOAD = XXX% X.XXKW

XXXXMODE

IN = XXXV XX.X Hz

XXXXMODE OUT = XXXV XX.X Hz

XXXXMODE BATTERY = XXXVDC

On Battery Alarm

When in the On Battery mode, the UPS power module will beep to inform you that it is using battery power to support connected equipment. If its connected batteries are at more than half capacity, it will beep every two seconds. If its connected batteries are below half capacity, it will beep twice a second. If its connected batteries are nearly depleted, the UPS power module will beep continuously.

To silence the On Battery Alarm, press the “ON/MUTE” button.

Overload Messages

When the UPS detects an output overload, its LCD will switch to the following display:

OVERLOAD!

LOAD = XXX% X.XXKW

The UPS will then begin a countdown. If the UPS is still overloaded at the end of the countdown, the UPS will automatically go to Bypass Mode to protect its inverter. The duration of the countdown varies with the severity of the overload, as follows:

 

Overload Condition

Countdown Duration

 

 

102% - 125%

1 minute

 

 

125% - 150%

30 seconds

 

>150%

Immediate

 

 

 

 

22

Operation continued

Bypass Messages

While in Bypass Mode, the UPS monitors its input voltage and passes that input power along to connected equipment. The UPS will not provide battery backup in Bypass Mode.

If the output voltage deviates from an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power to the load, and its LCD reports that output voltage was too high or too low at one time, but has returned to nominal.

 

 

BYPASS VOLTAGE

 

LCD DISPLAY

 

 

 

 

CONDITIONS

 

MESSAGES

 

 

 

 

 

 

 

 

 

 

 

>15% Higher

 

 

 

 

 

 

 

NO OUTPUT

 

 

 

 

Than Nominal

 

BYPASS AC TOO HI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

>20% Lower

 

 

 

 

 

 

 

NO OUTPUT

 

 

 

 

Than Nominal

 

BYPASS AC TOO LO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Was Too High,

 

BYPASS MODE

 

 

 

 

Now Nominal

 

BYPASS AC WAS HI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Was Too Low,

 

BYPASS MODE

 

 

 

 

Now Nominal

 

BYPASS AC WAS LO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shutdown Messages

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: During all these conditions, the “Input,” “Output” and “Bypass” LEDs will be illuminated.

 

SHUTDOWN

 

LCD DISPLAY

 

 

CONDITIONS

 

MESSAGES

 

 

 

 

 

 

 

 

 

 

 

 

Extended

 

SHUT DOWN

 

 

Overload

 

OVERLOAD XXX%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Short

 

SHUT DOWN

 

 

Circuit

 

O/P SHORT CIRCUIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote Shutdown

 

SHUT DOWN

 

 

Command (Via DB9)

 

REMOTE COMMAND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote Shutdown

 

SHUT DOWN

 

 

Command (Via EPO)

 

EMERGENCY STOP!

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Internal

 

SHUT DOWN

 

 

Faults

 

+ DC BUS HIGH

 

 

 

 

 

 

 

 

 

SHUT DOWN

 

 

 

 

+ DC BUS LOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHUT DOWN

 

 

 

 

- DC BUS HIGH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHUT DOWN

 

 

 

 

- DC BUS LOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHUT DOWN

 

 

 

 

OVERTEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

23

Storage, Service, Warranty, Warranty Registration and Insurance

Storage

Before storing your UPS, turn it completely OFF. If you store your UPS for an extended period of time, recharge the UPS batteries for 4 to 6 hours once every three months. Note: after you connect the UPS to utility power, it will automatically begin charging its batteries. If you leave your UPS batteries discharged for an extended period of time, they will suffer a permanent loss of capacity.

Service

Your SmartOnline UPS System is covered by the 2-year limited warranty period described below. A variety of Extended Warranty and On-Site Service Programs are also available from Tripp Lite. For more information on service, call Tripp Lite Customer Support at (773) 869-1234.

Before returning your UPS for service, follow these steps:

1.Review the installation and operation instructions in this manual to ensure that the service problem does not originate from a misreading of the instructions. Also, check that the UPS System's circuit breaker(s) are not tripped. This is the most common cause of service inquiries which can be easily remedied by following the resetting instructions in this manual.

2.If the problem continues, do not contact or return the UPS to the dealer. Instead, call Tripp Lite at (773) 869-1233. A service technician will ask for the UPS's model number, serial number and purchase date and will attempt to correct the problem over the phone.

3.If the problem requires service, the technician will issue you a Returned Material Authorization (RMA) number, which is required for service. They will also discuss proper packaging and shipping procedures. Any damages (direct, indirect, special, incidental or consequential) to the UPS incurred during shipment to Tripp Lite or an authorized Tripp Lite service center is not covered under warranty. UPS Systems shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation charges prepaid. Mark the RMA number on the outside of the package. If the UPS System is within the 2-year warranty period, enclose a copy of your sales receipt. Return the UPS for service using an insured carrier to the address given to you by the Tripp Lite service technician.

2-Year Limited Warranty

TRIPP LITE warrants its products including batteries to be free from defects in materials and workmanship for a period of two years from the date of initial purchase. After 90 days from the date of purchase, TRIPP LITE’s obligation under this warranty is limited to replacing parts on such defective products. To obtain service under this warranty, you must call TRIPP LITE or an authorized TRIPP LITE service center. Products must be returned to TRIPP LITE or an authorized TRIPP LITE service center with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does not apply to equipment which has been damaged by accident, negligence or misapplication or has been altered or modified in any way. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.

The warranties of all TRIPP LITE surge suppressors are null and void if they have been connected to the output of any UPS system. The warranties of all TRIPP LITE UPS Systems are null and void if a surge suppressor has been connected to its output receptacles.

EXCEPT AS PROVIDED HEREIN, TRIPP LITE MAKES NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser.

EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, TRIPP LITE is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.

The policy of TRIPP LITE is one of continuous improvement. Specifications are subject to change without notice.

FCC RADIO/TV INTERFERENCE NOTICE:

WARRANTY REGISTRATION

Visit www.tripplite.com/warranty today to register the warranty for your new Tripp Lite product. You’ll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product!*

* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.

Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy, and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. Operation of this equipment is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

The user must use shielded cables and connectors with this product. Any changes or modifications to this product not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.

Regulatory Compliance Identification Numbers

For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking name or model number of the product.

This product designed and engineered in the USA.

24

Specifications

The models listed below include a power module, one or two battery modules, and a transformer module. All models include all three types of modules, with the exception of hardwired (HV) models, which do not include transformer modules. Depending on the model ordered, the included battery module may be either expandable or nonexpandable. However, if extended runtime is required, all power modules are fully compatible with expandable Tripp Lite battery modules (Tripp Lite Model # BP240V10RT-3U, sold separately)

Model Information

Model #(s)

SU5000RT3UHV* & SU5000RT3U

SU6000RT3UHV* & SU6000RT3U

SU6000RT3UXR

SU10KRT3UHV* & SU10KRT3U

 

Package Includes:

 

 

 

 

 

Power Module

(model: SU5000RT3UPM;

(model: SU6000RT3UPM;

(model: SU6000RT3UPM;

(model: SU10KRT3UPM;

 

 

series: AGPS5124)

series: AGSU60003U)

series: AGSU60003U)

series: AGSU100003U)

 

Battery Module #1

(model: BP240V5RT2U;

(model: BP240V7RT3U;

(model: BP240V10RT-3U;

(model: BP240V10RT-3U;

 

 

series: AGBP5161)

series: AGBP240V7RT3U)

series: AGBP240V7RT3U)

series: AGBP240V7RT3U)

 

 

Non-expandable

Non-expandable

Non-expandable

EXPANDABLE

 

Battery Module #2

N/A

N/A

(model: BP240V7RT3U;

N/A

 

 

 

 

series: AGBP240V7RT3U)

 

 

 

 

 

EXPANDABLE

 

 

Transformer Module

(model: SU5000XFMRT2U;

(model: SU6000XFMRRT3U;

(model: SU6000XFMRRT3U;

(model: SU10KXFMRRT3U;

 

 

series: AGAC5125)

series: AGSM6000SDRT3U)

series: AGSM6000SDRT3U)

series: AGSM10KSDRT3U)

Approvals: All power modules (UL, cUL, NOM, CE, GOST, SASO, IRAM, FCC Class A). All battery modules except BP240V5RT2U (UL, cUL, NOM). All transformer modules (UL, cUL, NOM, FCC Class A) * Transformer module not included with hardwired (HV) models.

Input

Input Connection Type

10 ft. cord with L6-30P plug

Hardwire

Hardwire

Hardwire

Input Voltage Range

156V~276V Single Phase

156V~276V Single Phase

156V~276V Single Phase

156V~276V Single Phase

Module Input Voltage

200/208/240V AC

200/208/240V AC

200/208/240V AC

200/208/240V AC

Input Frequency

50/60 Hz ± 3 Hz

50/60 Hz ± 3 Hz

50/60 Hz ± 3 Hz

50/60 Hz ± 3 Hz

Input Current

20A

22.6A

22.6A

40A

Inrush Current

<150A

<150A

<150A

<200A

Power Factor (Full Load)

>0.97

>0.97

>0.97

>0.97

Efficiency (Full Load/On-Line)

>87%

>87%

>87%

>88%

Power Module Circuit Breaker

N/A

40A (2 pole)

40A (2 pole)

63A (2 pole)

Transformer Module Circuit Breaker

N/A

40A (2 pole)

40A (2 pole)

63A (2 pole)

 

 

 

 

 

Output

 

 

 

 

VA

5000

6000

6000

10000

Watts (Power Factor: 0.7)

3500

4200

4200

7000

Output Connection Type

4 receptacles on power module

Hardwire

Hardwire

Hardwire

 

(2 L6-20R and 2 L6-30R) &

Optional corded backplate outlet kits available: SUPDM11

 

 

12 receptacles on transformer

(SU6000RT3UHV); SUPDM12 (SU6000RT3U & SU6000RT3UXR);

 

 

module (5-15/20R)

SUPDM13 (SU6000RT3U & SU6000RT3UXR); SUPDM15

 

 

 

(SU6000RT3U & SU6000RT3UXR); SUPDM16 (SU6000RT3U

 

 

 

and SU6000RT3UXR)

 

Waveform (On-Line)

Sinewave

Sinewave

Sinewave

Sinewave

Waveform (On-Battery)

Sinewave

Sinewave

Sinewave

Sinewave

Output Voltage (RMS)

120*/200/208/240V AC

100/120/200/208/240V AC

100/120/200/208/240V AC

100/120/200/208/240V AC

Output Frequency

50/60 Hz (± 0.2 Hz on battery)

50/60 Hz (± 0.2 Hz on battery)

50/60 Hz (± 0.2 Hz on battery)

50/60 Hz (± 0.2 Hz on battery)

Voltage Regulation

±3%

±3%

±3%

±3%

Max. Harmonic Distortion

 

 

 

 

(Linear Full Load)

<3%

<3%

<3%

<3%

(Non-Linear Full Load)

<6%

<6%

<6%

<6%

Overload Capabilities

102% (continuous)

102% (continuous)

102% (continuous)

102% (continuous)

 

102%~125% (1 min.)

102%~125% (1 min.)

102%~125% (1 min.)

102%~125% (1 min.)

 

125%~150% (30 sec.)

125%~150% (30 sec.)

125%~150% (30 sec.)

125%~150% (30 sec.)

 

>150% (Immediate)

>150% (Immediate)

>150% (Immediate)

>150% (Immediate)

Short Circuit Capability

90A

90A*

90A*

160A*

Power Module Circuit Breaker

20A (2 pole)

40A

40A

63A

Transformer Module* Circuit Breaker

Four 20A (single pole)

30A (3 pole)

30A (3 pole)

63A (3 pole)

Crest Factor

3:1

3:1

3:1

3:1

* The short circuit capability at 1ø 2W 120V for the SU6000RT3U and SU6000RT3UXR is greater than 180A, and for the SU10KRT3U is greater than 320A.

Operation

On-Line Transfer Time

 

 

 

 

(Line to Battery, Battery to Line)

0 ms.

0 ms

0 ms

0 ms

Audible Noise (Full Load @ 1 m)

<50 dBA

<50 dBA

<55 dBA

<55 dBA

 

 

 

 

 

Indicators

Includes an LCD Display and LEDs (I/P (input), BATTERY, AC/DC, BYPASS DC/AC, O/P (output)).

Communications

Includes an RS-232 DB9 female connector, a dry contact DB9 female connector and an accessory slot.

Physical Specifications

Unit Dimensions (H x W x D)

 

 

 

 

Power Module

5.25 (3U) x 17.5 x 26 in.

5.25 (3U) x 17.5 x 22.5 in.

5.25 (3U) x 17.5 x 22.5 in.

5.25 (3U) x 17.5 x 22.5 in.

 

[13.4 x 44.5 x 66 cm.]

[13.4 x 44.5 x 57.2 cm.]

[13.4 x 44.5 x 57.2 cm.]

[13.4 x 44.5 x 57.2 cm.]

Transformer Module*

3.5 (2U) x 17.5 x 20.75 in.

5.25 (3U) x 17.5 x 26 in.

5.25 (3U) x 17.5 x 26 in.

5.25 (3U) x 17.5 x 26 in.

 

[8.9 x 44.5 x 52.7 cm.]

[13.4 x 44.5 x 66.1 cm.]

[13.4 x 44.5 x 66.1 cm.]

[13.4 x 44.5 x 66.1 cm.]

Battery Module #1

3.5 (2U) x 17.5 x 22.50 in.

5.25 (3U) x 17.5 x 22.5 in.

5.25 (3U) x 17.5 x 22.5 in.

5.25 (3U) x 17.5 x 22.5 in.

 

[8.9 x 44.5 x 52.7 cm.]

[13.4 x 44.5 x 57.2 cm.]

[13.4 x 44.5 x 57.2 cm.]

[13.4 x 44.5 x 57.2 cm.]

Battery Module #2 (if applicable)

N/A

N/A

5.25 (3U) x 17.5 x 22.5 in.

N/A

 

 

 

[13.4 x 44.5 x 57.2 cm.]

 

 

 

 

 

 

Shipping Weight

 

 

 

 

Power Module

58 lb. [27 kg.]

58 lb. [27 kg.]

58 lb. [27 kg.]

68 lb. [31 kg.]

Transformer Module*

60 lb. [28 kg.]

124 lb. [57 kg.]

124 lb. [57 kg.]

124 lb. [57 kg.]

Battery Module #1

138 lb. [63 kg.]

160 lb. [73 kg.]

160 lb. [73 kg.]

160 lb. [73 kg.]

Battery Module #2 (if applicable)

N/A

N/A

160 lb. [73 kg.]

N/A

* Transformer Module not included with hardwire (HV) models.

25

Manual del propietario

SmartOnlinemonofásico de 5 kVA, 6 kVA y 10 kVA

Sistemas UPS inteligentes realmente en línea (Montaje en bastidor/torre)

Para todos los módulos del sistema UPS (módulo de potencia, módulo de transformador y módulo de batería) vendidos por separado o combinados. Los módulos de sistemas UPS exclusivos pueden incluir hojas separadas de instrucciones o de advertencias que deben usarse junto con este manual.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Advertencias de seguridad

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Montaje

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Características

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conexión

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Conexión opcional

42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Encendido y apagado

43

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operación de derivación manual

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operación

46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Almacenamiento, Servicio y Garantía

49

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Especificaciones

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

English/Français/Русский

1/51/76

 

 

 

 

 

 

 

 

 

 

1111 W. 35th Street • Chicago, IL 60609 USA

Soporte al cliente: (773) 869-1234 o Servicios de aplicaciones: (773) 869-1236 o www.tripplite.com

Copyright ©2005 Tripp Lite. Todos los derechos reservados

Advertencias de seguridad importantes

GUARDE ESTAS INSTRUCCIONES. Este manual contiene importantes instrucciones y advertencias que debe seguir durante la instalación y el mantenimiento de todos los sistemas UPS SmartOnline de Tripp Lite de montaje en torre o bastidor, y sus baterías.

Advertencias sobre la ubicación del UPS

Instale su UPS bajo techo, lejos de la humedad, el calor, el polvo, la luz solar directa y los contaminantes conductores.

Instale su UPS en un área estructuralmente sólida. Su UPS es muy pesado; tenga cuidado al mover y levantar la unidad.

Sólo opere su UPS a temperaturas bajo techo entre 32° F y 104° F (entre 0° C y 40° C) Para obtener mejores resultados, mantenga las temperaturas bajo techo entre 62° F y 84° F (entre 17° C y 29° C).

Deje una cantidad adecuada de espacio alrededor de todos los lados del UPS para una adecuada ventilación.

No instale el UPS cerca de medios de almacenamiento magnético ya que puede dañar los datos.

Advertencias sobre la conexión del UPS

El suministro de alimentación eléctrica para esta unidad debe ser monofásico y debe estar de acuerdo con la placa del equipo. También debe estar puesta a tierra apropiadamente.

Advertencias sobre la conexión de equipos

No utilice un UPS de Tripp Lite para aplicaciones de soporte de vida en las que un funcionamiento defectuoso o una falla del UPS pudiera causar la falla o una alteración importante en el funcionamiento de algún dispositivo de soporte de vida.

Conecte el terminal de tierra del módulo de potencia y/o del módulo del transformador de su no-break a un conductor del electrodo de tierra.

El UPS está conectado a una fuente de energía de corriente continua (batería). Los terminales de salida pueden estar con energía cuando el UPS no está conectado a un suministro de corriente alterna.

Advertencias de mantenimiento

Los módulos de potencia, del transformador y de la batería de su no-break no requieren ningún mantenimiento de rutina. No los abra por ninguna razón. No hay partes en su interior que requieran mantenimiento por parte del usuario.

Advertencias sobre la batería

No opere su UPS sin conectarlo a un módulo de batería externa.

Sólo conecte módulos de batería Tripp Lite (del tipo y voltaje correctos) al conector de batería externa del módulo de potencia de su no-break.

Debido a que las baterías presentan un peligro de choque eléctrico y quemaduras por las altas corrientes de cortocircuito, tome las precauciones adecuadas. No deseche las baterías en un incinerador. No abra las baterías. No ponga los terminales de la batería en corto o en puente con ningún objeto. Apague y desconecte el UPS antes de reemplazar la batería. Sólo debe cambiar las baterías personal técnico debidamente capacitado. Use herramientas con mangos aislados y reemplace las baterías existentes con el mismo número y tipo de baterías nuevas (plomo-ácido selladas). Las baterías del UPS son reciclables. Consulte la reglamentación local para los requisitos de disposición de desechos; para los EE.UU. solamente consulte estas fuentes para información sobre reciclaje: 1-800- SAV-LEAD (1-800-728-5323); 1-800-8-BATTERY (1-800-822-8837); www.rbrc.com. Tripp Lite ofrece una línea completa de Cartuchos de reemplazo de batería para UPS (R.B.C.). Visite Tripp Lite en la web en www.tripplite.com/support/battery/index.cfm para localizar la batería de reemplazo específica para su UPS.

Los fusibles deben ser reemplazados sólo por personal autorizado por la fábrica. Los fusibles quemados sólo deben reemplazarse con fusibles del mismo número y tipo.

El servicio y la reparación sólo deben llevarse a cabo por personal entrenado. Antes de cualquier trabajo de servicio realizado en módulos de potencia cableados, éstos deben apagarse o ser puestos en puente manualmente mediante el transformador. Antes de cualquier trabajo de servicio realizado en módulos de potencia conectados directamente en tomas de corriente de pared, éstos deben apagarse y desconectarse. Observe que existen voltajes potencialmente fatales dentro de esta unidad mientras está conectada la alimentación a la batería.

No conecte ni desconecte los módulos de batería mientras el no-break esté operando con la alimentación de batería o cuando el módulo de transformador no esté en modo bypass (si su no-break incluye un módulo de transformador con un interruptor de bypass).

Durante un reemplazo de su banco de baterías en operación (hot-swap), su UPS no podrá proporcionar respaldo de baterías en caso de una falla del servicio eléctrico.

27

Montaje (Bastidor)

Monte su equipo en un bastidor o en una caja de bastidor de 2 o 4 postes. El usuario debe determinar la idoneidad de los materiales y accesorios así como de los procedimientos antes del montaje. Si los materiales y procedimientos no son adecuados para su aplicación, contacte con el fabricante de su bastidor. Los procedimientos descritos en este manual son para bastidores y cajas de bastidores comunes y podrían no ser apropiados para todas las aplicaciones.

¡ADVERTENCIA!

¡Todos los módulos de no-break son muy pesados! ¡Tenga cuidado al levantarlos y montarlos! ¡El usuario debe estabilizar apropiadamente el módulo al levantarlo y montarlo!

Montaje de 4 postes

1Conecte los dos segmentos de cada anaquel A usando los tornillos incluidos y las tuercas de mariposa B . Deje los tornillos ligeramente flojos de modo que los anaqueles puedan ajustarse en el siguiente paso.

2Ajuste cada anaquel para que se acomode a su bastidor y luego instálelo en el espacio más bajo disponible del bastidor con los tornillos, las tuercas y las arandelas suministradas C . Note que los bordes de apoyo deben mirar hacia adentro. Apriete las tuercas de mariposa que conectan los segmentos de los anaqueles.

3Fije las orejas de montaje E a los agujeros de montaje de la parte delantera de su equipo F usando los tornillos suministrados G . Las orejas deben mirar hacia adelante.

4Con la ayuda de otra persona levante su equipo y deslícelo en los anaqueles de montaje. Fije su equipo al bastidor pasando los tornillos, las tuercas y las arandelas (suministradas por el usuario) H a través de las orejas de montaje y dentro de los rieles del bastidor.

Montaje de 2 postes (Telecomunicaciones)

Para montar su equipo en un bastidor de 2 postes, debe comprar un kit de instalación para montaje en bastidor de 2 postes (modelo: 2POSTRMKIT, vendido por separado) para cada módulo instalado. Consulte el manual del propietario del kit de instalación para obtener completas instrucciones de montaje.

 

B

 

1

A

B

 

 

 

C

 

2

D

 

F

 

3

E

G

 

H

 

4

 

 

28

Montaje (en torre)

Todos los módulos pueden montarse en posición vertical, de torre, cuando se emplean con bases de soporte ajustables opcionales, vendidas por separado por Tripp Lite (modelo #: 2-9USTAND). Al montar módulos en las bases de soporte ajustables asegúrese que el panel de control del módulo de potencia esté hacia la parte superior. Además, si está instalando un módulo de transformador, colóquelo entre el módulo de potencia y su módulo de batería.

¡ADVERTENCIA!

¡Todos los módulos de no-break son muy pesados! ¡Tenga cuidado al levantarlos y montarlos! ¡El usuario debe estabilizar apropiadamente el módulo al levantarlo y montarlo!

Gire el panel de control del módulo de potencia para obtener mejor visibilidad mientras el UPS esté montado en torre. Introduzca un pequeño destornillador u otra herramienta en las ranuras en cualquier lado del panel de control. Saque el panel, gírelo y colóquelo en posición nuevamente.

29

Loading...
+ 67 hidden pages