- Data Brochure
D 055
Room Temperature Unit (RTU) 055
70
(21)
60
(16)
50°F
(10°C)
80 (27)
70 (21)
60 (16)
50°F (10°C)
80
(27)
The tekmar Room Temperature Unit (RTU) 055 consists of a temperature sensor and an adjustable dial
which is used to set the desired indoor temperature. The RTU 055 dial has a temperature range from 50 to
80°F (10 to 27°C). The RTU is designed to be mounted onto a standard 2'' x 4" electrical box or to be
surface mounted. A 10K temperature sensor (e.g. 071, 072, etc.) can be connected to the RTU 055 and
mounted separately from the RTU in order to provide remote temperature sensing and control. This 10K
RTU does not work with older tekmar controls that require a 2K RTU. If a greater temperature range is
required, the RTU 054 can be used.
03/97
Installation
STEP ONE
REMOVING THE FRONT COVER
To remove the front cover, grasp the cover by the top and bottom and pull it away from the RTU.
STEP TWO
MOUNTING THE RTU
• The RTU should be installed on an interior wall of the desired zone to be controlled. Do not
mount the RTU in a location that may be affected by localized heat sources or cold drafts.
It may be necessary to install a draft barrier and / or insulation behind the enclosure in order
to prevent air from blowing through the wiring hole and affecting the RTU reading.
• For surface mounting, mount the RTU directly to the wall using two #6-1” screws. The
screws are inserted through the mounting holes and must be securely fastened to the wall.
If possible, at least one of the screws should enter a wall stud.
• For mounting on an electrical box, ensure that the electrical box is properly insulated and
protected from drafts. Mount the RTU on the electrical box using the appropriate screws.
STEP THREE
WIRING THE RTU
Run 18 AWG or similar wire between the RTU and the
Com Sen-RTU
Insert the wires through the hole provided in the back of the RTU enclosure and connect them
to the
RT-Com
terminals on the RTU terminal block. Do not run the wires parallel to telephone
or power lines. If the RTU wires are located in an area with strong sources of electromagnetic
noise, shielded cable or twisted pair should be used or the wires can be run in a grounded
metal conduit.
If installing a remote temperature sensor, run 18 AWG or similar wire between the remote sensor and the RTU. Insert the wires through
the back of the RTU and connect them to the
Com-Ext
terminals on the RTU terminal block. Cut the jumper in the RTU in order to disable
the RTU's internal sensor. Run 18 AWG or similar wire between the RTU and the
wires through the back of the RTU and connect them to the
Com-RT
and the remote sensor should be approximately at the same temperature.
RRTT
ComCom
ExtExt
70
(21)
60
(16)
50°F
(10°C)
80 (27)
70 (21)
60 (16)
50°F (10°C)
terminals on the control.
Com Sen-RTU
RTU 055 Heating
terminals on the control. Insert the
terminals on the RTU terminal block. For best accuracy, the RTU
80
(27)
STEP FOUR
TESTING THE RTU
A good quality test meter capable of measuring up to 5000 kΩ ( 1 kΩ = 1000 Ω) is required to measure the sensor resistance. In addition
to this, the actual temperature must be measured with either a good quality digital thermometer or, if a thermometer is not available,
a second sensor can be placed alongside the one to be tested and the readings compared.
First measure the room temperature using the thermometer. The RTU must be disconnected from the control
before it is tested. Turn the RTU dial to 70°F (21°C). Measure the resistance of the RTU by touching the test
leads on the wires running to the RTU. Reverse the leads and measure the RTU resistance again. It is necessary
Cut for Ext
to measure the resistance through the RTU in both directions because there will be two different "Ohm" values
read by the meter. The lower “Ohm” reading is the combined resistance of the dial and the sensor, and the higher
“Ohm” reading is the resistance of the sensor alone.
Using the chart on the following page, estimate the room temperature based on the sensor only (highest)
resistance measurement. Compare the sensor temperature measurement with the thermometer reading. If the
RRTT
ComCom
70
(21)
ExtExt
sensor temperature is significantly above the thermometer reading, the wiring may be shorted, moisture may be
in the sensor or the sensor may be defective. If the sensor temperature is significantly below the thermometer
reading, there may be a broken wire, a loose connection or a defective sensor. If a defective sensor is suspected,
first measure the sensor resistance directly at the RTU terminals using the above procedure. Ensure that the RTU
is not connected to the control by removing the wires leading to the control from the RTU terminal block.
80
(27)
60
(16)
If the RTU is being used in a remote sensing application, first ensure that the jumper inside the RTU has been cut. Disconnect the RTU
from the control at the RTU terminal block. Measure the resistance through the RTU in both directions in order to determine the sensor
reading. Compare the sensor only (highest) reading with the chart below. If the RTU reads properly, the problem lies in the wiring
between the RTU and the control. If the sensor reading still differs significantly from the thermometer reading, check the remote sensor
directly. Disconnect the sensor from the RTU at the sensor. Measure the sensor's resistance and compare the value with the chart
supplied with the sensor. If the sensor reads properly, the problem lies in the wiring between the sensor and the RTU. If the sensor
reading differs significantly from the chart values, the sensor is defective.
Do not apply voltage to a Room Temperature Unit (RTU) at any time as damage to the RTU may result.
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
°F
46
48
50
52
54
STEP FIVE
°C
8
9
10
11
12
Ω
21,900
20,800
19,700
18,700
17,700
°F
56
58
60
62
64
°C
13
14
16
17
18
Ω
16,800
15,900
15,000
14,300
13,500
INSTALLING THE FRONT COVER
°F
66
68
70
72
74
°C
19
20
21
22
23
Ω
12,800
12,200
11,500
10,900
10,400
°F
76
78
80
82
84
°C
24
26
27
28
29
Ω
9,800
9,300
8,800
8,400
7,900
To install the front cover, align the cover over the front of the RTU and press firmly until the cover snaps into place. Adjust the indicator
dial to the desired temperature.
Technical Data
Room Temperature Unit (RTU) 055
Literature — D 055
Packaged weight — 0.16 lb. (72 g), Enclosure B, white PVC plastic
Dimensions — 4-1/2" H x 2-3/4" W x 7/8" D (115 x 70 x 22 mm)
Sensor — NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C), ß=3892
Setpoint range
— 50 to 80°F (10 to 27°C)
70
(21)
60
80
(16)
(27)
50°F
(10°C)
80 (27)
70 (21)
60 (16)
50°F (10°C)
Limited Warranty and Product Return Procedure
Limited Warranty
Control Systems, Inc. ("tekmar") under this warranty is limited. Please read
and understand the conditions appearing herein.
tekmar warrants each tekmar product against defects in workmanship and materials,
when the product is installed and used in compliance with tekmar's instructions. The
warranty period is for a period of twenty-four (24) months from the production date
if the product is not installed during that period, or twelve (12) months from the
documented date of installation if installed within twenty-four (24) months from the
production date, but in any event the warranty period shall not extend beyond thirtysix (36) months from the production date. During the warranty period, tekmar will,
at its discretion, either repair at no charge, exchange or give credit for the defective
product, provided the product is returned to tekmar.
The liability of tekmar shall be limited to the cost of parts and labour provided by
tekmar to correct defects in materials and / or work-manship or to the exchange of
the defective product for a replacement product or to the granting of credit limited
to the original cost of the product, at tekmar's discretion, and such repair, exchange or
credit shall be deemed to be the sole remedy available from tekmar. This warranty
does not cover the cost of the parts or labour to remove or to transport the defective
product, or to reinstall the repaired or replacement product. Returned products that
are not defective are not covered by this warranty.
This warranty does not apply if the product has been damaged by accident, abuse,
misuse, negligence, fire, Act of God, or has been damaged by modifications,
alterations or attachments made subsequent to purchase which have not been
authorized by tekmar, or if the product was not installed in compliance with the
local codes and ordinances, or if due to defective installation of the product.
The liability of tekmar Control Systems Ltd. and tekmar
tekmar Control Systems Ltd., Canada
Control Systems
tekmar Control Systems, Inc., U.S.A.
Head Office: 5100 Silver Star Road
Vernon, B.C. Canada V1B 3K4
Tel. (250) 545-7749 Fax. (250) 545-0650
Product design, software and literature are Copyright © 1997 by:
tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
The warranty applicable to a product is as set out in the statement of warranty
policy (the "Warranty") above, receipt of which is hereby acknowledged. The
liability of tekmar is limited to those obligations identified in the warranty as
obligations of tekmar. The warranty is understood to be in substitution for any
loss, costs or damages for which tekmar might otherwise be liable at law or in
equity and in particular, in lieu of any liability for fundamental breach of contract.
tekmar disclaims any responsibility for losses, expenses, inconveniences, or
any special, indirect, secondary, incidental or consequential damages arising
from ownership or use of any items subject to any claim hereunder, regardless
of whether such claim is stated in contract, tort or strict product liability.
This warranty is in lieu of all other warranties, express or implied, including,
without limitation, warranties of merchantability, fitness for a particular
purpose, durability or description of the product, its non-infringement of any
relevant patents or trademarks, and its compliance with or non-violation of
any applicable environmental, health or safety legislation. No implied warranties
shall extend beyond twenty-four (24) months from the production date.
Some states or provinces do not allow limitations on how long an implied warranty lasts,
so the above limitation may not apply to you.This warranty gives you specific legal
rights and you may also have other rights which vary from state to state or
province to province.
Product Return Procedures Products that are believed to have defects in
workmanship or materials must be returned, together with a written description of
the defect, to the tekmar representative for that territory. If the address of the
representative is not known, please request it from tekmar at the telephone number
listed below.
2
All specifications are subject to change without notice.
Printed in Canada on recycled paper.