INSTALLATION AND MAINTENANCE INSTRUCTIONS
Series
SENS-RDR |
|
3825 Ohio Avenue, St. Charles, Illinois 60174 |
|
Sensitivity Reader |
|
1-800-SENSOR2, FAX: 630-377-6495 |
|
|
www.systemsensor.com |
||
|
|
|
|
Environmental Specifications |
|
|
|
Operating Temperature Range: |
32 to 120°F (0 to 49°C) |
||
Storage Temperature Range (without batteries): |
5 to 140°F (–15 to 60°C) |
||
Operating Humidity Range: |
10 to 90% RH non-condensing |
||
|
|
|
|
Before Using |
|
onds, followed by a textual status indication (See Table |
|
The SENS-RDR sensitivity reader is a tool to measure the |
|||
1). The reader will continue to display both results for |
|||
sensitivity of i3 smoke detectors as well as 100 series con- |
|||
up to 30 minutes, or until the reader is reset. |
|||
ventional smoke detectors (only models 2151 and 2151T |
|||
Figure 1: Reader location on compatible System Sen- |
|||
manufactured after April 2006). It CANNOT be used on the |
|||
200, 300, 400, 500, or 800 Series detectors. |
|
sor smoke detectors |
|
NOTICE: This manual shall be left with the owner/user of |
POSITION SENS-RDR |
||
this equipment. |
|
AT AN ANGLE ON THE |
|
|
OVAL AREA OR AT THE |
||
IMPORTANT: Use of the SENS-RDR is designed to “...assure |
CHAMBER OPENING |
||
BY THE WORD “PAINT” |
|||
that each smoke detector is within its listed and marked |
FOR 100-SERIES |
||
DETECTORS, PLACE |
|||
sensitivity range...” per NFPA 72. The SENS-RDR CANNOT, |
THE SENS-RDR AT THE |
||
however, initiate a detector/sensor alarm. Sensitivity testing |
SMALL CIRCULAR |
||
INDENTATION NEAR |
shall not be used as a substitute for smoke entry testing. |
THE WORDS |
|
DO NOT PAINT. |
||
|
||
General Description |
|
This battery-powered device is equipped with an infrared optical interface for reading data automatically sent by the smoke detector every ten seconds. The SENS-RDR decodes the sensitivity and status data, and displays the information on its LCD display.
The SENS-RDR may be used either as a hand-held device, or with a standard threaded extension pole.
SENS-RDR Operation
1.Turn the reader on by pressing and holding the button for approximately 2 seconds until the reader sounds. The LCD will display the word “READY”. The “READY” status indicates that the SENS-RDR is ready for accepting data from an i3 Series smoke detector.
2.Place the reader by the smoke detector being tested. Position the reader at an angle on the oval area or at the chamber opening by the word “PAINT” (See Figures 1 and 2). A ledge and an anti-skid tip is provided on the reader to maintain the reader in place while it reads the sensitivity.
3.Hold the reader in this position up to 10 seconds until the reader sounds and the reader’s red LED illuminates. NOTE: If the reader does not sound after 10 seconds, verify that the reader is properly positioned, and the LCD displays “READY”.
4.The LED and sounder indicate a valid reading is received. The reader will automatically display two results. The first is a percent per foot obscuration measurement, which is displayed for approximately 3 sec-
LED
RECESSED TEST SWITCH |
S0135-01 |
Figure 2: Position Reader on compatible System Sensor smoke detectors
OR
S0227-00
NOTE: No further readings may be taken until the reader is reset.
5.To measure the sensitivity of the next detector, reset the reader by momentarily pressing the button. The LCD will again display the word “READY”. Repeat steps 2 through 4, as necessary.
6.When finished, turn off the reader by pressing and holding the button for approximately 2 seconds until the reader sounds.
D100-98-00 |
1 |
I56-1801-003 |
1-003I56 -801