System Sensor 2112-24R, 2112-24TR User Manual

0 (0)
System Sensor 2112-24R, 2112-24TR User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS

2112/24R and 2112/24TR Photoelectronic

Smoke Detectors

Figure 1. Wiring diagram for the 2112/24R and 2112/24TR detector:

POWER + TO

DETECTORS

 

 

 

+

P

 

 

 

 

 

+ W

 

 

 

 

 

R

 

 

UL LISTED

 

 

A

ALARM

 

 

 

 

A

CONTACT

 

COMPATIBLE

 

NC

NC

CONTROL

(OPTIONAL)

NC A

(OPTIONAL)

COMMON

COMMON

PANEL

RELEASING

C

U

RELEASING

 

NO

NO

 

DEVICE

NO X

DEVICE

 

 

 

INITIATING

LOOP

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

 

 

EOL POWER

 

 

SUPERVISION

 

 

RELAY (SHOWN

+

P

ENERGIZED)

+ W

A77-716 12/24V

 

R

 

A

ALARM

 

A

CONTACT

EOL RESISTOR

NC A

SPECIFIED BY

C

U

PANEL

NO X

MANUFACTURER

OPTIONAL CLASS A WIRING

A78-2336-16

Specifications

 

Diameter:

5.5 inches (140 mm)

Height (including mounting bracket):

1.7 inches (43 mm)

Weight:

6.8 oz. (190 g)

Operating Temperature Range

Model 2112/24R: 32°F to 120°F (0°C to 49°C)

 

Model 2112/24TR: 32°F to 100°F (0°C to 39°C)

Operating Humidity Range:

10% to 93% Relative Humidity, Noncondensing

Latching Alarm:

Reset by momentary power interruption

Heat Sensor (Model 2112/24TR only):

135°F Fixed Temperature Electronic Thermistor

Electrical Ratings

 

System Voltage (nominal):

12 or 24 VDC

Minimum:

10 VDC

Maximum:

35 VDC

Maximum Ripple Voltage:

30% of nom. Voltage (peak to peak)

Standby Current:

50 µA maximum

Alarm Current:

28 mA typical, 35 mA max. at 12V

 

36 mA typical, 45 mA max. at 24V

Reset Voltage:

0.8 VDC minimum

Reset Time:

0.3 seconds maximum

Start-up Time:

30 seconds maximum (after 60 sec. reset)

EOL Relay:

A77-716B, 12/24 VDC

Alarm Initiation and Auxiliary Relay:

1A @ 30 VAC

Contact Ratings, Resistive Load:

1A @ 30 VDC

D200-83-00

1

I56-1239-02R

Figure 2. Surface mounting of 2112/24R and 2112/24TR smoke detector on 312-inch and 4-inch octagonal box:

A78-2563-01

Before Installing

Please thoroughly read the System Sensor manual I56-407,

Guide for Proper Use of System Smoke Detectors, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor.

NOTICE: This manual shall be left with the owner/user of this equipment.

IMPORTANT: This detector must be tested and maintained following NFPA 72 requirements. The detector should be cleaned at least once a year.

General Description

Models 2112/24R and 2112/24TR are 4-wire photoelectronic smoke detectors that use a state-of-the-art optical sensing chamber. The 2112/24TR also provides restorable, 135˚F fixed-temperature heat detection. The 2112/24TR heat-detection unit is integrated with the photoelectronic sensor.

Installation of this detector is simplified by the use of a mounting bracket and a plug-in screw terminal block that can be prewired to the system, allowing the detector to be easily installed or removed for cleaning. The detector’s sensitivity can be tested in place using the MOD400R Test Module.

An LED on the detector provides a local visual indication of the detector’s status. If power is applied to the detector and it is functioning normally in standby within the listed sensitivity ranges, the status LED blinks every ten seconds. The LED also latches on in alarm.

If the LED stops blinking, the unit should be removed for maintenance and inspection.

Mounting

Each 2112/24R and 2112/24TR detector is supplied with a mounting bracket that permits the detector to be mounted:

1.To a single gang box, or

2.Directly to a 312 inch or 4 inch octagonal box, or

3.To a 4 inch square electrical box by using a plaster ring.

4.Directly to the ceiling using drywall anchors, if permitted by local codes and/or the authority having jurisdiction.

Tamper-resistant Feature

This detector includes a tamper-resistant feature that prevents its removal from the bracket without the use of a tool. To make the detector tamper-resistant, remove the smaller tab by breaking it at the scribed line on the tamper resistant tab on the detector mounting bracket (see Figure 3), then install the detector. To remove the detector from the bracket once it has been made tamper resistant, use a small screwdriver to depress the tamper-resistant tab, located in the slot on the mounting bracket, and turn the detector counterclockwise.

Wiring Installation Guidelines

All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of the local authority having jurisdiction. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.

The screw terminal block accepts 14 – 22 gauge wire. For best system performance, all wiring should be installed in separate grounded conduit. Do not mix fire system wiring in the same conduit as any other electrical wiring. Twisted pair may be used to provide additional protection against electrical interference.

Figure 3. 2112/24R and 2112/24TR smoke detector mounting bracket:

TAMPER SLOT (DEPRESS TAB TO REMOVE DETECTOR)

TAMPER RESISTANT TAB (CUT OFF SMALL TAB TO ACTIVATE TAMPER-RESIST FEATURE)

ALIGNMENT

ARROWS

A78-2333-04

D200-83-00

2

I56-1239-02R