INSTALLATION AND MAINTENANCE INSTRUCTIONS
M500M Monitor Module and |
|
A Division of Pittway |
M500CH Control Module |
|
3825 Ohio Avenue, St. Charles, Illinois 60174 |
|
1-800-SENSOR2, FAX: 630-377-6495 |
|
Before Installing |
|
must be placed into the barrier and attached to the junc- |
This information is included as a quick reference installation |
|
tion box (Figure 2A). The power-limited wiring must be |
guide. Refer to the control panel installation manual for detailed |
|
placed into the isolated quadrant of the module barrier |
system information. If the modules will be installed in an existing |
|
(Figure 2B). |
operational system, inform the operator and local authority that |
1. |
Install module wiring in accordance with the job drawings and |
the system will be temporarily out of service. Disconnect power |
|
appropriate wiring diagrams (Figures 3 - 9). |
to the control panel before installing the modules. |
2. |
Set the address on the module per job drawings. |
NOTICE: This manual should be left with the owner/user of this |
3. Secure module to electrical box (supplied by installer), as |
|
equipment. |
|
shown in Figure 2A. |
General Description |
Magnet Test |
|
M500M Monitor Modules provide a two-wire, or fault-tolerant, |
The monitor and control modules can be tested with a test mag- |
|
initiating circuit for normally open contact fire alarm and supervi- |
net available from System Sensor (M02-04-01, see Figure 1). The |
|
sory devices, or either normally open or normally closed security |
magnet test checks the module electronics and connections to the |
|
devices. The LED indicator can be latched on or returned to the |
control panel. Interfaced initiating and indicating devices must be |
|
normal mode by code command from the panel. Convenient rota- |
tested independently. |
|
ry decade switches are used to set the address of each module. |
|
|
M500CH Control Modules allow a compatible control panel to |
|
|
switch discrete contacts by code command. The control module |
Figure 1. Monitor and control module controls and indicators: |
|
has a status LED that can be latched on or returned to the normal |
||
mode by code command from the panel. Rotary decade switches |
|
|
are used to set the address of each module. |
|
|
The control module offers two modes of switching operation. |
|
|
As shipped, the module is configured for switching an external |
|
|
power source to notification appliances. The external power |
|
|
|
|
|
source can be a DC power supply or an audio amplifier (up to |
|
|
|
|
|
70.7 Vrms). In this mode, the module reports supervision status |
|
|
|
|
|
of the connected loads to the control panel. Load circuit status is |
|
|
|
|
|
reported as a NORMAL, OPEN, or SHORTED circuit. Two pairs of |
|
C0554-00 |
output termination points are available for fault-tolerant wiring. |
|
|
|
|
|
The second mode of switching operation allows the panel to con- |
|
|
trol one Form-C (SPDT) set of contacts. Circuit connections to the |
Figure 2A. Module mounting with barrier: |
|
contacts are not supervised by the module. This mode is enabled |
|
|
by breaking two external tabs on the module. |
|
|
Compatibility Requirements |
|
|
To insure proper operation, these modules shall be connected to |
|
|
listed compatible system control panels only. |
|
|
|
|
Figure 2B: |
Mounting M500M and M500CH Devices |
|
|
M500M and M500CH modules mount directly to 4″ square electri- |
|
|
cal boxes as shown in Figure 2A. The box must have a minimum |
|
|
depth of 21⁄8″. |
|
|
Wiring |
|
|
NOTE: All wiring must conform to applicable local codes, ordi- |
|
|
nances and regulations. When using control modules in |
|
|
nonpower limited applications, the System Sensor CB500 |
|
ISOLATED |
|
QUADRANT |
Module Barrier must be used to meet UL requirements
for the separation of power-limited and nonpower-lim-
C0485-00
ited terminals and wiring. The barrier must be inserted in a 4″x4″x21⁄8″ junction box, and the control module
C0494-00
M500-05-00 |
1 |
I56-314-14 |
M500M Monitor Module Wiring Diagrams
Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style A or B:
|
|
|
|
|
|
|
|
||
|
|
|||
|
|
|
||
|
|
|
||
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|||
|
|
|
||
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
C0573-00 |
|
|
|
|
|
Figure 4. Typical fault tolerant initiating circuit configuration, NFPA Style D:
|
|
|
|
|
|
|
|||
|
|
|
||
|
|
|||
|
|
|||
|
|
|
||
|
|
|
|
|
|
|
|
||
|
|
|
||
|
|
|
||
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
||
|
C0574-00
|
|
|
|
|
|
|
|
|
M500CH Control Module Wiring Diagrams |
|
|
|
|
|
|
|
|
Figure 5. Typical indicating circuit configuration, NFPA Style W: |
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|||
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|||
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|||
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
C0575-00 |
|
|
||
|
M500-05-00 |
2 |
I56-314-14 |