SMA MLX User Manual [en, es, fr, de]

4 (1)

SMA Solar Technology AG

Solar Inverters

MLX Series

Installation Guide / Guía de instalacíon / Guide d’installation / Installationsanleitung

www.SMA.de

Choice of Language - Selección de idioma - Choix de la langue - Sprachauswahl

Page

5

English UK

Página

40

Español

Page

78

Français

Seite

116

Deutsch

L00410644-01_2q / Rev. date: 2014-06-02

1

IMPORTANT SAFETY INSTRUCTIO...

IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS

Safety Message Types

The following symbols are used in this document:

DANGER

Indicates a potentially hazardous situation which will result in death or serious injury.

General Safety

CAUTION

This manual contains important instructions that shall be followed during installation and maintenance of the MLX inverter.

WARNING

Indicates a potentially hazardous situation which could result in death or serious injury.

NOTICE

BEFORE INSTALLATION

Check for damage to equipment and packaging. If in doubt, contact the supplier before commencing installation.

CAUTION

Indicates a potentially hazardous situation which could result in minor or moderate injury. It may also be used to alert against unsafe practices.

NOTICE

Indicates important information, including situations which may result in damage to equipment or property.

WARNING

INSTALLATION

For optimum safety, follow the steps described in this document. Keep in mind that the inverter has 2 voltagecarrying sides; the PV input and the AC grid.

DANGER

DISCONNECTING THE INVERTER

Before starting work on the inverter, switch off AC at the mains switch and PV using the PV load switch. Ensure that the inverter cannot be unintentionally reconnected. Use a voltage tester to ensure that the unit is disconnected and voltage free. The inverter can still be charged with very high voltage at hazardous levels even when it is disconnected from AC grid and solar modules. Wait at least 5 minutes following disconnection from grid and PV panels before proceeding.

L00410644-01_2q / Rev. date: 2014-06-02

IMPORTANT SAFETY INSTRUCTIO...

1 PV load switch (optional)

Illustration 1.1

WARNING

RISK OF ELECTRIC SHOCK

These servicing instructions are for use by qualified personnel only. To reduce the risk of electric shock, do not perform any servicing other than that specified in the operating instructions unless you are qualified to do so.

WARNING

The inverter is not equipped with an isolation transformer and is intended to be installed according to NFPA 70, 690.35 with an ungrounded (floating) PV array.

WARNING

Input and output circuits are isolated from the enclosure. System grounding, when required by the Canadian Electrical Code, Part I, is the responsibility of the installer.

CAUTION

All persons installing and servicing inverters must be:

Trained and authorised in general safety rules for work on electrical equipment.

NOTICE

The PV load switch can be secured in the ‘Off’ position using a padlock.

CAUTION

DC voltages up to 1000 V are present in a PV system even when the inverter is disconnected from the AC grid. Faults or inappropriate use may lead to electric arcing.

CAUTION

MAINTENANCE AND MODIFICATION

Only authorised personnel are permitted to modify the inverter. To ensure personal safety, use only original spare parts available from the supplier. If non-original spare parts are used, compliance with CE/UL guidelines in respect of electrical safety, EMC, and machine safety is not guaranteed.

WARNING

INSTALLER

Observe the National Electric Code, ANSI/NFPA 70.

Input and output circuits are isolated from the enclosure. System grounding is the responsibility of the installer.

Familiar with local requirements, rules, and regulations for the installation.

CAUTION

The inverter does not provide overcurrent protection. This must be provided by the installer. See Table 5.8.

CAUTION

The temperature of the cooling racks and components inside the inverter can exceed 70 °C/158 °F. Observe the danger of burn injury.

The inverter is to be installed so that it is not expected to be contacted by persons.

CAUTION

To reduce the risk of fire, connect only to a circuit provided with 125 A maximum branch-circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70.

NOTICE

Use 75 °C or 90 °C wire, either AWG copper or AWG aluminium. See 2.7 Cable Entry.

L00410644-01_2q / Rev. date: 2014-06-02

IMPORTANT SAFETY INSTRUCTIO...

NOTICE

The symbol for protective earth used in this manual is identified in Illustration 2.18.

The on/off symbol is identified in 3.2.2 Turn PV Load Switch On.

NOTICE

For information about ambient temperature rating, see

5.4 Installation Conditions.

NOTICE

This manual contains information about field wiring connections and torque specifications. See 5.5 Torque Specifications.

NOTICE

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by 1 or more of the following measures:

Reorient or relocate the receiving antenna.

Increase the distance between the equipment and receiver.

Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

Consult the dealer or an experienced radio/TV technician for help.

Conformity

Go to the download area at www.sma.de for information.

See also 5 Technical Data.

L00410644-01_2q / Rev. date: 2014-06-02

Contents

Contents

1 Introduction

7

1.1 Purpose of the Manual

8

1.2 Unpacking

10

1.3 Identification of Inverter

10

1.4 Installation Sequence

10

1.5 Overview of Installation Area

11

2 Installation

12

2.1 Environment and Clearances

12

2.2 Mounting the Mounting Plate

13

2.3 Mounting the Inverter

14

2.4 Removing the Inverter

15

2.5 Access to the Installation Area

15

2.6 AC Grid Connection

16

2.7 Cable Entry

17

2.8 Ethernet Connections

17

2.9 PV Connection

18

2.9.1 External String Combiners

18

2.10 Closure

19

3 Initial Setup and Start

20

3.1 User Interface

20

3.1.1 Operation Modes

20

3.2 Display

20

3.2.1 Initial Setup via LCS Tool

21

3.2.2 Turn PV Load Switch On

21

3.2.3 Start-up

21

3.3 LCS Tool

22

3.3.1 Getting Started

22

4 Service

28

4.1 Troubleshooting

28

4.2 Maintenance

30

5 Technical Data

31

5.1 Specifications

31

5.2 Trip Settings

32

5.3 Conformity

33

5.4 Installation Conditions

34

5.5 Torque Specifications

34

L00410644-01_2q / Rev. date: 2014-06-02

5

Contents

5.6 Mains Circuit Specifications

35

5.7 Auxiliary Interface Specifications

35

5.8 Ethernet Connections

36

6

L00410644-01_2q / Rev. date: 2014-06-02

Introduction

1 Introduction

1 1

The MLX inverters are designed to act exclusively as gridtied inverters for photovoltaic (PV) systems. The inverter converts DC voltage generated by a solar array into electrical AC power. The unit must be tied to the utility grid and a photovoltaic system in order to operate properly. It is not suitable for any other applications (such as a battery back-up or wind-powered systems).

The MLX system consists of 4 main components (see also

Illustration 1.1):

MLX inverter.

DC combiner.

The DC combiner makes it possible to combine the needed number of PV strings for the MLX inverter. A DC combiner is needed for each MLX inverter.

MLX Inverter Manager.

The MLX Inverter Manager is required for operating the MLX inverters. Each Inverter Manager can handle up to 42 inverters. The Inverter Manager handles all communication to the inverters. It forms a single point of interface for data accusation systems, upload to cloud services and power-plant control.

LCS Tool.

The LCS Tool is required for commissioning and servicing MLX inverters, via the Inverter Manager. The LCS Tool acts as the primary user interface for the MLX system.

L00410644-01_2q / Rev. date: 2014-06-02

7

Introduction

1 1

Illustration 1.1 System Overview

1PV array

2 DC combiner

3MLX inverter

4 MLX Inverter Manager

5LCS Tool

6 CLX portal or third party

7 Utility control

8 SCADA system

9Transformer

Table 1.1 System Overview

1.1 Purpose of the Manual

The Installation Guide provides information required to install and commission the MLX series inverter.

Additional resources available:

Inverter Manager Installation Poster, for information required to commission the MLX

inverter as well as setup of inverter communication (EU).

Inverter Manager Assembly Installation Guide, for information required to commission the MLX inverter as well as setup of inverter communication (US).

Design Guide, for information required for detailed inverter layout planning in a diversity of solar energy applications.

Fan Installation Instruction, for information required to replace a fan.

SPD Installation Instruction, for information required to replace surge protection devices.

These documents are available from the download area at www.sma.de, or from the supplier of the solar inverter.

8

L00410644-01_2q / Rev. date: 2014-06-02

Introduction

 

Abbreviation

Description

 

 

 

ANSI

American National Standards Institute

 

 

 

AWG

American Wire Gauge

1

1

 

cat5e

Category 5 twisted pair cable (enhanced)

 

DHCP

Dynamic Host Configuration Protocol

 

 

 

DNO

Distribution Network Operator

 

 

 

DSL

Digital Subscriber Line

 

 

 

EMC (Directive)

Electromagnetic Compatibility Directive

 

 

 

ESD

Electrostatic Discharge

 

 

 

FCC

Federal Communications Commission

 

 

 

FRT

Fault Ride Through

 

 

 

GSM

Global System for Mobile Communications

 

 

 

HDD

Hard Disk Drive

 

 

 

IEC

International Electrotechnical Commission

 

 

 

IT

Isolated Terra

 

 

 

LCS

Local Commissioning and Service

 

 

 

LED

Light-Emitting Diode

 

 

 

LVD (Directive)

Low Voltage Directive

 

 

 

MCB

Miniature Circuit Breaker

 

 

 

MPP

Maximum Power Point

 

 

 

MPPT

Maximum Power Point Tracking

 

 

 

NFPA

National Fire Protection Association

 

 

Illustration 1.2 MLX Inverter

P

P is the symbol for active power and is

 

 

 

 

measured in Watts (W).

 

 

 

PCB

Printed Circuit Board

 

 

 

PCC

Point of Common Coupling

 

 

 

 

The point on the public electricity network to

 

 

 

 

which other customers are, or could be,

 

 

 

 

connected.

 

 

 

PE

Protective Earth

 

 

 

PELV

Protected Extra-Low Voltage

 

 

 

PLA

Power Level Adjustment

 

 

 

PNOM

Power, Nominal conditions

 

 

 

POC

Point of Connection

 

 

 

 

The point at which the PV system is connected

 

 

 

 

to the public electricity grid.

 

 

 

PSTC

Power, Standard Test Conditions

 

 

 

PV

Photovoltaic, photovoltaic cells

 

 

 

RCD

Residual-Current Device

 

 

 

RCMU

Residual Current Monitoring Unit

 

 

 

RISO

Insulation Resistance

 

 

 

ROCOF

Rate Of Change Of Frequency

 

 

 

Q

Q is the symbol for reactive power and is

 

 

 

 

measured in reactive volt-amperes (VAr).

 

 

 

S

S is the symbol for apparent power and is

 

 

 

 

measured in volt-amperes (VA).

 

 

 

STC

Standard Test Conditions

 

 

 

SW

Software

 

 

 

THD

Total Harmonic Distortion

 

 

 

TN-S

Terra Neutral - Separate. AC Network

 

 

 

TN-C

Terra Neutral - Combined. AC Network

 

 

 

TN-C-S

Terra Neutral - Combined - Separate. AC

 

 

 

 

Network

 

 

 

TT

Terra Terra. AC Network

 

 

Table 1.2 Abbreviations

L00410644-01_2q / Rev. date: 2014-06-02

9

Introduction

 

 

1.2

Unpacking

 

 

Contents:

 

1

1

 

Inverter

 

 

 

Mounting plate

 

 

 

 

Accessories bag, containing:

 

 

 

6 wall plugs 8 x 50 mm

 

 

 

6 mounting screws 6 x 60 mm

 

 

 

1 M25 cable gland with sealing

 

 

 

 

grummet for Ethernet cables

 

 

 

2 x conduit bracket (2 in)

 

 

 

1 equipment grounding bolt M6 x 12

 

 

 

 

mm

 

 

Installation guide, booklet format

 

 

Quick guide, poster format

 

 

1.3

Identification of Inverter

1.4Installation Sequence

1.Pay special attention to the important safety instructions at the beginning of this manual.

2.Install the inverter according to 2.1 Environment and Clearances, 2.2 Mounting the Mounting Plate, and 2.3 Mounting the Inverter.

3.Open the inverter according to 2.5 Access to the Installation Area.

4.Install AC according to 2.6 AC Grid Connection.

5.Install Ethernet according to 2.8.1 Ethernet Connections.

6.Install PV according to 2.9 PV Connection.

7.Close the inverter according to 2.5 Access to the Installation Area.

8.Turn on AC.

9.Finalise commissioning by using the Local Commissioning and Service Tool (LCS Tool). The tool is available from the download area at www.sma.de. The hardware requirements for the LCS Tool are:

PC running WindowsTM 7 and onwards

150 Mb HDD

2 Gb RAM

For setup via the LCS Tool, refer to 3.3 LCS Tool.

10.Turn on PV by turning on the PV load switch. Refer to 2.9.2 Connection of PV.

11.Verify the installation by:

Inverter display: LED ‘On’ is solid green.

LCS Tool: In inverter view status is ‘On grid’.

12.The inverter is now in operation.

Illustration 1.3 Product Label, Example

The product label on the side of the inverter shows:

Inverter type.

Important specifications.

Serial number, located under the bar code, for inverter identification.

10

L00410644-01_2q / Rev. date: 2014-06-02

SMA MLX User Manual

Introduction

1.5 Overview of Installation Area

1 1

Illustration 1.4 Overview of Installation Area

PELV (Safe to touch)

2 Equipment grounding

7Ethernet interface x 2

8RS-485 interface (not in use)

Live Part

1 AC connection terminals

5PV connection terminals

Other

3 Surge Protection AC

4Surge Protection DC

6PV load switch (optional)

Table 1.3 Overview of Installation Area

L00410644-01_2q / Rev. date: 2014-06-02

11

Installation

2 Installation

2.1 Environment and Clearances

2 2

Illustration 2.6 Mount Upright on Vertical Surface. Backwards tilt of up to 10 degrees is permitted

Illustration 2.1 Avoid Constant Stream of Water

Illustration 2.7 Prevent Dust and Ammonia Gases

Illustration 2.2 Avoid Direct Sunlight

NOTICE

When planning the installation site, ensure that the inverter product label and warning labels remain visible. For details, refer to 5 Technical Data.

Illustration 2.3 Ensure Adequate Air Flow

Illustration 2.4 Ensure Adequate Air Flow

Illustration 2.5 Mount on Non-flammable Surface

12

L00410644-01_2q / Rev. date: 2014-06-02

Installation

2.2 Mounting the Mounting Plate

2 2

Illustration 2.8 Safe Clearances

NOTICE

Ensure 620 mm / 24 in base clearance for adequate airflow.

L00410644-01_2q / Rev. date: 2014-06-02

13

Installation

2 2

Illustration 2.10 Mounting the Mounting Plate

Illustration 2.9 Mounting Plate

NOTICE

Use of the mounting plate delivered with the inverter is mandatory. If the inverter is mounted without the mounting plate, the guarantee becomes void.

It is highly recommended to use all 6 mounting holes.

Mount the mounting plate:

Install in the defined environment.

Use screws and wall plugs that can safely carry the weight of the inverter.

Ensure that the mounting plate is correctly aligned.

Observe safe clearances when installing 1 or more inverters, to ensure adequate airflow. Clearances are specified in Illustration 2.8 and on the mounting plate label.

Mounting multiple inverters in a single row is recommended. Contact the supplier for guidelines when mounting inverters in more than 1 row.

Ensure adequate clearance at the front, for safe installation and service access to the inverter.

.

2.3 Mounting the Inverter

CAUTION

Refer to local health and safety regulations when handling the inverter.

Procedure:

1.Lift the inverter. Locate the slots on the side of the mounting plate. Use M12 or ½ in lifting bolts and matching nuts (not part of delivery).

Illustration 2.11 Position the inverter

14

L00410644-01_2q / Rev. date: 2014-06-02

Installation

2.4 Removing the Inverter

Procedure:

1.Perform removal in the reverse order of mounting.

2. Lift the inverter.

2

2

 

 

3.Lift and slide the inverter out of the mounting

 

 

plate slots.

Illustration 2.12 Lifting Bolts

4.

Lift the inverter free of the mounting plate.

 

2.On the inverter, position the side screws against the mounting plate slots.

3.Push the inverter as shown so the side screws slide into the 2 lower slots and the 2 upper slots. See Illustration 2.13 and Illustration 2.14.

Illustration 2.13 Slide into Slots

2.5 Access to the Installation Area

DANGER

Before starting work on the inverter, switch off AC at the mains switch and PV using the PV load switch. Ensure that the inverter cannot be unintentionally reconnected. Use a voltage tester to ensure that the unit is disconnected and voltage free. The inverter can still be charged with very high voltage at hazardous levels even when it is disconnected from AC grid and solar modules. Wait at least 5 minutes following disconnection from grid and PV panels before proceeding.

CAUTION

Observe ESD safety regulations. Discharge any electrostatic charge by touching the grounded enclosure, before handling any electronic component.

Procedure:

1.To open the cover, loosen the 3 lower front screws using a TX 30 screwdriver. The screws are captive screws and cannot fall out.

2.Lift the cover 180°. A magnet holds the cover open.

3.To close the cover, lower it into place and fasten the 3 front screws.

Illustration 2.14 Detail of Sliding into Slot

4.Check that the 4 side screws sit securely in the mounting plate slots.

5.Release the inverter.

L00410644-01_2q / Rev. date: 2014-06-02

15

Installation

2 2

Insulation Resistance Detection

The inverter has a built-in Insulation Resistance Detection / ISO circuit, which is certified according to the UL 1741 for Non-Isolated EPS Interactive PV Inverters. The Insulation Resistance Detector performs a measurement of the connected PV system resistance to ground before the inverter connects to the grid. If the resistance is below the grid code set value, the inverter will wait and re-measure the resistance after a short while. When the resistance is above the grid code set value, the inverter performs a selftest and connects to the grid.

Illustration 2.15 Loosen Front Screws and Lift Cover

2.6 AC Grid Connection

DANGER

These instructions for AC grid connection are for qualified personnel only. To reduce the risk of electric shock, do not perform any servicing other than that specified in the operating instructions unless you are qualified to do so.

CAUTION

For fuse and RCD information, refer to 5 Technical Data. AC fuse rating must not exceed the ampacity of the conductors used.

NOTICE

Wiring methods used shall be in accordance with the National Electric Code, ANSI/NFPA 70, and the Canadian Electrical Code, Part I.

Always observe local regulations.

All installers must observe the relevant wiring methods.

IMI Detection

The inverter has built-in IMI/RCMU (Insulation Monitoring Interrupter / Residual Current Monitoring Unit). Certification is according to the UL 1741 for Non-Isolated EPS Interactive PV Inverters. The IMI/RCMU circuit is 100% single fault immune. It acts on a continuous ground fault current and a sudden change in the ground fault current. This functionality is running during normal operation.

Illustration 2.16 Installation Area

Illustration 2.17 AC Cable Wire Strip

The MLX inverter must only be connected to a 3-phase grid.

16

L00410644-01_2q / Rev. date: 2014-06-02

Installation

On the AC cable, strip insulation on all 4 wires. The protective earth wire (PE) must be longer than the mains wires. See Illustration 2.17.

2.7 Cable Entry

Options for cable entry

Cable glands (premounted), or

1.Verify that the inverter rating matches the grid.

2.Ensure that main circuit breaker is released, and take precautions to prevent connection.

3.Open the front cover.

4.Insert the cable through the AC gland to the terminal blocks.

5.Connect the 3 mains wires (L1, L2, L3) and the PE wire to the terminal block with the respective markings. The PE wire is marked with the symbol shown in Illustration 2.18.

6.Optional: Make an extra PE connection at the secondary PE earthing points using the external equipment grounding bolt delivered with the inverter. See Illustration 5.2.

7.All wires must be properly fastened with the correct torque. See 5.5 Torque Specifications.

2-inch conduit adapters (supplied in accessories

bag) 2 2 If changing to the 2-inch conduit adapters, ensure to

tighten the screws in the order shown in Illustration 2.19 and Illustration 2.20. First tighten all screws with 0.75 Nm (6.5 in-lbf) and then 1.5 Nm (13 in-lbf).

Illustration 2.19 AC Mounting Bracket

Illustration 2.18 Protective Earth Symbol

 

 

 

Illustration 2.20 DC Mounting Bracket

 

 

 

 

 

Terminal

Range 1)

Max. conductor temperature rating

Conductor material

Cable jacket diameter with supplied cable gland

AC

16-95 mm2

90 ºC

Al/Cu

37-44 mm

 

6-4/0 AWG

 

 

 

 

 

 

 

 

PV

16-95 mm2

90 ºC

Al/Cu

14-21 mm

 

6-4/0 AWG

 

 

 

 

 

 

 

 

Table 2.1 Acceptable Conductor Sizes

1) Always observe current capacity of cables used.

2.8 Ethernet Connections

Before connecting Ethernet cables, refer to the requirements in 5.8 Ethernet Connections.

Procedure:

1.Do not remove the RJ-45 connector on the Ethernet cable.

2.Run the cables through the base of the inverter via cable glands. See Illustration 2.21.

3.Cut slice in rubber grummet. Place the grummet in the gland to ensure proper seal.

4.Plug into the Ethernet connector.

L00410644-01_2q / Rev. date: 2014-06-02

17

Installation

5.Fasten cables with cable ties to ensure a durable connection over time. See Illustration 2.22.

CAUTION

PV array is floating, with both the (+) and (-) conductors connected to the inverters' PV inputs. Neither conductor is to be connected to earth.

2 2 A DC load switch on either the DC combiner or inverter (optional) for safe disconnect of DC power to inverter is required.

CAUTION

Do NOT connect PV to earth!

Illustration 2.21 Run Cables Through Cable Glands

Illustration 2.22 Fasten with Cable Ties

2.9 PV Connection

2.9.1 External String Combiners

PV strings must be connected to the DC input via an external string combiner. The purpose of the string combiner is to combine the PV strings from the PV array and secure the individual strings against overcurrent.

NOTICE

Illustration 2.23 Do Not Connect PV to Earth

It is essential that all PV strings connected to the DC combiner are even in number and type of modules and tilt and orientation.

NOTICE

Observe correct fuse rating. Consult module manufacturers' manuals for information on correct string fuse rating.

Use a suitable voltmeter that can measure up to 1000 V DC. Verify the polarity and maximum voltage of the PV arrays by measuring the PV open-circuit voltage. The inverter is protected against reversed polarity and will not generate power until the polarity is correct.

The combined output from the DC combiner must be connected to the DC input of the MLX inverter.

18

L00410644-01_2q / Rev. date: 2014-06-02

Installation

2 2

Illustration 2.26 DC Label

2.10 Closure

1. Close the cover of the inverter installation area.

Illustration 2.24 DC Connection Area

Fasten the 3 front screws. See 5.5 Torque Specifications.

1.On the inverter or string combiner turn the PV load switch into off position.

2.Connect the PV cables from the external string combiner to the inverter. Ensure correct polarity, see Illustration 2.25.

3.All wires must be properly fastened with the correct torque. See 5.5 Torque Specifications.

2.Turn on AC power.

Illustration 2.25 Connect to PV Input

L00410644-01_2q / Rev. date: 2014-06-02

19

Initial Setup and Start

3 Initial Setup and Start

3.1 User Interface

The user interface comprises:

On grid (Green LED on)

#60.

The inverter is connected to the grid and energises the grid. The inverter disconnects when:

Local display, for all inverter variants. The local

3 3 display enables read-only status information of the inverter. It is not possible to configure or set up the MLX inverter via the display. The ‘#’ in the display explains the operation modes.

Local Commissioning and Service Tool (LCS Tool). The LCS Tool enables configuration of 1 or multiple MLX inverters.

3.1.1 Operation Modes

The inverter has 5 operation modes, indicated by LEDs.

Status

LEDs

 

 

 

 

Off grid

Green

- - - - - - - - - - - - - - - - -

 

 

Red

 

 

- - - - - - - - - - - - - - - - -

Connecting

Green

██████████

Red

 

 

- - - - - - - - - - - - - - - - -

On grid

Green

██████████████████

Red

 

 

- - - - - - - - - - - - - - - - -

Internal inverter event

Green

██████████

Red

 

 

- - - - - - - - - - - - - - - - -

Fail safe

Green

- - - - - - - - - - - - - - - - -

 

 

Red

██████████

 

it detects abnormal grid conditions (dependent on grid code), or

an internal event occurs, or

PV power is insufficient (no power is supplied to the grid for 10 minutes).

The inverter then enters connecting mode or off grid mode.

Internal Inverter Event (Green LED flashing)

#54.

The inverter is waiting for an internal condition to be within limits (for example a too high temperature) before it will go back on grid.

Fail Safe (Red LED flashing)

#70.

If the inverter detects an error in its circuits during the selftest (in connecting mode) or during operation, the inverter goes into fail safe mode, disconnecting from grid. The inverter will remain in fail safe mode until power has been absent for a minimum of 10 minutes, or the inverter has been shut down completely (AC+PV).

3.2 Display

Table 3.1 Operation Modes

Off grid (standby) (LEDs off)

#0-51.

When no power has been delivered to the AC grid for more than 10 minutes, the inverter disconnects from the grid and shuts down. User and communication interfaces remain powered for communication purposes.

Connecting (Green LED flashing)

#52-53.

The inverter starts up when the PV input voltage reaches the minimum DC feed-in voltage. The inverter performs a series of internal self-tests, including measurement of the resistance between the PV arrays and earth. Meanwhile, it also monitors the grid parameters. When the grid parameters have been within the specifications for the required amount of time (depends on grid code), the inverter starts to energise the grid.

NOTICE

It can take up to 10 sec. until the display activates, after power up.

The integrated display on the inverter front gives the user access to information about the PV system and the inverter.

20

L00410644-01_2q / Rev. date: 2014-06-02

Initial Setup and Start

Illustration 3.1 Overview of Display Buttons and Functionality

Key

Function

 

Adjust contrast level of display. Use

F1

arrow up/down button while holding

 

down the F1 button.

 

 

F2

 

 

 

F3

Not in use

 

 

F4

 

 

 

Home

Return to main screen

 

 

OK

Not in use

 

 

Arrow Up

A step up

 

 

Arrow Down

A step down

 

 

Arrow Right

Toggles screen right

 

 

Arrow Left

Toggles screen left

 

 

Back

Return to main screen

On - Green LED

 

Alarm - Red LED

 

Table 3.2 Overview of Display Buttons and Functionality

The screen structure is divided into 3 sections:

1.Main screen. Current and daily production. This section contains:

Actual power output (kW)

Energy counter current day (kWh)

Total energy counter (kWh)

Current date

Current time

Operation mode (#)

2.Inverter information. This section contains:

Inverter type

Inverter name

Serial no.

 

IP address

 

 

 

Inverter Manager MAC address

 

 

 

Inverter software version

 

 

3.

Actual values. This section contains:

 

 

 

PV voltage and current

 

 

 

Phase-to-phase voltages

 

 

 

Phase currents

3

3

 

Grid frequency

 

 

 

3.2.1

Initial Setup via LCS Tool

 

 

The LCS Tool makes it possible to chose from a list of predefined settings for different grids. All grid-specific limits must be configured using the LCS Tool.

After installation, check all cables and close the inverter. Turn on AC power.

WARNING

Correct selection of grid code is essential to comply with local and national standards.

3.2.2 Turn PV Load Switch On

Illustration 3.2 PV Load Switch

Turn PV load switch on, either via inverter or string combiner.

3.2.3 Start-up

The inverter starts automatically if sufficient solar irradiation is available. The start-up takes a few minutes. During this period, the inverter performs a self-test procedure.

NOTICE

The inverter is protected against reversed polarity. The inverter does not generate power until any reversed polarity is corrected.

L00410644-01_2q / Rev. date: 2014-06-02

21

Initial Setup and Start

3.3 LCS Tool

The MLX inverters and Inverter Managers must be commissioned via the Local Commissioning and Service Tool (LCS Tool). Commissioning is required before the MLX inverters can connect to the AC grid and start to convert power.

2 Gb RAM

The LCS Tool must be installed on a local PC drive. The PC must be connected to the Inverter Manager’s LAN 1 port via Ethernet.

NOTICE

The LCS Tool is available from the download area at

www.sma.de.

3 3

The hardware requirements for the LCS Tool are:

PC running WindowsTM 7 and onwards

150 Mb HDD

The Inverter Manager must have an IP address assigned by a DHCP server on the LAN 1 port.

It is important that the PC running the LCS Tool is connected to the same IP subnet as the Inverter Manager.

Port LAN 2 is intended for MLX inverters exclusively.

Illustration 3.3 Commissioning of Inverters Using LCS Tool

1

 

LCS Tool

 

several minutes before the LCS Tool has

2

 

Router/DHCP

 

identified all Inverter Managers.

3

 

MLX Inverter Manager

2.

The screen now shows a list of all Inverter

4

 

MLX inverter

 

Managers (see Illustration 3.4). To start the wizard,

5

 

LAN 2

 

click the Inverter Manager to be configured. By

6

 

LAN 1

 

clicking the Inverter Manager, the inverter(s)

 

 

 

 

discovered by the Inverter Manager are displayed.

3.3.1

Getting Started

 

Uncommissioned inverters (no grid code

 

 

 

 

assigned) are presented with a blue square

1.

 

Start up the LCS Tool. The tool displays a list of

 

together with their software version.

 

 

 

all identified Inverter Managers. It can take

22

L00410644-01_2q / Rev. date: 2014-06-02

Initial Setup and Start

3 3

Illustration 3.4 LCS Tool - Initial Screen

3.Verify that date and time are correct. If not, set date and time and continue. See Illustration 3.5.

Illustration 3.5 LCS Tool - Verify Date and Time

4.

A list of inverters identified by the selected

inverters even if not all inverters are discovered.

 

Inverter Manager is shown. See Illustration 3.6.

The undiscovered inverters can always be

 

Verify that the list of inverters is complete.

configured later.

 

Verify that all inverters are present. It is possible

 

 

to continue the configuration of the listed

 

L00410644-01_2q / Rev. date: 2014-06-02

23

Initial Setup and Start

3 3

Illustration 3.6 LCS Tool - List of Connected Inverters

5.Select the desired country from the list of options available for the inverters in the network. See

Illustration 3.7.

6.Select the desired grid code from the list of options available for the selected country. If

needed, load a custom grid code by clicking the ‘Load’ button. See Illustration 3.7. The ‘Create’ button is inactive and cannot be used.

Illustration 3.7 LCS Tool - Select Country and Grid Code

7.The LCS Tool prompts for a confirmation of the selected country and grid code. See

Illustration 3.8. Incorrect configuration can be changed using the ‘Back’ button and changing the settings in the previous windows.

24

L00410644-01_2q / Rev. date: 2014-06-02

Initial Setup and Start

3 3

Illustration 3.8 LCS Tool - Verification of Country and Grid Code

8.The system now applies the selected grid code to the Inverter Manager and the discovered inverters. Any inverter added at a later stage automatically inherits the same grid code. Only 1 grid code per Inverter Manager is possible.

9.A green square identifies the commissioned inverters. However, the inverters do not connect to grid before a ‘Start’ command is issued from the bar below the top menu. See Illustration 3.9.

NOTICE

It is essential to choose the correct grid code. The grid code cannot be changed afterwards without contacting SMA.

L00410644-01_2q / Rev. date: 2014-06-02

25

Initial Setup and Start

3 3

Illustration 3.9 LCS Tool - List of all Inverters Connected to the Inverter Manager

10.

If sufficient PV power is present and the grid

The report contains all information about inverter

 

code conditions are met, the inverters connect to

settings, including actual disconnect values for

 

the grid.

each inverter. See Illustration 3.10.

11.Upon commissioning, it is possible to download a commissioning report under the menu ‘Reports’.

Illustration 3.10 LCS Tool - Commissioning Report

26

L00410644-01_2q / Rev. date: 2014-06-02

Initial Setup and Start

NOTICE

If the desired grid code is not available, or if the LCS Tool warns about incompatible software versions, the grid code and software library must be updated on the LCS Tool.

For utility-interactive inverters, field adjustable trip limits and trip times can be altered from default settings. See

5.2 Trip Settings. After user registration and authorisation, 3 3 authorised service personnel can generate new grid code

settings at www.sma.de. The new grid code settings can be downloaded as a file and applied to the MLX inverters via the LCS Tool. These grid code files are encoded and can only be used for the particular installation.

L00410644-01_2q / Rev. date: 2014-06-02

27

Service

4 Service

4.1 Troubleshooting

The information is organised in tables showing messages appearing in the LCS Tool, known as events. The tables contain descriptions of events as well as explanations of which actions to take when an event occurs.

4

4

 

Event Type

 

Indicates whether the event relates to grid, PV, internal or fail safe issues.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ID

 

 

 

The specific event ID.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display

 

Text shown in display.

 

 

 

 

 

 

 

Description

 

Description of the event.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Action

 

 

 

Description of which action to take prior to contacting any other parties.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DNO

 

 

 

If the prescribed action has not identified the malfunction, contact the DNO for further assistance.

 

 

 

 

 

Hotline

 

 

 

If the prescribed action has not identified the malfunction, contact the inverter hotline for further assistance.

 

 

 

 

PV

 

 

 

If the prescribed action has not identified the malfunction, contact the PV supplier for further assistance.

 

 

 

 

Grid-related Events

 

 

 

 

 

 

 

 

 

ID

 

Status

 

Description

Action

DNO

Hotline

PV

 

 

 

 

 

message

 

 

 

 

 

 

 

 

 

 

1–6

 

 

 

Grid voltage too low.

Check voltage and AC installation. If the voltage is

x

-

-

 

 

 

 

 

 

 

 

 

zero, check the fuses.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7–9

 

 

 

Grid voltage average over 10 minutes

Check that the installation is correct according to

x

-

-

 

 

 

 

 

 

 

too high.

the installation guide. If so, increase the mean

 

 

 

 

 

 

 

 

 

 

 

 

voltage limit according to 3.3.1 Getting Started.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10–15

 

 

 

Grid voltage too high.

Check voltage and AC installation.

x

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16–18

 

 

 

The inverter has detected a voltage peak

Check voltage and AC installation.

x

-

-

 

 

 

 

 

 

 

on the grid.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19, 22

 

 

 

Grid frequency too low or too high.

Check grid frequency.

x

-

-

 

 

 

31–33

 

 

 

DC grid current too high.

For repeated daily occurrences, perform onsite grid

-

x

-

 

 

 

 

 

 

 

 

 

analysis.

 

 

 

 

 

 

34–37

 

 

 

Residual Current Monitoring Unit (RCMU)

Turn both DC and AC off and wait until the display

-

x

-

 

 

 

 

 

 

 

has measured an excessive current.

turns off. Then turn on DC and AC and observe if

 

 

 

 

 

 

 

 

 

 

 

 

the event reoccurs.

 

 

 

 

 

 

 

 

 

 

 

 

Visual inspection of all PV cables and modules.

 

 

 

 

 

 

40

 

AC grid not

 

The AC grid has been out of range for

Check grid frequency, grid voltage, SW version, and

x

-

-

 

 

 

 

 

OK

 

more than 10 minutes (frequency and/or

grid code setting.

 

 

 

 

 

 

 

 

 

 

voltage).

 

 

 

 

 

 

 

41–43

 

 

 

Fault ride through. The inverter has

If this event is reported several times each day,

 

 

 

 

 

 

 

 

 

 

detected that grid voltage was below or

perform onsite grid analysis.

 

 

 

 

 

 

 

 

 

 

above a certain level.

 

 

 

 

 

 

 

48, 51

 

 

 

Grid frequency too low or too high.

Check grid frequency and AC installation.

x

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54–56

 

 

 

DC grid current too high (stage 2).

For repeated daily occurrences, perform onsite grid

x

-

-

 

 

 

 

 

 

 

 

 

analysis.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

61

 

 

 

Loss of mains, open phase detected.

If the event reoccurs several times each day, contact

x

-

-

 

 

 

 

 

 

 

 

 

the DNO.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

 

 

 

Loss of mains.

If the event reoccurs several times each day, contact

x

-

-

 

 

 

 

 

 

 

 

 

the DNO.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 4.1 Grid-related Events

 

 

 

 

28

L00410644-01_2q / Rev. date: 2014-06-02

Service

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PV-related Events

 

 

 

 

 

 

 

 

 

 

 

 

ID

Status

 

Description

 

Action

DNO

Hotline

PV

 

 

 

 

 

message

 

 

 

 

 

 

 

 

 

 

 

 

103

PV current is too

 

Too many PV modules connected in

 

Check number of strings in parallel and current

-

x

x

 

 

 

 

 

high/waiting

 

parallel. Should only appear on newly

 

ratings. Has the current limit been exceeded?

 

 

 

 

 

 

 

 

 

 

 

installed systems.

 

Reconnect strings in parallel.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

115,

PV ISO too low

 

The resistance between ground and PV

 

Make a visual inspection of all PV cables and

-

x

x

 

 

 

 

260

 

 

 

is too low for the inverter to start up.

 

modules for correct installation according to the

 

 

 

 

 

 

 

 

 

 

 

This will force the inverter to make a

 

installation guide. The event could indicate that

 

 

 

 

 

 

 

 

 

 

 

new measurement after 10 minutes.

 

the PE connection is missing.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

258

PV voltage too

 

DC voltage is too high.

 

Check that PV installation and layout correspond

-

x

x

 

 

 

 

 

high/waiting

 

 

 

to recommendations in the manuals.

 

 

 

 

 

4

4

 

 

 

 

 

 

 

 

 

 

 

 

278

 

 

 

DC voltage high warning.

 

Check that PV installation and layout correspond

-

x

x

 

 

 

 

 

 

to recommendations in the manuals.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 4.2 PV-related Events

 

 

 

 

 

 

 

 

 

Internal Events

 

 

 

 

 

 

 

 

 

 

 

 

ID

 

Status

Description

 

Action

DNO

Hotline

PV

 

 

 

 

 

 

message

 

 

 

 

 

 

 

 

 

 

 

 

201–208

 

The internal temperature of the inverter is

 

Check that the inverter is not covered and

-

x

-

 

 

 

 

 

 

 

too high.

 

that the ventilation duct is not blocked.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

209, 210

 

Voltage on DC bus is too high.

 

If event persists, reset the inverter by discon-

-

x

-

 

 

 

 

 

 

 

 

 

 

 

necting DC and AC, using the switches. If the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

event is repeated, check the maximum PV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

voltage using the display to see if it is above

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the limits.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

211

 

Fan rpm low

Fan speed is too low.

 

Check if the inverter fan is blocked.

-

x

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

213–215

 

Internal error. Voltage measured before and

Call service.

-

x

-

 

 

 

 

 

 

 

after the relay differs too much.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

216–218

 

Current measured on AC side is too high.

 

Call service.

-

x

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

219–221

 

Internal error. Voltage measured before and

Call service.

-

x

-

 

 

 

 

 

 

 

after the relay differs too much.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

225–240,

 

Failure in memory/EEPROM.

 

Restart the inverter. If event persists, call

-

x

-

 

 

 

 

275

 

 

 

 

 

 

service.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

241, 242,

 

Internal communication error.

 

Restart the inverter. If event persists, call

-

x

-

 

 

 

 

245, 249

 

 

 

 

 

service.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

248

 

 

Internal CPU error.

 

Restart the inverter. If event persists, call

-

x

-

 

 

 

 

 

 

 

 

 

 

 

service.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

252–254

 

Current measured on AC side is too high.

 

If the event is repeated, call service.

-

x

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

243, 263

 

Internal error.

 

Restart the inverter. If event persists, call

-

x

-

 

 

 

 

 

 

 

 

 

 

 

service.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

279

 

 

Temperature sensor error.

 

If the event is repeated, call service.

-

x

-

 

 

 

 

280

 

 

Self-test 24-hour timeout. Self-test must run

None.

-

-

-

 

 

 

 

 

 

 

at least once per 24 hours.

 

 

 

 

 

 

 

 

 

281

 

 

Too many RCMU events during the past 24

 

Wait up to 24 hours. If event 34 also occurs,

-

x

-

 

 

 

 

 

 

 

hours.

 

follow the action for event 34.

 

 

 

 

 

 

 

 

 

 

Only 4 automatic reconnect attempts after

 

 

 

 

 

 

 

 

 

 

 

 

event 34 is allowed during a 24-hour period.

 

 

 

 

 

 

 

 

 

 

 

The inverter will automatically try to

 

 

 

 

 

 

 

 

 

 

 

 

reconnect after a certain period.

 

 

 

 

 

 

 

 

 

282

 

 

Grid code settings invalid.

 

Restart the inverter. If event persists,

-

x

-

 

 

 

 

 

 

 

 

 

 

 

reconfigure the grid code settings.

 

 

 

 

 

 

 

283

 

 

Gatedrive error.

 

Restart the inverter. If event persists, call

-

x

-

 

 

 

 

 

 

 

 

 

 

 

service.

 

 

 

 

 

 

 

L00410644-01_2q / Rev. date: 2014-06-02

29

Loading...
+ 123 hidden pages