SilentKnight SKE-ZN4 User Manual

SKE-ZN4 Zone Splitter Installation Instructions
The SKE-ZN4 is an evacuation zone splitter for use with the SKE-450. The SKE-ZN4 is capable of splitting the audio output from the main amp into four separate audio output zones or channels.
Note: Installation and wiring of this device must be done in
accordance with NFPA 72 and local ordinances.
Compatibility
The SKE-ZN4 is compatible with the SKE-450 control panel.
Mounting
3. Remove the SKE-ZN4 access plate.
4. Mount the SKE-ZN4 to the SKE-450 cabinet mounting standoffs with the 7/10” screw-in standoffs provided.
SKE-ZN4 Mounting Standoffs
Figure 2: SKE-ZN4 Mounting Standoff Locations
5. Connect wiring harness to the expansion connector on the SKE-450 and to the direct connect pins on the SKE-ZN4. See Figure 3.
Note: Speaker outputs of the SKE-450 must not be used with the
SKE-ZN4 because supervision will not be provided at the SKE-450.
1. Unlock and open the SKE-450 control panel cabinet door.
2. Open the control panel cover door by removing the two retaining screws and rotating the door to the left. See Figure 1.
SKE-ZN4 Access Plate
Control Panel Cover Retaining Screws
Control Panel Cover Door
Figure 1: SKE-450 Cabinet With Control Panel Cover In
Place
Wiring Harness
(PN 130398)
15 kΩ EOL
UL Listed
Model 7630
Figure 3: View With SKE-ZN4 Installed
SKE-
ZN4
Cover
6. Wire speaker to zone outputs as required by the installation specifications. See the Speaker Wiring section.
7. Attach the cover plate to the SKE-ZN4. See Figure 3.
P/N 151394
SKE-ZN4 Zone Splitter Installation Instructions
Speaker Wiring
Each SKE-ZN4 supplies four Notification Appliance Circuits for speaker connection. The circuits can be supervised and wired Class B (Style Y) or Class A (Style Z). Each circuit is capable of 50 watts of power.
Note: The system can support a maximum of 50 watts of power.
1. Remove the cover plate on the SKE-ZN4. See Figure 3.
2. Set the Speaker Circuit Supervision Selector to the appropriate position for Class B or Class A wiring. See Figure 4.
Figure 4: Speaker Circuit Supervision Selections
3. To wire speakers to the control panel using Class B (Style Y) supervision see Figure 5.
FACP Alarm Control Wiring
This section describes how to connect relay outputs from a FACP to control the four separate zones on the SKE-ZN4 four zone splitter.
1. Connect an active low relay or contact from the FACP to the Alarm Selects on the SKE­ZN4. See Figure 7.
Supervised
Power Limited
4.7 kΩ UL Listed EOL Model 7628
Non-Supervised Power Limited
Supervised
15 kΩ EOL
UL Listed
Model 7630
Figure 5: Class B (Style Y) Speaker Configuration
Power Limited
4. To wire speaker circuits to the control panel in a Class A (Style Z) configuration see Figure 6.
Supervised Power Limited
Must be wired within 20 feet and in conduit
Figure 7: FACP Alarm Control Outputs
Electrical Specifications
Ground Fault Impedance To Any Terminal: 0 Ω
Audio Circuit: 25 Vrms or 70.7 Vrms
Standby Input Power: 27.4 VDC @ 45 mA
Alarm Input Power: 27.4 VDC @ 250 mA
Figure 6: Class A (Style Z) Speaker Configuration
2
Maple Grove, MN 55369-4927
763-493-6455 or 800-328-0103
© 2005 Silent Knight PN 151394 Rev B
7550 Meridian Circle
Fax: 763-493-6475
www.silentknight.com
Loading...