Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
1.1How to use the documentation
The manual is part of the product and contains important information on operation and
service. The manual is written for all employees who assemble, install, startup, and
service the product.
The manual must be accessible and legible. Make sure that persons responsible for the
system and its operation, as well as persons who work independently on the unit, have
read through the manual carefully and understood it. If you ar e unclear about any of the
information in this documentation, or if you require further information, contact SEWEURODRIVE.
1.2Structure of the safety notes
1.2.1Meaning of the signal words
The following table shows the grading and meaning of the signal words for safety notes,
notes on potential risks of damage to propert y, an d ot he r no te s.
Signal wordMeaningConsequences if disregarded
DANGERImminent dangerSevere or fatal injuries
WARNINGPossible dangerous situationSevere or fatal injuries
CAUTIONPossible dangerous situationMinor injuries
NOTICEPossible damage to propertyDamage to the drive system or its
INFORMATIONUseful information or tip: Simplifies the
handling of the drive system.
environment
1.2.2Structure of section safety notes
Section safety notes do not apply to a specific action, but to several actions pertaining
to one subject. The used symbols indicate either a general or a specific hazard.
This is the formal structure of a section safety note:
SIGNAL WORD
Type and source of danger.
Possible consequence(s) if disregarded.
•Measure(s) to prevent the danger.
1.2.3Structure of embedded safety notes
Embedded safety notes are directly integrated in the instructions just before the
description of the dangerous action.
This is the formal structure of an embedded safety note:
•SIGNAL WORD Nature and source of hazard.
Possible consequence(s) if disregarded.
– Measure(s) to prevent the danger.
6
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
A requirement of fault-free operation and fulfillment of any rights to claim under limited
warranty is that you adhere to the information in the documentation. Therefore, read the
manual before you start operating the device.
Make sure that the manual is available to persons responsible for the plant and its
operation as well as to persons wh o work independently on the device. You must also
ensure that the documentation is legible.
1.4Exclusion of liability
You must observe this documentation and the documentation of the co nnected devices
from SEW-EURODRIVE to ensure safe operation and to achieve the specified product
characteristics and performance requirements. SEW-EURODRIVE assumes no liability
for injury to persons or damage to equipment or property resulting from no n-observance
of these operating instructions. In such cases, any liability for defects is excluded.
•Read through this document carefully before you commence inst allation and st artup
of the DH.21B/41B options.
The following publications and documents apply to the connected units:
•Operating instructions for the units (such as for MOVIDRIVE
MOVIAXIS
•Only electrical specialists are allowed to perform installation and startup observing
the relevant accident prevention regulations and the operating instructions of the
connected units (such units are, for example, MOVIDRIVE
MOVITRAC
•For units with functional safety, also observe the corresponding manual "Functional
Safety" or "Safe Disconnection – Conditions".
•You must adhere to the information in the documentation as a prerequisite to faultfree operation and fulfillment of warranty claims.
®
)
®
B, MOVIAXIS®).
®
B, MOVITRAC® B,
®
MDX60B/61B,
2.2Bus systems
The DH.21B and DH.41B options support various bus systems. A bus system makes it
possible to adapt frequency inverters to the particulars of the machinery within wide
limits. As with all bus systems, there is a danger of invisible, external (as far as the
inverter is concerned) modifications to the parameters which give rise to changes in the
unit behavior. This may result in unexpected, though not uncontrolled, syste m behavior.
2.3Safety functions
MOVIDRIVE® MDX60B/61B and MOVITRAC® B inverters may not perform any safety
functions without higher-level safety systems. Use higher-level safety systems to ensure
protection of equipment and personnel. For safety applications, en sure that the information in the following publications is observed: "Safe Disconnection for MOVIDRIVE
MDX60B/61B / MOVITRAC® B".
2.4Hoist applications
MOVIDRIVE® MDX60B/61B, MOVITRAC® B and MOVIAXIS® must not be used as a
safety device in hoist applications.
Use monitoring systems or mechanical protection devices as safety equipment to avoid
possible damage to property or injury to people.
®
8
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
•How to install the DH.21B/41B options in MOVIDRIVE
®
MDX61B
•Interfaces and LEDs of the DH.21B/41B options
•How to install the DH.21B/41B options in MOVIDRIVE
MOVITRAC
®
B inverters, in MOVIAXIS® servo inverters, and in stand-alone
®
MDX61B and
housings
•Engineering access to the DH.21B/41B options
•Project planning and startup of DH.21B/41B options
To be able to configure and start up the DH.21B/41B options simp ly and effectively, you
should also order the following publications in addition to this manual:
•"DHF21B/41B Controller PROFIBUS DP-V1 and DeviceNet Fieldbus Interfaces"
manual
3.2.1Freely programmable motion and logic controller (MOVI-PLC®)
The controller can be operated as freely programmable motion and logic controller
MOVI-PLC
programmable motion and logic controllers. It allows drive solutions, logic processes
and sequence controls to be automated simply and efficiently using IEC 61131-3
compliant programming languages.
•MOVI-PLC
SEW inverters and offers a simple upgrade to a more powerful MOVI-PLC
due to the fact that all possible programs can be executed.
•MOVI-PLC
advanced, etc.) and modular software concept s (libraries for numerous applications).
•MOVI-PLC
synchronous operation) and the control of demanding app lications (such as material
handling).
®
when using SD cards of the type OMH41B. MOVI-PLC® is a series of
®
is a universal solution because it is able to control the entire portfo lio of
®
is scalable due to several different hardware platforms (standard,
®
is powerful due to extensive technologies (such as electronic cam,
Introduction
®
version
3
Performance class
MOVI-PLC
standard
Performance class
MOVI-PLC
advanced
3.2.2Configurable application controller (CCU)
CCU standard
performance class
®
®
•DH.21B controllers enable coordinated single axis movements and integration of
external inputs/outputs as we ll as Drive Operator Panels (DOP). The DH.21B.. option
is therefore suitable for use as a module controller or stand-alone controller for
machines of medium complexity.
•The DH.41B controller is characterized by a great variety of interfaces and a higher
performance level, which allows complex calculations and interpolated movements,
for example. The DH.41B option is therefore suitable for the automation of cells and
machines. The integrated Ethernet interface enables direct connection of the
DH.41B controller to the control level.
The controller can be used as configurable application controller (CCU) by using SD
cards of the type OMC41B. Only standardized application modules created by
SEW-EURODRIVE can be executed. The application modules can be sta rted up quickly
and conveniently by graphical configuration. A defined process data interface provides
this functionality to a higher-level controller. A process data monitor with control mode
is available to support the startup procedure.
The "CCU standard" performance class is intended for application mod ules with singleaxis functionality and medium response times. A maximum of 16 axes can be connected
to a configurable application controller. The following application modules are available
and can be started up using the AxisConfigurator tool.
•Speed specification
•Cam positioning
•Bus positioning with 6 process data
•Single-axis universal module
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
The "CCU advanced" performance class is intended for application modules with singleaxis and multi-axis functionality and fast response times. The following application
modules are available:
•Single-axis functionality:
– Speed specification
– Cam positioning
– Bus positioning 6 process data
– Single-axis universal module
The DH.21B/41B option is equipped with numerous communication interfaces.
The two system bus interfaces CAN 1 and CAN 2 are primarily used for co nnecting and
controlling several inverters and for integrating decentralized I/O modules.
You can operate this machine module on a higher-level controller using the integrated
fieldbus interface.
An operator terminal (e.g. DOP11B) or a MOVIMOT
frequency inverter is connected to the RS485 interfaces.
SEW drives and SEW I/O modules with EtherCAT interface ca n be connected to the
PLUS®
SBUS
system bus interface.
®
gearmotor with integrated
12
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
[1] Engineering interface USB (X35) and Ethernet 2 (X37)
[2] SEW inverter with SBus interface (X32/X33)
[3] SEW inverter with EtherCAT interface (X36)
[4] 2 × RS485 interfaces (X34)
Engineering of the DH.21B/41B option includes the following activities:
•Configuration
•Parameterization
•Programming (only MOVI-PLC
These activities are carried out using the MOVITOOLS
software. The software has a number of useful features for startup an d diagnostics of all
SEW-EURODRIVE units. The DH.21B/41B option is connected with the engineering PC
®
)
®
MotionStudio engineering
via
•Ethernet communication interface (X37)
•USB interface (X35)
•Engineering channels of the fieldbus system used
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
You can use the DH.21B/41B option to control a machine module by connecting se veral
inverters via the system bus. The DH.21B/41B option controls all drives within the
machine module and in this way takes load off the higher-leve l controller (e.g. machine/
system PLC). You can connect a total of maximum 16 units to the DH.21B option, and
a total of maximum 64 units to the DH.41B option via system buses CAN 1, CAN 2,
and Ethernet 1:
®
•MOVITRAC
•MOVIDRIVE
•MOVIAXIS
•Gearmotor with integrated frequency inverter MOVIMOT
DeviceNet MFD... required)
•I/O coupler (OCC11B/OCE11B)
Connect one of the following devices each to the RS485 interfaces COM1 or COM2:
B frequency inverter
®
MDX60B/61B drive inverter
®
servo inverter
®
(Fieldbus interface
•DOP11B operator terminal
•MOVIMOT
3.3.7Ethernet 2
You can implement the following functions and connections using the Ethernet 2
communication interface:
•Connection of a DOP11B operator terminal
•PC visualization (e.g. OPC interface)
•Connection to master level
3.3.8Binary inputs and outputs
Binary inputs and outputs enable you to switch actuators (e.g. valves) and evaluate
binary input signals (e.g. sensors).
3.3.9Diagnostic LEDs
The LEDs of the DH.21B/41B options indicate the following states:
•Voltage supply of the binary inputs and outputs
•General state of the DH.21B/41B options
®
gearmotor with integrated frequency inverter
•State of the control program
•State of the fieldbus interface (DHF/DHR)
•State of the Ethernet interface
•State of both CAN interfaces
You can connect operator terminals to perform diagnostics. It is recommended to
connect an operator terminal to the communication interface Ethernet 2.
14
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
•You can insert the DH.21B/41B option in the MOVIDRIVE®MDX61B inverter. Do
not insert it in the MOVIDRIVE
•Option cards can only be installed or remove d for M OVIDRIVE
to 6.
•The installation or removal of option cards for MOVIDRIVE
inverters must only be carried out by SEW-EURODRIVE engineers.
•The installation or removal of the DH.21B/41B option in MOVIAXIS
installation of the stand-alone housing DH.21B41B/UOH..B must only be carried
out by SEW-EURODRIVE engineers.
4.2Installing the DH.21B/41B option in MOVIDRIVE®MDX61B
®
MDX60B inverter.
®
MDX61B sizes 1
®
MDX61B size 0
®
as well as the
4
•You must insert the DHE21B/DHE41B option into the fieldbus slot of
•Y ou must inser t the DHF21B/DHR21B and DHF41B/DHR41B opti ons into the expan-
4.2.1Before you start
Read the following notes before installing or removing DH.21B/41B options:
•Disconnect the inverter from power. Switch off the DC 24 V and the line voltage.
•Before touching the DH.21B/41B option, take appropriate measures (discharge
•Before installing the DH.21B/41B option, remove the keypad and the front cover.
•After installing the DH.21B/41B option, replace the front cover and the keypad.
•Keep the DH.21B/41B option in its original packaging until immediately before you
•Hold the DH.21B/41B option only by its edges. Do not touch any of the components.
•Never place the DH.21B/41B option on a conductive surface.
®
MOVIDRIVE
DHE21B/41B option into the expansion slot.
sion slot of MOVIDRIVE
size 0.
strap, conductive shoes, etc.) to protect it from electrostatic charge.
are ready to install it.
MDX61B. If the fieldbus slot is not available, you can plug the
®
MDX61B. It cannot be installed in MOVIDRIVE® MDX61B
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Installing the DH.21B/41B option in MOVIDRIVE®MDX61B
4.3Installing the DH.21B/41B option in MOVIDRIVE®MDX61B
INFORMATION
The DH.21B/41B option is installed as described in the "Installation options of DH.21B/
41B" chapter. The DH.21B/41B option is powered via MOVIDRIVE
separate voltage supply is only required for the binary inputs and outputs (connector
X31). For wiring the system bus, connect the X33 plug (CAN 1) or X32 (CAN 2) of the
DH.21B/41B option with X12 of MOVIDRIVE
®
MDX61B.
4.4Installing the DH.21B/41B option in the MOVIAXIS® master module
INFORMATION
The DH.21B/41B option is installed as described in the "Installation options of DH.21B/
41B" chapter. For wiring the system bus, connect connector X33 (CAN 1) or X32
(CAN 2) of the DH.21B/41B option with X9 (signal bus of the MOVIAXIS
module or of a MOVIAXIS
axis module). The MOVIAXIS® master module provides additional connections that
are described in the following section.
®
axis module), or with X12 (CAN 2 bus of a MOVIAXIS
®
MDX61B. A
®
supply
4
®
4.4.1Functional description of terminals X5a / X5b (MOVIAXIS® master module)
MOVIAXIS® master
module MXM
1
X5b
2
3
4
1
X5a
2
3
4
2107418379
•The terminals X5a and X5b are connected in parallel. In this way, the voltage supply
of the MOVIAXIS
DesignationTerminalFunction
X5b connector X5b:1
X5b:2
X5b:3
X5b:4
Terminal X5aX5a:1
X5a:2
X5a:3
X5a:4
®
master module can be provided from the right to X5b or from
DC 24 V
DGND
DC 24 V
BGND
DC 24 V
DGND
DC 24 V
BGND
Voltage supply for control electronics
E
Reference potential for control electronics
Voltage supply for brake
B
Reference potential for brake connection
Voltage supply for control electronics
E
Reference potential for control electronics
Voltage supply for brake
B
Reference potential for brake connection
below to X5a. With connection to X5a, further modules can be connected via X5b
(e.g. supply module, axis module). The voltage supply for the brake (X5a/b:3,4) is fed
through the MOVIAXIS
•The DH.21B/41B option can be supplied from the MOVIAXIS
®
master module.
®
supply (MXS) or from an external voltage source. To do so, connect X5 between the
individual units.
•If the DH.21B/41B option is connected with DC 24 V from the MOVIAXIS
mode power supply, the functioning of the DH.21B/41B option is maintained after
disconnection from the power supply. This is the case if the DC link voltage is
maintained or an external DC 24 V supply is present from the MOVIAXIS
mode power supply.
switched-mode power
®
switched-
®
switched-
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Installing the DH.21B/41B option in MOVITRAC® B / stand-alone unit
4.5Installing the DH.21B/41B option in MOVITRAC® B / stand-alone unit
INFORMATION
The DH.21B/41B option is installed as described in the "Installation options of DH.21B/
41B" chapter. The option card slot MOVITRAC
additional connections for the DH.21B/41B option. These connections are described
below.
The connectors X24 and X34:1/3/5 are connected in parallel. You can connect a
DOP11B operator terminal at X24. If X24 is unassigned, you can connect an operator
terminal or a gearmotor with integrated MOVIMOT
DGND
RS–
RS+
5V
CAN 1H
CAN 1L
DGND
Reserved
Reserved
DGND
DC 24 V
®
Function
Reserved
Reserved
Reference potential COM 1
Signal RS485–
Signal RS485+
Voltage output DC +5 V
System bus CAN 1 high
System bus CAN 1 low
Reference potential control/CAN1
-
Reference potential control/CAN1
Voltage supply for controller
frequency inveter to X34:1/3/5.
For more information, refer to "RS485 interface connection (X34) ".
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Installing the DH.21B/41B option in MOVITRAC® B / stand-alone unit
4.5.3Connecting CAN 1 system bus/voltage supply (X26)
X26:1/2/3 and connector X33 are connected in parallel. The DH.21B/41B option in the
compact controller is supplied with voltage via X26:6/7.
The DHE21B/41B option can be supplied with the required voltage by MOVITRAC
To do so, connect X26:3 (6)/7 with X46:3 (6)/7 or with X12:9/8. If MOVITRAC
supplies the DHE21B/41B option with DC 24 V, then the functions of the DHE21B/41B
option are also ensured after disconnection from the supply system. This requires an
external DC 24 V supply to X12:8/9 of MOVITRAC
®
B.
®
B
®
B.
2108499339
20
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Only use shielded cables and connection elements that also meet the requirements of
category 5, class 2 in compliance with IEC 11801 edition 2.0.
Correct shielding of the bus cable atte nuates electrical interference that can occur in
industrial environments. The following measures ensure the best possible shielding:
•Manually tighten the mounting screws on the connectors, modules, and equipotential
bonding conductors.
•Use only connectors with a metal housing or metallized housing.
•Connect the shielding in the connector over a wide surface area.
•Apply the shielding of the bus cable on both ends.
•Route signal and bus cables in separate cable ducts. Do not route them parallel to
power cables (motor leads).
•Use metallic, grounded cable racks in industrial environments.
•Route the signal cable and the corresponding equipotential bonding close to each
other using the shortest possible route.
•Avoid using plug connectors to extend bus cables.
•Route the bus cables closely along existing grounding surfaces.
NOTICE
In case of fluctuations in the ground potential, a compensating current may flow via the
bilaterally connected shield that is also connected to the protective earth (PE). In such
a case, make sure you supply adequate equipotential bonding in accordance with
relevant VDE regulations.
22
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
State of voltage supply I/O
State of input or output DIO 0/1
State of input or output DIO 2/3
State of input or output DIO 4/5
State of input or output DIO 6/7
Freely programmable
State of control firmware
State of control program
State of CAN 2 system bus
State of CAN 1 system bus
Voltage input DC +24 V
Reference potential for binary signals
Binary input or output (DIO 0)
Binary input or output (DIO 1)
Binary input or output (DIO 2)
Binary input or output (DIO 3)
Binary input or output (DIO 4)
Binary input or output (DIO 5)
Binary input or output (DIO 6)
Binary input or output (DIO 7)
Signal RS485+ (COM 1)
Signal RS485+ insulated (COM 2)
Signal RS485– (COM 1)
Signal RS485– insulated (COM 2)
Reference potential (COM 1)
Reference potential (COM 2)
Standard USB-B assignment
X37 terminal:
X37
Standard Ethernet assignment
Ethernet 2 connection
(RJ45 socket)
X32 terminal:
CAN 2 system bus
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
(electrically isolated)
(plug-in terminals)
X33 terminals:
C
AN 1 system bus
(plug-in terminals)
DIP switchS1
X32:1
X32:2
X32:3
X33:
X33:2
X33:3
1
BZG_CAN 2
CAN 2H
CAN 2L
DGND
CAN 1H
CAN 1L
Up
Down
Reference potential for system bus
CAN 2
System bus CAN 2 high
System bus CAN 2 low
Reference potential for system bus
CAN 1
System bus CAN 1 high
System bus CAN 1 low
Default IP address (192.168.10.4)
IP parameter from SD memory card
4.7.2Connecting binary inputs and outputs (X31 terminal)
Terminal X31 provides eight binary inputs or outputs (e.g. for controlling external
actuators/sensors).
Binary inputs•The binary inputs are electrically isolated by optocouplers.
•The permitted input voltages are defined according to IEC 61131.
+13 V – +30 V = "1" = contact closed
–3 V – +5 V = "0" = contact open
2102458763
Binary outputs•The binary outputs are electrically isolated by optocouplers.
•The binary outputs are short-circuit proof but not interference-voltage-proof.
•The maximum permitted output current is 150 mA per binary output. All eight bi nary
outputs can be operated simultaneo usly with this current.
NOTICE
The supply voltage must be present on X31:1/2 when using binary inputs and outputs.
The DH.21B/41B option might be damaged. In this case, the specified function of the
binary inputs and outputs is no longer ensured.
If the supply voltage is switched off, you must switch off all ot he r vo lta ges at X31:1 to
10, e.g. DC 24 V of switches and sensors at the binary inputs.
•To prevent dangerous voltage peaks from occurring, do not connect inductive loads
to the supply voltage or the binary inputs or outputs without free running diodes.
Cable specification•Only connect cables with a minimum core cross section of 0.25 mm
a maximum core cross section of 1 mm
sleeves is possible in accordance with IEC 60999.
•Choose the type and core cross section of the connected cable in dependency of the
required cable length and the load expected from your application.
For more information on binary inputs or outputs, refer to the "Technical Data" chapter.
2
(AWG18). Clamping without conductor end
2
(AWG23) and
24
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
4.7.3Connnection to system bus CAN 2 (X32) / CAN 1 (X33)
You can connect a maximum of 16 units to the DH21B option and a maximum of 64 units
to the DH.41B option on the CAN 2 or CAN 1 system bus. The system bus supports the
address range 0 to 63.
INFORMATION
•The CAN 2 system bus is electrically isolated. We therefore recommend to use
the CAN 2 ( X32) interface for connecting field devices (e .g . CANop en inpu ts and
outputs).
•The CAN 1 system bus is not electrically isolated. We therefore recommend to
use the CAN 1(X33) interface to connect inverters via the system bus in the
control cabinet.
•A system CAN connection is required for communication between
MOVIDRIVE
The CAN system bus supports transmission systems compliant with ISO 11898. The
"Serial Communication" manual contains detailed information on the system bus. This
manual can be ordered from SEW-EURODRIVE.
®
MDX61B and the integrated controller.
4
Wiring diagram for CAN 1 system bus
MOVITRAC® B
S1
ON
OFF
X44
FSC11B
X46
X45
23456HL ⊥
1
S2
7
MDX60B/61B
X12
ON OFF
DGND
SC11
SC12
S12
1
2
3
MDX61B
DHE41B
X31X32X33
1
2
3
1
2
3
ON OFF
X12:
DGND
1
2
3
1
2
3
SC11
SC12
S12
1
2
3
2102461835
Cable specification•Use a 2 × 2-core twisted and shielded copper cable (data transmission cable with
braided copper shield). Clamping without conductor end sleeves is possible in
accordance with IEC 60999. The cable must meet the following specifications:
2
– Cable cross section 0.2 mm
– 1.0 mm2 (AWG24–AWG18)
– Cable resistance 120 Ω at 1 MHz
– Capacita nce per unit length ≤ 40 pF/m at 1 kHz
Suitable cables include CAN bus or DeviceNet cables.
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Cable length•The permitted total cable length depends on the baud r ate setting of the system bus:
– 125 kBaud → 500 m
– 250 kBaud → 250 m
– 500 kBaud → 100 m
– 1000 kBaud → 40 m
Terminating
resistor
•Switch-on the system bus terminating resistor at the start an d end of the CAN system
bus connection (MOVIDRIVE
S1 = ON). For all other devices, switch off the terminating resistor (MOVIDRIVE
DIP switch S12 = OFF; MOVITRAC
DH.21B/DH.41B option is located at the end of the CAN 2 system bus, you have to
connect a terminating resistor of 120 Ω between pins X32:2 and X32:3 (for CAN 1:
terminating resistor between pins X33:2 and X33:3).
NOTICE
•There must not be any potential displacement between the units connected via
CAN 2 system bus.
•There must not be any potential displacement between the units connected via
CAN 1 system bus.
•Take suitable measures to avoid potential displacement, such as connecting the
unit ground connectors using a separate cable.
4.7.4RS485 interface connection (X34)
NOTICE
•There must not be any potential displacement between the units connected via
RS485. Take suitable measures to avoid potential displacement, such as
connecting the unit ground connectors using a separate ca ble.
•Dynamic terminating resistors are installed. Do not connect any external
terminating resistors.
®
B, DIP switch S12 = ON; MOVITRAC® B, DIP switch
®
B, DIP switch S1 = OFF). For example, if the
®
B,
You can connect one of the following units to each of the RS485 interfaces COM1/2
(terminal X34).
•DOP11B operator terminal
•MOVIMOT
®
gearmotor with integrated frequency inverter
INFORMATION
For more information on how to connect the DOP11B operator terminal, refer to the
sections "Installation" and "Pin assignment" in the DOP11B operator terminal manual.
26
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
The SD memory card is required for operating the DH.21B/41B option. It stores the
firmware, the IEC program and user data (e.g. recipes). You can use the memory card
for data backup and automatic parameterization in the event o f an axis replacement.
The SD memory card is available in 26 variants (T0 – T25). The different variants let you
execute different technology functions. The technology level can be changed by
changing the SD memory card.
OMH41B-T. typeWith the SD memory card type OMH41B -T., the DH.21B/41B opti on is used as freely
programmable controller. The SD memory card OMH41B-T. is inserted in the DH.21B/
41B option. If the delivery also includes a compact controller, a MOVIAXIS
module or an inverter with installed DH.2 1B/41B option, then the SD memory card is
already installed in the DH.21B/41B option.
SD memory card OMH41B-T.
Technology
levels
T0 – T25
T01821 204 2•Speed control management
T11821 205 0Additional technology functions for T0:
Type OMC41B-T.The SD memory card OMC41B-T.. lets you use the DH.21B/41B option as configurable
application controller (CCU). A certain technology level is required for this purpose
depending on the application module used. Refer to the documentation of the
application module for information on the required technology level.
PROFIBUS communication state
PROFIBUS bus electronics state
The two-color LEDs 13 – 16 indicate the
current state of the fieldbus interface and the
DeviceNet system
Reserved
Reserved
Reference potential for PROFIBUS
Signal receive transmit negative
Terminal unassigned
DC +5 V potential for bus terminator
Reference potential for PROFIBUS
PROFIBUS control signal for repeater
Signal receive transmit positive
Terminal unassigned
Terminal unassigned
0V24
CAN_L
DRAIN
CAN_H
24 V
Fieldbus interface PROFIBUS (X30P) active
Fieldbus interface DeviceNet (X30D) active
32
1
1
2103268363
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
For PROFIBUS mode: DIP
switch for setting the
PROFIBUS station address
For operation via
DeviceNet:
DIP switch for setting the
MAC-ID and baud rate
X38 terminal:
SEW safety bus
(plug-in terminals)
Reset button T1T1Reset
4.8.2Connecting PROFIBUS (X30P)
Connection to the PROFIBUS system is made using a 9-pin D-sub conn ector according
to IEC 61158. The T-bus connection must be made using a connector with the
corresponding configuration. The following figure shows the PROFIBUS connector that
is connected to X30P of the DHF21B/41B option.
DIP switches 20–25 are used to set the MAC
ID (Media Access Control Identifier). The
MAC ID represents the node address
(address range 0 – 63)
Setting the baud rate
Setting the baud rate
Reserved
Reserved
Reserved
[1]9-pin D-sub connector
[2]Signal line, twisted
[3]Conductive connection over a large area between plug housing and shield
Connecting the
DHF21B/41B
controller to
PROFIBUS
The DHF21B/41B option is usually connected to the PROFIBUS system using a
shielded twisted-pair cable. Observe the maximum supported transmission rate when
selecting the bus connector.
The twisted-pair cable is connected to the PROFIBUS connector at pin 3 (RxD/TxD-P)
and pin 8 (RxD/TxD-N). Communication takes place using these two pins. The RS485
signals RxD/TxD-P and RxD/TxD-N must all be connected to the same contacts in all
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
PROFIBUS stations. Else, the bus components cannot communicate via the bus
medium.
The PROFIBUS interface sends a TTL control signal for a repeater or fiber optic adapter
(reference = pin 9) via pin 4 (CNTR-P).
Baud rates greater
than 1.5 MBaud
Operating the DHF21B/41B option with baud rates > 1.5 MBaud is only possible with
special 12 MBaud PROFIBUS connectors.
Bus terminationYou need not equip the DHF21B/41B option with bus terminating resistors. This m eans
the PROFIBUS system can be put into operation more easily and the number of error
sources during installation is reduced.
When the DHF21B/41B option is located at the start or end of a PROFIBUS segment
and when there is only one PROFIBUS cable connected to the DHF21B/41B op tion, you
must use a plug with an integrated bus terminating resistor.
Switch on the bus terminating resistors for this PROFIBUS connector.
0
Setting the station
address
To set the PROFIBUS station address, use DIP switches 2
option.
– 26 on the DHF21B/41B
The DHF21B/41B option supports address range 0 – 125.
The default setting for the station address is 4:
DHF41B
0
2
1
2
2
2
3
2
4
2
5
2
6
2
7
2
ON
0
2
→ Significance: 1 × 0 = 0
1
2
→ Significance: 2 × 0 = 0
2
→ Significance: 4 × 1 = 4
2
3
→ Significance: 8 × 0 = 0
2
4
2
→ Significance: 16 × 0 = 0
5
→ Significance: 32 × 0 = 0
2
6
2
→ Significance: 64 × 0 = 0
Any change made to the PROFIBUS station address duri ng ongoing operatio n does not
take effect immediately. You have to switch the compact controller or the inverter in
which DHF21B/41B option is installed on and off again for the changes to take effect
(power +24 V off/on).
4.8.3LEDs in PROFIBUS mode
LED L17
(PROFIBUS fault)
LED L17 (PROFIBUS fault) indicates that communication via the PROFIBUS interface
is working properly.
State of the
L17 LED
Off•The DHF21B/41B option exchanges data
Red•Connection to the DP master has failed.
Flashing red
(1 Hz)
2103383051
DiagnosticsRemedy
with the PROFIBUS-DP master (data
exchange state).
•The DHF21B/41B option does not detect
the PROFIBUS baud rate.
•Bus interruption.
•PROFIBUS-DP master not in operation.
•The DHF21B/41B option does not detect
the baud rate. However, the DP master
does not address the DHF21B/41B option.
•The DHF21B/41B option was either not
configured in the DP master or it was
configured incorrectly.
-
•Check the PROFIBUS connection of
•Check project planning of the
•Check all the cables in the
•Check and correct the PROFIBUS
•Check and correct the configuration
•Use the GSD file SEW_6007.GSD
the unit.
PROFIBUS DP master.
PROFIBUS network.
station address set in the DHF21B/
41B option and in the configuration
software of the DP master.
of the DP master.
with the designation MOVI-PLC for
configuration.
34
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
LED L18 (Run PROFIBUS) indicates that the PROFIBUS electronics (hardware) is
working properly.
State of the
L18 LED
Green•PROFIBUS hardware OK. -
Flashing
green
(1 Hz)
DiagnosticsRemedy
•The PROFIBUS station address set on
the DIP switches exceeds 125. If the
PROFIBUS station address is set to a
value higher than 125, the DHF21B/41B
option will use PROFIBUS station
address 4.
1. Check and correct the PROFIBUS
station address set on the DIP
switches.
2. Switch on all inverters again. The
modified PROFIBUS address will
only take effect after a restart.
4.8.4Connecting Devi ce Ne t (X 30D)
The connection to the DeviceNet fieldbus system is in preparation.
Pin assignmentThe assignment of connecting terminals is described in the DeviceNet specification
(Volume I, Appendix A).
2103385739
The DHF21B/41B option is opto-decoupled on the driver side in accordance with the
DeviceNet specification (Volume I, Chapter 9). This m eans the CAN bus driver mu st be
powered with 24 V voltage via the bus cable. The cable to be used is also described in
the DeviceNet specification (Volume I, Appendix B). The connection must be made
according to the color code specified in the following table.
To set the DeviceNet station address, use DIP switches 20 – 25 on the DHF21B/41B
option. The DHF21B/41B option supports address range 0 – 63.
INFORMATION
Always de-energize the DHF21B/41B option before changing the DIP switch setting.
DIP switch settings are adopted during initialization only.
0
2
–25 = MAC ID setting
6
–27 = Baud rate setting
2
2103383051
Setting the MAC IDThe MAC ID (Media Access Control Identifier) is set on the DHF21B/41B option using
DIP switches 2
address of the DHF21B/41B option. The DHF21B/41B option supports address range
0–63.
Setting the baud
The baud rate is set using DIP switches 2
rate
0
– 25 in a binary coded manner. The MAC ID represents the node
6
and 27.
DIP switch
6
2
00125 kBaud
10250 kBaud
01500 kBaud
11Invalid
7
2
Baud rate
A maximum of 64 DeviceNet data words can be exchanged between the DeviceNet
module and the DHF21B/41B option. The number is set using the DeviceNet scanner.
4.8.5LEDs in DeviceNet mode
The DHF21B/41B option card comes equipped with four two-color LEDs for diagnostics
of the DeviceNet system. They indicate the current state of the DHF21B/41B option and
the DeviceNet system. The unit state indicated by the LEDs is described in the "Error
diagnostics" section.
LED
DesignationAbbreviationComplete LED designation
L16MOD/NETModule/Network state
L15PIOPolled I/O
L14BIOBit-strobe IO
L13BUS FAULTBUS FAULT
36
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
4.9.2Connecting the DHR21B/ 41 B co n trolle r to the Eth e rne t ne t wo rk
To connect DHR21B/41B to the Ethernet network, connect Ethernet interface X30-1 or
X30-2 (RJ45 plug connector) to the other network stations using a category 5, class D
twisted-pair cable in accordance with IEC 11801 edition 2.0. The integrated switch
supports you in implementing a line topology and offers auto-crossing functions.
INFORMATION
•According to IEC 802.3, the maximum cable length for 10/100 MBd Ethernet
(10BaseT / 100BaseT), e.g. between two network stations, is 100 m.
•We recommend that you do not directly connect non-SEW end devices to the
DFR21B/41B option in order to minimize the load on the end devices in EtherNet/
IP networks caused by undesired multicast data traffic. Connect non-SEW
devices via a network component that supports the IGMP snooping functionality
(e.g. managed switch).
Managed switches with IGMP snooping functionality are not required for
PROFINET IO and Modbus/TCP networks.
DIP switch "21" is used to set the fieldbus protocol that is currently used.
1
•2
= "1" (= right = ON): The EtherNet/IP / Modbus TCP/IP fieldbus protocol is active
1
•2
= "0" (= left = OFF): The PROFINET fieldbus protocol is active.
You can use the integrated Ethernet switch to achieve line topologies known from the
fieldbus technology via X30-1 and X30-2. Other bus topologies, such as star or tree, are
also possible. Ring topologies are not supported.
INFORMATION
The number of industrial Ethernet switches connected in line impacts the telegram
runtime. If a telegram passes through the units, the telegram runtime is delayed by the
store & forward function of the Ethernet switch:
•For a telegram length of 64 bytes by approximately 10 µs (at 100 Mbit/s)
•For a telegram length of 1500 bytes by approximately 130 µs (at 100 Mbit/s)
This means that the more units a telegram has to pass through, the higher the
telegram runtime is.
Auto-crossingThe two ports leading out of the Ethernet switch have auto-crossing functionality. This
means that they can use both patch and cross-over cables to connect to the next
Ethernet station.
Auto-negotiationThe baud rate and the duplex mode are negotiated by both Ethernet nodes when
establishing the connection. For this purpose, both Ethernet ports of the EtherNet/IP
connection support an auto-negotiation functionality and wor k with a b aud ra te of ei ther
100 Mbit or 10 Mbit in full duplex or half-duplex mode.
Notes on multicast
handling
•The integrated Ethernet switch does not provide a filter function for Ethernet
multicast telegrams. Multicast telegrams that are usually sent in Ethernet/IP
networks from the adapters to the scanner s (PLC) are passed on to all switch ports.
•IGMP snooping (managed switch) is not supported.
•SEW-EURODRIVE therefore recommends to connect the DHR21B/41B option in
EtherNet/IP networks only with network components that support IGMP snooping
(e.g. managed switch) or that have safety mechanisms integrated against excess
multicast load (e.g. units from SEW-EURODRIVE). Units that do not have this
integrated function can fail due to high network loads. This restrictio n does not apply
to PROFINET IO or Modbus/TCP networks.
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
IntroductionThe settings for the address of the IP protocol are made using the following parameters:
•MAC address
•IP address
•Subnet mask
•Standard gateway
The addressing mechanisms and subdivision of the IP networks into subnets are
explained in this chapter to help you set the parameters correctly.
MAC addressThe MAC address (Media Access Controller) is the basis for all address settings. The
MAC address is a worldwide unique 6-byte value (48 bits) assigned to the Ethernet
device. SEW Ethernet devices have the MAC address 00-0F-69-xx-xx-xx. The MAC
address is difficult to handle for large networks. This is why freely assignable IP
addresses are used.
IP addressThe IP address is a 32-bit value that uniquely identifies a station in the network. An IP
address is represented by 4 decimal numbers separated by decimal points.
Example: 192.168.10.4
Each decimal number stands for one byte (= 8 bits) of the address and can also be
represented using binary code (see following table).
Byte 1Byte 2Byte 3Byte 4
11000000.10101000.00001010.00000100
The IP address comprises a network address and a station address (see following
table).
Network addressStation address
192.168.104
The part of the IP address that denotes the network and the part that identifies the
station is determined by the network class and the subnet mask.
Station addresses cannot consist of only zeros or ones ( binary) because they represent
the network itself or a broadcast address.
Network classesThe first byte of the IP address determines the networ k class and as such represents
the division into network addresses and station addresses.
Subnet maskA subnet mask is used to divide the network classes into even finer sections. Like the
IP address, the subnet mask is represented by 4 decimal numbers separated by decimal
points.
Example: 255.255.255.128
Each decimal number stands for one byte (= 8 bits) of the subnet mask and can al so be
represented using binary code (see following table).
Byte 1Byte 2Byte 3Byte 4
11111111.11111111.11111111.10000000
If you compare the IP addr esses with the subnet masks, you see that in the binary
representation of the subnet mask all ones determine the network address and all the
zeros determine the station address (see following table).
The class C network with the address 192.168.10. is further subdivided into
255.255.255.128 using the subnet mask. Two networks are created with the address
192.168.10.0 and 192.168.10.128.
The following station addresses are permitted in the two networks:
•192.168.10.1 ... 192.168.10.126
•192.168.10.129 ... 192.168.10.254
The network stations use a logical AND o peration for the IP address and the subnet
mask to determine whether there is a communication partner in the same network or in
a different network. If the communication partner is in a different network, the standard
gateway is addressed for passing on the data.
Standard gatewayThe standard gateway is also addressed via a 32-bit address. The 32-bit address is
represented by 4 decimal numbers separated by decimal points.
Example: 192.168.10.1
The standard gateway establishes a connection to other networks. In this way, a
network station that wants to address an other station can use a logical AND operation
with the IP address and the subnet mask to determine whether the required station is
located in the same network. If this is not the case, the station addresses the standard
gateway (router), which must be part of the actual networ k. The standa rd ga tewa y th en
takes on the job of transmitting the data packages.
DHCP (Dynamic
Host Configuration
Protocol)
Instead of setting the 3 parameters IP address, subnet mask and standard gateway
manually, they can be assigned automatically by a DHCP server in the Ethernet
network.
This means the IP address is assigned from a table, which contains the allocation of
MAC address to IP address.
Parameter P785 indicates whether the DHR21B/41B option expects the IP parameters
to be assigned manually or via DHCP.
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Link/Activity LEDThe two LEDs Link (green) and Activity (yellow) integrated in the RJ45 plug
connectors (X30-1, X30-2) display the state of the Ethernet connection.
2104908939
LED/stateMeaning
Link/greenThere is an Ethernet connection.
Link/offThere is no Ethernet connection.
Activity/yellowData is currently being exchanged via Ethernet.
4
4.9.7Setting IP address parameters via DCP
Initial startupFor PROFINET IO, the IP address parameters are determined via the "DCP" protocol
(Discovery and Configuration Protocol). DCP operates with device names. The device
name uniquely identifies a PROFINET IO station in the network. It is identified with the
PROFINET IO controller when configuring the station and is set using the project
planning software on the PROFINET IO device. With the aid of the device name, the
controller identifies the device during startup and transfers the correspondin g IP address
parameters. Settings directly on the slave are no longer required.
Resetting IP
address
parameters
If you do not know the IP address parameters and cannot access the inverte r usin g the
serial interface or the DBG60B keypad, you can reset the IP address parameters to the
default values using DIP switch "2
0
".
This action resets the DHR21B/41B option to the following default values:
•IP address: 192.168.10.4
•Subnet mask: 255.255.255.0
•Default gateway: 1.0.0.0
•PROFINET device name: PNETDeviceName_MACID
Proceed as follows to reset the IP address parameters to the default values:
•Switch off the 24 V DC supply voltage and the line voltage.
•On the DHR21B/41B option, set DIP switch "2
0
" to "1" (= right = ON).
•Switch the DC 24 V supply voltage and the line voltage back on.
•Wait until the DHR21B/41B option has booted up. This is indicated by the green
"Run" LED.
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
You can now access the inverter via the IP address 192.168.10.4. Proceed as follows
to set new IP address parameters:
•Start MOVITOOLS
•Select the required address parameters.
•On the DHR21B/41B option, set DIP switch "2
•The new address parameters are adopted af ter the u nit is switched off and switched
on again.
4.9.8LEDs in EtherNet/IP and Modbus/TCP mode
LEDs L13 and L14 of the DHR21B/41B indicate the current state of the DHR21B/41B
option and the EtherNet/IP or Modbus/TCP system.
LED L13LED L13 (NETWORK STATUS).
State of the L13 LEDMeaning
OffThe DHR21B/41B option does not yet have any IP parameters.
Flashing green/redThe DHR21B/41B option card performs an LED test.
Flashing greenThere is no controlling IO connection.
GreenThere is a controlling EtherNet/IP IO connection.
RedConflict detected in the assigned IP addresses. Another station in the network
Flashing redThe previously established controlling IO connection is in timeout state. The
®
MotionStudio.
0
" to "0" (= left = OFF).
uses the same IP address.
state is reset by restarting communication.
LED L14LED L14 (MODULE STATUS).
State of the L14 LEDMeaning
OffThe DHR21B/41B option is not supplied with voltage or is defective
Flashing green•If the NETWORK STATUS LED is off at the same time, the TCP/IP stack of
Flashing green/redThe DHR21B/41B option performs an LED test.
GreenIndicates the standard operating state of the DHR21B/41B option
RedThe DHR21B/41B option is in fault state.
Flashing redConflict detected in the assigned IP addresses. Another station in the network
the DHR21B/41B option will be started. If this state persists and DHCP is
activated, the DHR21B/41B option will wait for data from the DHCP server.
•If the NETWORK STATUS LED is flashing green at the same time , the
application of the DHR21B/41B option is started.
uses the same IP address.
46
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
LED Link / ActivityThe two LEDs Link (green) and Activity (yellow) integrated in the RJ45 plug
connectors (X30-1, X30-2) display the state of the Ethernet connection.
4
LED/stateMeaning
Link/greenThere is an Ethernet connection.
Link/offThere is no Ethernet connection.
Link/flashesFunction for localizing in the SEW Address Editor (see chapter "Operating the
Activity/yellowData is currently being exchanged via Ethernet.
4.9.9Setting IP address parameters
INFORMATION
•DHCP remains disabled when you reset the DIP switch "20" to "0" (= left = OFF).
You can re-activate DHCP via the EtherNet/IP TCP/IP interface object, parameter
P785 or the DHCP server by Rockwell Automation.
•DHCP remains active when resetting the values to the default setting (P802 Factory setting).
LED "Link"
LED "Activity"
MOVITOOLS MotionStudio
X30-1
X30-2
2104908939
®
")
Initial startupIf the EtherNet/IP and MODBUS TCP protocol is set using the DIP switch, the default
protocol for the DHR21B/41B option will be "DHCP" (Dynamic Host ConfigurationProtocol). This means that the option expects its IP address parameters from a DHCP
server.
INFORMATION
There is a free DHCP server available on the Rockwell Automation homepage. The
tool is known as "BOOTP Utility" and can be downloaded from the following website:
Once the DHCP server has been configured and the settings have been made for the
subnet mask and the standard gateway, the DHR21B/41B option must be inserted in the
assignment list of the DHCP server. In doing so, the MAC ID of the DHR21B/41B option
is allocated a valid IP address.
INFORMATION
The configured IP address parameters are adopted p ermanently by the parameter set
when DHCP is deactivated after the IP address has been assigned.
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Changing the IP
address parameters after successful initial startup
Deactivating/
activating the
DHCP
If the DHR21B/41B was started using a valid IP address, you can also access the IP
address parameters via Ethernet interface.
You can change the IP address parameters via Ethernet by one of the following
methods:
®
•Using the MOVITOOLS
•Using the EtherNet/IP TCP/IP interface object (see section "EtherNet/IP CIP object
directory")
•Using the SEW Address Editor
You can also change IP address parameters via the other interface of the DHR21B/41B
option.
If the IP address parameters are assigned to the DHR21B/41B option by a DHCP
server, you can only change the parameters by adjusting the settings of the DHCP
server.
The methods listed above for changing the IP address parameters only come into effect
once the supply voltage (DC 24 V) has been switched off and back on again.
The type of IP address allocation is determined by the setting of the attribute
Configuration Control of the EtherNet/IP TCP/IP interface object. The value is displayed
or modified in the P785 DHCP/Startup Configuration parameter.
•"Stored IP parameters" setting
MotionStudio software
Resetting IP
address
parameters
The stored IP address parameters are used.
•"DHCP" setting
The IP address parameters are requested by a DHCP server.
If you use the DHCP server from Rockwell Automation, you can activate or
deactivate the DHCP by clicking a button. In this case, an EtherNet/IP telegram is
sent to the TCP/IP interface object of the station that is being addressed.
If you do not know the IP address parameters and there is no serial interface or DBG60B
keypad for reading the IP address, you can reset the IP address parameters to the
default values using the DIP switch "2
This action resets the DHR21B/41B option to the following default values:
•IP address: 192.168.10.4
•Subnet mask: 255.255.255.0
•Default gateway: 192.168.10.4
•DHCP / Startup Configuration: Stored IP parameters (DHCP is disabled)
Proceed as follows to reset the IP address parameters to the default values:
•Switch off the 24 V DC supply voltage and the line voltage.
•On the DHR21B/41B option, set DIP switch "2
0
".
0
" to "1" (= right = ON).
•Switch the DC 24 V supply voltage and the line voltage back on.
48
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
You can also use the SEW Address Editor to access the IP settings of DHR21B/41B
without the Ethernet settings of the PC and DHR41B having to match.
The IP settings of all SEW units can be made and displayed in the local subnet using
the Address Editor in MOVITOOLS
•In this way, you can determine the PC settings required to provide for an access with
the required diagnostics and engineering tools via Ethernet while the inst allation is in
progress.
•When starting up a unit, the IP settings can be assigned to the DHR2 1B/4 1B optio n
without having to change network connections or PC settings.
®
MotionStudio.
4.10Engineering interfaces of the DH.21B/41B option
The engineering access to the DH.21B/41B option is made via Ethernet 2 interface
(X37) or USB interface (X35). With option DHF21B/41B, engineering access is possible
via PROFIBUS (X30P). With option DHR21B/41B, engineering access is possible via
Ethernet (X30-1/2).
INFORMATION
Refer to the following publications for more information:
Project Planning and Startup with MOVITOOLS® MotionStudio
About MOVITOOLS® MotionStudio
5Project Planning and Startup with MOVITOOLS® MotionStudio
5.1About MOVITOOLS® MotionStudio
5.1.1Tasks
The software package enables you to perform the following tasks:
•Establishing communication with units
•Executing functions with the units
5.1.2Establishing communication with other units
The SEW Communication Server is integrated into the MOVITOOLS
software package for establishing communication with the units.
The SEW Communication Server allows you to create communication channels.
Once the channels are established, the units communicate via these channels using
their communication options. You can operate up to four commu nication channels at the
same time.
®
MOVITOOLS
MotionStudio supports the following types of communication channels:
®
MotionStudio
•Serial (RS-485) via interface adapters
•System bus (SBus) via interface adapters
•Ethernet
•EtherCAT
•Fieldbus (PROFIBUS DP/DP-V1)
•Tool Calling Interface
The available channels can vary depending on the units and their communication
options.
5.1.3Executing functions with the units
The software package offer uniformity in executing the following functions:
•Parameterization (for example in the parameter tree of the unit)
•Startup
•Visualization and diagnostics
•Programming
The following basic components a re integrated into the MOVITOOLS
software package, allowing you to use the units to execute functions:
•MotionStudio
•MOVITOOLS
®
®
MotionStudio
All functions communicate using tools. MOVITOOLS® MotionStudio provides the right
tools for every unit type.
50
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Project Planning and Startup with MOVITOOLS® MotionStudio
Project Planning and Startup with MOVITOOLS® MotionStudio
Connection mode
®
MOVITOOLS
tion mode. You can select the communication mode yourself. Depending on the
selected communication mode, you can choose offline or online tools specific to your
unit.
The following figure illustrates the two types of tools:
MotionStudio differentiates between "online" and "offline" communica-
[1] Hard drive of the engineering PC
[2] RAM of the engineering PC
[3] Engineering PC
[4] Unit
ToolsDescription
Offline
tools
Online
tools
Changes made using offline tools affect "ONLY" the RAM [2].
•Save your project so that the changes can be stored on the hard disk [1] of your
engineering PC [3].
•Perform the "Download (PC->unit)" function if you want to transfer the changes to your
unit [4] as well.
Changes made using online tools affect "ONLY" the unit [4].
•Perform the "Upload (unit->PC)" function if you want to transfer the changes to your RAM.
•Save your project so that the changes can be stored on the hard disk [1] of your
engineering PC [3].
9007200497934219
52
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Project Planning and Startup with MOVITOOLS® MotionStudio
•The "online" communication mode is NOT a response message which informs
you that you are currently connected to the unit or that your unit is ready for
communication. Should you require this feedback, observe section "Setting the
cyclical accessibility test" in the online help (or the manual) of
MOVITOOLS
•Project management commands (such as download and upload), the online unit
status, and the unit scan work independent of the set communication mode.
•MOVITOOLS
before you closed down.
5.3.2Selecting the communication mode (online or offline)
Proceed as follows to select the communication mode:
1. Select the communication mode:
•"Switch to online mode" [1] for functions (online tools) that should directly
influence the unit.
®
MotionStudio.
®
MotionStudio starts up in the communication mode that you set
Connection mode
5
•"Switch to offline mode" [2] for functions ( offline tools) that should influenc e your
project.
[1] [2]
9007200389198219
[1] "Switch to online mode" icon
[2] "Switch to offline mode" icon
2. Select the unit node.
3. Right-click to open the context menu and display the tools for configuring the unit.
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Project Planning and Startup with MOVITOOLS® MotionStudio
Communication via USB
5.4Communication via USB
5.4.1Connecting the unit with the PC via USB
The illustration shows how the unit (in the example a DH.21B/41B controller [3])) is
connected with the PC [1] using a USB connection cable [2]. It also shows how the
controller [3] is connected with the lower-level unit [5] via SBus (CAN).
[1]
1
5
[1] PC with USB interface
[2] USB connection cable
[3] Controller (DHF41B for example)
[4] SBus connection (CAN based) between controller and lower-level unit
[5] Lower-level unit (MOVIAXIS
®
in this example)
[2]
[3]
[4]
[5]
1716605579
Do the following to connect the DH.21B/41B controller with the PC and the lower-level
unit:
1. Insert the USB-A connector of the USB cable [2] into a free USB port on your PC [1].
2. Insert the USB-B connector of the USB cable [2] into the USB port on your DH.21B/
41B option [3].
3. Connect the SBus interface of the controller [3] with the SBus interface of the lowerlevel unit [5].
54
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Project Planning and Startup with MOVITOOLS® MotionStudio
Project Planning and Startup with MOVITOOLS® MotionStudio
Communication via Ethernet
5.5Communication via Ethernet
5.5.1Direct communication
OverviewThe figure shows the network with direct communication using Ethernet:
[2]
[1]
ETHERNET
[3]
[1] PC with Ethernet TCP/IP interface
[2] Ethernet TCP/IP connection
[3] Switch
[4] Units (examples) with Ethernet interfaces
FunctionParameter requests from MOVITOOLS
from a PC [1] to a switch [3] using the Ethernet TCP/IP interface.
The parameter requests are then passed directly on to the Ethernet interface of the units
[4] from the switch [3].
[4]
EURODRIVEEURODRIVE
1193501835
®
MotionStudio are transferred via Ethernet [2]
58
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Project Planning and Startup with MOVITOOLS® MotionStudio
The Address Editor can only be used with the DHR21B/41B option (connection via
X30-1/-2).
OverviewThe Address Editor is a freeware tool by SEW-EURODRIVE GmbH & Co KG.
®
It is available once the "MOVITOOLS
However, it is used separately.
You can use the Address Editor to establish a communication for your units via Ethernet
and to address the units.
If you use a patch cable to connect the Ethernet interface of your engine ering PC to the
Ethernet, the Address Editor detects all Ethernet stations in the connected network
segment (local network).
®
Unlike with "MOVITOOLS
the engineering PC to the local network.
This means the Address Editor is a useful addition to "MOVITOOLS
MotionStudio", you will not have to adjust the IP address of
MotionStudio" engineering software is installed.
®
MotionStudio".
5
Start the Address
Editor
Searching for
Ethernet stations
Proceed as follows if you have added other Ethernet stations to an existing network:
•Start the Address Editor
•Search for Ethernet stations
Once you have found the added Ethernet stations, you have two options:
•Set (address) the detected Ethernet stations according to the network
•Adjust (address) the engineering PC according to the network
You can use the Address Editor once MOVITOOLS
Do the following to start the Address Editor:
®
1. Close MOVITOOLS
2. Start the Address Editor from the Windows start menu via:
[Start] / [Programs] / [SEW] / MOVITOOLS MotionStudio] / [Address Editor
(Address Tool)]
You can use the Address Editor to find Ethernet stations in a network. This is especially
useful for finding recently added Ethernet stations. The Address Editor also helps you
to locate the Ethernet interface of detected Ethernet stations.
Do the following to search for Ethernet stations and localize the hardware:
1. Select "Ethernet" as the interface for PC and unit. To do so, click on the
corresponding option field in the lower part of the window.
2. Click [Next] to confirm your selection and proceed to the next dialog.
MotionStudio.
®
MotionStudio has been installed.
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Project Planning and Startup with MOVITOOLS® MotionStudio
Communication via Ethernet
3. Wait for the network scan to start automatically. The default setting for the waiting
time (scan timeout) is 3 s [2]
Note: If you no units are detected during the network scan, the wiring might be
inadequate, or you have several network cards installed (activated) in your PC.
In this case, proceed as follows:
•Select the required card. To do so, click "Select network card" [3] in the toolbar.
•Start the network scan manually. To do so, click "Start network scan" [1] in the
As a result, the current addresses of a ll Ethernet stations in the connected network
will be displayed.
4. Mark the "Localize" checkbox [4] to localize an Ethernet station.
The link/act LED of the first Ethernet interface of the respective Ethernet station will
flash green.
60
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Project Planning and Startup with MOVITOOLS® MotionStudio
Project Planning and Startup with MOVITOOLS® MotionStudio
Communication via Ethernet
8. For the engineering PC, enter an IP address that meets the following conditions:
•In the blocks that define the network, the address segment for the engineering
PC must correspond to the other Ethernet stations.
•In the blocks that define the station, the address segment for the engineering PC
must differ from the other stations.
•The last block must not contain the values "0", "4", "127" or "255".
NOTE: In the IP address of the subnet mask (such as 255.255.255.0), the values
in the blocks have the following meaning:
– "255", defines the address of the network where th e stations are located.
– "0", defines the address of the actual station to distinguish it from other
stations.
5.5.3Configuring the communication channel via Ethernet
Do the following to configure a communication channel for Ethernet:
1. Click on "Configure communication connections" [1] in the toolbar.
9007200388082827
[1] "Configure communication connections" icon
This opens the "Configure communication connections" window.
9007200399122315
[1] "Type of communication" dropdown menu
[2] "Activate" checkbox
[3] [Edit...] button
2. From the list [1], select "Ethernet" as the communication type .
In the example, "ETHERNET" is activated as the communication type for the first
communication channel [2].
[1]
62
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Project Planning and Startup with MOVITOOLS® MotionStudio
Project Planning and Startup with MOVITOOLS® MotionStudio
Communication via Ethernet
Proceed as follows to set the Ethernet communication parameters:
1. Change the set communication parameters if necessary. Refer to the detailed
description of the communication parameters for SMLP.
NOTE: During a unit scan, the system recognizes only units that are in the same
(local) network segment as the PC that is running on MOVITOOLS
you have units that are outside the local network segment, add the IP addresses of
these units to the list of SMLP servers.
2. Add an IP address by opening the context menu and selecting [Add IP address] [1]..
®
MotionStudio. If
[1] [Add IP address] button
[2] "IP address" input field
3. Enter the IP address in the input field [2] and click the [OK] button.
64
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
18014399832166155
Project Planning and Startup with MOVITOOLS® MotionStudio
The following table describes the communication parameters for SMLP:
Communication parametersDescriptionNote
TimeoutWaiting time in ms that the client
Broadcast IP addressIP address of the local network
IP address of SMLP serverIP address of the SMLP server or
Excluded IP addressIP addresses of units that should
Communication via Ethernet
waits for a response from the
server after it has made a
request.
segment within which the unit
scan is carried out.
of other units that are to be
included in the unit scan but are
outside the local network
segment.
not be included in the unit scan
5
•Default setting: 1000 ms
•Increase the value as
required if a delay in
communication is causing
malfunctions.
In the default setting, the unit
scan only detects units that are in
the local network segment.
•Enter the IP address of units
that are to be included in the
unit scan but are outside the
local network segment.
•Enter the IP address of the
SIMATIC S7 control, if you
are operating an indirect
Ethernet to PROFIBUS
communication via SIMATIC
S7.
Enter the IP address of units that
should not be included in the unit
scan. This can be units that are
not ready for communication (for
example because they have not
been started up yet)
5.5.6Communication ports used
The following table describes the communication ports MOVITOOLS
uses:
ApplicationNo. of communication
ETH server300 For using a PC as Ethernet gateway with
SEW communication server301 For communication between
Offline data server302For communication of
®
MOVIVISION
MOVI-PLC
TCI server305For communication via TCI
EcEngineeringServer remote
control (in preparation)
EcEngineeringServer mailbox
gateway (in preparation)
server 303For communication with a PC with active
®
visualization304For communication between MOVI-PLC®
®
MotionStudio
Description
port
the program "ETHServer.exe"
®
MOVITOOLS
SEW Communication Server
MOVITOOLS
mode
MOVIVISION
and the 3D simulation of
MOVITOOLS
306For direct communication (without master)
with SEW EtherCAT slaves
307For direct communication (without master)
with SEW EtherCAT slaves
MotionStudio and the
®
MotionStudio in offline
®
server
®
MotionStudio
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
Project Planning and Startup with MOVITOOLS® MotionStudio
Configuration and startup of the drives
5.7Configuration and startup of the drives
Configuration and startup of the drives is described in the following library manuals:
DriveManual
MOVIDRIVE
MOVIAXIS
MOVITRAC
MOVIMOT
®
®
®
®
B
07 / B
INFORMATION
If you want to operate the DH.21B/41B option installed in MOVIDRIVE® MDX61B,
then the firmware of the MOVIDRIVE
".16".
This applies regardless of whether the inverter is cont rolled via the insta lled D H.21B /
41B option or whether the slot of the inverter is only used for installing the DH.21B/41B
option while it is simultaneously used to control other inverters (e.g. MOVITRAC
MPLCMotion_MDX and MPLCMotion_MX for MOVI-PLC® libraries
MPLCMotion_MC07 and MPLCMotion_MM for MOVI-PLC® libraries
®
MDX61B inverter must have at least status
®
B).
5.8Configuration and startup in the PLC Editor
INFORMATION
•For further information on configuration and startup of the DH.21B/41B option,
refer to the "MOVI-PLC
•For information on how to configure the master in the various fieldbus systems,
refer to the following documents:
– DHF21B/41B Controller Fieldbus Interf aces DeviceNet and PROFIBUS DP-V1
– DHR21B/41B Controller Fieldbus Interfaces EtherNet/IP, Modbus/TCP and
PROFINET IO
®
programming in the PLC Editor" system manual.
5.9Replacing the unit
For replacing a DHF21B/41B option, a compact controller or a controlled drive, follow
the instructions in the "Assembly and Installation Notes" chapter. Insert the SD card of
the previous controller into the new controller.
INFORMATION
The variable values stored remanently on the DH.21B/41B option are not stored on
the SD card by default. This can be programmed through the application (IEC
program), or the data backup must be imported through the project management in
MOVITOOLS
For information on replacing the drives, please refer to the manual of the inverter in
question.
®
MotionStudio.
68
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
The general technical data listed in the following table applies to:
•DH.21B/41B option installed in the inverter
•DH.21B/41B/UOH.B stand-alone unit
General technical data
Interference immunityMeets EN 61800-3
Ambient temperatureInstalled in MOVIDRIVE
•0 °C to +60 °C
(Derating at 40 °C to 60 °C → System manual MOVIDRIVE
61B)
Installed in MOVITRAC
•–10 °C to +60 °C
(Derating at 40 °C to 60 °C → System manual MOVITRAC
Installed in MOVITRAC
•0 °C to +60 °C
(Derating at 40 °C to 60 °C → System manual MOVITRAC
Installed in the MOVIAXIS
•0 °C to +45 °C
Compact controller:
•–10 °C to +60 °C
Climate classEN 60721-3-3, class 3K3
Storage temperature–25 °C to +70 °C
Climate classEN 60721-3-3, class 3K3
Type of coolingConvection cooling
Degree of protectionIP20
Duty cycleContinuous duty
(see MOVIDRIVE
manuals)
Pollution class2 according to IEC 60664-1 (VDE0110-1)
Installation altitudemax. 4000 m (NN)
®
MDX61B:
®
MDX60B/
®
B (AC 230 V; AC 400/500 V up to 4 kW):
®
®
B (AC 400/500 V over 4 kW):
®
master module:
®
MDX60B/61B, MOVITRAC® B, MOVIAXIS® system
B)
®
B)
70
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
DHE21B/41B option
Part number•DHE21B option: 1823 607 3
Electrical supplyThe following applies to all units (MDX, MX, compact controller):
Potential levelsOption DHE21B/41B has the following potential levels:
Memory•Retain data: 32 kByte
Binary inputsIsolated (optocoupler), PLC compatible (IEC 61131-2), sampling interval corresponds to task cycle time.
X31:3 – X31:10Can be configured as binary inputs or outputs
Internal resistanceR
Signal levelDC (+13 V to +30 V) = "1" = contact closed (according to IEC 61131)
Binary outputsPLC-compatible (IEC 61131-2), response time 1 ms
X31:3 – X31:10Can be configured as binary inputs or outputs
Signal level"0" = 0 V "1" = DC +24 V
CAN 2 system bus
X32:1–X32:3
CAN 1 system bus
X33:1–X33:3
DHE41B option: 1821 160 7
•You have to supply the binary inputs and outputs separately with DC 24 V (X31:1/2).
Installed in MOVIDRIVE
•Power consumption: P
•Option DHE21B/41B is supplied by MOVIDRIVE
•In the case of disconnection from the power supply, continued function is guaranteed by the DC 24
backup mode (external DC 24 V supply to X10:9/10 of MOVIDRIVE
Installed in the MOVIAXIS
•Power consumption: P
•U = DC 24 V (–15 % / +20 %)
•I
•Option DHE21B/41B can be supplied from the MOVIAXIS
•If the DHE21B/41B option is supplied with DC 24 V from the MOVIAXIS
DC (–3 V to +5 V) = "0 " = contact open (according to IEC 61131)
Maximum permitted output current I
All 8 binary outputs can be subject to the maximum approved output current I
time.
•System bus CAN 1 and CAN 2 to CAN specification 2.0, parts A and B, transmission technology to
•The CAN 2 system bus is electrically isolated
•Max. 64 stations (DHE41B) / 16 stations (DHE21B) per CAN system bus
•Max. 64 (DHE41B) / 16 (DHE21B) SCOM transmit objects / 256 receive objects per CAN system bus
•Address range 0 - 63
•Baud rate: 125 kBd–1MBd
•If X32 or X33 is the bus terminator, you must connect a terminating resistor (120 Ω) externally.
•You can remove connector X32 or X33 without interrupting the system bus.
•The system bus can be run in layer 2 (SCOM cyclic, acyclic) or in accordance with the SEW-
= 600 mA
max
from an external voltage source. To do so, connect X5 between the individual units.
supply, then the function of the DHE21B/41B option is ensured when power supply is switched off
(external DC 24 V supply at X16 of the MOVIAXIS
≈ 3kΩ, IE≈ 10 mA
i
ISO 11898
MOVILINK
®
protocol.
®
MDX61B:
= 6.8 W
max
®
master module (MXM):
= 8.5 W
max
= DC 150 mA per binary output
A_max
®
MDX61B via backplane connector.
®
MDX61B required).
®
switched-mode power supply (MXS) or
®
switched-mode power
®
switched-mode power supply).
load at the same
A_max
7
Manual – Controllers DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)