SEW Eurodrive DFS21B User Manual

Drive Technology \ Drive Automation \ System Integration \ Services
Manual
DFS21B Fieldbus Interface
PROFINET IO with PROFIsafe (Safe Stop)
Edition 03/2010 16916816 / EN
SEW-EURODRIVE—Driving the world
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
1.1 How to use the manual .......... ... .... ... ... ... ....................................... ... ... .... ... .... 5
1.2 Structure of the safety notes .......................................................................... 5
1.3 Rights to claim under limited warranty........................................................... 6
1.4 Exclusion of liability........................................................................................ 6
1.5 Copyright........................................................................................................ 6
2 Safety Notes ......................... .... ...................................... .... ... ... ... ........................... 7
2.1 Other applicable documentation .................................................................... 7
2.2 General safety notes for bus systems............................................................ 7
2.3 Safety functions ............... ... ... ... .... ...................................... .... ... ... ... ... ........... 7
2.4 Hoist applications....................................................................... ... ... ... .... ... .... 7
2.5 Product names and trademarks.......................................................... .... ....... 7
2.6 Disposal ......................................................................................................... 8
3 Introduction ............................................................................................................ 9
3.1 Content of this manual ................................................................................... 9
3.2 Additional documentation................. ... ... ....................................... ... ... .... ... ... . 9
3.3 Characteristics ............................................................................................... 9
4 Integrated Safety Technology............................................................................. 11
4.1 Safety concept for PROFIsafe fieldbus interfaces ....................................... 11
4.2 Safety concept for MOVIDRIVE
®
and MOVITRAC®.................................... 12
5 Safety Conditions.............................. ....................................... ... .... ... ... ............... 14
5.1 Installation requirements............................................................ ... ... ............ 14
6 Assembly and Installation Notes........................................................................ 15
6.1 Installing the DFS21B option card in MOVIDRIVE
6.2 Installing the DFS21B option card in MOVITRAC
®
MDX61B..................... 15
®
B.................................. 18
6.3 Installing the DFS21B/UOH11B gateway..................................................... 21
6.4 Connection and terminal description DFS21B option .................................. 22
6.5 Wiring diagrams for safe technology............................................................ 23
6.6 Pin assignment ............................................................................................ 27
6.7 Shielding and routing bus cables................................................................. 28
6.8 TCP/IP addressing and subnetworks........................................................... 29
6.9 Setting the IP address parameters via DCP ................................................ 31
6.10 Procedure after a unit replacement.............................................................. 32
6.11 Operating displays of the DFS21B op tio n.................................................. .. 33
7 Configuration with PROFINET ......... .... ...................................... .... ... ... ... ............ 36
7.1 Configuration of the PROFINET IO controller.............................................. 36
7.2 Auto setup for gateway operation ................................................................ 52
7.3 Setup of the MOVIDRIVE
7.4 Setup of the MOVITRAC
®
MDX61B inverter.............................................. 54
®
B inverter........................................................... 55
7.5 Configuration of PROFIsafe with STEP7..................................................... 56
7.6 Data exchange with PROFIsafe option DFS................................................ 62
7.7 Response times of the PROFIsafe option DFS ... ... .... ... ... ............................ 65
7.8 Diagnostics with the PROFIsafe option DFS ............................................... 66
7.9 Error states of the PROFIsafe option DFS................................................... 67
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
3
8 Operating Behavior in Conjunction with PROFINET ......... ...... .... ... ... ... ... .... ... .. 70
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
8.1 Introduction .................................................................................................. 70
8.2 The integrated Ethernet switch .................................................................... 72
8.3 Process data configuration .......................................................................... 73
8.4 Control of the MOVIDRIVE
8.5 Control of the MOVITRAC
®
MDX61B inverter................ ... .... ..................... 7 4
®
B inverter (gateway) ........................................ 76
8.6 SIMATIC S7 sample program ...................................................................... 78
8.7 PROFINET alarms using the example of MOVIDRIVE
®
B.......................... 79
8.8 PROFINET configuration with topology detection............ ... .... ... ... ...... .... ... .. 81
9 Parameterization via PROFIdrive Data Set 47 ................................................... 89
9.1 Introduction to PROFINET data records...................................................... 89
9.2 Structure of the PROFINET parameter channel .......................................... 91
9.3 Read/write parameters via data set 47 ...................................................... 105
10 Integrated Web Server ....................................................................................... 107
10.1 Software require m en ts.................................................. ... .......................... 10 7
10.2 Security settings......................................................................................... 107
10.3 Homepage layout MOVIDRIVE
®
MDX61B with DFS21B option ............... 108
10.4 Structure of the diagnostics applet............................................................. 109
10.5 Access protection....................................................................................... 113
11 MOVITOOLS
11.1 About MOVITOOLS
®
MotionStudio Operation............... ... ... ... .... ... ... ... .... ... ... ... ... .... ... 114
®
MotionStudio ................................. ... .... ................... 114
11.2 First steps .................................................................................................. 115
11.3 Starting the software and creating the project............................................ 115
11.4 Establishing communication and scanning the network............................. 115
11.5 Configuring units........................................................................................ 116
11.6 Connection mode....................................................................................... 117
11.7 Serial (RS-485) communication via interface adapter................................ 119
11.8 Communication SBus (CAN) via interface adapter ................................... 125
11.9 Communication via Ethernet...................................................................... 131
11.10 Executing functions with the units....................... ... .................................... 138
12 Error Diagnostics............................................................................................... 140
12.1 Diagnostic procedure................................................................................. 140
12.2 Error list in gateway operation.................................................................... 143
13 Technical Data.................................................................................................... 144
13.1 DFS21B for MOVIDRIVE
13.2 DFS21B safety module for MOVIDRIV E
®
B, MOVITRAC® B and UOH11B gateway ...... 144
®
MDX61B and MOVITRAC® B..145
13.3 Dimension drawing of DFS2 1B in UOH 11 B ga te way hou sin g...... ... .......... 146
14 Index.................................................................................................................... 147
4
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
General Information
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
How to use the manual
1
1 General Information
Handbuch
1.1 How to use the manual
The manual is part of the product and contains important information on operation and service. The manual is written for all employees who assemble, install, startup, and ser­vice the product.
The manual must be accessible and legible. Make sure that persons responsible for the system and its operation, as well as persons who work independently on the unit, have read through the manual carefully and understood it. If you are unclear about any of the information in this documentation, or if you require further information, contact SEW­EURODRIVE.
1.2 Structure of the safety notes
1.2.1 Meaning of the signal words
The following table shows the grading and meaning of the signal words for safety notes, notes on potential risks of damage to property, and other notes.
Signal word Meaning Consequences if disregarded
DANGER Imminent danger Severe or fatal injuries WARNING Possible dangerous situation Severe or fatal injuries CAUTION Possible dangerous situation Minor injuries
NOTICE Possible damage to property Damage to the drive system or its envi-
INFORMATION Useful information or tip: Simplifies the
handling of the drive system.
ronment
1.2.2 Structure of the section-related safety notes
Section safety notes do not apply to a specific action, but to several actions pertaining to one subject. The used symbols indicate either a general or a specific hazard.
This is the formal structure of a section safety note:
SIGNAL WORD
Type and source of danger. Possible consequence(s) if disregarded.
Measure(s) to prevent the danger.
1.2.3 Structure of the embedded safety notes
Embedded safety notes are directly integrated in the instructions just before the descrip­tion of the dangerous action.
This is the formal structure of an embedded safety note:
SIGNAL WORD Nature and source of hazard.
Possible consequence(s) if disregarded. – Measure(s) to prevent the danger.
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
5
1
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
General Information
Rights to claim under limited warranty
1.3 Rights to claim under limited warranty
A requirement of fault-free operation and fulfillment of any rights to claim under limited warranty is that you adhere to the information in the manual. Therefore, read the manual before you start operating the device.
1.4 Exclusion of liability
You must comply with the information contained in the MOVIDRIVE® / MOVITRAC documentation to ensure safe operation and to achieve the specified product character­istics and performance requirements. SEW-EURODRIVE assumes no liability for injury to persons or damage to equipment or property resulting from non-observance of the operating instructions. In such cases, any liability for defects is excluded.
1.5 Copyright
© 2010 - SEW-EURODRIVE. All rights reserved. Copyright law prohibits the unauthorized duplication, modification, distribution, and use
of this document, in whole or in part.
®
6
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
Other applicable documentation
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
2 Safety Notes
2.1 Other applicable documentation
Installation and startup only by trained personnel observing the relevant accident prevention regulations and the following documents:
– "MOVIDRIVE – "MOVITRAC
Read through this manual carefully before you commence installation and startup of the DFS21B option.
You must adhere to the information in the documentation as a prerequisite to fault­free operation and fulfillment of warranty claims.
2.2 General safety notes for bus systems
This communication system allows you to adapt the MOVIDRIVE® inverter to your ap­plication. As with all bus systems, there is a danger of invisible, external (as far as the inverter is concerned) modifications to the parameters which give rise to changes in the unit behavior. This may result in unexpected (not uncontrolled) system behavior.
®
MDX60B / 61B operating instructions
®
B" operating instructions
Safety Notes
2
2.3 Safety functions
The MOVIDRIVE® MDX60B/61B and MOVITRAC® B drive inverters may not perform safety functions without higher-level safety systems. Use higher-level safety systems to ensure protection of equipment and personnel.
For safety applications, refer to the information in the following publications.
Safe disconnection for MOVIDRIVE
Use only those components in safety applications that were explicitly designed and de­livered for this purpose by SEW-EURODRIVE.
2.4 Hoist applications
MOVIDRIVE® MDX60B/61B and MOVITRAC® B are not designed for use as a safety device in hoist applications..
Use monitoring systems or mechanical protection devices as safety equipment to avoid possible damage to property or injury to people.
2.5 Product names and trademarks
The brands and product names contained within this manual are trademarks or regis­tered trademarks of the titleholders.
®
/ MOVITRAC® B
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
7
2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
2.6 Disposal
Safety Notes
Disposal
Observe the applicable national regulations.
Dispose of the following materials separately in accordance with the country-specific regulations in force, as:
Electronics scrap
Plastic
Sheet metal
Copper
8
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
3 Introduction
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
3.1 Content of this manual
This user manual illustrates:
How to install the 'DFS21B PROFINET IO with PROFIsafe' option card in the MOVIDRIVE
How to use the 'DFS21B PROFINET IO with PROFIsafe' option card in the MOVITRAC
The startup of MOVIDRIVE
The start up of MOVITRAC
The configuration of PROFINET via GSD files
The operation of MOVITOOLS
Diagnostics via integrated web server
Introduction
Content of this manual
®
MDX61B inverter.
®
B frequency inverter and in the UOH11B gateway housing.
®
B in the PROFINET fieldbus system.
®
B connected to the PROFINET gateway.
®
MotionStudio via PROFINET.
3
3.2 Additional documentation
For information on how to connect MOVIDRIVE® / MOVITRAC® B easily and effectively to the PROFINET IO fieldbus system, you should request the following additional publi­cations about fieldbus technology:
•'MOVIDRIVE
•MOVITRAC
®
®
B / MOVIDRIVE® B system manual
Manuals on safe disconnection for MOVITRAC
Manuals on safe disconnection for MOVIDRIVE
Apart from describing the fieldbus parameters and the corresponding coding, the MOVIDRIVE
®
fieldbus unit profile manual and the MOVITRAC® B system manual pro-
vide examples to illustrate various control concepts and possible applications. The MOVIDRIVE
®
rameters that can be read and written via the different communication interfaces such as system bus, RS485 and via the field bus interface.
3.3 Characteristics
With the DFS21B PROFINET IO with PROFIsafe option and its powerful universal field­bus interface, the MOVIDRIVE quency inverter allow for a connection to higher-level automation systems via PROFINET IO.
Fieldbus Unit Profile' manual
®
B
®
B
fieldbus unit profile manual provides a list of all the drive inverter pa-
®
MDX61B drive inverter and the MOVITRAC® B fre-
®
3.3.1 MOVIDRIVE
B, MOVITRAC® B and PROFINET
The behavior of the inverter which forms the basis of PROFINET operation, the so­called unit profile, is independent of any particular fieldbus and is therefore a uniform feature. This allows the user to develop fieldbus-independent drive applications. This makes it much easier to change to other bus systems, such as DeviceNet (option DFD).
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
9
3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
3.3.2 Access to all information
Introduction
Characteristics
MOVIDRIVE and functions via the PROFINET interface. The drive inverter is controlled via fast, cyclic process data. Via this process data channel, you can enter setpoints such as the set­point speed, ramp generator time for acceleration / deceleration, etc. as well as trigger various drive functions such as enable, control inhibit, normal stop, rapid stop, etc. At the same time you can also use this channel to read back actual values from the drive inverter, such as actual speed, current, unit status, error number or reference signals.
3.3.3 Monitoring functions
Using a fieldbus system requires additional monitoring functions for the drive technolo­gy, for example, time monitoring of the fieldbus (fieldbus timeout) or rapid stop concepts. You can, for example, adapt the monitoring functions of MOVIDRIVE specifically to your application. You can determine, for instance, which of the drive in­verter’s error responses should be triggered in the event of a bus error. A rapid stop makes sense for many applications, although this can also be achieved by 'freezing' the last setpoints so the drive continues operating with the most recently valid setpoints (such as with a conveyor belt). As the range of functions for the control terminals is also guaranteed in fieldbus mode, you can continue to implement rapid stop concepts using the terminals of the drive inverter, irrespective of the fieldbus used.
®
MDX61B and MOVITRAC® B offer digital access to all drive parameters
®
/ MOVITRAC
®
3.3.4 Diagnostics
The MOVIDRIVE numerous diagnostics options for startup and service. You can, for instance, use the fieldbus monitor integrated in MOVITOOLS sent from the higher-level controller as well as the actual values. The integrated Web server allows you to access the diagnostic values using a standard browser.
3.3.5 Fieldbus monitor
Furthermore, you are supplied with a variety of additional information about the status of the fieldbus interface. The fieldbus monitor function in conjunction with the MOVITOOLS setting all drive parameters (including the fieldbus parameters) and for displaying the fieldbus and device status information in detail.
®
drive inverter and the MOVITRAC® B frequency inverter offer you
®
MotionStudio to control setpoint values
®
MotionStudio PC software offers you an easy-to-use diagnostic tool for
10
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
Integrated Safety Technology
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Safety concept for PROFIsafe fieldbus interfaces
4 Integrated Safety Technology
4.1 Safety concept for PROFIsafe fieldbus interfaces
Within the DFS.. PROFIsafe interface, PROFIsafe fieldbus interfaces are equipped with an integrated safety-oriented electronics components with a failsafe output (F-DO). The safety concept of this subassembly is based on the fact that there is a safe state for all safety-oriented process values. For the DFS.. PROFIsafe interface, this is the value "0" for the F-DO output.
The following requirements are fulfilled by means of a 2-channel redundant system structure of the safety component with suitable monitoring mechanisms:
SIL3 according to EN 61508
Category 4 according to EN 954-1
Performance level e according to EN ISO 13849-1 When the system detects a fault, the system responds by reverting to a safe status.
This makes the safety function available in the form of a failsafe input connected to a higher-level safety control via the PROFIsafe communication. The safe output on the safety component of the DFS interface is neither evaluated locally nor processed logically.
The safe output F-DO can be used to disable the 24 V input "Safe stop" at X17 of the MOVIDRIVE Refer to the safety concept described in the following for MOVIDRIVE installation instructions in this manual.
®
/ MOVITRAC® inverter and in this way safely disconnects the drive.
®
/MOVITRAC® inverters as well as all safety notes, requirements and
4
WARNING
The safety function of MOVIDRIVE® B/ MOVITRAC® B is only permitted for ap­plications up to category 3 according to EN 954-1.
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
11
4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Integrated Safety Technology
Safety concept for MOVIDRIVE® and MOVITRAC®
4.2 Safety concept for MOVIDRIVE® and MOVITRAC
In case of danger, any potential risk related to a machine must be eliminated as quickly as possible. Standstill with restart prevention is generally the safe condition for preventing dangerous movements.
The MOVIDRIVE ized by the optional connection of an external failsafe, approved emergency stop re­lay (according to safety category 3, EN 954-1). The safety relay disconnects all active elements (disconnection of the safety-relevant 24 V power supply of the output stage control) that generate the pulse trains to the power output stage (IGBT) when a con­nected control device (E-STOP button with latching function) is activated.
Disconnecting the 24 V at the positive and negative poles ensures that the supply voltages required for operating the inverter and consequently for generating a rotat­ing field of pulse patterns (which allow the generation of a rotating field) are safely interrupted. Automatic restart is prevented in this way.
Instead of galvanic separation of the drive from the power supply by means of relays or switches, the disconnection of the 24 V supply described here safely prevents the control of the power semiconductors in the drive inverter. This process disconnects the rotating field generation for the respective motor. The individual motor cannot de­velop any torque in this state even though the line voltage is still present.
The requirements for the safety relay are clearly defined in the following sections and must be strictly observed.
Using a suitable external circuit via a safety relay with
Approval for at least safety category 3 Disconnection for at least safety category 3
Allows for operating the MOVIDRIVE ers with safe disconnection according to stop category 0 or 1 (to EN 60204-1) and ensures protection against restart according to safety category 3 (to EN 954-1).
®
MDX60B/61B and MOVITRAC® B drive inverters are character-
®
MDX60B/61B and MOVITRAC® B invert-
®
4.2.1 Limitations
WARNING
If the DC 24 V link voltage is safely disconnected a t the positive pole only, no test pulses must be applied to this pole in disconnected condition.
The safety concept is only suitable for performing mechanical work on driv­en system/machine components.
A system/machine-specific risk analysis must be carried out by the sys­tem/machine manufacturer and taken into account for the use of the MOVIDRIVE
When the 24 V voltage supply is disconnected, mains supply voltage is still present on the drive inverter’s DC link.
If work is carried out on the electrical section of the d rive syst em, the supply voltage must be disconnected using an external maintenance switch.
®
B/ MOVITRAC® B inverter.
12
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
Integrated Safety Technology
S24V
S0V24
M
CAN
RS485
Binary
OUT
Binary
IN
Analog
IN
Analog
OUT
SNT
HV
SNT
NV
Uz+ Uz-
PWM
Uz-
Uz+
24V
GND
24V
SNT
S
24
S0V24
[1]
[2]
[17]
[16]
[15]
[14] [13 ]
[12]
[11]
[10]
[9]
[8]
[7]
[6]
[5]
L1L2 L3
24V ext.
24V ext./ 24V int.
24V
int.
24V
int.
[4]
[3]
GND
V
I
MOVIDRIVE
®
B
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Safety concept for MOVIDRIVE® and MOVITRAC®
4.2.2 Schematic representation of the safety concept using the example of MOVIDRIVE® B
4
[1] High voltage switched-mode power supply
[2] Low voltage switched-mode power supply
[3] Safety relay (external) approved for at least category 3 according to EN 954-1
[4] Safety-oriented 24 V voltage supply
[5] Safety switched-mode power supply (SNT)
[6] Electrical isolation
[7] Safety circuit
[8] Feedback to the processor core: Voltage supply for output stage control OK (not in safety circuit)
[9] Voltage supply for control of power transistors
[10] DC 24 V safety switched-mode power supply disconnected / brake applied (not in safety circuit)
[11] Motor
[12] Power section
[13] Temperature detection
[14] Position detection
[15] Pulse width modulated signals for the output stage
[16] Computer core
[17] Fieldbus connection
INFORMATION
This basic representation also applies to MOVITRAC®B.
61519AXX
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
13
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Safety Conditions
Installation requirements
5 Safety Conditions
INFORMATION
For information on the safety-relevant conditions, refer to the following documents:
•"MOVIDRIVE
"MOVITRAC
5.1 Installation requirements
5.1.1 F-DO connection
®
MDX60B/61B Safe Disconnection – Conditions" manual
®
B Safe Disconnection – Conditions" manual
Only connect cables with a core cross section of a minimum of 0.25 mm up to a maximum 1 mm X31:2) of the DFS21B option. Clamping without conductor end sleeves is possible in accordance with IEC 60999.
The maximum current load of the F-DO safety-related binary output is DC 1 A.
The safety-related binary output is 2-pole, designed as P-M switch, and controlled via PROFIsafe
An actuator must generally be connected with the safe output F-DO with a 2-pole connection between the P switch output and the M switch output (F-DO_P and F-DO_M).
It is not permitted to make a 1-pole connection between F-DO_P and the GND refer­ence potential as doing so would cause an error as soon as the output is controlled.
Internal testing of the safe output is cyclical. However, when decoupling takes place, the test pulses at the connection terminals are not visible and need not be taken into account during operation.
5.1.2 DC 24 V voltage supply
The 24 V supply voltage(s) of the DFS21B and all stations connected to the fieldbus must be designed as safety extra-low voltage. The voltage must lie within the limits de­fined in the technical data. In addition, the following voltage values must not be exceed­ed if a fault occurs (according to EN 60950): Max. DC 60 V, max. DC 120 V for 200 ms.
2
(AWG18) to the safety-related binary output F-DO (X31:1,
®
by a higher-level safety control.
2
(AWG23)
14
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
Assembly and Installation Notes
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installing the DFS21B option card in MOVIDRIVE® MDX61B
6 Assembly and Installation Notes
6
This section contains information about assembly and installation of the DFS21B PROFINET IO option card in MOVIDRIVE gateway housing.
®
MDX61B, MOVITRAC® B and the UOH11B
6.1 Installing the DFS21B option card in MOVIDRIVE® MDX61B
INFORMATION
Only SEW-EURODRIVE engineers are allowed to install or remove option cards for MOVIDRIVE
Users may only install or remove option cards for MOVIDRIVE sizes 1 to 6.
You have to insert the DFS21B PROFINET IO option in fieldbus slot [1].
Only use connectors and cables approved for PROFINET IO when cabling.
[1]
®
MDX61B size 0.
®
MDX61B
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
62179AXX
15
6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
6.1.1 Before you start
Assembly and Installation Notes
Installing the DFS21B option card in MOVIDRIVE® MDX61B
Observe the following notes before installing or removing an option card:
Disconnect the inverter from the power. Switch off the DC 24 V and the line voltage.
Take appropriate measures to protect the option card from electrostatic charge (use discharge strap, conductive shoes, etc.) before touching it.
Before installing the option card, remove the keypad and the front cover (MOVIDRIVE
After installing the option card, replace the front cover and the keypad (MOVIDRIVE
Keep the option card in its original packaging until immediately before you are ready to install it.
Hold the option card by its edges only. Do not touch any of the components.
®
MDX60B/61B operating instructions, section 'Installation').
®
MDX60B/61B operating instructions, sec. "Installation").
16
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
Assembly and Installation Notes
1.
4.
4.
1.
2.
3.
3.
3.
2.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installing the DFS21B option card in MOVIDRIVE® MDX61B
6.1.2 Basic procedure for installing and removing an option card (MDX61B, BG 1 - 6)
6
60039AXX
1. Remove the two retaining screws holding the card retaining bracket. Pull the card re­taining bracket out evenly from the slot (do not twist!).
2. Remove the 2 retaining screws from the black cover plate on the card retaining bracket. Remove the black cover plate.
3. Position the option card onto the retaining bracket so that the three retaining screws fit into the corresponding bores on the card retaining bracket.
4. Insert the retaining bracket with the installed option card into the slot, pressing slight­ly so it is seated properly. Secure the card retaining bracket with the two retaining screws.
5. To remove the option card, follow the instructions in reverse order.
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
17
6
X45
X46
1
23456HL
FSC11B
S1
OFF
ON
7
S2
X44
X26
1234567
X24
H1
H2
X12
1 2 3 4 5 6 7 8
24V IO
DC 24 V
+
9
GND
=
X30X32
Def IP
PROFINET IO
AS
01
DFS21B
X31
FSR FDOBF
12 34 56
FDO LS PS
01
2 2 2 2
0 1 2 3
2 2 2
4 5 6
2
7
2
8
2
9
F-ADDRESS
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Assembly and Installation Notes
Installing the DFS21B option card in MOVITRAC® B
6.2 Installing the DFS21B option card in MOVITRAC® B
INFORMATION
•MOVITRAC® B does not require a special firmware status.
Only SEW-EURODRIVE personnel may install or remove options cards for MOVITRAC
6.2.1 Connecting a system bus (SBus 1) between MOVITRAC® B and the DFS21B option
®
B.
X46 X26 Terminal assignment
X46:1 X26:1 SC11 SBus +, CAN high
X46:2 X26:2 SC12 SBus -, CAN low
X46:3 X26:3 GND, CAN GND
X46:7 X26:7 DC 24 V
X12 Terminal assignment
X12:8 DC+24 V input
X12:9 GND reference potential for binary inputs
To simplify cabling, the DFS21B option can be supplied with DC 24 V from X46:7 of
®
B to X26:7.
®
B must be supplied with DC 24 V at terminals X12:8 and X12:9 when it
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
18
MOVITRAC MOVITRAC
supplies the DFS21B option. Activate the system bus terminating resistor at the FSC11B option (S1 = ON).
62409AXX
Assembly and Installation Notes
X45
X46
1
23456HL ^
FSC11B
MOVITRAC® B
S1
OFF
ON
7
S2
X44
X45
X46
1
23456HL ^
FSC11B
MOVITRAC® B
S1
OFF
ON
7
S2
X44
X45
X46
1
23456HL^
FSC11B
MOVITRAC® B
S1
OFF
ON
7
S2
X44
X26
1234567
X24
H1
H2
X12
1 2 3 4 5 6 7 8
24V IO
DC 24 V
-
+
9
GND
=
X30X32
Def IP
PROFINET IO
AS
01
DFS21B
X31
FSR FDOBF
12 34 56
FDO LS PS
01
2 2 2 2
0 1 2 3
2 2 2
4 5 6
2
7
2
8
2
9
F-ADDRESS
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installing the DFS21B option card in MOVITRAC® B
6.2.2 Connecting a system bus (SBus 1) between several MOVITRAC® B units
6
MOVITRAC® B DFS21B via UOH11B gateway housing X46 Terminal assignment X26 Terminal assignment
X46:1 SC11 (System bus high, incoming) X26:1 SC11 SBus +, CAN High
62408AXX
X46:2 SC12 (System bus low, incoming) X26:2 SC12 SBus -, CAN Low
X46:3 GND (System bus reference) X26:3 GND, CAN GND
X46:4 SC21 (System bus high, outgoing)
X46:5 SC22 (System bus low, outgoing)
X46:6 GND (System bus reference)
X46:7 DC 24 V X26:7 DC 24 V
X12 Terminal assignment
X12:8 DC+24 V input
X12:9 GND reference potential for binary inputs
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
19
6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Assembly and Installation Notes
Installing the DFS21B option card in MOVITRAC® B
Please note:
Use a 2x2 core twisted pair and shielded copper cable (data transmission cable with braided copper shield). Connect the shield flatly on both sides of the electronics shield clamp of MOVITRAC ble must meet the following specifications:
– Cable cross section 0.25 mm – Line resistance 120 Ω at 1 MHz – Capacitance per unit length 40 pF/m at 1 kHz
Suitable cables are CAN or DeviceNet cables.
The permitted total cable length depends on the baud rate setting of the SBus: – 250 kBaud: 160 m
– 500 kBaud: 80 m – 1000 kBaud: 40 m
Connect the system bus terminating resistor (S1 = ON) at the end of the system bus connection. Switch off the terminating resistor on the other units (S1 = OFF). The DFS21B gateway must always be connected either at the beginning or the end of the system bus connection and feature a permanently installed terminating resistor.
®
B. Also connect the ends of the shield to GND. The ca-
2
(AWG18) ... 0.75 mm2 (AWG23)
INFORMATION
There must not be any potential displacement between the units connected with the SBus. Take suitable measures to avoid potential displacement, such as con­necting the unit ground connectors using a separate cable.
Point-to-point wiring is not permitted.
20
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
Assembly and Installation Notes
X26
1
23456
7
SEW Drive
UOH11B
DC+24 V GND
X24
H1
H2
SC11 Systembus +, CAN high
SC12 Systembus -, CAN low
GND, CAN GND
X30X32
Def IP
PROFINET IO
AS
01
DFS21B
X31
FSR FDOBF
12 34 56
FDO LS PS
01
2 2 2 2
0 1 2 3
2 2 2
4 5 6
2
7
2
8
2
9
F-ADDRESS
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installing the DFS21B/UOH11B gateway
6.3 Installing the DFS21B/UOH11B gateway
The following figure shows the connection of the DFS21B option via the UOH11B:X26 gateway housing.
INFORMATION
Only SEW-EURODRIVE engineers are allowed to install or remove option cards in/from the UOH11B gateway housing.
6
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
UOH11B gateway housing X26 Terminal assignment
X26:1 SC11 System bus +, CAN high
X26:2 SC12 system bus -, CAN low
X26:3 GND, CAN GND
X26:4 Reserved
X26:5 Reserved
X26:6 GND, CAN GND
X26:7 DC 24 V
The gateway housing is powered with DC 24 V at X26. Connect the system bus terminating resistor at the end of the system bus connection.
62407AXX
21
6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Assembly and Installation Notes
Connection and terminal description DFS21B option
6.4 Connection and terminal description DFS21B option
Part number PROFINET IO fieldbus interface option, type DFS21B: 1821 183 6
INFORMATION
The "DFS21B PROFINET IO fieldbus interface " option is only possible in conjunc­tion with MOVIDRIVE
Plug the DFS21B option into the fieldbus slot.
®
MDX61B, not with MDX60B.
Front view of DFS11B
DFS21B
FSR FDOBF
2 2 2 2 2 2 2 2 2 2
FDO LS PS
0 1 2 3 4 5 6 7 8 9
12 34
X31
56
F-ADDRESS
01
X30X32
Description
Diagnostic LEDs: R
X31 connection 1 (F_DO_M)
F-ADDRESS: DIP switch for setting the failsafe address
X30: Ethernet connection LED Link (green) LED Activity (yellow)
DIP switch Terminal
FS MP FDO
2 (F_DO_P) 3 (GND) 4 (24 V_LS) 5 (GND) 6 (24 V_PS)
0
2
1
2
2
2
3
2
4
2
5
2
6
2
7
2
8
2
9
2
Function
RUN - Component status (green) Failsafe status - Status of the safety option (green during standard operation) BUS FAULT - Bus status (red if a fault occurs, else disabled) Failsafe output - Status of the safe output (orange)
Safe output Safe output Supply of the safe output Supply of the safe output Power supply to control electronics Power supply to control electronics
Significance: 1 Significance: 2 Significance: 4 Significance: 8 Significance: 16 Significance: 32 Significance: 64 Significance: 128 Significance: 256 Significance: 512
1)
1)
X32: Ethernet connection LED Link (green) LED Activity (yellow)
Def IP
AS
01
PROFINET IO
62396AXX
1) The 24 V supply voltage(s) of the DFS21B and all stations connected to the fieldbus must be designed as safety extra-low voltage. The voltage must lie within the limits defined in the technical data. In addition, the following voltage values must not be exceeded if a fault occurs (according to EN 60950): Max. DC 60 V, max. DC 120 V for 200 ms.
22
DIP switch AS
DEF IP
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
Auto-setup for gateway operation Resets the address parameters to the following default values:
IP address: 192.168.10.4
Subnet mask: 255.255.255.0
Gateway: 1.0.0.0
PROFINET device name: PNETDeviceName_MACID
Assembly and Installation Notes
X24
H1
H2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Wiring diagrams for safe technology
6
Front view of MOVITRAC
®
B,
Description Function
DFS21B and UOH11B
LED H1 (red) LED H2 (green)
X24 X terminal
System bus error (only for gateway functions)
Reserved
RS485 interface for diagnostics via PC and MOVITOOLS MotionStudio (only for MOVITRAC
58129axx
6.5 Wiring diagrams for safe technology
6.5.1 Individual wiring of MOVIDRIVE® MDX60B/61B and MOVITRAC® B
Voltage
supply
24V
MOVIDRIVE® B MOVITRAC
®
B
X31:1 - F-DO_M
DFS21B
12
GND
34 56
F-ADDRESS
01
+
=
FSR FDOBF
X31
2 2 2 2 2 2 2 2 2 2
FDOFDO LS PSGND
0 1 2 3 4 5 6 7 8 9
X31:2 - F_DO_P
[1]
®
®
B)
Cable specification
X30X32
Binary signal reference potential
Reference DC +24 V input safe stop
DC +24 V input safe stop
DC +24 V output
Def IP
AS
01
PROFINET IO
62410AEN
X17:
VO24
1 DGND
234
SVI24
SOV24
[1] The 24 V supply voltage(s) of the DFS21B and all stations connected to the fieldbus must be
designed as safety extra-low voltage. The voltage must lie within the limits defined in the technical data. In addition, the following voltage values must not be exceeded if a fault occurs (according to EN 60950): Max. DC 60 V, max. DC 120 V for 200 ms.
2
Only connect cables with a core cross section of a minimum of 0.25 mm
2
to a maximum 1 mm
(AWG18) to the safety-related binary output F-DO (X31:1, X31:2)
(AWG23) up
of the DFS21B option. Clamping without conductor end sleeves is possible in accor­dance with IEC 60999. The maximum line length is 30 m.
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
23
6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Assembly and Installation Notes
Wiring diagrams for safe technology
F-DO connection The safety-related binary output F-DO is 2-pole, designed as P-M switch, and con-
trolled via PROFIsafe
An actuator must generally be connected with the safe output F-DO with a 2-pole connection between the P switch output and the M switch output (F-DO_P and F-DO_M).
It is not permitted to make a 1-pole connection between F-DO_P and the GND refer­ence potential as doing so would cause an error as soon as the output is controlled.
Internal testing of the safe output is cyclical. However, when decoupling takes place, the test pulses at the connection terminals are not visible and need not be taken into account during operation.
Internal tests and monitoring processes are able to detect various external faults: When the output is switched on, the following faults can be detected:
Short circuit between P output and reference potential
Short circuit between M output and DC +24 V supply voltage
Short circuit between P output and M output
When the output is switched off, the following faults can be detected:
Short circuit between P output and reference potential
Short circuit between M output and reference potential
Short circuit between P output and DC +24 V supply voltage
Short circuit between M output and DC +24 V supply voltage
®
by a higher-level safety controller.
Whenever the system detects a fault, it reverts to a safe status, i.e. all safety-related pro­cess values (F-DO) are set to "0". In addition, the safety component is passivated. The fault is indicated by the "FS" LED (failsafe status) ( page 34).
The 24 V supply voltage(s) of the DFS21B and all stations connected to the fieldbus must be designed as safety extra-low voltage. The voltage must lie within the limits de­fined in the technical data. In addition, the following voltage values must not be exceed­ed if a fault occurs (according to EN 60950): Max. DC 60 V, max. DC 120 V for 200 ms.
24
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
Assembly and Installation Notes
1 DGND
X17:
Binary signal reference potential
Reference DC +24 V input safe stop
DC +24 V input safe stop
DC +24 V output
VO24
SOV24
SVI24
234
MOVIDRIVE® B MOVITRAC
®
B
1 DGND
X17:
Binary signal reference potential
Reference DC +24 V input safe stop
DC +24 V input safe stop
DC +24 V output
VO24
SOV24
SVI24
234
MOVIDRIVE® B MOVITRAC
®
B
1 DGND
X17:
Binary signal reference potential
Reference DC +24 V input safe stop
DC +24 V input safe stop
DC +24 V output
VO24
SOV24
SVI24
234
MOVIDRIVE® B MOVITRAC
®
B
DFS21B
01
2 2 2 2
0 1 2 3
2 2 2
4 5 6
2
7
2
8
2
9
F-ADDRESS
X31
FSR FDOBF
12 34 56
FDOFDO LS PSGND
GND
24V
+
=
X31:1 - F-DO_M X31:2 - F_DO_P
Voltage
supply
[1]
X30X32
Def IP
PROFINET IO
AS
01
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Wiring diagrams for safe technology
6.5.2 Group wiring of MOVIDRIVE® MDX60B/61B and MOVITRAC® B
6
[1] The 24 V supply voltage(s) of the DFS21B and all stations connected to the fieldbus must be
designed as safety extra-low voltage. The voltage must lie within the limits defined in the technical data. In addition, the following voltage values must not be exceeded if a fault occurs (according to EN 60950): Max. DC 60 V, max. DC 120 V for 200 ms.
WARNING
Observe that the maximum current load of the F-DO safety-related binary output is DC 1 A.
The DFS21B option card might be destroyed if the maximum current load (DC 1 A) of the safety-related binary output F-DO is exceeded. In this case, the safety function of MOVIDRIVE
®
B / MOVITRAC® B is not ensured.
62411AEN
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
25
6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Assembly and Installation Notes
Wiring diagrams for safe technology
Cable specification
Only connect cables with a core cross section of a minimum of 0.25 mm2 (AWG23) up
2
to a maximum 1 mm
(AWG18) to the safety-related binary output F-DO (X31:1, X31:2) of the DFS21B option. Clamping without conductor end sleeves is possible in accor­dance with IEC 60999.
Power consumption X17:4
Size MOVIDRIVE® B MOVITRAC® B
03 W
15 W
2, 2S 6 W
3 7.5 W
48 W
5 10 W
66 W -
26
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
6.6 Pin assignment
[3]
[2]
[1]
2
3
6
1
[6]
AB
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Use prefabricated, shielded RJ45 plug connectors compliant with IEC 11801 edition 2.0, category 5.
Assembly and Installation Notes
Pin assignment
6
Figure 1: Pin assignment of an RJ45 plug connector
A = Front view B = View from back [1] Pin 1 TX+ Transmit Plus [2] Pin 2 TX- Transmit Minus [3] Pin 3 RX+ Receive Plus [6] Pin 6 RX- Receive Minus
Connection between MOVIDRIVE
To connect the DFS21B, connect the Ethernet interface X30 or X32 (RJ45 connector) using a category 5, class D shielded twisted-pair cable in compliance with IEC 11801 edition 2.0. The integrated switch provides support for realizing a line topology.
INFORMATION
According to IEC 802.3, the maximum cable length for 10 / 100 Mbaud Ethernet (10BaseT/100BaseT), e.g. between DFS21B and switch, is 100 m.
VLAN tag prioritized Ethernet frames with the frame identification 8892 for the real-time data exchange with PROFINET IO. This requires switched net­works. The switches must support prioritization. Hubs are not permitted. Data transmission takes place using the full duplex process with 100 Mbit. Detailed in­formation on cabling can be found in the 'PROFINET installation guideline' publica­tion that was issued by the PROFINET user organization.
®
B / MOVITRAC® B / Ethernet
are used
hex
54174AXX
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
27
6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Assembly and Installation Notes
Shielding and routing bus cables
6.7 Shielding and routing bus cables
Only use shielded cables and connection elements that meet the requirements of cate­gory 5, class D according to IEC 11801 edition 2.0.
Correct shielding of the bus cable attenuates electrical interference that can occur in in­dustrial environments. The following measures ensure the best possible shielding:
Manually tighten the mounting screws on the connectors, modules, and equipotential bonding conductors.
Use only connectors with a metal housing or a metalized housing.
Connect the shielding in the connector over a wide surface area.
Apply the shielding of the bus cable on both ends.
Route signal and bus cables in separate cable ducts. Do not route them parallel to power cables (motor leads).
Use metallic, grounded cable racks in industrial environments.
Route the signal cable and the corresponding equipotential bonding close to each other using the shortest possible route.
Avoid using plug connectors to extend bus cables.
Route the bus cables closely along existing grounding surfaces.
WARNING
In case of fluctuations in the ground potential, a compensating current may flow via the bilaterally connected shield that is also connected to the protective earth (PE). Make sure you supply adequate equipotential bonding in accordance with relevant VDE reg­ulations in such a case.
28
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
Assembly and Installation Notes
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
TCP/IP addressing and subnetworks
6.8 TCP/IP addressing and subnetworks
Introduction The settings for the address of the IP protocol are made using the following parameters:
IP address
Subnet mask
Standard gateway
The addressing mechanisms and subdivision of the IP networks into subnets are ex­plained in this chapter to help you set the parameters correctly.
IP address The IP address is a 32-bit value that uniquely identifies a node in the network. An IP ad-
dress is represented by four decimal numbers separated by decimal points. Example: 192.168.10.4 Each decimal number stands for one byte (= 8 bits) of the address and can also be rep-
resented using binary code ( following table).
Byte 1 Byte 2 Byte 3 Byte 4
11000000 . 10101000 . 00001010 . 00000100
6
The IP address comprises a network address and a node address ( following table).
Network address Node address
192.168.10 4
The part of the IP address that denotes the network and the part that identifies the node is determined by the network class and the subnet mask.
Node addresses cannot consist of only zeros or ones (binary) because they represent the network itself or a broadcast address.
Network classes The first byte of the IP address determines the network class and as such represents
the division into network addresses and node addresses.
Value range Byte 1
0 ... 127 A 10.1.22.3 10 = Network address
128 ... 191 B 172.16.52.4 172.16 = Network address
192 ... 223 C 192.168.10.4 192.168.10 = Network address
Network class
Complete network address (Example)
Meaning
1.22.3 = node address
52.4 = node address
4 = node address
This rough division is not sufficient for a number of networks. They also use an explicit, adjustable subnet mask.
Subnet mask A subnet mask is used to divide the network classes into even finer sections. Like the
IP address, the subnetwork mask is represented by four decimal numbers separated by decimal points. Every decimal number stands for one byte.
Example: 255.255.255.128 Each decimal number stands for one byte (= 8 bits) of the subnet mask and can also be
represented using binary code ( following table).
Byte 1 Byte 2 Byte 3 Byte 4
11111111 . 11111111 . 11111111 . 10000000
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
29
6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Assembly and Installation Notes
TCP/IP addressing and subnetworks
If you compare the IP addresses with the subnetwork masks, you see that in the binary representation of the subnetwork mask all ones determine the network address and all the zeros determine the station address ( following table).
Byte 1 Byte 2 Byte 3 Byte 4
IP address
Subnet mask
The class C network with the address 192.168.10. is further subdivided into
255.255.255.128 using the subnet mask. Two networks are created with the address
192.168.10.0 and 192.168.10.128.
The following node addresses are permitted in the two networks:
192.168.10.1 ... 192.168.10.126
192.168.10.129 ... 192.168.10.254
The network nodes use a logical AND operation for the IP address and the subnet mask to determine whether there is a communication partner in the same network or in a dif­ferent network. If the communication partner is in a different network, the standard gate­way is addressed.
decimal 192 . 168. . 10 . 128
binary 11000000 . 10101000 . 00001010 . 10000000
decimal 255 . 255 . 255 . 128
binary 11111111 . 11111111 . 11111111 . 10000000
Standard gateway The standard gateway is also addressed via a 32-bit address. The 32-bit address is rep-
resented by four decimal numbers separated by decimal points. Example: 192.168.10.1 The standard gateway establishes a connection to other networks. In this way, a net-
work node that wants to address another node can use a logical AND operation with the IP address and the subnetwork mask to decide whether the desired node is located in the same network. If this is not the case, the node addresses the standard gateway (router), which must be part of the actual network. The standard gateway then takes on the job of transmitting the data packages.
30
Manual – DFS21B Fieldbus Interface PROFINET IO with PROFIsafe (Safe Stop)
Loading...
+ 119 hidden pages