Schneider Electric PM5100 User Manual

PQS
PowerLogic™ PM5100 Series Power and Energy Meter
User Guide
EAV15105 - EN03 04/2014
Safety Information
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure .
The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
Please note
WARNING indicates a potentially hazardous situation which, if not avoided, can
result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, can
result in minor or moderate injury.
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this signal word.
Electrical equipment should be installed, operated, serviced and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.
PowerLogic™ PM5100 series user guide Table of Contents
Chapter 1: Introduction Power and Energy Meter Hardware ................................................................................. 9
Parts and Accessories .................................................................................................. 9
Box Contents ................................................................................................................ 9
Firmware .......................................................................................................................... 9
Chapter 2: Safety Precau-
tions
Chapter 3: Hardware Refer-
ence
Chapter 4: Front panel dis-
play and meter setup
Before You Begin ........................................................................................................... 11
Notices ........................................................................................................................... 11
Models, Features and Options ....................................................................................... 13
Functions and Characteristics ........................................................................................ 13
Technical Specifications ................................................................................................. 14
Before you begin ............................................................................................................ 16
Safety precautions .......................................................................................................... 16
Dimension ......................................................................................................................17
Meter mounting .............................................................................................................. 17
Mounting the PM5100 ................................................................................................. 18
Meter wiring .................................................................................................................... 19
Recommended cables ................................................................................................ 20
Wiring Diagrams ............................................................................................................. 21
Power system ................................................................................................................. 22
Direct connect voltage limits ....................................................................................... 22
Voltage and current input wiring ................................................................................. 24
Balanced system considerations ................................................................................ 25
Control power wiring ....................................................................................................... 25
Communications ............................................................................................................. 25
Serial communications ................................................................................................ 25
Digital outputs ................................................................................................................. 27
LED indicators ................................................................................................................ 29
Heartbeat / communications LED ............................................................................... 29
Alarm / energy pulsing LED modes ............................................................................ 29
Notification icons ............................................................................................................ 30
Meter screen menus ....................................................................................................... 30
Menu tree .................................................................................................................... 31
Meter setup screen navigation .................................................................................... 32
Front panel meter setup ................................................................................................. 32
Configuring the basic setup parameters ..................................................................... 32
Communications setup ................................................................................................... 34
Setting up serial communications ............................................................................... 34
HMI settings ...................................................................................................................35
Setting up the display .................................................................................................. 35
Setting up regional settings ......................................................................................... 35
Setting up the screen passwords ................................................................................... 36
Lost password ............................................................................................................. 37
Setting the clock ............................................................................................................. 37
Advanced setup .............................................................................................................. 38
Setting up the alarm / energy pulsing LED ..................................................................... 39
Output setup ...................................................................................................................40
Demand setup ................................................................................................................ 40
Alarms setup .................................................................................................................. 41
Remote Meter Setup ...................................................................................................... 41
Chapter 5: Viewing Meter
Data
Viewing meter data from the front panel ........................................................................ 43
Meter data display screens ............................................................................................ 43
Using ION Setup to view or modify configuration data ................................................... 46
Using software to view meter data ................................................................................. 46
Chapter 6: Input / Output Digital output applications ........................................................................................... 47
Digital output setup ..................................................................................................... 47
Alarm / energy pulsing LED setup .................................................................................. 48
© 2014 Schneider Electric All Rights Reserved
5
Table of Contents PowerLogic™ PM5100 series user guide
Chapter 7: Alarms About Alarms ..................................................................................................................51
1-Second Alarms ......................................................................................................... 51
Unary Alarms ...............................................................................................................53
Alarm Priorities ............................................................................................................53
Alarm Setup ...................................................................................................................54
Setting Up 1-Second Alarms .......................................................................................55
Setting Up Unary Alarms .............................................................................................57
Viewing Alarm Activity and History ................................................................................. 57
Viewing Active Alarms and Alarm Counters ................................................................58
Viewing Unacknowledged Alarms and the Alarm History Log .................................... 59
Chapter 8: Measurements
and calculations
Real-time readings ..........................................................................................................61
Energy ............................................................................................................................ 61
Min/max values ............................................................................................................... 61
Power factor ....................................................................................................................61
Power factor min/max convention ...............................................................................62
Power factor sign convention ......................................................................................62
Demand .......................................................................................................................... 63
Power demand calculation methods ...........................................................................63
Current demand ..........................................................................................................65
Predicted demand .......................................................................................................65
Peak demand ..............................................................................................................66
Chapter 9: Power quality Harmonics overview .......................................................................................................67
Total Harmonic Distortion and Total Demand Distortion ............................................. 67
Displaying harmonics data ..............................................................................................68
Viewing harmonics using the front panel .....................................................................68
Viewing TDD ...............................................................................................................69
Viewing THD/thd using the front panel ........................................................................ 69
Chapter 10: Verifying accura-
cy
Testing overview ............................................................................................................. 71
Accuracy test requirements .........................................................................................71
Verifying accuracy test ....................................................................................................73
Energy pulsing considerations ....................................................................................75
Test points ...................................................................................................................76
Typical sources of test errors ......................................................................................76
Chapter 11: Meter resets Front panel meter reset screens ..................................................................................... 77
Global resets ................................................................................................................... 77
Single resets ................................................................................................................... 78
Chapter 12: Maintenance and
Upgrades
Password Recovery ........................................................................................................ 81
Power Meter Memory .....................................................................................................81
Identifying the Firmware Version, Model, and Serial Number ........................................81
Additional Meter Status Information ................................................................................82
Downloading Firmware ...................................................................................................82
Troubleshooting .............................................................................................................. 83
Heartbeat/Comms LED ...............................................................................................83
Getting Technical Support ..............................................................................................84
Register List ....................................................................................................................84
Chapter 13: MID Compliance MID overview ..................................................................................................................85
MID compliance for the meter .........................................................................................85
Specifications relevant to MID ........................................................................................ 85
Safety precautions ..........................................................................................................86
Installation and wiring .....................................................................................................86
Installing the terminal covers ..........................................................................................87
PM5111 default screen ...................................................................................................87
© 2014 Schneider Electric All Rights Reserved6
PowerLogic™ PM5100 series user guide Table of Contents
Meter firmware version ................................................................................................... 88
MID-protected setup parameters .................................................................................... 88
Lock-protected setup parameters ................................................................................... 88
Lock-protected functions ................................................................................................ 88
Setting up the PM5111 ................................................................................................... 89
Basic setup menu ....................................................................................................... 89
Advanced setup menu ................................................................................................ 89
Clock setup menu ....................................................................................................... 89
Passwords setup menu ............................................................................................... 89
Initializing the meter ....................................................................................................... 89
Locking or unlocking the meter ...................................................................................... 89
Setting up lock password ............................................................................................ 90
Glossary Terms ............................................................................................................................. 91
Abbreviations ..................................................................................................................93
© 2014 Schneider Electric All Rights Reserved
7
Table of Contents PowerLogic™ PM5100 series user guide
© 2014 Schneider Electric All Rights Reserved8
PowerLogic™ PM5100 user guide Chapter 1—Introduction
Chapter 1—Introduction
This user guide explains how to operate and configure a PowerLogic™ PM5100 Series Power and Energy Meter.

Power and Energy Meter Hardware

Parts of the meter (rear view)
A Voltage inputs
B Control power
C Current inputs
D Digital output
E Communications port - RS-485(optional)
FGasket

Parts and Accessories

Box Contents

Firmware

Table 1– 1 Meter Models
Description Model Numbers
Power and Energy meter with Integrated Display
PowerLogic
TM
PM5100, PM5110, and PM5111
1. Power and Energy Meter (1)
2. Installation Guide (1)
3. Calibration Certificate (1)
4. Connectors
5. Retainer Clips (2)
This user guide is written to be used with firmware version 01.00.0 and higher. See “Identifying the Firmware Version, Model, and Serial Number” on page 81 for instructions on determining the firmware version.
© 2014 Schneider Electric All Rights Reserved
9
Chapter 1—Introduction PowerLogic™ PM5100 user guide
© 2014 Schneider Electric All Rights Reserved10
PowerLogic™ PM5100 series user guide Chapter 2—Safety Precautions
Chapter 2—Safety Precautions

Before You Begin

Installation, wiring, testing and service must be performed in accordance with all local and national electrical codes.
This section contains important safety precautions that must be followed before attempting to install, service, or maintain electrical equipment. Carefully read and follow the safety precautions outlined below.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. In the USA, see NFPA 70E or CSAZ462.
• Only qualified electrical workers should install this equipment. Such work should be performed only after reading this entire set of instructions.
• If the equipment is not used in a manner specified by the manufacturer, the protection provided by the equipment may be impaired.
• NEVER work alone.
• Before performing visual inspections, tests, or maintenance on this equipment, disconnect all sources of electric power. Assume that all circuits are live until they have been completely de-energized, tested, and tagged. Pay particular attention to the design of the power system. Consider all sources of power, including the possibility of back feeding.
• Turn off all power supplying the meter and the equipment in which it is installed before working on it.
• Always use a properly rated voltage sensing device to confirm that all power is off.
• Before closing all covers and doors, inspect the work area for tools and objects that may have been left inside the equipment.
• When removing or installing panels, do not allow them to extend into the energized bus.
• The successful operation of this equipment depends upon proper handling, installation, and operation. Neglecting fundamental installation requirements may lead to personal injury as well as damage to electrical equipment or other property.
• Before performing Dielectric (Hi-Pot) or Megger testing on any equipment in which the energy meter is installed, disconnect all input and output wires to the energy meter. High voltage testing may damage electronic components contained in the meter.
• This equipment should be installed in a suitable electrical enclosure.
Failure to follow these instructions will result in death or serious injury.

Notices

FCC PART 15 NOTICE This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
© 2014 Schneider Electric All Rights Reserved
11
PowerLogic™ PM5100 series user guide Chapter 2—Safety Precautions
Increase the separation between the equipment and receiver.
Connect the equipment to an outlet on a circuit different from that to which the receiver
is connected.
Consult the dealer or an experienced radio/TV technician for help.
This Class B digital apparatus complies with Canadian ICES-003.
© 2014 Schneider Electric All Rights Reserved12
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
Chapter 3—Hardware Reference
This section supplements the meter’s installation sheet and provides additional information about the meter’s physical characteristics and capabilities.

Models, Features and Options

Table 3 –1: PM5100 Series - Models, Features and Options
Features and Options
Installation
Fast installation, panel mount with integrated display
Accuracy Cl 0.5S Cl 0.5S Cl 0.5S Display
Backlit LCD, multilingual, bar graphs, 6 lines, 4 concurrent values
Power and energy metering
3-phase voltage, current, power, demand, energy, frequency, power factor
Power quality analysis
THD, thd, TDD
Harmonics, individual (odd) up to 15th 15th 15th
I/Os
Digital output 1DO 1DO 1DO
Alarms and control
Alarms 33 33 33 Set point response time, seconds 1 1 1
Communications
Serial ports with modbus protocol 0 1 1
MID ready compliance, EN50470-1/3, Annex B and Annex D
Class C
PM5100 PM5110 PM5111
PM5100 series
 
 
 
 

Functions and Characteristics

Table 3 –2: Functions and Characteristics
General PM5100 Series
Use on LV and MV systems
Basic metering with THD and min/max readings
Instantaneous rms values
Current (per phase and neutral)
Voltage (total, per phase L-L and L-N)
Frequency
Real, reactive, and apparent power (Total and per phase) Signed, Four Quadrant True Power Factor (Total and per phase) Signed, Four Quadrant Displacement PF (Total and per phase) Signed, Four Quadrant
% Unbalanced I, V L-N, V L-L
© 2014 Schneider Electric All Rights Reserved 13
 
  
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
Energy Values*
Accumulated Active, Reactive and Apparent Energy Received/Delivered; Net and absolute
Demand Values*
Current average
Active power
Reactive power
Apparent power
Demand calculation (Sliding, fixed and rolling block, thermal methods)
Synchronization of the measurement window to input, communication command or internal clock
Settable Demand intervals
Present, Last, Predicted, Peak, and Peak
Date Time
Present, Last, Predicted, Peak, and Peak
Date Time
Present, Last, Predicted, Peak, and Peak
Date Time
Present, Last, Predicted, Peak, and Peak
Date Time
Other Measurements*
Operating timer
Load timer
Alarm counters and alarm logs
  
Power Quality Measurements
THD, thd (Total Harmonic Distortion) I, V L-N, V L-L per phase I, V L-N, V L-L
TDD (Total Demand Distortion)
Individual harmonics (odds) 15th
Data Recording
Min/max of instantaneous values, plus phase identification*
Alarms with 1s timestamp*
Min/max log
  
I/Os
Digital output
Timestamp resolution in seconds 1
1
(kWh only)

Technical Specifications

NOTE: *Stored in non-volatile memory
Electrical Characteristics
Type of measurement: True rms on three-phase (3P, 3P + N), zero blind
Measurement accuracy
IEC 61557-12 Active Energy Reactive Energy Active Power Class 0.5 as per IEC 61557-12 Reactive Power Class 2 as per IEC 61557-12 Apparent Power Class 0.5 as per IEC 61557-12 Current, Phase Class 0.5 as per IEC 61557-12 Voltage, L-N Class 0.5 as per IEC 61557-12 Frequency Class 0.05 as per IEC 61557-12
1
2
2
64 samples per cycle
PMD/[SD|SS]/K70/0.5 Class 0.5S as per IEC 62053-22 Class 2S as per IEC 62053-23
© 2014 Schneider Electric All Rights Reserved14
1
1
1
1
1
1
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
Power Factor Class 0.5 as per IEC 61557-12 Voltage Harmonics Class 5 as per IEC 61557-12 Voltage THD/thd Class 5 as per IEC 61557-12 Current Harmonics Class 5 as per IEC 61557-12 Current THD/thd Class 5 as per IEC 61557-12
1
1
1
1
1
MID Directive (2004/22/EC) Annex B and Annex D (PM5111) Class C
Input-voltage (up to 1.0 MV AC max, with voltage transformer)
UL: 20-347 V L-N/35-600 V L-L
Nominal Measured Voltage range
IEC: 20-400 V L-N/35-690 V L-L
(absolute range 35 V L-L to 760 V L-L) Impedance 5 M F nom 50/60 Hz
Input-current (configurable for 1 or 5 A secondary CTs)
I nom 5 A
Measured Amps with over range and Crest Factor
Starting current: 5mA
Operating range: 50mA to 8.5A Withstand Continuous 20 A,10s/hr 50 A, 1s/hr 500 A Impedance < 0.3 m F nom 50/60 Hz Burden <0.026VA at 8.5A
Frequency measurement
Measurement range 45 to 65 Hz
AC control power
Operating range
100 - 277 V AC L-N / 415 V L-L +/-10%
CAT III 300V class per IEC 61010 Burden <5 W,11 VA at 415 V L-L Frequency 45 to 65 Hz
80 mS typical at 120V AC and maximum burden.
Ride-through time
100 mS typical at 230 V AC and maximum burden
100 mS typical at 415 V AC and maximum burden
DC control power
Operating range 125-250 V DC ±20% Burden <4 W at 250 V DC Ride-through time 50 mS typical at 125 V DC and maximum burden
Outputs
Digital output
Max load voltage 40 V DC Max load current 20 mA On Resistance 50 max
Meter constant
from 1 to 9,999,999 pulses per k_h (k_h = kWh,
kVARh or kVAh depending on the energy parameter
selected)
Pulse width for Digital Output 50% duty cycle Pulse frequency for Digital Output 25 Hz max. Leakage current 0.03 micro Amps Isolation 5 kV rms
Optical outputs
Pulse width (LED) 200
s
Pulse frequency 50 Hz. max. Meter constant from 1 to 9,999,999 pulses per k_h
Mechanical Characteristics
Product weight 380 g IP degree of protection (IEC 60529) IP52 front display, IP30 meter body
Dimensions W x H x D [protrusion from cabinet]
96 x 96 x 72mm (depth of meter from housing
mounting flange) [13mm]
Mounting position Vertical Panel thickness 6 mm maximum
Environmental Characteristics
Operating temperature
Meter -25 °C to +70 °C Display (Display functions to -25º with reduced
performance) Storage temp. -40 °C to +85 °C Humidity range 5 to 95% RH at 50 °C (non-condensing)
-25 °C to +70 °C
© 2014 Schneider Electric All Rights Reserved 15
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
Pollution degree 2 Altitude 2000 m CAT III / 3000 m CAT II For indoor use only
Electromagnetic Compatibility
Electrostatic discharge IEC 61000-4-2 Immunity to radiated fields IEC 61000-4-3 Immunity to fast transients IEC 61000-4-4 Immunity to surge IEC 61000-4-5 Conducted immunity 150kHz to 80MHz IEC 61000-4-6 Immunity to magnetic fields IEC 61000-4-8 Immunity to voltage dips IEC 61000-4-11 Radiated emissions FCC part 15, EN 55022 Class B Conducted emissions FCC part 15, EN 55022 Class B
3
Safety
Europe
U.S. and Canada
Measurement category (Voltage and Current inputs) CAT III up to 400 V L-N / 690 V L-L Dielectric As per IEC/UL 61010-1 (3rd Edition) Protective Class II, Double insulated for user accessible parts
CE, as per IEC 61010-1 (3rd Edition), IEC 62052-11 & IEC61557-12
cULus as per UL61010-1 (3rd Edition) CAN/CSA-C22.2 No. 61010-1 (3rd Edition)
1
Communication
RS-485 port Modbus RTU, Modbus ASCII (7 or 8 bit), JBUS
Firmware and language file update Meter firmware update via the communication ports Isolation 2.5 kVrms, double insulated
2-Wire, 9600,19200 or 38400 baud, Parity - Even, Odd, None, 1 stop bit if parity Odd or Even, 2 stop bits if None; (Optional)
Human Machine Interface
Display type Monochrome Graphics LCD Resolution 128 x 128 Backlight White LED Viewable area (W x H) 67 x 62.5 mm Keypad 4-button Indicator Heartbeat / Comm activity Green LED Energy pulse output / Active alarm indication (configurable) Optical, amber LED Wavelength 590 to 635 nm Maximum pulse rate 2.5 kHz

Before you begin

Safety precautions

1
For firmware version 1.1.1 and higher
2
For 1A nominal CT when I > 0.15A
3
Tests are conducted as per IEC 61557-12 (IEC 61326-1), 62052-11 and EN50470
Carefully read and follow the safety precautions before working with the meter.
Installation, wiring, testing and service must be performed in accordance with all local and national electrical codes.
© 2014 Schneider Electric All Rights Reserved16
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
DANGER
90.00°
90.00°
96.00mm
96.00
mm
78.5 mm
12.8 mm
107.4
mm
90.6
mm
72.00 mm
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA or applicable local standards.
• Turn off all power supplying this device before working on it.
• Always use a properly rated voltage sensing device to confirm that all power is off.
• Do not exceed the device’s ratings for maximum limits.
• Always use grounded external CTs for current inputs.
Failure to follow these instructions will result in death or serious injury.
1. Turn off all power supplying this device before working on it.
2. Always use a properly rated voltage sensing device to confirm that all power is off.

Dimension

Figure 3–1: Dimension

Meter mounting

This section describes how to mount the meter.
© 2014 Schneider Electric All Rights Reserved 17
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
92.0 mm
+0.8
-
0.0
92.0
mm
+0.8
-
0.0
CLICK
CLIC
K

Mounting the PM5100

The meter is designed to be mounted inside a 1/4-DIN panel cutout.
1. Inspect the gasket (installed around the perimeter of the front display) and make sure it is secured properly and not damaged.
2. Insert the meter through the mounting hole.
3. Line up the tabs of the retainer clips with the slots on either side of the meter. While holding the retainers at a slight angle, push the retainers in and forward to position them in place. In situations where the spacing between meters is tight, use a flat-head screwdriver with a long, narrow shaft to help secure the clips.
4. Push the middle of the clip assembly to lock the retainer in place and secure the meter.
© 2014 Schneider Electric All Rights Reserved18
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference

Meter wiring

For wiring instructions and safety precautions, see the meter installation sheet that was shipped with your meter, or download a copy at www.schneider-electric.com.
Wire connections to the meter’s voltage inputs, control power, digital output, and RS-
485 communications are terminated using the supplied pluggable wire connectors.
When wiring the meter’s current inputs, terminate the wire ends with ring or split-ring
crimp connectors.
Use the meter installation sheet when wiring the meter.
UL: CAT III
20-347VLN/35-600VLL
IEC: CAT III
20-400VLN/35-690VLL
9/19//s
s+]9$

9s:

_
+
Modbus RS-485
_
+
Serial No. Description Specification
Wire size: 0.82 - 3.31 mm
Voltage Inputs (V1, V2, V3, VN)
Control Power (L1, L2)
Digital Output (D1+, -/C)
Current Inputs
, I1-, I2+, I2-, I3+, I3-)
(I
1+
Modbus RS-485 (+,-, , C)
Wire strip length: 0.28 in (7 mm)
Torque: 0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
Screw driver type: M3
Wire size: 0.82 - 3.31 mm
Wire strip length: 0.28 in (7 mm)
Torque: 0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
Screw driver type: M3
Wire size: 0.33 - 3.31 mm
Wire strip length: 0.24 in (6 mm)
Torque: 0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
Screw driver type: M2
Wire size: 0.82 - 3.31 mm
Wire strip length:0.28 in (7 mm)
Torque: 0.9 - 1.0 N·m (8.0 - 9.0 in·lb)
Screw driver type: PH1
Wire size: 0.33 - 3.31 mm
Wire strip length: 0.24 in (6 mm)
Torque: 0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
Screw driver type: M3
I
I
I
1+
2+
1-
$$120$
2
2
2
2
2
I
I
I
2-
3+
3-
0V
Modbus RS-485
D0 = Rx-, Tx­D1 = Rx+,Tx+
(18 - 12 AWG)
(18 - 12 AWG)
(22 - 12 AWG)
(18 - 12 AWG)
(22 - 12 AWG)
© 2014 Schneider Electric All Rights Reserved 19
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference

Recommended cables

Communication Make Part code Description
RS-485 Belden
3105A Multi-Conductor - EIA Industrial RS-485 PLTC/CM
3106A Multi-Conductor - EIA Industrial RS-485 PLTC/CM
© 2014 Schneider Electric All Rights Reserved20
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
B
A
+
-
+
-
+
-
+
L
B
A
(I1) (I2) (I3)
V1 V2 V3VN
+
-
+
-
+
-
+
A
B
+
-
+
-
+
-
+
B
A
+
-
+
-
+
-
+
A
B
+
-
+
-
+
-
+
B
A
+-+-+
-
+
+
L
B
A
(I1) (I2) (
V1 V2 V3VN
+
-
+
-
+
+
A B
+-+-+
-
+
+
+
B
A
+
-
+
-
+
-
+
L1 L2 L3
A B
V1 V2 V3VN
(I1) (I2) (I3)
+-+-+
-
+
+
A B
+-+-+
-
+
C
A
B
+-+-+
-
+
+
+
C
A
B
+-+-+
-
+
+
C
L1
A
V1 V2 V3VN
B
(I1) (I2) (I3)
+-+-+
-
+
C
L1 L2 L3
A
V1 V2 V3VN
B
(I1) (I2) (I3)
+
+
-
+-+
-
L1 L2 L3 N
A
B
V1 V2 V3VN
(I1) (I2) (I3)
+-+-+
-
+
+
+
L1 L2 L3 N
B
V1 V2 V3VN
(I1) (I2) (I3)
A
+-+-+
-
+
L1 L2 L3 N
A
C
V1 V2 V3VN
B
(I1) (I2) (I3)
+
+
+
+
-
+-+
-
L1 L2 L3 N
A
C
V1 V2 V3VNB(I1) (I2) (I3)
+-+-+
-
+
+
L1 L2 L3 N
A
C
V1 V2 V3VN
B
(I1) (I2) (I3)
+-+-+
-
+

Wiring Diagrams

1PH
1PH2WLN 1PH2WLL 1PH3WLL with N
V1 V2 V3VN
L N
(I1) (I2) (I3)
3PH3W
3CT 2CT 1CT *
V1 V2 V3VN (I1) (I2) (I3)
L1 L2 L3
2VT, 3CT 2VT, 2CT 2VT, 1CT *
V1 V2 V3VN
L1 L2 L3
(I1) (I2) (I3)
3PH4W
3CT 2CT * 1CT *
V1 V2 V3VN
L1 L2
V1 V2 V3VN
L N
V1 V2 V3VN
L1 L2 L3
(I1) (I2) (I3)
(I1) (I2) (I3)
(I1) (I2) (I3)
V1 V2 V3VN
V1 V2 V3VN
V1 V2 V3VN
L1
L1
L2
L
L2
N
N
V1 V2 V3VN (I1) (I2) (I3)
L1 L2 L3
(I1) (I2) (I3)
(I1) (I2) (I3)
(I1) (I2) (I3)
© 2014 Schneider Electric All Rights Reserved 21
V1 V2 V3VN
L1 L2 L3 N
A
(I1) (I2) (I3)
+-+-+
B
+
-
+
3VT, 3CT 3VT, 2CT * 3VT, 1CT *
NOTE: According to Blondel's theorem, in an N wire system a minimum of N-1 measuring elements are required for correct measurement.
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
Symbol Description
500 mA fused disconnect / circuit breaker (not supplied)
Shorting block (not supplied)
PT primary fuses and disconnect switch (not supplied)
*
Indicates wiring for a balanced system
NOTE:
Clearly label the device’s disconnect circuit mechanism and install it within easy reach
of the operator.
The fuses / circuit breakers must be rated for the installation voltage and sized for the
available fault current.
Fuse for neutral terminal is required if the source neutral connection is not grounded.
Potential Transformer
IEC
ANSI
Current Transformer

Power system

Direct connect voltage limits

This section outlines typical requirements for wiring the voltage and current inputs of the meter to the electrical power system.
For wiring instructions and safety precautions, see the meter installation sheet that was shipped with your meter, or download a copy at www.schneider-electric.com.
You can connect the meter’s voltage inputs directly to the phase voltage lines of the power system if the power system’s line-to-line or line-to-neutral voltages do not exceed the meter’s direct connect maximum voltage limits. The meter's voltage measurement inputs are rated by the manufacturer for up to 400 V L-N / 690 V L-L. However, the maximum voltage allowed for direct connection may be lower, depending on the local electrical codes and regulations. In US and Canada the maximum voltage on the meter voltage measurement inputs may not exceed 347 V L-N / 600 V L-L.
If your system voltage is greater than the specified direct connect maximum voltage, you must use VTs (voltage transformers) to step down the voltages.
© 2014 Schneider Electric All Rights Reserved22
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
N
Power system setup parameters
Power system description — Meter setting
Single-phase 2-wire line-to-neutral
1PH2W LN
Single-phase 2-wire line-to-line
1PH2W LL
Single-phase 3-wire line-to-line with neutral
1PH3W LL with N
3-phase 3-wire Delta ungrounded
3PH3W Dlt Ungnd
3-phase 3-wire Delta corner grounded
3PH3W Dlt Crnr Gnd
Symbol
Direct connect maximum
UL IEC
347 V L-N 400 V L-N 1 VT
600 V L-L 600 V L-L 1VT
347 V L-N /
600 V L-L
600 V L-L 600 V L-L 2 VT
600 V L-L 600 V L-L 2 VT
400 V L-N /
690 V L-L
# of VTs
(if required)
2VT
3-phase 3-wire Wye ungrounded
3PH3W Wye Ungnd
3-phase 3-wire Wye grounded
3PH3W Wye Gnd
3-phase 3-wire Wye resistance­grounded
3PH3W Wye Res Gnd
3-phase 4-wire open Delta center­tapped
3PH4W Opn Dlt Ctr Tp
600 V L-L 600 V L-L 2 VT
600 V L-L 600 V L-L 2 VT
600 V L-L 600 V L-L 2 VT
240 V L-N / 415 V L-N /
480 V L-L
240 V L-N / 415 V L-N /
480 V L-L
3 VT
© 2014 Schneider Electric All Rights Reserved 23
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
N
N
N
Power system setup parameters (continued)
Power system description — Meter setting
3-phase 4-wire Delta center-tapped
3PH4W Dlt Ctr Tp
3-phase 4-wire ungrounded Wye
3PH4W Wye Ungnd
3-phase 4-wire grounded Wye
3PH4W Wye Gnd
3-phase 4-wire resistance-grounded Wye
3PH4W Wye Res Gnd
Symbol
Direct connect maximum
UL IEC
240 V L-N / 415 V L-N /
480 V L-L
347 V L-N /
600 V L-L
347 V L-N /
600 V L-L
347 V L-N /
600 V L-L
240 V L-N / 415 V L-N /
480 V L-L
347 V L-N /
600 V L-L
400 V L-N /
690 V L-L
347 V L-N /
600 V L-L
# of VTs
(if required)
3 VT
3 VT or 2 VT
3 VT or 2 VT
3 VT or 2 VT

Voltage and current input wiring

For wiring instructions and safety precautions, see the meter installation sheet that was shipped with your meter, or download a copy at www.schneider-electric.com.
Voltage input protection
The meter’s voltage inputs must be wired to fuses/breakers and a disconnect switch. If using a voltage transformer (VT), both primary and secondary sides of the VT must be wired to fuses/breakers and disconnect switches.
Clearly label the device’s disconnect circuit mechanism and install it within easy reach
of the operator.
The fuses / circuit breakers must be rated for the installation voltage and sized for the
available fault current.
Fuse for neutral terminal is required if the source neutral connection is not grounded.
See the meter installation sheet for fuse ratings.
Current input protection
For all connected current inputs, use a CT shorting block to short-circuit the secondary leads of the CTs before removing the current input connections to the meter.
NOTE: Ground any unused current inputs.
© 2014 Schneider Electric All Rights Reserved24
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference

Balanced system considerations

In situations where you are monitoring a balanced 3-phase load, you may choose to connect only one or two CTs on the phase(s) you want to measure, and then configure the meter so it calculates the current on the unconnected current input(s).
NOTE: For a balanced 4-wire Wye system, the meter’s calculations assume that there is
no current flowing through the neutral conductor.
Balanced 3-phase Wye system with 2 CTs
The current for the unconnected current input is calculated so that the vector sum for all three phase currents equal zero.
Balanced 3-phase Wye or Delta system with 1 CT
The currents for the unconnected current inputs are calculated so that their magnitude and phase angle are identical and equally distributed, and the vector sum for all three phase currents equal zero.
NOTE: You must always use 3 CTs for 3-phase 4-wire center-tapped Delta or
center-tapped open Delta systems.

Control power wiring

Communications

Serial communications

For wiring instructions and safety precautions, see the meter installation sheet that was shipped with your meter, or download a copy at www.schneider-electric.com.
The meter can be powered from an AC or DC power source.
L1 and L2 are non-polarized. If using an AC power supply with neutral, connect
neutral to the meter’s L2 terminal.
Always use a fuse on L1. Fuse L2 when connecting an ungrounded neutral to the
control power.
If using a control power transformer, fuse both primary and secondary sides of the
transformer.
The fuses / circuit breakers must be rated for the installation voltage and sized for the
available fault current.
This section provides additional information about the communications ports and topologies supported by the meter. You must wire and configure the RS-485 port in order to communicate with the meter.
The meter supports serial communications through the RS-485 port. Up to 32 devices can be connected on a single RS-485 bus.
In an RS-485 network, there is one master device, typically an Ethernet to RS-485 gateway. It provides the means for RS-485 communications with multiple slave devices (for example, meters). For applications that require only one dedicated computer to communicate with the slave devices, an RS-232 to RS-485 converter can be used as the master device.
© 2014 Schneider Electric All Rights Reserved 25
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
+
-
C
D1 (+)
D0 (-)
+
-
C
120 Ω
120 Ω
Master Slaves
RS-485 wiring
Connect the devices on the RS-485 bus in a point-to-point configuration, with the (+) and (-) terminals from one device connected to the corresponding (+) and (-) terminals on the next device.
RS-485 wiring
RS-485 cable
Use a shielded 1.5 twisted pair or 2 twisted pair RS-485 cable to wire the devices. Use one twisted pair to connect the (+) and (-) terminals, and use the other insulated wire to connect the C terminals.
RS-485 terminals
Common. This provides the voltage reference (zero volts) for the data plus and data minus signals.
C
Shield. Connect the bare wire to this terminal to help suppress signal noise that may be present. Ground the shield wiring at one end only (either at the master or the last slave device, but not both).
Data minus. This transmits/receives the inverting data signals.
-
Data plus. This transmits/receives the non-inverting data signal.
+
RS-485 maximum cable length
The total distance for devices connected on an RS-485 bus should not exceed 1200 m (4000 ft).
RS-485 network configuration
After you have wired the RS-485 port and powered up the meter, you must configure the serial communications port in order to communicate with the meter.
Each device on the same RS-485 communications bus must have a unique address and all connected devices must be set to the same protocol, baud rate, and parity (data format).
NOTE: To communicate with the meter using ION Setup, you must set the parity to
“None” for all devices in the RS-485 network.
For meters that do not have a display, you must first wire and configure each one separately before connecting these meters to the same RS-485 bus.
© 2014 Schneider Electric All Rights Reserved26
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
D1 -/C
(60)
(57)
LOAD
< 20mA
< 40Vdc
Related topics
To configure RS-485 communications, see “Setting up serial communications” on
page 34.

Digital outputs

The meter is equipped with a digital output port (D1). You can configure the digital output for use in the following application:
energy pulsing applications, where a receiving device determines energy usage by
counting the k_h pulses (k_h = kWh, kVARh or kVAh depending on the energy parameter selected) coming from the meter’s digital output port.
The digital output can handle voltages less than 40 V DC. For higher voltage applications, use an external relay in the switching circuit.
Digital output connections
Related topics
See “Digital output applications” on page 47 for digital output use and configuration
details.
© 2014 Schneider Electric All Rights Reserved 27
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
© 2014 Schneider Electric All Rights Reserved28
PowerLogic™ PM5100 series user guide Chapter 4—Front panel display and meter setup
B
A
C
G
E
F
D
C
B
Chapter 4—Front panel display and meter setup
The front panel display lets you use the meter to perform various tasks such as setting up the meter, displaying data screens, acknowledging alarms, or performing resets.
Parts of the display
A Navigation / menu selection buttons
B Heartbeat / communications LED (green)
C Alarm / energy pulsing LED (orange)
D Navigation symbols or menu options
E Right notification area
F Screen title
G Left notification area

LED indicators

The meter has two LED indicators on the front panel.
Front panel LEDs

Heartbeat / communications LED

The (green) heartbeat / communications LED blinks at a slow, steady rate to indicate the meter is operational. The LED flashes at a variable, faster rate when the meter is communicating over a Modbus serial communications port.
You cannot configure this LED for other purposes.
NOTE: A heartbeat LED that remains lit and does not blink (or flash) indicates a
possible hardware problem. In this case, power down the meter and reapply power. If the LED still does not blink or flash, contact Technical Support.

Alarm / energy pulsing LED modes

The (orange) alarm / energy pulsing LED can be configured for alarm notification or energy pulsing.
Alarm / energy pulsing LED (orange)
Heartbeat / communications LED (green)
When configured for alarm notification, this LED flashes when a high, medium or
low priority alarm is active. This provides a visual indication of an active alarm condition, or an inactive but unacknowledged high priority alarm.
When configured for energy pulsing, this LED flashes at a rate proportional to the
amount of energy consumed. This is typically used to verify the meter’s accuracy.
© 2014 Schneider Electric All Rights Reserved 29
Loading...
+ 67 hidden pages