PowerLogic™ ION Enterprise™ software is a complete power management solution
for utility, industrial or commercial operations. Engineering and management
personnel can cut energy-related costs, avoid downtime, and optimise equipment
operations by using the information provided by PowerLogic ION Enterprise
software. PowerLogic ION Enterprise also enables tracking of real-time power
conditions, analysis of power quality and reliability, and quick response to alarms to
avoid critical situations. The software forms a layer of energy intelligence across your
facility, campus, service area, or your entire enterprise, acting as a unied interface
to all electrical and piped utilities.
Typical applications
PowerLogic ION Enterprise software has many applications:
Reduce peak demand surcharges and power factor penalties
b
Enable participation in load curtailment programs (e.g. demand response)
b
Verify that power quality complies with the energy contract
b
Verify the reliable operation of equipment
b
Improve response to power quality-related problems
b
Leverage existing infrastructure capacity and avoid over-building
b
Support proactive maintenance to prolong asset life
b
For electric utilities:
Improve T&D network reliability
b
Enhance substation automation
b
Maximise the use of existing infrastructure
b
Verify compliance with new power quality standards
b
Analyse and isolate the source of power quality problems
b
Help customers manage reliability using operational and power quality data
b
Scalable, exible architecture
Grow to hundreds of metering points
b
Add distributed servers and clients
b
Use modular programming for complex processing and control
b
Integrate legacy and third-party devices
b
Leverage and optimise existing infrastructure
b
Functional components
The functional components of PowerLogic ION Enterprise software can reside on
the main server or on one or more workstations.
Management Console
b
Use this component to congure your PowerLogic ION Enterprise network,
v
including communication paths, devices and logical groups
Designer
b
Designer allows you to customise the modular functionality of your ION devices
v
and Virtual Processors
Vista
b
Offers real-time displays of measurements and status indicators; power quality
v
analysis; historical trending; alarms; and manual control
Web Reporter
b
Produces predened or custom reports and offers support for third-party reporting
v
tools
Data acquisition and management
Virtual Processor
b
The Virtual Processor performs multi-site aggregation; coordinated control;
v
complex calculations and alarming; and logging for non-recording devices (e.g.
interval kWh).
Site Server
b
Continuous or scheduled retrieval of data from up to hundreds of remote devices
v
over Internet, Ethernet, telephone, serial, wireless, or satellite connections.
system data and events with accurate meter synchronisation (+ 16 ms or +1 ms
using GPS) for precise event timestamping, power quality analysis and revenue
billing. This data is accessible using industry-standard database tools and you can
add distributed databases and servers for load balancing.
OPC DA (client), OPC DA Server (optional), and PQDIF Exporter (optional)
b
Supports data import/export with compliant devices and systems
v
2
Version 4.0
432E3040.indd
Communication
and supervision
PE86182
PowerLogic ION Enterprise™
Functions and characteristics
Reporting
The powerful, intuitive Web Reporter module lets users see critical information
exactly how, where, and when they need it.
Reports can be generated manually, on schedule or event-driven. Distribute
automatically as email or HTML. .
Precongured or fully customised
b
Support MS Excel and other third-party reporting tools
b
Manual, scheduled, or alarm/event-triggered distribution via email or web
b
Reports accessible via a web browser
b
Support WAGES (Water, Air, Gas, Electricity, Steam) measurements
b
Per User Security Model (View, Edit, Create, and Delete)
b
Can be generated in PDF format
b
Can export data in XML format
b
Support remote report development and uploading
b
Includes:
Energy Cost Report
b
Load Prole Report
b
Power Quality Report
b
IEC 61000-4-30 and EN50160 compliance reports
b
Energy Period over Period Comparison (compare energy consumption of
b
different periods)
Energy by Shift Report (compare energy over different
b
user-dened shifts)
Trending Report (trend multiple measurements for one device
b
or one measurement for multiple devices over time)
Tabular Report (show logged measurements and
b
associated time in a raw tabular format)
Alarm & Event Report (show events / alarms from
b
specic devices based on priority level)
100 Millisecond Report (show Power Quality millisecond
b
time-stamped data from devices supporting millisecond
logging of PQ measurements
System Conguration Report (get a quick inventory of your
b
system – Device Name, Group, Connection, and Device Address)
Web Reporter allows users to create and customise a wide
variety of reports, such as period or shift comparisons and
trends, by building, process, or region.
432E3040.indd
Version 4.0
3
Communication
and supervision
PE86098
Connect to meters, sensors, controllers, web services and
other systems. Extract values from spreadsheets to combine
with dynamic power and energy calculations.
PE86099
ION Enterprise™™
Functions and Characteristics (cont.)
Functions
PowerLogic ION Enterprise offers a wide range of functions:
Data acquisition and integration.
b
Alarms and events.
b
Manual and automated control.
b
Real-time monitoring.
b
Reporting.
b
Trend analysis.
b
Power quality analysis.
b
Patented ION® technology.
b
Data acquisition and integration
Integrate WAGES (water, air, gas, electricity, steam) metering. Native, out-of-the-box
support for all PowerLogic ION series, PowerLogic PM800 series, PM750, PM710
and PM210 power and energy meters, PowerLogic CM3250, CM3350, CM4000,
CM4250, CM4000T, circuit monitors, Micrologic Compact NSX Type A and Type E
breakers, MicroLogic A, P and H circuit breaker control units, the PowerLogic BCPM,
branch circuit power meter and the Sepam series 10, 20, 40 and 80 protective relays.
Also supports legacy ACM series meters. Enables access to meter data, control of
on-board relays and digital outputs, remote conguration and rmware upgrading.
Interface with third-party meters, transducers, PLCs, RTUs and power distribution or
mitigation equipment. Add and congure direct communications with remote devices
over Modbus RTU or Modbus TCP protocols using easy-to-use device templates.
Scalable platform enables remote device and user client addition as needs grow
while maintaining original investment. Integrate other energy management or
automation systems (e.g. SCADA, BAC, DCS, ERP) through ODBC, XML, OPC,
email, FTP, CSV and PQDIF compliance; integrate with web services through XML.
Alarms and events
PowerLogic ION Enterprise software allows you to receive alerts to outages or
impending problems that could lead to equipment stress, failures, or downtime.
Trigger on complex conditions
b
Generate & distribute alarm notications
b
b
Log all relevant data sequence of events for diagnosis
Flag & avert potential problems
b
Alert key personnel 24/7
b
Optimise maintenance scheduling
b
Respond to a notication, then click an on-screen indicator to
retrieve the time, location, and nature of the event. Click again
to study waveforms, tolerance curves or a report.
PE86125
Control loads, generation, and power quality mitigation
equipment across your enterprise or service area. Optimise
switching with the latest status and base loading data.
4
Manual and automated control
Perform fast, manual control operations by clicking on-screen trigger buttons, and
operate remote breakers, relays, and other power distribution and mitigation
equipment.
Perform manual or setpoint-triggered functions
b
Coordinate control of multiple loads, generators, relays, etc.
b
Support energy-saving applications
b
Manage distributed energy assets
b
Automate substations & reduce service time
b
Web portal
Allow multi-user access
b
Use multi-level security checks
b
Version 4.0
432E3040.indd
Communication
and supervision
PE86101
PowerLogic ION Enterprise™
Functions and characteristics (cont.)
Real-time monitoring
View, from any local or globally located workstation, key distribution points across
one or more facilities or substations.
Collect system-wide data
b
Perform calculations, display and log derived data
b
Customise views of data – digital figures, dials, bar or trend graphs, one-line
b
diagrams, etc.
Communicate over Internet, Ethernet, wireless
b
Desktop access to power system information from any
department, building or region. Graphical views of relevant,
actionable information customised for each user.
PE86102
Allocate costs, consolidate billing or negotiate contract volume
pricing. Assure compliance with PQ standards and verify the
results of operational improvements.
Trend analysis
Trend any parameter to reveal demand peaks and track system-wide energy
costs.
b
Graph any combination of measured parameters
b
Aggregate loads
b
Identify dangerous trends and redistribute loads
Optimise network capacity and avoid over-building
b
Avoid peak demand surcharges and power factor penalties
b
PE86103
Support load studies or expansion planning, optimise equipment
use by maximising capacity or balancing loads. Reveal critical
trends, expensive processes or energy waste.
432E3040.indd
Interoperability
Integrate all energy management and automation
b
systems (SCADA, BAC, DCS,ERP, etc.)
Share data with third-party SCADA, automation,
b
and accounting systems
Comply with ODBC, OPC, and PQDIF standards
b
Version 4.0
5
Communication
and supervision
PE86104
Minimise equipment damage and downtime by pinpointing the
source of disturbances, verifying the effect of system
upgrades, and validating compliance with power quality
standards.
PowerLogic ION Enterprise™
Functions and characteristics (cont.)
Power quality analysis
PowerLogic ION Enterprise software allows continuous, wide-area monitoring and
data capture for power quality and reliability conditions. IEC 61000-4-30 and
EN50160 compliance reporting veries power quality performance to international
standards and allows you to quickly review power quality indices as numeric charts
or graphic proles (requires PowerLogic ION7650 meters or other devices that
support compliance monitoring). Display harmonic histograms, odd/even
harmonics, THD, K-factor, crest factor, phasor diagrams, and symmetrical
components. Plot waveforms of up to many seconds in duration, with overlays that
correlate phase-to-phase relationships between voltages, currents, and cascading
failures. Plot sags, swells, short duration transients and other disturbance events on
industry-standard voltage tolerance curves, including ITIC (CBEMA) and SEMI. For
any event, you can display a list of associated time-stamped incidents, then click on
any incident to see more detailed information.
PowerLogic ION Enterprise supports a wide range of applications:
Diagnose and isolate PQ problems to increase reliability
b
Benchmark performance and compare service areas
b
Track contracted service compliance
b
PE86105
Use drag-and-drop icons to quickly create customised ION
metering, logging, or control functionality within your software
or hardware.
Patented ION technology
PowerLogic ION Enterprise software and a variety of PowerLogic ION metering
products feature the unique ION architecture. This modular, exible architecture
offers extensive customisation of functionality using a simple “building block”
approach. The technology uniquely addresses advanced monitoring and control
applications and adapts to changing needs, avoiding obsolescence.
Part numbers*
New systems
and add-ons
OptionsIONE-SQL-2005Integrated SQL Server 2005 Standard Edition (for use
Upgrades from
ION Enterprise
5.5/5.6
PowerLogic
ION Enterprise
documentation
(1) An appropriate device licence (IE60-DL-S, DL-M, or DL-E) is required for each meter or device connected to your
PowerLogic ION Enterprise system. Device licences have a minimum order quantity of ten (10).
(2) A client licence is required for each workstation that is used to connect to your primary PowerLogic ION
Enterprise server.
* Please refer to Schneider Electric sales representative for full pricing and part numbers information.
IE60-BASE-ENGPowerLogic ION Enterprise base software
IE60-DL-S
IE60-DL-M
IE60-DL-E
IE60-CL
IONE-SQL-2005-CPUAdditional CPU Licence for Integrated SQL Server
IONE-OPC-V1OPC DA Server for ION Enterprise
IONE-PQDIF-V1PQDIF Exporter for ION Enterprise
IE60-BASE-ENG-UPGPowerLogic ION Enterprise base software (English,
IE60-DL-S-UPGIndividual Device Licence Upgrade for High-End
IE60-DL-M-UPGIndividual Device Licence Upgrade for Mid-Range
IE60-DL-E-UPGIndividual Device Licence Upgrade for Entry-Range
IE60-CL-UPGPowerLogic ION Enterprise Client Licence - upgrade
CD-TECHDOCCompact disc containing the latest version of technical
(1)
(1)
(1)
(2)
(English, DVD)
Individual Device Licence for High-End Devices,
compatible with all supported device types
Individual Device Licence for Mid-Range Devices,
compatible with all supported device types
Individual Device Licence for Entry-Range Devices,
compatible with Entry-Range devices
PowerLogic ION Enterprise Client Licence
with ION Enterprise only) – Processor Licence for 1
CPU
2005
DVD) - upgrade from v5.5 SP2 or later
Devices, compatible with all supported device types
Devices, compatible Mid- and Entry-Range devices
Devices, compatible with Entry-Range devices
documentation
6
Version 4.0
432E3040.indd
Communication
and supervision
PowerLogic ION EnterpriseION Enterprise™ 0
Functions and characteristics (cont.)
FeaturesStandard Optional
Automated data acquisition from sites/devices
SQL 2005 Express Edition database
SQL 2005 Standard Edition databaseWeb-enabled real-time monitoring
Web Reporter
Trend analysis
Power quality analysis, compliance reporting
Alarms and events
Manual and automated control
OPC DA client
OPC DA serverPQDIF data export-
Minimum system requirements
Please consult your local Schneider Electric representative for complete system
requirements and commissioning information for PowerLogic ION Enterprise. The following
are minimum requirements to support 1 to 25 meters with factory default settings.
Server hardware: CPU requirements are dependent on number of devices and clients to
b
be supported; recommended is 2+ GHz Dual Core or Dual CPU, 4 GB RAM, 60 GB disk drive
DVD drive
Server software: The Primary Server computer should be Windows Server 2003 or 2008
b
certied, as per the hardware compatibility list on the Microsoft website. Windows XP
Professional SP3 or Windows Vista may be used for standalone Primary Server applications
using 1-25 networked devices, and no ION Enterprise client computers. Server must have a
CD-ROM drive, Ethernet communications port and other standard hardware.
Secondary server: Hardware and software requirements vary according to application
b
needs. Contact Technical Support for assistance.
Database server: PowerLogic ION Enterprise can install SQL Server 2005 Express on the
b
Primary Server and automatically set up the databases on that computer. Note: SQL Server
2005 Express has database size limitations. Databases over 4 GB require SQL Server 2005
Standard Edition on the Primary Server, or on a separate server optimised for disk capacity
and performance. SQL Server 2000 and MSDE are not supported. (Note: SQL Server 2000
and MSDE are not MS Windows Vista compatible).
Supported devices
PowerLogic power and energy meters:
ION8800
b
ION8600
b
ION7650/7550 series
b
PM800 series
b
ION7300 series
b
PM710, PM750
b
ION6200
b
PM210
b
PowerLogic circuit monitors:
CM3250, CM3350
b
CM4000, CM4250, CM4000T
b
PowerLogic branch circuit power meters:
BCPM
b
Circuit breaker control units
Micrologic A, P and H devices
b
Micrologic Compact NSX Type A and Type E
b
Protective relays
Sepam series 10, 20, 40, 80
b
Power Measurement power and energy meters:
ION8500/8400/8300
b
ION7700
b
ION7600/7500 series
b
ACM3720
b
ACM3710
b
ACM3300
b
Other
Modbus-compatible devices
b
Other devices through OPC
b
b
b
b
b
b
b
b
b
b
-
-
b
-
-
-
-
-
-
-
b
b
432E3040.indd
Version 4.0
7
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.