Schneider Electric PF-305, PF-306, PF-307, PF-308 Data Sheet

For use with Schneider Electric reversible control actuators and for controlling differential pressures, static pressures or air velocities in duct systems.
Other Applications:
Static pressure control in hospital white rooms.
Draft and exhaust damper control.
Liquid level control in closed tanks.
Option: Non
ACCESSORIES
AP-301 Static probe for pressure .24 kPa (1" water)
AP-305 Static probe for pressures below .24 kPa
AT-208 Duct mounting bracket for probes other than
e
and up
(1" water)
AP-301 an
d AP-305
INSTALLATION
Caution: These units are for use with air or non-combustible gases only.
PF-305, PF-306, PF-307, PF-308
Floating Differential Pressure
Electric Air Flow Switch
General Instructions
3. Mount the unit with mounting screws supplied. Note: The diaphragm must be mounted in a vertical plane in a location free from vibration. See Figure 3 for mounting details.
4. Connect the probe(s) to the pressure taps using the 3/8" O.D. plastic tubing su
5. Make all connections in accordance with job wiring diagrams and in compliance with national and local codes.
pplied.
Typical Actuators:
One Schneider Electric MP-300, -400, -2000 and -9700 series actuator directly. An AM-345 or AE-347 time delay relay is required for use with the MP-9200, -9400, -9600, and
-9800 series actuator.
An SPDT floating switch action where “Common” makes to “Normally Closed” on a decrease in differential pressure between input ports, and to “Normally Open” on an increase in differential between input ports.
1. Select appropriate probes from Table 1.
2. Install probe. See Figure 4. Sampling probes should be located in areas of minimum air turbulence (6 to 8 duct diameters downstream from fan outlet, elbows, tees, ordampers). If this is not possible locate the probe tip as close to the center of the duct as possible.
Figure-1 Typical Wiring.
Printed in U.S.A. 5/10 © Copyright 2010 Schneider Electric All Rights Reserved. F-17492-3
Table-1 Specification Table.
Differential Pressure
Part Number
PF-305
PF-306
PF-307
PF-308
* Min. null is with 127 μm (.005 in.) contact gap. Max null is 635 μM (.025
contact gap.
Setpoint Range kPa
(in. of water)
-.12 to +.12 (-.5 to +.5)
.04 to .32 (.2 to 1.3)
.27 to .87
(1.1 to 3.5)
.79 to 2.48
(3.2 to 10)
At Minimum Setpoint
kPa (in. of water)
.01 to .03
(.06 to .14)
.01 to .03
(.05 to.13)
.01 to .03
(.06 to .17)
.02 to .09 (.12 to .4)
Adjustable Null S
At Maxi
Probes 3 and 4 (see Figure 4) can be constructed from 1/4 inch O.D., copper, brass, or aluminum tubing. The ends of the probes should be cut square to the sides of the tube and deburred. Total pressure probe must have the sensing end bent at 90° approximately 25 to 76 mm (1 to 3 inches) from the tip.
pan*
mum Setpoint
(in. of water)
.01 to .03
(.07 to .14)
.03 to .06
(.13 to .28)
.02 to .07
(.11 to .31)
.06 to .19
(.24 to .8)
Velocity Range M/S
PM) 21°C (70°F)
(F
Air
2 to 14
(400 to 2800)
9 to 23
(1800 to 4600)
22 to 38
(4200 to 7500)
37 to 71
(7200 to 14000)
Maximum Pressure
Differential 3 kPa
(12" Water)
INPUT
7 kPa (28” W
ater)
Figure-2 Optional Probes.
Figure-3 Mounting.
Table-2 Remote Mounting of Probe(s).
Static Veloc ity
High
Press.
Ta p
Low
Press.
Ta p
a
Pilot can be used instead of two probes.
b
Highest (absolute) pressure should be applied to high pressure tap.
Probe 3 Probe 4 Probe 4 Probe 3 Probe 4
b
Pr
a
Total ΔStatic ΔTotal
obe 3 Probe 3 Probe 4
Δ = ΔDifferential.
Figure-4
Figure-5
2 © Copyright 2010 Schneider Electric All Rights Reserved. F-17492-3
Loading...
+ 2 hidden pages