Schneider Electric PC-301 Data Sheet

Application
For low or line voltage control of static, velocity or total pressures, or differential static or total pressures of air and non-combustible gases only.
Specifications
Setpoint:
Factory Set, 0.07" (1.8 mm) W.C.
(3 mm) W.C. at maximum setpoint.
Environment:
Ambient Temperature Limits,
Shipping, -40 to 140°F (-40 to 60°C).
Operating, 35 to 140°F (0 to 60°C).
Humidity, 5 to 95% R.H., non-condensing.
Locations, NEMA Type 1 indoor only. Maximum Pressure: 12" (305 mm) W.C. Electrical Switch: Snap action SPDT.
Ratings, See Table-1.
Connections, Code screw terminals Case: All metal with 1/2" conduit opening. Mounting: In vertical position on any surface free of
n.
vibratio
Dimensio
mm x 121 mm x 11
Accessories
AP-302 Static probe for turbulent air AP-305 Static probe for low actuating pressure AT-208 Duct mtg. kit for remote probes other than
ns: 5-1/8" high x 4-3/4" wide x 4-3/8" deep (130
1 mm).
AP-302 or
AP-305
to 0.1"
Pre-Installation
Inspection
Visually inspect the carton for damage. If damaged, notify the appropriate carrier immediately. Visually inspect the device for obvious damage due to shipping. Return damaged parts to place of purchase.
Required Installation Items
Wiring or piping diagrams
Appropriate screwdrivers (not provided) for mounting
screws (provided)
Conduit fittings (not provided)
PC-301
Differential Pressure Switch
General Instructions
Installation
Caution:
1. Installer must be a qualified, experienced technician.
2. Disconnect power supply before installation to prevent electrical shock.
3. Make all connections in accordance with the wiring diagram, and in accordance with national and local electrical codes. Use copper conductors only.
4. Avoid locations where excessive moisture, corrosive fumes or vibrations are pre intended for indoor use primarily to provide a degree of protection against contact with the enclosed equipment.
5. For use with air or non-combustible gases only.
Table-1 Maximum Electrical Switch Ratings
Full Load
Vac
24V -- -- 60 --
120V 6.25 37.5 300 --
240V 3.1 18.6 300 --
277V 2.7 16.2 300 10
Amps
Locked
Rotor Amps
sent. NEMA 1 devices are
Pilot Duty
(VA)
Non-Inductiv
e
Amps
Printed in U.S.A. 5/10 © Copyright 2010 Schneider Electric All Rights Reserved. F-16160-9
6. Make all connections in accordance with job wiring diagrams and in compliance with national and local codes. On an increase of air pressure to above setpoint, common contact of switch is made to normally open contact. On a decrease of air pressure to below setpoint, common contact of switch is made to normally closed contact.
Table-2 Direct Mount of One Probe.
Static Veloc ity Total Δ Static Δ Total
High Pres.
Ta p*
Low Pres.
p
Ta
Probe 1 Probe 2 P
Probe 3
-­Remote
robe 2 Probe 1 Probe 2
Pr
--
obe 3
Remote
Table-3 Remote Mounting of Probe(s).
Static Velo city** To tal Δ Static Δ Total
High Pres.
Tap*
Low Pres.
Ta p
* Highest (absolute) pressure should be applied to high pressure tap. **Pilot can be used instead of two probes
Probe 3 Probe 4 Pro
-- Probe 3 -- Probe 3 Probe 4
be 4 Probe 3 Probe 4
Δ = Differential
Probe 4 Remote
Figure-6 Part Identification.
Adjustment
To increase setpoint, turn adjustment screw clockwise. Adjustable 0.07" ±0.02" to 1.0" (1.78 mm ±0.5 mm to 25 mm) W.C. To decrease setpoint, turn adjustment screw counterclockwise.
Note: Units are shipped at minimum setpoint.
If readjustment to minimum setpoint is required, proceed as follows without any air pressure applied to diaphragm.
1. Turn adjustment screw full CCW.
2. Push on spring at point A (Figure 6) and maintain pressure during step
3. Turn adjustment screw CW until common contact is made
rmally open contact.
to no
4. Turn adjustment screw CCW until common is made to normally closed contact. Then turn adjustment screw 1/8 turn more CCW.
s 3 and 4.
F-16160-9 © Copyright 2010 Schneider Electric All Rights Reserved. 3
On Octo be r 1st, 200 9, TAC became the Buildings bu sine ss of its pa ren t comp any Schn eid er Ele c tric. This docu ment refl ects the vi sual ide nt ity of Schnei d er El ec tr ic, however t her e rema ins references to TAC as a corporate bra nd in the body c opy. As each document i s up dated, t he body copy wil l be change d to reflect app ropr iat e
corpora te b rand chan
g
Copyright 2010, Schneider Electric All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
F-16160-9