Schneider Electric i2865-V, i2866-V, i2885-V Specifications

Andover ContinuumTM Infinet II
i2865/866/885-V VAV Controllers with Built-in Actuator
The i2865-V, i2866-V, and i2885-V are unique, low-cost VAV box controllers that come equipped with a built-in actuator to streamline hardware installation and save commissioning time.
Andover Continuum Infinet II i2865/866/885-V VAV Controllers with Built-in Actuator Features
Universal inputs, an airflow sensor, Form A triac-based outputs, and an integrated damper actuator make these controllers perfect for VAV applications.
The i2865/866-V models feature a room sensor input, which supports an Andover Continuum Smart Sensor, or any standard room temperature sensor.
i28 65-V i28 66-V i28 85-V
Universal Inputs 4 4 2
Airflow Sensor Yes Yes Yes
PRODUCT AT A GLANCE
Low-cost VAV control in compact package
Built-in damper actuator simplifies
hardware installation
Universal inputs with Form A, Form K, and
analog outputs for flexible control options
Non-volatile flash memory stores both
application program and operating system
Easy on-line software updates
On-board airflow sensor
Optional Andover Continuum Smart
Sensor Display
Local on-board service port
Support for Wireless Andover Continuum
Infinet II Field Bus communications
Smart Sensor Inpu
Form A Triac Output s
Analog Outputs - 2 -
Integrated Actuator
Service Port Yes Yes Yes
Wireless O ption Yes Ye s Yes
• The i2865-V is the base model with four universal inputs, an airflow sensor, three Form A triac-based outputs, and an integrated damper actuator.
• The i2866-V model is identical to the i2865-V, with the exception that it also offers damper position feedback and two analog outputs to control reheat valves, lighting ballasts, etc.
• The i2885-V has a reduced I/O point count for smaller VAV applications.
All VAV models feature Flash memory, user memory for programs and a fast (32-bit) processor for faster can times, with plenty of additional memory available for data logging of your critical data.
The i2865/866-V VAV controllers communicate with the entire Andover Andover Continuum Infinet RS­485 field bus (i.e. both Andover Continuum Infinet and Andover Continuum Infinet II controllers) and are compatible with both the Andover Continuum CyberStation and Infinity SX 8000 front ends. The i2885-V VAV controllers are compatible with the Andover Continuum CyberStation front end (v1.5 and higher). Up to 254 Infinet devices can be networked to any Andover Continuum network controller.
t Yes Yes No
3 3 2
Yes Yes Yes
02
Schneider Electric SDS-I2865/866/885-US.BU.N.EN.7.2018.0.02.CC
Andover Continuum Infinet II i2865/866/885-V VAV Controllers with Built-in Actuator
03
Features
(continued)
Increased Reliability with Flash Memory
The i2865/866/885-V controller’s non-volatile Flash memory stores your operating system and application programs, so that in the event of a power loss, your application is restored when power is returned. In addition, the Flash memory allows for easy upgrades of your operating system via software downloads, eliminating the need to swap out memory chips. Each controller, except the i2885-V, includes an on-board battery to safeguard your runtime data — protecting all point data and log data from being lost if power is removed.
Optional Wireless Andover Continuum Infinet
The i2865/866/885-V Andover Continuum Infinet controllers can also communicate using a wireless mesh network. Simply plug Andover Continuum Wireless Adapters into the service ports of these controllers with wireless compatible firmware to create a wireless mesh network that sends and receives Infinet messages.
Dimensional Drawing
Inputs
The input configuration on the i2865/866-V controllers consist of four full-range Universal inputs that accept voltage (0-5VDC), digital (on/off), counter signals (up to 4Hz), or temperature signals, plus an on-board air flow sensor. The i2885-V controller consists of two full-range Universal inputs. The i2865/866-V models also offer an additional input to support the Andover Continuum Smart Sensor, or any standard room temperature sensor.
Outputs
The i2865/866-V controllers contain three Form A Triac-based outputs. The i2885-V controllers contains two Form A Triac-based outputs. These outputs can be used separately for on/off or pulsed control of lighting, heat, and fan units or for bi-directional control of dampers and valves; or configured into one Form K Tri-state output and one Form A output. (Note: Any two consecutive Triac outputs can be configured as a Form K output.) Outputs are rated for AC loads only. The i2866-V controller also offers two (0-10V) analog outputs.
Schneider Electric
SDS-I2865/866/885-US.BU.N.EN.7.2018.0.02.CC
Andover Continuum Infinet II i2865/866/885-V VAV Controllers with Built-in Actuator
04
Features
(continued)
Damper Actuator
The integrated damper actuator allows simple direct mounting of the controller directly over the existing damper shaft. This eliminates the need for separate mounting, wiring, and positioning of the damper motor. Also, the actuator has a built-in clutch button to temporarily disengage the direct-drive gears during commissioning. The controller’s actuator may be preset for a limited range of motion using the mechanical “stops” provided.
Software Capabilities
The dynamic memory of the controllers can be allocated for any combination of programs, scheduling, alarming, and data logging using the powerful Andover Plain English programming language. Our object-oriented Plain English language with intuitive keywords provides an easy method to tailor the controller to meet your exact requirements. Programs are entered into the controllers using the Andover Continuum CyberStation application. Programs are then stored and executed by the controller. Programming multiple controllers is inherently easy with Plain English. A complete copy of one i2865/866/885-V’s programs can be loaded directly into other i2865/866/885-Vs without changing any point names or programs.
Smart Sensor Interface
The i2865/866-V controllers provide a built-in connection for Andover Continuum Smart Sensor. The Smart Sensor provides a two-character LED display and a six-button programmable keypad that enables operators and occupants to change setpoints, balance VAV boxes, monitor occupancy status, and turn equipment on and off. An enhanced version of the Smart Sensor is also available with a four-digit custom LCD that provides the following icons: PM, %, °, Setpoint, Cool, Heat, CFM, Fan, OA, and SP.
Connection Labels
(LOW)
(HIGH)
2
3
4
5
6
7
8
9
10
11
(LOW)
(HIGH)
2
3
4
5
6
7
8
9
10
11
(LOW)
(HIGH)
2
3
4
5
AIR FLOW INPUT
CAUTION
IN 1 1
IN 2
RET
IN 3
IN 4
RET
SPWR
RET
IN 5
24 VAC
IN 1 1
IN 2
RET
IN 3
IN 4
RET
SPWR
RET
IN 5
24 VAC
IN 1 1
IN 2
RET
24 VAC
MORE THAN ONE DISCONNECT SWITCH MAY BE REQUIRED TO DE-ENERGIZE THI S EQUIPMENT BEFORE SERVICING.
UNIVERSAL INPUT S
This equipment complies with part 15 of the FCC rules. Operation is subject to the following two conditions. (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation.
SMART SENSOR
USE COPPER CO NDUCTORS ONLY
INPUT
:
CLASS 2 POWER ONLY
24VAC , 0.42 A, 10VA, 50/6 0HZ
AIR FLOW INPUT
CAUTION
MORE THAN ONE DISCONNECT SWITCH MAY BE REQUIRED TO DE-ENERGIZE THI S EQUIPMENT BEFORE SERVICING.
UNIVERSAL INPUT S
This equipment complies with part 15 of the FCC rules. Operation is subject to the following two conditions. (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation.
SMART SENSOR
USE COPPER CO NDUCTORS ONLY
INPUT
:
CLASS 2 POWER ONLY
24VAC , 0.42 A, 10VA, 50/6 0HZ
AIR FLOW INPUT
UNIVERSAL INPUT S
USE COPPER CO NDUCTORS ONLY
INPUT
:
CLASS 2 POWER ONLY
24VAC , 0.42 A, 10VA, 50/6 0HZ
CAUTION
MORE THAN ONE DISC ONNECT SWITCH MAY BE REQUIRED TO DE-ENERGIZE TH IS EQUIPMENT BEFORE SERVICING.
This equipment complies with part 15 of the FCC rules. Operation is subject to the following two conditions. (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation.
865-V
OUTPUTS
24V AC ,
866-V
OUTPUTS
0-10 VDC
OUTPUTS
24V AC ,
885-V
OUTPUTS
24V AC ,
RS-485
PORT
DIGITAL
0.5A
RS-485
PORT
ANALOG
DIGITAL
0.5A
RS-485
PORT
DIGITAL
0.5A
COM
COM
SHIELD
TRIAC REF
OUT5
OUT4
OUT3
COM
COM
SHIELD
A07
RET
AO6
TRIAC REF
OUT5
OUT4
OUT3
COM
COM
SHIELD
TRIAC REF
NOT USED
OUT4
OUT3
18
17
16
15
14
13
12
21
20
19
18
17
16
15
14
13
12
12
11
10
9
8
7
6
Schneider Electric One High Stre et, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674
SDS-I2865/866/885-US.BU.N.EN.7.2018.0.02.CC
Andover Continuum Infinet II i2865/866/885-V VAV Controllers with Built-in Actuator Specifications
i2865/866/885-V Controller
05
Electrical
Power
24 VAC, +10%-15%, 50/60 Hz,
Class 2 Limited Power
Power Consumption
Less than 10 VA
Overload Protection
Fused, MOV protected
Mechanical
Operation Environment
32° to 122°F (0-50°C),
10 - 90% RH (non-condensing)
Dimensions
7.75˝ W x 6.25˝ L x 2.5˝ H
(197 mm W x 159 mm L x63 mm H)
Weight
2.30 lbs (1.04 kg)
Battery
Battery Backup
Replaceable, rechargeable battery.
Provides 30 days typical accumulated
power failure backup of RAM memory.
All data stored in Flash on power loss.
Communications
RS-485 port for implementing Andover
Continuum Andover Continuum Infinet II
connection, including:
Three-position removable screw terminal
Standard service port,
four-position shrouded connector
LEDs:
TD = Transmit Enable
RD = Received Data
Wired/Wireless Field Bus
RS-485 port for implementing Wireless
Andover Continuum Infinet II connection,
including:
four-position shrouded connector
Standard service port,
User LEDs
Status Indicator LEDs
CPU CPU Active
Yellow = Infinet II
Damper Shaft Mounting Screws
Torque Minimum
Varies according to shaft material
Torque Maximum
30 inch-pounds (3.4 Nm)
Hex Screws
10-32 (with supplied hex wrench)
Airflow Input
Range
0 to 1˝ W.C. (0-250 Pa)
Resolution
0.0013˝ W.C. (0.33Pa) @ 73°F (23°C)
Accuracy
+ 0.05˝ W.C. (12.50 Pa) @ 73°F (23°C)
Damper Actuator Motor
Shaft Diameter
1/2˝ (with a 3/8˝ adapter)
12.6 mm (with a 9.45 mm adapter)
Shaft Torque
53 inch-pounds (5.989 Nm)
Damper Speed
180 sec. @ 60 Hz and
216 sec @ 50 Hz: for 90°
adjustable end limits with two set screws
Motor
Type: 24 VAC synchronous
Motor Protection: Mechanical clutch
Manual clutch override with a
push-button release
Hardware position feedback
(model i2866-V only)
Universal Inputs
Connections
Model i2865 -V:
Four inputs and two returns
Model i2866-V:
Four inputs and two returns
Model i2885-V: Two inputs and one return
Input Voltage Range
0 to 5.115 VDC
Input Impedance
10K ohm to 5.120 V
Input Voltage Resolution
5.0 mV
Digital Resolution
10 bits
Input Voltage Accuracy
+ 15m V
Temperature Range
-30° to 230°F (-34° to 110°C)
Temperature Accuracy
+ 1° F from -10° to 150°F
(+ 0.56°C from -23° to +66°C)
Counter Frequency
4 Hz @ 50% duty cycle
Input Protection
+ 1000 V transients
Input Filter
16 Hz with one pole RC filter
Connector
Removable, 5 mm screw terminal
Schneider Electric SDS-I2865/866/885-US.BU.N.EN.7.2018.0.02.CC
Andover Continuum Infinet II i2865/866/885-V VAV Controllers with Built-in Actuator
06
Specifications
(continued)
i2865/866/885-V Controller
Smart Sensor Interface
Connections
Model i2865-V: One input, SPWR,
and return
Model i2866-V: One input, SPWR,
and return
Model i2885-V: Not available
Digital Outputs
Connections
Model i2865-V:
Three triac outputs and one reference
Model i2866-V:
Three triac outputs and one reference
Model i2885-V: Two triac outputs
and one reference
SPST Accuracy
0.1 second for pulse width modulation
Contact Ratings
0.5 A Maximum, 24 VAC
Connector
Removable, 5mm screw terminal
Analog Outputs
Connections
Model i2865 : Not available
Model i2866:
Two analog outputs and one return
Model i2885: Not available
Analog Output Channels Required
Two, voltage only
Voltage Output Range
0 - 10 V
Output Source Current
5 mA Maximum
Voltage Output Load
2K ohm Minimum Impedance
Voltage Output Resolution
50 mV
Digital Resolution
8 bits
Output Voltage Accuracy
100 mV
Connector
Removable, 5mm screw terminal
Agency Listings
FCC Rules and Regulations CFR 47,
Part 15, Class A, ICES-003, AS/NZS 3548,
European Union (EU) Directive 2002/96/EC
Options
UL864, Smoke Control System Equipment,
UUKL (i2865-V-S, i2866-V-S, i2885-V-S)
Models
i2865-V
Infinet II 865-V VAV Controller
i2866-V
Infinet II 866-V VAV Controller
i2885-V
Infinet II 885-V VAV Controller
i2865-V-WL
Wireless Infinet II 865-V VAV Controller
i2866-V-WL
Wireless Infinet II 866-V VAV Controller
i2885-V-WL
Wireless Infinet II 885-V VAV Controller
All brand names, trademarks and registered trademarks are the propert y of their respective owners. Information contained within this document is subject to change without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual ide ntity of Schneider Electric, how­ever there remains references to TAC as a corporate brand in the body copy. As each docume nt is updated, the body copy will be changed to reflect appropriate corporate brand changes.
Schneider Electric SDS-I2865/866/885-US.BU.N.EN.7.2018.0.02.CC
July 2018 gg
© 2007-2018 Schneider Electric. All rights re served.