The i2865-V, i2866-V, and i2885-V are unique, low-cost VAV
box controllers that come equipped with a built-in actuator to
streamline hardware installation and save commissioning time.
Andover Continuum Infinet II
i2865/866/885-V VAV Controllers with Built-in Actuator
Features
Universal inputs, an airflow sensor, Form
A triac-based outputs, and an integrated
damper actuator make these controllers
perfect for VAV applications.
The i2865/866-V models feature a room sensor input,
which supports an Andover Continuum Smart Sensor,
or any standard room temperature sensor.
i28 65-Vi28 66-Vi28 85-V
Universal Inputs442
Airflow SensorYesYesYes
PRODUCT AT A GLANCE
• Low-cost VAV control in compact package
• Built-in damper actuator simplifies
hardware installation
•
Universal inputs with Form A, Form K, and
analog outputs for flexible control options
•
Non-volatile flash memory stores both
application program and operating system
• Easy on-line software updates
•
On-board airflow sensor
• Optional Andover Continuum Smart
Sensor Display
•
Local on-board service port
• Support for Wireless Andover Continuum
Infinet II Field Bus communications
Smart Sensor Inpu
Form A Triac Output s
Analog Outputs-2-
Integrated
Actuator
Service PortYesYesYes
Wireless O ptionYesYe sYes
• The i2865-V is the base model with four universal
inputs, an airflow sensor, three Form A triac-based
outputs, and an integrated damper actuator.
• The i2866-V model is identical to the i2865-V, with
the exception that it also offers damper position
feedback and two analog outputs to control reheat
valves, lighting ballasts, etc.
• The i2885-V has a reduced I/O point count for
smaller VAV applications.
•
All VAV models feature Flash memory, user memory
for programs and a fast (32-bit) processor for
faster can times, with plenty of additional memory
available for data logging of your critical data.
The i2865/866-V VAV controllers communicate with
the entire Andover Andover Continuum Infinet RS485 field bus (i.e. both Andover Continuum Infinet
and Andover Continuum Infinet II controllers) and
are compatible with both the Andover Continuum
CyberStation and Infinity SX 8000 front ends. The
i2885-V VAV controllers are compatible with the
Andover Continuum CyberStation front end (v1.5 and
higher). Up to 254 Infinet devices can be networked to
any Andover Continuum network controller.
tYesYesNo
332
YesYesYes
02
Schneider Electric SDS-I2865/866/885-US.BU.N.EN.7.2018.0.02.CC
Andover Continuum Infinet II
i2865/866/885-V VAV Controllers with Built-in Actuator
03
Features
(continued)
Increased Reliability with Flash Memory
The i2865/866/885-V controller’s non-volatile
Flash memory stores your operating system and
application programs, so that in the event of a power
loss, your application is restored when power is
returned. In addition, the Flash memory allows for
easy upgrades of your operating system via software
downloads, eliminating the need to swap out memory
chips. Each controller, except the i2885-V, includes
an on-board battery to safeguard your runtime data
— protecting all point data and log data from being
lost if power is removed.
Optional Wireless Andover Continuum Infinet
The i2865/866/885-V Andover Continuum Infinet
controllers can also communicate using a wireless
mesh network. Simply plug Andover Continuum
Wireless Adapters into the service ports of these
controllers with wireless compatible firmware to create
a wireless mesh network that sends and receives
Infinet messages.
Dimensional Drawing
Inputs
The input configuration on the i2865/866-V controllers
consist of four full-range Universal inputs that accept
voltage (0-5VDC), digital (on/off), counter signals (up
to 4Hz), or temperature signals, plus an on-board air
flow sensor. The i2885-V controller consists of two
full-range Universal inputs. The i2865/866-V models
also offer an additional input to support the Andover
Continuum Smart Sensor, or any standard room
temperature sensor.
Outputs
The i2865/866-V controllers contain three Form
A Triac-based outputs. The i2885-V controllers
contains two Form A Triac-based outputs. These
outputs can be used separately for on/off or
pulsed control of lighting, heat, and fan units or
for bi-directional control of dampers and valves; or
configured into one Form K Tri-state output and one
Form A output. (Note: Any two consecutive Triac
outputs can be configured as a Form K output.)
Outputs are rated for AC loads only. The i2866-V
controller also offers two (0-10V) analog outputs.
Schneider Electric
SDS-I2865/866/885-US.BU.N.EN.7.2018.0.02.CC
Andover Continuum Infinet II
i2865/866/885-V VAV Controllers with Built-in Actuator
04
Features
(continued)
Damper Actuator
The integrated damper actuator allows simple direct
mounting of the controller directly over the existing
damper shaft. This eliminates the need for separate
mounting, wiring, and positioning of the damper
motor. Also, the actuator has a built-in clutch button
to temporarily disengage the direct-drive gears
during commissioning. The controller’s actuator may
be preset for a limited range of motion using the
mechanical “stops” provided.
Software Capabilities
The dynamic memory of the controllers can
be allocated for any combination of programs,
scheduling, alarming, and data logging using the
powerful Andover Plain English programming
language. Our object-oriented Plain English language
with intuitive keywords provides an easy method to
tailor the controller to meet your exact requirements.
Programs are entered into the controllers using
the Andover Continuum CyberStation application.
Programs are then stored and executed by the
controller. Programming multiple controllers is
inherently easy with Plain English. A complete copy
of one i2865/866/885-V’s programs can be loaded
directly into other i2865/866/885-Vs without changing
any point names or programs.
Smart Sensor Interface
The i2865/866-V controllers provide a built-in
connection for Andover Continuum Smart Sensor. The
Smart Sensor provides a two-character LED display
and a six-button programmable keypad that enables
operators and occupants to change setpoints,
balance VAV boxes, monitor occupancy status, and
turn equipment on and off. An enhanced version of the
Smart Sensor is also available with a four-digit custom
LCD that provides the following icons: PM, %, °,
Setpoint, Cool, Heat, CFM, Fan, OA, and SP.
Connection Labels
(LOW)
(HIGH)
2
3
4
5
6
7
8
9
10
11
(LOW)
(HIGH)
2
3
4
5
6
7
8
9
10
11
(LOW)
(HIGH)
2
3
4
5
AIR FLOW
INPUT
CAUTION
IN 1 1
IN 2
RET
IN 3
IN 4
RET
SPWR
RET
IN 5
24 VAC
IN 1 1
IN 2
RET
IN 3
IN 4
RET
SPWR
RET
IN 5
24 VAC
IN 1 1
IN 2
RET
24 VAC
MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED
TO DE-ENERGIZE THI S EQUIPMENT
BEFORE SERVICING.
UNIVERSAL
INPUT S
This equipment complies with part 15
of the FCC rules. Operation is subject
to the following two conditions.
(1) This device may not cause harmful
interference.
(2) This device must accept any
interference received, including
interference that may cause
undesired operation.
SMART
SENSOR
USE COPPER CO NDUCTORS ONLY
INPUT
:
CLASS 2 POWER ONLY
24VAC , 0.42 A, 10VA, 50/6 0HZ
AIR FLOW
INPUT
CAUTION
MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED
TO DE-ENERGIZE THI S EQUIPMENT
BEFORE SERVICING.
UNIVERSAL
INPUT S
This equipment complies with part 15
of the FCC rules. Operation is subject
to the following two conditions.
(1) This device may not cause harmful
interference.
(2) This device must accept any
interference received, including
interference that may cause
undesired operation.
SMART
SENSOR
USE COPPER CO NDUCTORS ONLY
INPUT
:
CLASS 2 POWER ONLY
24VAC , 0.42 A, 10VA, 50/6 0HZ
AIR FLOW
INPUT
UNIVERSAL
INPUT S
USE COPPER CO NDUCTORS ONLY
INPUT
:
CLASS 2 POWER ONLY
24VAC , 0.42 A, 10VA, 50/6 0HZ
CAUTION
MORE THAN ONE DISC ONNECT
SWITCH MAY BE REQUIRED
TO DE-ENERGIZE TH IS EQUIPMENT
BEFORE SERVICING.
This equipment complies with part 15
of the FCC rules. Operation is subject
to the following two conditions.
(1) This device may not cause harmful
interference.
(2) This device must accept any
interference received, including
interference that may cause
undesired operation.
865-V
OUTPUTS
24V AC ,
866-V
OUTPUTS
0-10 VDC
OUTPUTS
24V AC ,
885-V
OUTPUTS
24V AC ,
RS-485
PORT
DIGITAL
0.5A
RS-485
PORT
ANALOG
DIGITAL
0.5A
RS-485
PORT
DIGITAL
0.5A
COM
COM
SHIELD
TRIAC REF
OUT5
OUT4
OUT3
COM
COM
SHIELD
A07
RET
AO6
TRIAC REF
OUT5
OUT4
OUT3
COM
COM
SHIELD
TRIAC REF
NOT USED
OUT4
OUT3
18
17
16
15
14
13
12
21
20
19
18
17
16
15
14
13
12
12
11
10
9
8
7
6
Schneider Electric One High Stre et, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674
SDS-I2865/866/885-US.BU.N.EN.7.2018.0.02.CC
Andover Continuum Infinet II
i2865/866/885-V VAV Controllers with Built-in Actuator
Specifications
i2865/866/885-V Controller
05
Electrical
Power
24 VAC, +10%-15%, 50/60 Hz,
Class 2 Limited Power
Power Consumption
Less than 10 VA
Overload Protection
Fused, MOV protected
Mechanical
Operation Environment
32° to 122°F (0-50°C),
10 - 90% RH (non-condensing)
Dimensions
7.75˝ W x 6.25˝ L x 2.5˝ H
(197 mm W x 159 mm L x63 mm H)
Weight
2.30 lbs (1.04 kg)
Battery
Battery Backup
Replaceable, rechargeable battery.
Provides 30 days typical accumulated
power failure backup of RAM memory.
All data stored in Flash on power loss.
Communications
RS-485 port for implementing Andover
Continuum Andover Continuum Infinet II
connection, including:
Three-position removable screw terminal
Standard service port,
four-position shrouded connector
LEDs:
TD = Transmit Enable
RD = Received Data
Wired/Wireless Field Bus
RS-485 port for implementing Wireless
Andover Continuum Infinet II connection,
including:
four-position shrouded connector
Standard service port,
User LEDs
Status Indicator LEDs
CPU CPU Active
Yellow = Infinet II
Damper Shaft Mounting Screws
Torque Minimum
Varies according to shaft material
Torque Maximum
30 inch-pounds (3.4 Nm)
Hex Screws
10-32 (with supplied hex wrench)
Airflow Input
Range
0 to 1˝ W.C. (0-250 Pa)
Resolution
0.0013˝ W.C. (0.33Pa) @ 73°F (23°C)
Accuracy
+ 0.05˝ W.C. (12.50 Pa) @ 73°F (23°C)
Damper Actuator Motor
Shaft Diameter
1/2˝ (with a 3/8˝ adapter)
12.6 mm (with a 9.45 mm adapter)
Shaft Torque
53 inch-pounds (5.989 Nm)
Damper Speed
180 sec. @ 60 Hz and
216 sec @ 50 Hz: for 90°
adjustable end limits with two set screws
Motor
Type: 24 VAC synchronous
Motor Protection: Mechanical clutch
Manual clutch override with a
push-button release
Hardware position feedback
(model i2866-V only)
Universal Inputs
Connections
Model i2865 -V:
Four inputs and two returns
Model i2866-V:
Four inputs and two returns
Model i2885-V: Two inputs and one return
Input Voltage Range
0 to 5.115 VDC
Input Impedance
10K ohm to 5.120 V
Input Voltage Resolution
5.0 mV
Digital Resolution
10 bits
Input Voltage Accuracy
+ 15m V
Temperature Range
-30° to 230°F (-34° to 110°C)
Temperature Accuracy
+ 1° F from -10° to 150°F
(+ 0.56°C from -23° to +66°C)
Counter Frequency
4 Hz @ 50% duty cycle
Input Protection
+ 1000 V transients
Input Filter
16 Hz with one pole RC filter
Connector
Removable, 5 mm screw terminal
Schneider Electric SDS-I2865/866/885-US.BU.N.EN.7.2018.0.02.CC
Andover Continuum Infinet II
i2865/866/885-V VAV Controllers with Built-in Actuator
06
Specifications
(continued)
i2865/866/885-V Controller
Smart Sensor Interface
Connections
Model i2865-V: One input, SPWR,
and return
Model i2866-V: One input, SPWR,
and return
Model i2885-V: Not available
Digital Outputs
Connections
Model i2865-V:
Three triac outputs and one reference
Model i2866-V:
Three triac outputs and one reference
Model i2885-V: Two triac outputs
and one reference
SPST Accuracy
0.1 second for pulse width modulation
Contact Ratings
0.5 A Maximum, 24 VAC
Connector
Removable, 5mm screw terminal
Analog Outputs
Connections
Model i2865 : Not available
Model i2866:
Two analog outputs and one return
Model i2885: Not available
Analog Output Channels Required
Two, voltage only
Voltage Output Range
0 - 10 V
Output Source Current
5 mA Maximum
Voltage Output Load
2K ohm Minimum Impedance
Voltage Output Resolution
50 mV
Digital Resolution
8 bits
Output Voltage Accuracy
100 mV
Connector
Removable, 5mm screw terminal
Agency Listings
FCC Rules and Regulations CFR 47,
Part 15, Class A, ICES-003, AS/NZS 3548,
European Union (EU) Directive 2002/96/EC
Options
UL864, Smoke Control System Equipment,
UUKL (i2865-V-S, i2866-V-S, i2885-V-S)
Models
i2865-V
Infinet II 865-V VAV Controller
i2866-V
Infinet II 866-V VAV Controller
i2885-V
Infinet II 885-V VAV Controller
i2865-V-WL
Wireless Infinet II 865-V VAV Controller
i2866-V-WL
Wireless Infinet II 866-V VAV Controller
i2885-V-WL
Wireless Infinet II 885-V VAV Controller
All brand names, trademarks and registered trademarks are the propert y of their respective owners. Information contained within this document is subject to change
without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual ide ntity of Schneider Electric, however there remains references to TAC as a corporate brand in the body copy. As each docume nt is updated, the body copy will be changed to reflect appropriate corporate