Short-Circuit Current Ratings (SCCR) and branch circuit protection

The table shows recommended fuse ratings for UL and CSA requirements. The components are for use together in accordance with standard UL508
Input
Voltage
+10%/-15%
60 Hz
Y
Without line
208/230V
Three-phase
With line
Without line
400/480 V
Three-phase
With line
ATV312 Drive
(kW) (HP) Reference
6
Input AIC
Rating
(kA)
Minimun
Inductance
(mH)
Line
Reactor
Reference
Output
Interrupt
Rating:
1
(kA)
With Circuit
Breaker
PowerPact
Z1, Z2
SCCR (kA)
With GVpP With Fuses
GV2P/3P
3
Type E
X
Z1, Z2
SCCR
3, 4
(kA)
Fuse (A) 5
Z1, Z2
Three-phase with or without line reactor
0.18 0.25 ATV312H018M3 5 - - 100 HxL36015 22 - - 3 22
0.37 0.5 ATV312H037M3 5 - - 100 HxL36015 22 - - 6 22
0.55 0.75 ATV312H055M3 5 - - 100 HxL36015 22 - - 10 22
0.75 1 ATV312H075M3 5 - - 100 HxL36015 22 - - 10 22
1.1 1.5 ATV312HU11 M3 5 - - 100 HxL36015 22 - - 15 22
1.5 2 ATV312HU15M3 5 - - 100 HxL36015 22 - - 15 22
2.2 3 ATV312 HU22M3 5 - - 100 HxL36020 22 - - 2 0 22
3 - ATV312HU30M3 5 - - 100 HxL36020 22 - - 25 22
reactor
4 5 ATV312HU40M3 5 - - 100 HxL36030 22 - - 35 22
5.5 7.5 ATV312HU55M3 22 - - 100 HxL36040 22 - - 50 22
7.5 10 ATV312HU75M3 22 - - 100 HxL36060 22 - - 60 22
11 15 ATV312HD11M3 22 - - 100 HxL36070 22 - - 80 22
15 20 ATV312HD15M3 22 - - 100 HxL36090 22 - - 110 22
0.18 0.25 ATV312H018M3 5 3 RL-00401 100 HxL36015 65 GV2P07 65 3 22
0.5 ATV312H037M3 5 3 RL-00401 100 H xL36015 65 GV2P08 65 6 22
0.37
0.55 0.75 ATV312H055M3 5 3 RL-00401 100 HxL36015 65 GV2P10 65 10 22
0.75
reactor
0.37 0.5 ATV312H037N4 5 - - 100 HxL36015 22 - - 3 22
0.55 0.75 ATV312H055N4 5 - - 100 HxL36015 22 - - 6 22
0.75
reactor
0.37 0.5 ATV312H037N4 5
0.55 0.75 ATV312H055N4 5
0.75 1 ATV312H075N4 5
reactor
1 ATV312H075M3 5 3 RL-00401 100 HxL36015 65 GV2P 10 65 10 22
1.1 1.5 ATV312HU11M3 5 1.5 RL-00801 100 HxL36015 65 GV2P14 65 15 22
1.5 2 ATV312HU15M3 5 1.5 RL-00801 100 HxL36015 65 GV2P14 65 15 22
2.2 3 ATV312 HU22M3 5 1.25 RL-01201 100 HxL36020 65
3 - ATV312HU30M3 5 1.25 RL-01801 100 HxL36020 65 GV3P18 65 25 22
4 5 ATV312HU40M3 5 1.25 RL-01801 100 HxL36030 65 GV3P25 65 35 22
5.5 7.5 ATV312HU55M3 22 0.5 RL-02501 100 HxL36040 65
7.5 10 ATV312HU75M3 22 0.4 RL-03501 100 HxL36060 65 GV 3P50 65 60 22
11 15 ATV312HD11M3 22 0.3 RL-04501 100 HxL36070 65 GV3P65 65 80 22
15 20 ATV312HD15M3 22 0.2 RL-08001 100 HxL36090 65 - - 110 22
1 ATV312H075N4 5 - - 100 HxL36015 22 - - 6 22
1.1 1.5 ATV312HU11N4 5 - - 100 HxL36015 22 - - 10 22
1.5 2 ATV312HU15N4 5 - - 100 HxL36015 22 - - 10 22
2.2 3 ATV312HU22N4 5 - - 100 HxL36015 22 - - 15 22
3 - ATV312HU30N4 5 - - 100 HxL36015 22 - - 15 22
4 5 ATV312HU40N4 5 - - 100 HxL36015 22 - - 20 22
5.5 7.5 ATV312HU55N4 22 - - 100 HxL36020 22 - - 30 22
7.5 10 ATV312HU75N4 22 - - 100 HxL36030 22 - - 35 22
11 15 ATV312HD11N 4 22 - - 100 HxL36035 22 - - 50 22
15 20 ATV312HD15N4 22 - - 100 HxL36050 22 - - 70 22
1.1 1.5 ATV312HU11N4 5
1.5 2 ATV312HU15N4 5
3ATV312HU22N4 5
2.2
3-ATV312HU30N45
45ATV312HU40N4 5
5.5 7.5 ATV312HU55N4 22
7.5 10 ATV312HU75N4 2 2
11 15 ATV312HD11N4 22
15 20 ATV312HD15N4 22
12 RL00201 100
12 RL00201 100
12 RL00201 100
6.5 RL00402 100
6.5 RL00402 100
5 RL00803 100
3 RL00802 100
3 RL00802 100
2.5 RL01202 100
1.5 RL01802 100
1.2 RL02502 100
0.8 RL03502 100
HxL36015 65
HxL36015 65
HxL36015 65
HxL36015 65
HxL36015 65
HxL36015 65
HxL36015 65
HxL36015 65
HxL36020 65
HxL36030 65
HxL36035 65
HxL36050 65
GV3P18 /
GV3P40/
GV2P07 65 3 100
GV2P07 65 6 100
GV2P08 65 6 100
GV2P08 65 10 100
GV2P10 65 10 100
GV2P14 65 15 100
GV2P14 65 15 100
GV3P13 65 20 100
GV3P18 65 30 100
GV3P25 65 35 100
GV3P32 65 50 100
GV3P40 65 70 100
65 20 22
13
65 50 22
32
SCCR
(kA)
2,3
X
Footnotes are on the reverse side.
www.schneider-electric.com 1/4 S1B16328 - 02/2012
Input
Voltage
+10%/-15%
60 Hz
Y
575/600 V
Three-phase
208/230 V
Single-phase
400/480 V
Single-phase
ATV312 Drive
(kW) (HP) Reference
0.75 1 ATV312H075S6 5
1.5 2 ATV312HU15S6 5
2.2 3 ATV312HU22S6 5
45ATV312HU40S6 5
5.5 7.5 ATV312HU55S6 22
reactor
With line
7.5 10 ATV312HU75S6 22
11 15 ATV312HD11S6 22
15 20 ATV312HD15S6 22
0.18 0.25 ATV312H018M2 1
0.37 0.5 ATV312H037M2 1
0.55 0.75 ATV312H055M2 1
0.75 1 ATV312H075M2 1
1.1 1.5 ATV312HU11M2 1
1.5 2 ATV312HU15M2 1
reactor
2.2 3 ATV3 12HU22M2 1
Without line
45ATV312HU75M3 2
5.5 7.5 ATV312HD11M3 2
7.5 10 ATV312HD15M3 2
45ATV312HU75M322
5.5 7.5 ATV312HD11M3 22
7.5 10 ATV312HD15M3 22
reactor
With line
0.37 0.5 ATV312H075N4 5
0.55 0.75 ATV312HU11N4 5
0.75 1 ATV312HU15N4 5
1.1 1.5 ATV312HU22N4 5
1.5 2 ATV312HU30N4 5
2.2 3 ATV312HU40N4 5
reactor
2.2 3 ATV 312HU55N4 22
Without line
45ATV312HU75N422
5.5 7.5 ATV312HD11N4 22
7.5 10 ATV312HD15N4 22
0.37 0.5 ATV312H075N4 5
0.55 0.75 ATV312HU11N4 5
0.75 1 ATV312HU15N4 5
1.1 1.5 ATV312HU22N4 5
1.5 2 ATV312HU30N4 5
2.2 3 ATV312HU40N4 5
reactor
With line
2.2 3 ATV 312HU55N4 22
45ATV312HU75N422
5.5 7.5 ATV312HD11N4 22
7.5 10 ATV312HD15N4 22
6
Input AIC
Rating
(kA)
Minimun
Inductance
(mH)
Line
Reactor
Reference
Output
Interrupt
Rating:
(kA)
Three-phase with line reactor
20 RL-00202 100
9 RL-00403 100
6.5 RL-00402 100
5RL-00803100
2.5 RL-01202 100
2.5 RL-01202 100
1.5 RL-01802 100
1.2 RL-02502 100
Single-phase with or without line reactor
--100
--100
-- 100
--100
--100
--100
--100
--100
--100
--100
0.75 RL-03502 100
0.375 RL-05502 100
0.278 RL-08002 100
--100
--100
-- 100
--100
--100
--100
--100
--100
--100
--100
5.79 RL-00402 100
4.27 RL-00402 100
4.27 RL-00803 100
2.77 RL-00802 100
2.77 RL-00802 100
1.68 RL-01202 100
1.29 RL-01802 100
0.912 RL-02502 100
0.694 RL-03502 100
0.569 RL-04502 100
PowerPact
1
Z1, Z2
FAL36015 22
FAL36015 22
FAL36015 22
FAL36025 22
FAL36040 22
FAL36050 22
FAL36070 22
FAL36080 22
HxL36060 22
HxL36070 22
HxL36090 22
HxL36060 65
HxL36070 65
HxL36090 65
HxL36015 22
HxL36015 22
HxL36015 22
HxL36015 22
HxL36015 22
HxL36015 22
HxL36020 22
HxL36030 22
HxL36035 22
HxL36050 22
HxL36015 65
HxL36015 65
HxL36015 65
HxL36015 65
HxL36015 65
HxL36015 65
HxL36020 65
HxL36030 65
HxL36035 65
HxL36050 65
With Circuit
Breaker
SCCR (kA)
--
--
--
--
--
--
--
With GVpP With Fu ses
GV2P/3P
3
Type E
X
Z1, Z2
GV3P50 65 60 22
GV3P65 65 80 22
GV2P08 65 6 22
GV2P08 65 10 22
GV2P10 65 10 22
GV2P14 65 15 22
GV2P14 65 15 22
GV3P13 65 20 22
GV3P18 65 30 22
GV3P25 65 35 22
GV3P32 6 5 50 22
GV3P40 65 70 22
SCCR
3, 4
(kA)
--622
--622
--1022
--1522
- - 20 22
--2522
--3522
--4522
--622
--1022
--1022
--1522
- - 20 22
- - 20 22
--3022
--6022
--8022
--11022
--11022
--622
--1022
--1022
--1522
--1522
- - 20 22
--3022
--3522
--5022
--7022
Fuse (A) 5
Z1, Z2
SCCR
(kA)
2,3
X
Suitable for use on a circuit capable of delivering not more than___X___rms symmetrical kiloAmperes,___Y___Volts maximum, when protected by___Z1___with a maximum rating of___Z2___.
1.
The Altivar 312 has a 100k SCC rati ng on the output of the drive as many other drives are rated. In addition to providin g a rating based on shorting the output of the drive, these short-circuit rating have been obtained by testing the weakest point inte rnal to the ATV312 per UL508C. These ratings allow proper coordination of short-circuit protection. The amp rating of the short-circuit protection devices in the table are maximum values. Smaller amp sizes may be used.
2.
Ratings also apply to ATV312 Type 1 product, ie: an ATV312 fitted with a conduit box.
3.
Ratings apply to an ATV312 mounted in a non-ventilated Type 1, 3R, 4(X) or 12 rated enclosure. Minimum enclosure volume is 3.375 times the drive
volume .
4.
480 V ratings are for Wye connected electrical distribution systems. GV2Ppp self protected manual combination starter must be used with
GV2GH7 insulating barrier to meet UL 508 Type E rating. GV3Ppp must be used with GV3G66 and GVAM11 in order to meet UL508 rating.
5.
Fuse type can be Class J, fast acting or time delay, or Class CC.
6.
Available also for B products. Example: ATV312H018M3B