ASCO 7000 SERIES 7ATB, 7ACTB, 7ADTB
Automatic Transfer & Bypass–Isolation Switches
G, Q, S, & U design
Installation Manual
381333-415 A
9/2016
An experienced licensed electrician must install
DANGER is used in this manual to warn of a
hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING is used in this manual to warn of a
hazardous situation which, if not avoided, could
result in death or serious injury.
the ATB.
The Transfer Switch nameplate includes data for each
specific 7000 Series ATB Use the switch only within
the limits shown on this nameplate. A typical Catalog
Number is shown below with its elements explained:
Nameplate
CAUTION is used in this manual to warn of a
hazardous situation which, if not avoided, could
result in minor or moderate injury.
Refer to the outline and wiring drawings provided with
your 7000 Series ATB for all installation and
connection details and accessories.
Refer to Group 5 Controller User’s Guide 381333–126
for ATS status display messages, time delays, pickup
& dropout settings, and adjustments.
Rating Label
Each 7000 Series ATB contains a rating label to
define the load and fault circuit withstand/closing
ratings. Refer to the label on the Transfer Switch for
specific values.
Do not exceed the values on the rating label.
Exceeding the rating can cause personal injury
or serious equipment damage.
Catalog Number Identification .................................................................................................................................. 3
Remove the Shipping Skid ....................................................................................................................................... 4
Supporting Foundation and Mounting ...................................................................................................................... 4
Remove Shipping Brackets/Angles from the Transfer Switch .................................................................................. 4
Testing Power Conductors ....................................................................................................................................... 5
Connecting Power Conductors ................................................................................................................................. 5
Bus Connections ...................................................................................................................................................... 5
Functional Test ......................................................................................................................................................... 6
Functional Test – Voltage Checks ............................................................................................................................ 6
Functional Test - -Electrical Operation .................................................................................................................... 6
Testing & Service ...................................................................................................................................................... 8
Transfer Test ............................................................................................................................................................ 8
Replacement Parts ................................................................................................................................................... 8
Manual Load Transfer .............................................................................................................................................. 8
Bypassing the ATS ................................................................................................................................................. 10
To Bypass Normal Source ...................................................................................................................................... 10
To Bypass Emergency Source ............................................................................................................................... 10
Isolating the ATS .................................................................................................................................................... 11
Return to Service .................................................................................................................................................... 13
Index .......................................................................................................................................................................... 15
2 381333-415 B
7000 Series ATB, ACTB, ADTB Installation Manual
Catalog Number Identification
Typical 7000 Series G7ATB catalog no. for overlapping neutral, 3 pole, 4000 A, 480 V, in a Type 1 enclosure:
G 07A TB C 3 4000 N 5
Design
prefix
letter
G
Q
S
U
Transition
Type
07A open
7AC closed
7AD delayed
Neutral Phase
A- solid
B- switching
C- overlapping*
blank-none
*Overlapping neutral
not available for
Q, S, & U-designs
Poles
single
2
3 three
Amperes
600
800
1000
1200
1600
2000
2600
3000
Voltage Controller
A 115
B 120
C 208
D 220
E 230
F 240
G 277
H 380
J 400
K 415
L 440
M 460
N 480
P 550
Q 575
R 600
4000
Status
Lights
&
Engine
Control
Bypass
Handle
Transfer Control
5 standard
if
5X
accessories
ordered
& Lights
C
Enclosure
C type 1
F type 3R
G type 4
L type 12
blanc –
open type
Isolation
Handle
Group 5 Controller
Transfer Switch
Typical G7ATB with lower doors open (transfer switch shown)
381333-415 B 3
Installation Manual Installation
INSTALLATION
The ASCO 7000 Series Automatic Transfer &
Bypass–Isolation Switch (ATB) consists of an upper
bypass–isolation switch, a lower transfer switch, a
monitoring and transfer controller, and door–mounted
controls. The ATB is factory wired and tested.
Installation requires removal of the shipping skid then
securing the enclosure to the supporting foundation.
Remove the Shipping Skid
Open the front lower door and remove the two front
lag screws securing the enclosure to the wood skid.
Next remove the rear lower panel and remove the two
rear lag screws securing the enclosure to the wood
skid.
Supporting Foundation and Mounting
The supporting foundation for the enclosure must be
level and straight. Allow at least 35 inches in front of
the enclosure for draw out of the Transfer Switch.
Refer to the enclosure outline drawing included with
the 7000 Series ATB for all mounting details including
door opening space.
To prevent serious damage, remove three or four
shipping brackets or L–angles from the Transfer
Switch carriage. Do not turn the Isolation Handle
until they are removed!
If bottom cable entry is used, the foundation must be
prepared so that the conduit stubs are located
correctly. Refer to the appropriate enclosure outline
drawing for specified cable entrance area and
location. Provide cable bending space and clearance
to live metal parts. When a concrete floor is poured,
use interlocking conduit spacer caps or a wood or
metal template to maintain proper conduit alignment.
Mounting
Refer to the enclosure outline drawing furnished with
this switch and mount the 7000 Series ATB according
to the details and instructions shown on the drawing.
Remove Shipping Brackets / Angles
from the Transfer Switch
Open the lower front door(s). The Transfer Switch
carriage is secured to the frame for shipment.
Remove the three or four shipping brackets or L–
angles: (1 upper left, 1 upper right, and 2 lower).
remove 3 or 4 shipping brackets ( L–angles)
Figure 1. 600–3000 A remove shipping brackets.
remove 2 upper shipping brackets
remove 2 lower
shipping brackets
Figure 2. 4000 A remove four shipping brackets.
4 381333-415 B
Installation Installation Manual
Bus Connections
De–energize the conductors before making any
line or auxiliary circuitry connections. Be sure
that Normal and Emergency line connections are
in proper phase rotation. Place engine generator
starting control in the OFF position. Make sure
engine generator is not in operation.
If bus connection is used, use SAE grade 5 hardware
to connect bus to appropriate terminal plates on
bypass switching device. Wipe off bus surfaces
before they are joined. If bus is dirty, gently clean
surfaces with a non-flammable solvent. Avoid
touching cleaned surfaces.
Testing Power Conductors
Do not connect the power conductors to the ATB
until they are tested. Installing power cables in
conduit, cable troughs, and ceiling-suspended
hangers often requires considerable force. The
pulling of cables can damage insulation and
stretch or break the conductor’s strands. For this
reason, after the cables are pulled into position,
and before they are connected they should be
tested to verify that they are not defective or
have been damaged during installation.
Protect the switch from construction grit and
metal chips to prevent malfunction or shortened
life of the ATB switch.
Connecting Power Conductors
A Wiring Diagram is furnished with the ATB. All
wiring must be made in accordance with the local
codes. After the power cables have been tested,
connect them to the appropriate terminal lugs on the
Bypass Switch as shown on the wiring diagram
provided with this ATB. Make sure that the lugs
provided are suitable for use with the cables being
installed. Standard terminal lugs are solderless screw
type and will accept the wire sizes listed on the
drawings provided with the ATB. Be careful when
stripping insulation from conductors; avoid nicking or
ringing the conductor. Remove surface oxides from
conductors by cleaning with a wire brush. Follow
conductor manufacturer’s instructions when aluminum
conductor is used. Apply joint compound to
conductor, then carefully wipe away excess
compound. Tighten the cable lugs to the torque
specified on the rating label.
Do not breathe cleaning solvent vapors.
Use SAE grade 5 hardware and tighten the
bolted joints to the torque specified in Table A.
The reliability of the connection depends
on how clean and how tight the joint is.
Table A. Tightening torque values for bolted joints.
Bolt Diameter
(Grade 5 hardware)
in inches
5/16 12
3/8 20
1/2 50
5/8 95
Recommended
Tightening Torque
in foot pounds
Harnesses
All internal connections are made at the factory. The
bypass switch, transfer switch, and control panel are
joined together by an interconnecting wire harness.
The disconnect plugs are already engaged on
enclosed switches. For open–type switches, the
plugs must be engaged after installation is completed.
Align harness plugs with sockets in the control and
push them together until they are secure.
Controller Ground
A grounding wire must be connected to the
controller’s lower left mounting stud. Because the
controller is mounted on the enclosure door, a
conductive strap must be used between the enclosure
and the door. This connection provides proper
grounding which does not rely upon the door hinges.
Engine Starting Contacts
and Auxiliary Circuits
Be sure that the Normal and Emergency power
connections are in proper phase rotation.
381333-415 B 5
The engine control contact signal connections and
auxiliary circuits are located on terminal block TB as
shown on the Wiring Diagram provided with the ATB.
Connect the signal wires to the appropriate terminals.
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.