The information provided in this documentation contains general descriptions and/or technical characteristics
of the performance of the products contained herein. This documentation is not intended as a substitute for
and is not to be used for determining suitability or reliability of these products for specific user applications. It
is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and
testing of the products with respect to the relevant specific application or use thereof. Neither Schneider
Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information
contained herein. If you have any suggestions for improvements or amendments or have found errors in this
publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including
photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be
followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in
injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
Read these instructions carefully, and look at the equipment to become familiar with the device before trying
to install, operate, or maintain it. The following special messages may appear throughout this documentation
or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard
exists, which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all
safety message that follow this symbol to avoid possible injury or death.
PLEASE NOTE
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious
injury.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious
injury or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment
damage.
CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially hazardous situation which, if not
avoided, can result in equipment damage.
The word “drive” as used in this manual refers to the controller portion of the adjustable speed drive as defined
by NEC.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No
responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
S1A53844 01/20115
Page 6
At a Glance
Document Scope
Validity Note
Related Documents
About the Book
The purpose of this document is to show you how to configure the Altivar 212 to use Modbus for monitoring
and control.
NOTE: Read and understand this document and all related documents (see below) before installing,
operating, or maintaining your ATV212.
This documentation is valid for the Altivar 212 Modbus fieldbus.
Title of DocumentationReference Number
ATV212 Quick StartS1A53825
ATV212 Installation manualS1A53832
ATV212 Programming manualS1A53838
ATV212 BACnet manualS1A53845
ATV212 Metasys N2 manualS1A53846
ATV212 Apogée FLN P1 manualS1A53847
ATV212 LonWorks manualS1A53848
ATV212 other option manuals: see www.schneider-electric.com
You can download the latest versions of these technical publications and other technical information from our
website at www.schneider-electric.com.
Product Related Information
UNINTENDED EQUIPMENT OPERATION
• Read and understand this manual before installing or operating the Altivar 212 drive.
• Any changes made to the parameter settings must be performed by qualified personnel.
Failure to follow these instructions will result in death or serious injury.
DANGER
6S1A53844 01/2011
Page 7
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Read and understand this manual before installing or operating the drive. Installation, adjustment, repair,
and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical code requirements with
respect to grounding of all equipment.
• Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH.
Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/– or across the DC bus capacitors.
• Before servicing the drive:
- Disconnect all power, including external control power that may be present.
- Place a “DO NOT TURN ON” label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
- Measure the voltage of the DC bus between the PA/+ and PC/– terminals to ensure that the voltage is
less than 42 Vdc.
- If the DC bus capacitors do not discharge completely, contact your local Schneider Electric
representative. Do not repair or operate the drive
• Install and close all covers before applying power or starting and stopping the drive.
Failure to follow these instructions will result in death or serious injury.
WARNING
DAMAGE DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure modes of control paths and, for
certain critical control functions, provide a means to achieve a safe state during and after a path failure.
Examples of critical control functions are emergency stop and overtravel stop.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications
of unanticipated transmission delays or failures of the link (1).
Failure to follow these instructions can result in death, serious injury, or equipment damage.
(1) For additional information, refer to NEMA ICS 1.1 (latest edition), “Safety Guidelines for the Application, Installation, and
Maintenance of Solid State Control” and to NEMA ICS 7.1 (latest edition), “Safety Standards for Construction and Guide
for Selection, Installation and Operation of Adjustable-Speed Drive Systems.”
S1A53844 01/20117
Page 8
8S1A53844 01/2011
Page 9
Introduction
Introduction
1
Data exchanges give access to all Altivar 212 functions:
The communication port has an RJ45 and an open style connector for the connection to the network. At the
physical layer, it supports 2-wire RS485 and transmission speed at 9600 or 19200 bps.
4 Modbus functions are available:
• 3 (16#03) Read Holding Registers
• 6 (16#06) Write Single Register
• 16 (16#10) Write Multiple Registers
• 43/14 (16#2B/0E) Read Device Identification
Function 3 has a restricted implementation:
• with length 1 it permits to read any parameter of the drive, one by one, see page 33.
• with lengths 1 to 5 it permits to read a particular block of 1 to 5 indirect parameters. These 5 parameters
can be configured through the operation panel to relevant monitoring parameters, see page 34.
Function 16 has a restricted implementation:
• with length 1 it permits to write any writable parameter of the drive, one by one, see page 37.
• with length 1 to 2 it permits to write a particular block of 1 to 2 indirect parameters. These 2 parameters can
be configured through the operation panel to relevant control parameters, see page 38.
S1A53844 01/20119
Page 10
Introduction
10S1A53844 01/2011
Page 11
Hardware setup
Hardware setup
What's in this Chapter?
This chapter contains the following topics:
Pin out of the Open Style Modbus connector12
Connection via Open Style wiring system13
Open Style Reference13
Pin out of the RJ45 Modbus connector13
Connection via RJ45 wiring system14
RJ45 Reference14
Protection Against Interference15
Description of terminals16
2
TopicPage
S1A53844 01/201111
Page 12
Pin out of the Open Style Modbus connector
Open Style Connector
RJ45
Diagnostic DELs
Line termination switch
PLCFM
Sink
SW102
FR
Source
SW101
RES PLC P24
IU
Term
SW103
CC FM
BAGNDSCR
FLA
FLB FLC RYA RYC
VIA U
VIB U
SW100
PPCCVIA VIB
I
PTC
Hardware setup
Open Style Connector (screwcage plug style)
B+
A–
GNDCommon
SCRShield
Note: It is possible to connect two wires
inside one cage in order to be compliant to
daisy chain requirements.
Cross section:
0.2 - 2.5 mm² / AWG 24-12
Tightening torque:
0.5-0.6 Nm / 4.4-5.3 lb/In.
DANGER
UNINTENDED EQUIPMENT OPERATION
• Modify only the setting of the switches when the product is switched off.
• Do not change the setting of the SW102 unless your system is wired for SINK logic.
Failure to follow these instructions will result in death or serious injury.
CAUTION
RISK OF BODY INJURY
Use a screwdriver to change the position of the switches.
Failure to follow these instructions will result in death or serious injury.
12S1A53844 01/2011
Page 13
Hardware setup
ATV 212
2
1
2
Master
1Modbus cable depending on the type of master
2RS 485 double shielded twisted pair cable
8........................1
Connection via Open Style wiring system
Open Style Reference
Modbus serial link connection is carried out using RS 485 double shielded twisted pair cables, supplied without
connector (reference: TSX CSA 100). Maximum length is 100 m (328 ft). The ATV212 drive includes a line
termination as standard. Set switch SW103 to Term to connect the internal 120 Ω termination resistor.
Pin out of the RJ45 Modbus connector
View from underneath
The following table describes the pin out of the ATV212 RJ45 connector.
PinSignal
1Not connected
2Common (common of the signal and power supply)
3Not connected
4D1 (Modbus name) or B (EIA / TIA485 name)
5D0 (Modbus name) or A (EIA / TIA485 name)
6Not connected
7VP, 10 Vdc (supply for RS232/RS485 converter or graphic display option)
8Common (common of the signal and power supply)
CAUTION
RISK OF DAMAGE TO THE DRIVE
Use wiring cables or taps that connect only signals D0, D1 and common.
Failure to follow this instruction can result in injury or equipment damage.
S1A53844 01/201113
Page 14
Connection via RJ45 wiring system
Master
1Modbus cable depending on the type of master
2Modbus splitter box
3Modbus drop cables
4Modbus T-junction box
5Line terminators
Hardware setup
1
ATV 212
3
2
5
33
344 5
33
Description
RJ45 is factory set to connect the graphic display option.
Use the open style connector to connect the drive to Modbus fieldbus.
Using RJ45 to connect Modbus fieldbus is still possible but requires to modify parameter [Com channel choice]
F807 value. Set F807 to 0 [RJ45].
RJ45 Reference
Connection accessories
DescriptionReference
Modbus splitter block10 RJ45 connectors and 1 screw terminalLU9 GC3
For RJ45 connectorR = 120 Ω, C = 1 nFVW3 A8 306 RC
R = 150 Ω VW3A8306R
Connecting cables
DescriptionLength
m
Cables for
Modbus bus
RS 485 double
shielded twisted pair
cables
Type of master Master interfaceModbus connection accessories for RJ45 wiring system
Twido PLC
TSX Premium PLCTSX SCY 11601 or
31 RJ45 connector and 1 stripped endVW3 A8 306 D30
0.32 RJ45 connectorsVW3 A8 306 R03
12 RJ45 connectorsVW3 A8 306 R10
32 RJ45 connectorsVW3 A8 306 R30
100Supplied without connectorTSX CSA 100
200Supplied without connectorTSX CSA 200
500Supplied without connectorTSX CSA 500
Adaptor or mini-DIN RS485
interface module
Adaptor or screw terminal
RS485 interface module
TSX SCY 21601 module
(SUB-D 25 socket)
PCMCIA card (TSX SCP114) Stripped cableTSX SCP CM 4030
ConnectorsReference
DescriptionReference
3 m cable fitted with a mini-DIN connector and an RJ45
connector
3 m cable fitted with an RJ45 connector and stripped at the other
end
Cable fitted with a SUB-D 25 connector and stripped at the other
end (for connection to the screw terminals of the LU9GC3 splitter
block)
TWD XCA RJ030
VW3 A8 306 D30
TSX SCY CM 6030
14S1A53844 01/2011
Page 15
Hardware setup
Ethernet bridge
(TSX ETG 100)
Serial port PCMale SUB-D 9 RS232 serial
Screw terminal RS4853 m cable fitted with an RJ45 connector and stripped at the other
port PC
Protection Against Interference
•
Use the Schneider Electric cable with 2 pairs of shielded twisted conductors (reference: TSXCSA100,
TSXCSA200, TSXCSA500).
• Keep the Modbus cable separated from the power cables (30 cm (11.8 in.) minimum).
• Make any crossovers of the Modbus cable and the power cables at right-angles, if necessary.
For more information, please refer to the TSX DG KBL E manual: “Electromagnetic compatibility of industrial
networks and fieldbuses”.
end
RS232/RS485 converter and
3 m cable fitted with an RJ45 connector and stripped at the other
end (for connection to the screw terminals of the LU9GC3 splitter
block)
It has forward rotation function in default setting.
ON: forward rotation drive
OFF: slowdown and stop
R
RES
Multifunctional programmable logic input.
It has Preset speed command input 1 in default setting.
Multifunctional programmable logic input.
It has Fault Reset in default setting
PPVoltage supply for reference potentiometer.
Switch-configurable voltage or current analog input using
SW100.
VIA
It has speed setpoint function in the default setting. (0 to 50
Hz frequency with 0 to 10 Vdc in voltage or with 0 to 20 mA
in current input). In addition,This analog input is also
configurable as a logic input.
Input for voltage-free contact
24 Vdc, 5 mA or less.
SINK/SOURCE can be selected with
SW102.
Voltage: 10 Vdc
Max current: 10 mA
Protected against short circuits.
Multifunction programmable analog input.
It has speed setpoint function in the default setting
VIB
(0 to 50 Hz frequency with 0 to 10 Vdc input). In addition,
this terminal can be used as PTC (2) input by setting switch
Voltage: 10 Vdc
Internal impedance: 30 kΩ
SW100 and the parameters [Mot PTC selection]F645
and [PTC resistor value]F646.
CCControl circuit equipotential terminal-
This terminal is only active when the switch (SINKSOURCE) is on PLC position. It allow to manage external
PLC
sink or source with static outputs. PLC shall be connected
Max. voltage: 50 Vdc
to 0V (CC terminal) or +24V according to the type of
outputs
P2424 Vdc power supply outputVoltage: 24 Vdc, 50 mA
Voltage analog output: 0...10 Vdc
FM
Switch-configurable voltage or current analog output using
SW101.
Minimum load impedance: 470 Ω
Current analog output: 0...20 mA
Maximum load impedance: 550 Ω
FLA
FLB
FLC
RYA
RYC
Multifunctional programmable relay contact outputs.
Default setting is set to detect the activation of the drive
protection function.
Contact across FLA-FLC is closed and FLB-FLC is open
during normal operation. RYA -RYC is open.
Voltage: 30 Vdc, 0.5 A
250 Vac, 1A
(cos
ϕ = 1)
Voltage: 250 Vac, 0.5A
(cos
ϕ = 0.4)
(2)
(1) Voltage conversion
(2) PTC (Positive Temperature Coefficient): Resettable thermal fuse resistor for over current protection.
16S1A53844 01/2011
Page 17
Hardware setup
B
A
BACnet open style connector
GND
RS485 transmission data, reception
data.
47k
4.7k
B
A
4.7k
47k
SCR
BACnet communication shield terminal.
This terminal is not connected to other circuits in the board.
Ground this terminal in a location separated from the ground of the power line.
GND
SCR
TERM
120
SW103
S1A53844 01/201117
Page 18
Hardware setup
18S1A53844 01/2011
Page 19
Configuration
Configuration
What's in this Chapter?
This chapter contains the following topics:
Configuration of the communication parameters20
Configuration of the control source21
Configuration of the indirect blocks27
Configuration of the communication interruption28
The settings of communication-related parameters can be changed from the operation panel or from Modbus
(PLC, computer or controller) or from graphic display option.
3
TopicPage
Note that there are two types of parameters: parameters whose settings take effect immediately after the
setting and parameters whose settings do not take effect until the drive is turned back on or reset. In the table
below, these 2 types are mentioned in the column "valid" by "After setting" and "After power cycle".
S1A53844 01/201119
Page 20
Configuration of the communication parameters
Access to the parameters
All parameters are accessible in the [COMMUNICATION MENU]COM submenu of [PROGRAMMING
MENU] Programming mode.
UNINTENDED EQUIPMENT OPERATION
Refer to «Serial communication parameters» in the Altivar 212 Programming manual, for more information
on how to set these serial communication parameters.
Failure to follow these instructions will result in death or serious injury.
• Baud rate and parity bit should be uniform inside the same network.
• Modbus address should not be duplicate inside the same network.
• Stop bit isn't configurable. ATV212 Tx is 2 stop bit, Rx is 1 or 2 stop bits. This permits a good comunication
with Master in 1 and 2 stop bits.
• F800 and F801 parameters are used to define the baudrate and parity of RJ45 port.
• F820 and F821 parameters are used to define the baudrate and parity of Open style connector port.
• F802 and F803 parameters are used to define the modbus address and communication time out for
both ports (RJ45 et Open style connector). Set F802 between 1 to 247 (address 0 is not active).
• F807 parameter enables to select the communication command channel: RJ45 or Open style connector.
The port not set as the communication command channel may be used for monitoring purposes to check
that the setting change on F807 was effectively taken into account.
20S1A53844 01/2011
Page 21
Configuration
0
1
2
1
2
3
4
5
4
0
1
LOC
REM
Commands CMOd
Operation panel
Modbus
commands
Terminals
Operation panel
Modbus
setpoint
UP/DOWN
Bit 15 of
command word FA00
Serial com. command priority bit
ON
Operation
panel
Commands
Setpoint
Modbus commands
Modbus setpoint
Setpoint
FMOd
OFF
ON
OFF
Operation
panel
VIB
VIA
Bit 14 of
command word FA00
Serial com. setpoint priority bit
REM
LOC
REM
LOC
F807
Communication
RJ45 channel: Modbus
Network channel:
Paremeter F829
Configuration of the control source
The Altivar 212 can receive commands and setpoint from the Modbus network or from the terminals (F, R,
RES, VIA, VIB). In the default configuration, both commands and setpoint come from the terminals.
The LOC/REM key of the operation panel is available to switch the control to the operation panel. The inputs
F, R or RES can be configured to switch the control from the Modbus network to the terminals.
Different usual possibilities are described in the chapters below:
• Control from the Modbus network,
• Control from the terminals, monitoring from the Modbus network,
• Control from the Modbus network or the terminals, switched via Modbus,
• Command from the Modbus network, setpoint from the Modbus network or the terminals switched to by a
logic input.
Refer to these examples.
Control by the Modbus network
The commands and the setpoint come from the Modbus network. The signals wired on the terminals are
ignored. The LOC/REM key is valid.
Below is the list of parameters that must be configured.
Remote mode secondary speed reference source
that may override the source selected by FMOd
[Com channel choice] (F807)
Selection of Communication channel: via RJ45 or
Open style connector port
3
16#3
4
16#4
274
16#112
519
16#207
2055
16#807
SettingDefault
setting
2 [Communication]
Serial communication
4 [Serial com ref.]
Serial communication
38 [Frequency source]
Configured to Frequency reference
source switching
1 [VIA]: VIA2Setting
0 [RJ45] or
1 [Open style]
Valid
after
0Setting
1Setting
6Setting
1Setting
S1A53844 01/201125
Page 26
Configuration
0
1
2
1
2
3
4
5
1
2
3
4
5
LOC
REM
0
1
CommandsCMOd
Operation panel
Terminals
UP/DOWN
SetpointFMOd
VIB
VIA
Operation panel
UP/DOWN
VIB
VIA
SetpointF207
Operation
panel
Operation
panel
OFF
ON
OFF
ON
Logic input R
[LI R selection]
F112 set to
38 [Frequency source] or
F200 [Auto/man speed ref]
REM
LOC
REM
LOC
Command
Setpoint
F807 [Com channel choice]
RJ45 channel: Modbus
Network channel:
parameter
F829 [Network protocol]
Bit 15 of
command word FA00
Serial com. command
priority bit
Bit 14 of
command word FA00
Serial com. setpoint
priority bit
OFF
ON
Modbus
commands
Modbus
setpoint
Modbus
setpoint
Modbus
commands
Modbus
setpoint
Modbus
setpoint
ON
OFF
Bit 14 of
command word FA00
Serial com. setpoint
priority bit
Commands CMOd
Modbus
commands
Bit 15 of
command word FA00
Serial com. command
priority bit
Operation
panel
Commands
Setpoint
Modbus
setpoint
Bit 14 of
command word FA00
Serial com. setpoint
priority bit
Logic input F, R or RES
F111 ... F113
configured to 48
[Forced local]
Logic input F, R or RES
F111 ... F113
configured to38
[Frequency source]
Operation
panel
Modbus
commands
Operation
panel
Modbus
setpoint
VIB
UP/DOWN
Setpoint FMOd
Setpoint F207
Terminals
VIA
Operation
panel
Modbus
setpoint
VIB
UP/DOWN
VIA
Operation
panel
Modbus
setpoint
Bit 14 of
command word FA00
Serial com. setpoint
priority bit
OFF
ON
REM
LOC
REM
LOC
REM
LOC
REM
LOC
ON
OFF
ON
OFF
ON
OFF
F807 [Com channel choice]
RJ45 channel: Modbus
Network channel:
parameter
F829 [Network protocol]
Complete control diagram
26S1A53844 01/2011
0
1
2
1
2
3
4
5
1
2
3
4
5
0
1
LOC
REM
Page 27
Configuration
Configuration of the indirect blocks
Configuration
These parameters configure the Modbus functions "Read indirect block (3)", page 34 and "Write indirect block
(16)", page 38.
Access to the parameters
All parameters are accessible in the [COMMUNICATION MENU]COM submenu of [PROGRAMMING
MENU] Programming mode.
Description
ParametersModbus
address
[Block write data 1] (F870)2160
16#870
[Block write data 2] (F871)2161
16#871
[Block read data 1] (F875)2165
16#875
[Block read data 2]
[Block read data 3] (F877)2167
[Block read data 4] (F878)2168
[Block read data 5] (F879)2169
(F876)2166
16#876
16#877
16#878
16#879
Adjustment rangeDefault
setting
0 [No select]: No selection
1 [Command word 1]
2 [Command word 2]
3 [Frequency Setpoint]
4 [Relay command]: Ouput data on the terminal board
5 [FM command]: Analog output for communication
6 [Speed Setpoint]
0 [No select]: No selection
1 [Status info]
2 [Freq. out]: Output frequency
3 [Motor current]: Ouput current
4 [Ouput volt]: Ouput voltage
5 [Alarm info]: Alarm information
6 [PID feedback value]
7 [Input term. mon]: Input terminal board monitor
8 [Out term. mon]: Output terminal board monitor
9 [VIA monitor]: VIA terminal board monitor
10 [VIB monitor]: VIB terminal board monitor
11 [Mot speed mon.]: Ouput motor speed monitor
0
0
Valid
after
Power
cycle
Power
cycle
S1A53844 01/201127
Page 28
Configuration of the communication interruption
ON:
OFF:
OpenStyle Tx
OpenStyle Rx
RJ45 Tx
RJ45 Rx
Mdb com stat
RJ45 B - A - COM
RxTxRxTx
RemLoc/Rem
RJ45:
Mb activity on RJ45 port
When Rx and/or Tx are
displayed in this row
their state is inactive
B-A-COM:
Mb activity
on OpenStyle port
Switch between local to remote
mode using the F4 button on the
display terminal
Mdb com stat
RJ45 B - A - COM
TxRxTx
Rx
RemLoc/Rem
Mdb com stat
RJ45 B - A - COM
RxRxTx
Tx
RemLoc/Rem
Configure the Modbus time out
A communication detected fault (Err5 and Err8) is triggered if the Altivar 212 does not receive any valid
Modbus requests at its address within a predefined time period (time out) set in the [Com. time out] (F803)
parameter. The timer starts when the communication has been established for the first time (valid frame, drive
address matches). Any Modbus request function is taken into account to reactivated the timer (read, write and
identification).
Access to the parameter
This parameter is accessible in the [COMMUNICATION MENU]COM submenu of [PROGRAMMING MENU]
Programming mode.
Description
Configuration
ParameterModbus
[Com. time out] (F803)
Communication time out
LOSS OF CONTROL
• If F803 is set to 0, communication control will be inhibited.
• For safety reasons, inhibiting the communication interruption detection should be restricted to the debug
phase or to special applications.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Monitoring the Modbus communication status
Modbus communication status are displayed in Monitoring mode. This parameter enables to check the
modbus communication on RJ45 and OpenStyle port.
On the embedded display terminal
Display
example
Mb
Display on graphic
display option
[Mdb com stat]
Modbus
communication status
address
2051
16#803
Description
SettingUnitDefault
setting
0: Communication detection disabled
1 ... 100: 1 to 100 seconds
s3Setting
WARNING
Valid
after
28S1A53844 01/2011
On the graphic display terminal
Example: With Communication on RJ45 port
Without Communication
Page 29
Configuration
Configure the drive behaviour
The drive trips in Err5[Com RJ45 fault] or Err8[Network error fault] if the communication was
established and the card no longer receives messages from the network.
The response of the drive in the event of a BACnet communication interruption can be configured by the
parameter [Com. fault setting]F851.
Access to the parameter
This parameter is accessible in the [COMMUNICATION MENU]COM submenu of [PROGRAMMING MENU]
Programming mode.
If F851 is set to 1, communication control will be inhibited.
For safety reasons, inhibiting the communication interruption detection should be restricted to the debug
phase or to special application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
LOSS OF CONTROL
Know and understand the setting of parameter F851. This parameter controls the behavior of the drive in
the event of a network communication loss. If the value of F851 is 0, 1, 2, or 3, the drive will not trip on
an Err8.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
S1A53844 01/201129
Page 30
Configuration
30S1A53844 01/2011
Page 31
Modbus services
Modbus services
What's in this Chapter?
This chapter contains the following topics:
Principle of the Modbus protocol32
RTU mode32
Modbus functions available33
Read one word (03)33
Read indirect block (3)34
Write Single Register (6)36
Write multiple registers (16)37
Write indirect block (16)38
Read Device Identification (43/14)40
Error response41
4
TopicPage
S1A53844 01/201131
Page 32
Principle of the Modbus protocol
Only one device can transmit on the line at any one time.
The master manages the exchanges and only it can take the initiative.
It interrogates each of the slaves in succession.
No slave can send a message unless it is invited to do so.
In the event of an error during data exchange, the master repeats the question and
declares the interrogated slave absent if no response is received within a given time
period.
If a slave does not understand a message, it sends an error response to the master. The
master may or may not repeat the request.
Master
Slave i
Slave k
Slave j
The Modbus protocol is a master-slave protocol.
Modbus services
RTU mode
Two types of dialog are possible between master and slaves:
• The master sends a request to a slave and waits for it to respond. The request contains the slave address
(1 ... 247).
• Broadcast: the master sends a request to all slaves. Slaves do not answer. The value of the slave address
is 0.
Direct slave-to-slave communications are not possible.
For slave-to-slave communication, the master’s application software must therefore be designed to interrogate
one slave and send back data received to the other slave.
ATV212 supports RTU mode.
The Modbus RTU frame contains no message header byte, nor end of message bytes.
It is defined as follows:
Slave addressFunction codeDataCRC16
The data is transmitted in binary code.
CRC16: Cyclic redundancy check parameter.
The end of the frame is detected on a silence greater than or equal to 3 characters.
The master must not introduce a space of more than 3.5 characters in a frame; otherwise the drive may
recognize it as a start of new frame.
32S1A53844 01/2011
Page 33
Modbus services
Modbus functions available
The following table indicates which Modbus functions are managed by the Altivar 212 and specifies their limits.
The "read" and "write" functions are defined from the point of view of the master.
CodeFunction nameSize of dataAltivar 212 function nameBroadcast
3 = 16#03Read Holding Registers1 objectRead one wordYes
6 = 16#06Write Single Register1 objectsYes
16 = 16#10Write Multiple Registers1 objectWrite one wordYes
The Read indirect block function permits to read 1 to 5 parameters. These parameters can be chosen by
parameters F875 ... F879 (refer to "Configuration of the indirect blocks", page 27)
Access to the parameter
This parameter is accessible in the [COMMUNICATION MENU]COM submenu of [PROGRAMMING MENU]
Programming mode.
Description
ParametersModbus
[Block read data 1] (F875)2165
[Block read data 2] (F876)2166
[Block read data 3] (F877)2167
[Block read data 4] (F878)2168
[Block read data 5] (F879)2169
address
16#875
16#876
16#877
16#878
16#879
Modbus services
Adjustment rangeDefault
setting
0 [No select]: No selection
1 [Status info]
2 [Freq. out]: Output frequency
3 [Motor current]: Ouput current
4 [Ouput volt]: Ouput voltage
5 [Alarm info]: Alarm information
6 [PID feedback value]
7 [Input term. mon]: Input terminal board monitor
8 [Out term. mon]: Output terminal board monitor
9 [VIA monitor]: VIA terminal board monitor
10 [VIB monitor]: VIB terminal board monitor
11 [Mot speed mon.]: Ouput motor speed monitor
0
Valid
after
Power
cycle
Request:
Slave no.Function code Starting addressQuantity of registersCRC16
Example: Read indirect block in an drive with slave address 1.
Configuration parameters:
[Block read data 1] (F875) = 1: [drive Status](Fd01)
[Block read data 2](F876) = 2: [Output frequency](Fd00)
[Block read data 3](F877) = 3: [Output current](FE03)
[Block read data 4](F878) = 4: [Output voltage](FE05)
[Block read data 5] (F879) = 5: [Alarm code](FC91)
• Read indirect block of 5 parameters:
Request:010318 7500 0592 B3
Response:01030A64 0417 7000 0026 FB00 801E 29
34S1A53844 01/2011
Page 35
Modbus services
• Read indirect block of 2 parameters:
Request:010318 7500 02D3 71
Response:01030464 0417 70AA D6
• Error response on invalid starting address:
Request:010318 7600 0223 71
Response:01830301 31
• Error response on invalid quantity of registers:
Request:010318 7500 06D2 B2
Response:01830301 31
Note: Reading values of parameters F875 to F879. Value of parameter F87p can be read by reading the address
187p.
Example for parameter F875:
0875: parameter assignment
1875: parameter value
S1A53844 01/201135
Page 36
Write Single Register (6)
The Write Single Register function permits to write value of one parameter. Not all Altivar 212 parameters can
be written.
Request and response:
Slave no.Function code
1 byte1 byte2 bytes2 bytes2 bytes
Error response:
Slave no.86Exception code
1byte1byte1byte1byte
Example: Write value 60 Hz to the parameter [Frequency reference from serial comm.](FA01) in Altivar
212 slave 1.
Request and response:
0106FA011770E6C6
06
Modbus services
Register addressRegister valueCRC16
HiLoHiLoLoHi
CRC16
LoHi
Example: Error response due to invalid register address.
Request:
0106FFFF000089EE
Error response:
018602C3A1
36S1A53844 01/2011
Page 37
Modbus services
Write multiple registers (16)
Function 16 = 16#10, quantity =1
This function code is used to write a block of contiguous registers (1 to approx. 120 registers). Read only
parameters can't be written.
Request:
Slave no. Function
1 byte1 byte2 bytes2 bytes1 byte2 bytes2 bytes
Response:
Slave no. Function code Starting addressQuantity of registerCRC16
1 byte1 byte2 bytes2 bytes2 bytes
Error response:
Slave no. Function code 90Exception code
code
10
10
Starting
address
Quantity of register Byte countFirst register value -------CRC16
00
(fixed)
01
(fixed)
00 (fixed)01 (fixed)
02 (fixed)
CRC16
1byte1byte1byte2 bytes
Refer to "Error response", page 41
.
Example: Write value 60Hz in the parameter [Frequency reference from serial comm.](FA01) in Altivar 212
slave 1.
Request:
0110FA 0100 010217 70F3 9A
Response:
0110FA 0100 0160 D1
S1A53844 01/201137
Page 38
Write indirect block (16)
Function 16 = 16#10, quantity = 2
The Write indirect block function permits to write 2 parameters. These parameters can be chosen by
parameters [Block write data 1] (F870)and [Block write data 2] (F871) (refer to"Configuration of the
indirect blocks", page 27
Access to the parameter
This parameter is accessible in the [COMMUNICATION MENU]COM submenu of [PROGRAMMING MENU]
Programming mode.
Description
ParametersModbus
[Block write data 1] (F870)2160
[Block write data 2] (F871)2161
Request:
Slave no. Function
1 byte1 byte2 bytes2 bytes1 byte2 bytes2 bytes
code
10
).
Adjustment rangeDefault
address
0 [No select]: No selection
16#870
16#871
Starting addressQuantity of registerByte
18
(fixed)
(fixed)
1 [Command word 1]
2 [Command word 2]
3 [Frequency Setpoint]
4 [Relay command]: Ouput data on the terminal board
5 [FM command]: Analog output for communication
6 [Speed Setpoint]
count
70
00
(fixed)
02
(fixed)
04 (fixed)
Modbus services
Valid
setting
First register value -------CRC16
after
Power
0
cycle
Response:
Slave no. Function code Starting addressQuantity of registerCRC16
10
1 byte1 byte2 bytes2 bytes2 bytes
18 (fixed)70 (fixed)00 (fixed)02 (fixed)
Error response:
Function code
Slave no.
1 byte1 byte1 byte2 bytes
90
Refer to "Error response", page 41
Exception code
.
CRC16
Example: Write value 60Hz in the parameter [Frequency Command](FA01) and run forward command in
Altivar 212 slave 1.
Configuration:
[Block write data 1] (F870) = 1: [Command word 1](FA00)
[Block write data 2](F871) = 3: [Frequency reference from serial comm.](FA01)
• The Altivar 212 accepts the request:
Request:011018 7000 0204C4 0017 706D AF
Response:011018 7000 0243 B3
• The Altivar 212 rejects the request because it is busy or F870 is 0:
Request:011018 7000 0204C4 0017 706D AF
Response:0190044D C3
38S1A53844 01/2011
Page 39
Modbus services
• The Altivar 212 rejects the request because of an invalid starting address:
Request:011018 7100 0204C4 0017 70AC 63
Response:0190030C 01
• The Altivar 212 rejects the request because of an invalid quantity of registers:
Request:011018 7000 0304C4 0017 706C 7E
Response:0190030C 01
• · The Altivar 212 rejects the request because of an invalid byte count:
Request:011018 7000 0203C4 0017 70D8 6F
Response:0190030C 01
Note: Reading values of parameters F870 and F871. Value of parameter F87p can be read by reading the address
187p.
Example for parameter F870:
0870: parameter assignment
1870: parameter value
S1A53844 01/201139
Page 40
Read Device Identification (43/14)
Function 43/14 = 16#2B/0E
Request:
Slave no.
1byte1byte1byte1byte1byte2bytes
Response:
Slave no.
1byte1byte1byte1byte1byte
Function code
2B0E01 ... 0300LoHi
Function code
2B
Modbus services
MEI type Read Device Id
code
MEI type Read Device Id code Conformity level -------
0E01 ... 0301
Object Id CRC16
-------More follows
00
1 byte1 byte1 byte
-------Id of object no. 1
00
1 byte1 byte13 bytes
-------Id of object no. 2
01
1 byte1 byte13 bytes
-------Id of object no. 3
02
1byte1byte04bytes
-------CRC16
LoHi
1byte1byte
Length of object no. 1
0D
Length of object no. 2
0D
Length of object no. 3
04
Next object Id
00
Number of objects03-------
Value of object no. 1
“Télémécanique”
Value of object no. 2
“ATV212H075M3X”
Value of object no. 3
“0182”
-------
-------
-------
The total response size given in this example equals 46 bytes.
The response contains the following four objects:
• Object no. 1:Manufacturer name (always "Télémécanique", i.e., 13 bytes).
• Object no. 2:Device catalog number (ASCII string; for example: “ATV212H075M3X”, i.e., 13 bytes).
The length of this object varies according to drive type. Use the “Length of object no. 2” field to
determine the length.
• Object no. 3:Control version, in "MMmm" format where "MM" represents the major revision and "mm" the
minor revision (4-byte ASCII string; for example: "0182" for version 1.82).
Error response:
CRC16
Slave no.Function code
AB
1byte1byte1byte1byte1byte
Refer to "Error response", page 41
40S1A53844 01/2011
Exception code
.
LoHi
Page 41
Modbus services
Error response
An error response is returned by the Altivar 212 when it is unable to perform the request.
Format of an error response:
Slave
no.
Function codeException codeCRC16
LoHi
1 byte1 byte1 byte2 bytes
Function code: request code + H’80.
Exception code:
Exception Code Description
01Unknown function:
The function code received in the query is not an allowable action for the drive.
- The function is not supported by the drive error.
- Function code 43 but MEI Type not equal: to 14.
02Illegal data address:The data address received in the query is not an allowable address for the drive.
03Illegal data value:
04Unable to execute:
- Modbus address is not supported.
- Request to write a read only parameter.
A value contained in the query data field is not an allowable value for the drive.
- Data range not allowed.
- Fixed data not allowed.
- Function code 43 and MEI Type 14 but invalid Read Device ID Code (Read Dev ID code > 3).
The request commands an operation that the Altivar 212 is not able to execute due to another task or
condition.
- Request to write in a parameter that cannot be changed during running.
- Request to write during executing "tyP" (return to factory setting ...).
- Interruption occurs during writing data.
S1A53844 01/201141
Page 42
Modbus services
42S1A53844 01/2011
Page 43
Parameter list
Parameter list
What's in this Chapter?
This chapter contains the following topics:
Referring to the Altivar 212 programming manual44
List of control parameters45
List of monitoring parameters46
Commands48
Setpoints50
Status51
Trip and alarm codes53
Monitoring and control of I/O from communication55
Identification58
5
TopicPage
S1A53844 01/201143
Page 44
Referring to the Altivar 212 programming manual
General
Parameters are decribed in the Altivar 212 programming manual.
For communication purposes, the section "Table of parameter and data" references Modbus address, unit,
range... The table below is an abstract, just for example.
Additionnal parameter, not listed in the Altivar 212 programming manual, are described in the present section.
Parameter list
Submenu or parameter
description
[5 LAST PARAM CHANGE] (AUH)
History function
[Quick menu] (AUF)
Wizard function
[Auto ramp] (AUI)
Automatic acceleration/ deceleration
[Acceleration time 1] (ACC)
Slope of the acceleration ramp and
the time it takes for the output
frequency of the
drive to increase from 0 Hz to the
setting of [Max frequency](FH)
Modbus
address
0
16#0
9
16#9
SettingUnitDefault
Operation panels parameters in groups of five in
the reverse order to that in which their settings
were changed (possible to edit).
The AUF submenu provides ready access to
the ten basic parameters commonly used in
programming the drive.
In many cases, programming the ATV212 drive
is complete when these 10 parameters and
motor parameters have been properly set.
0 [Disabled]: Manual
1 [Enable]: [Acceleration time 1](ACC) and
[Deceleration time 1](dEC)
2 [ACC only]: [Acceleration time 1](ACC) only
0.0 to 3200sAccording
• "Modbus address" identifies the parameter for communication.
In Modbus protocol, it is also called "register address" or "Parameter address".
setting
--
--
-1
to drive
model
• "Adjusment range" or "Range" means the data cannot be written outside the range.
The data is expressed in the decimal notation. For writing the data through the communication function,
take the minimum setting unit into consideration, and use hexadecimal notation.
• "Minimum setting unit" is the unit of a single data.
For example, the "Minimum setting unit" of [Acceleration time 1] (ACC) is 0.1. 1 corresponds to 0.1s. For
setting the ACC to 10 seconds, transmit 16#03E8 by communication [10÷0.01=1000=16#03E8].
44S1A53844 01/2011
Page 45
Parameter list
List of control parameters
These parameters are only in the RAM and not in the EEPROM, they return to initial values when the power
is turned off, after the drive has been reseted, or when factory setting is done.
Commands from serial communication
Parameter
description
Command word 1 (FA00)
from serial communication
Command word 2 (FA20)
from serial communication
Setpoints from serial communication
Parameter
description
Frequency reference from serial comm.
(FA01)
Speed reference from network (FA13) 64019
Outputs control from serial communication
Parameter
description
Terminal output data from comm. (FA50) 64080
Analog output data from comm. (FA51)64081
Modbus
address
64000
16#FA00
64032
16#FA20
Modbus
address
64001
16#FA01
16#FA13
Modbus
address
16#FA50
16#FA51
RangeMin.
setting unit
0 to 65535 -0YesNone
0 to 65535 -0YesNone
RangeMin.
setting unit
0 to Max.
frequency
(FH)
0 to 24000
RangeMin.
0 to 25500YesNone
0 to 1023
(10-bit
resolution)
0.01 Hz0YesNone
1 min
(1 rpm)
setting unit
00YesNone
Initial
value
Initial
value
-1
0YesNone
Initial
value
Write during
operation
Write during
operation
Write during
operation
EEPROM
EEPROM
EEPROM
S1A53844 01/201145
Page 46
List of monitoring parameters
General
Monitoring parameters are read only.
Status
Parameter
description
Status word (Fd01)64769 16#FD01
Status word 2 (Fd42)64834 16#FD42
Status word 3 (Fd49)64841 16#FD49
Status word at last trip (FE01)65025 16#FE01
Status word 2 at last trip (FE42)65090 16#FE42
Status word 3 at last trip (FE49)65097 16#FE49
Command mode status (FE45)65093 16#FE45
Setpoint mode status (FE46)65094 16#FE46
Frequency and speed
ParameterModbus
Output frequency (Fd00)64768 16#FD00HzCurrent value
Output frequency at last trip (FEOO)65024 16#FE00HzValue before trip
Output speed (FE90)65168 16#FE90rpm-
Estimated speed (FE16)65046 16#FE16HzValue before trip
Frequency reference before ramp
(FE02)
Frequency reference after ramp (FE15)65045 16#FE15HzValue before trip (after PI and speed ramp)
PID feedback value (FE22)65058 16#FE22HzValue before trip
Parameter list
Modbus
address
UnitDescription
address
65026 16#FE02HzValue before trip (before PI and speed ramp)
Commands and setpoint can be enabled through communication irrespective of settings of the command
mode (CMOd) and setpoint mode (FMOd).
Refer to "Configuration of the control source", page 21.
Once the command word (FA00) is set to enable communication command priority and frequency priority,
both priorities will be enabled unless OFF is set, power is turned off or is reset, or factory setting (tYP) is
selected.
Emergency stop, RY terminal output hold and OUT terminal output hold are enabled even though
communication command priority is not set.
If the command word (FA00) is enabled and the "Preset speed operation is used (bits 0, 1 or 2 set to "1"),
the analog setpoint is disabled, the velocity is controlled by preset speeds through the communication,
irrespective of the setpoint selection.
48S1A53844 01/2011
Page 49
Parameter list
Examples:
Run forward (CMOd and FMOd configured to serial communication)
FA00 = 16# 0400
Run reverse (CMOd and FMOd configured to serial communication)
FA00 = 16# 0600
Run forward, commands and setpoint from Modbus (irrespective of CMOd and FMOd)
FA00 = 16# C400
Run reverse, commands and setpoint from Modbus (irrespective of CMOd and FMOd)
This command is enabled regardless of the command priority selection (bit 15 of common word (FA00)).
It is necessary to reset it after the command is performed.
Over-current stall level change (bit 12):
This command word is enabled only when the communication command is enabled. Set Bit 15 of the
Command word (FA00) to "1" [enabled].
This command word will be disabled is set (value 0), power is turned off or is reset, or factory setting
[Parameter reset](tYP) is selected.
S1A53844 01/201149
Page 50
Setpoints
Frequency setpoint (FA01)
Frequency setpoint from Modbus
Unit: 0.01 Hz
Range: 0 to [Maximum frequency](FH)
This setpoint is enabled by setting 4 [serial communication] to the setpoint selection parameter (FMOd) or
setting to1 [enabled] setpoint priority selection (Bit 14 of Command word (FA00)).
Once enabled, this setpoint selection is enabled till disabled ("0") is set in the setpoint priority selection (bit 14
of the command word (FA00)), power is turned off or is reset, or factory setting (tYP) is selected.
Example: Frequency setpoint 80Hz
80Hz = 80 ÷ 0.01 = 8000 = 16# 1F40
Request:0106FA 011F 40B5 A6
Response:0106FA 011F 40B5 A6
Parameter list
Speed setpoint (FA13)
Speed setpoint from Modbus
Unit: min-1 (rpm)
Range: 0 ... 24 000 min-1
With this setpoint, it is possible to control the drive with rpm instead of Hz.
This reference is converted into Frequency Setpoint using "Number of motor poles" (F856).
50S1A53844 01/2011
Page 51
Parameter list
Status
Status word (FE0I Fd01)
Status immediately before the occurrence of a trip: [Communication Number](FE01)
Current status: [Communication Number] (Fd01)
Bit Specifications01Remarks
0FL stateNot activeActive
1Drive stateNot trippedTrippedTrip statuses include rtry
2AlarmNo alarmAlarm issued
3MOFFNormalMOFFMain circuit undervoltage
4Motor section (1 or 2)
(THR 2 selection)
5PI control OFFPI control permittedPI control prohibited
Trip code (current status: FC90, historic records: FE10 to FE13)
CodeValue
(hexadecimal number)
NErr
OC1
OC2
OC3
OCL
OCA
EPHI
EPHO
OP1
OP2
OP3
OL1
OL2
OH
E
EEP1
EEP2
EEP3
Err1
Err2
Err3
Err4
Err5
Err7
Err8
Err9
UC
UP1
Ot
EF2
OC1P
OC2P
OC3P
EtYP
OH2
SOUt
E-18
E-19
E-20
E-21
Etn1
Fd1
Fd2
CFI2
00[No error]
11[Over-current during acceleration]
22[Over-current during deceleration]
33[Over-current during constant speed operation]
44[Over-current in load at startup]
55[Short circuit in arm]
88[Input phase failure]
99[Output phase failure]
A10[Overvoltage during acceleration]
B11[Overvoltage during deceleration]
C12[Overvoltage during constant speed operation]
D13[Over-LOAD in inverter]
E14[Over-LOAD in motor]
1016[Overheat trip]
1117[Emergency stop]
1218[EEPROM fault 1] (writing operation)
1319[EEPROM fault 2] (reading operation)
1420[EEPROM fault 3] (other)
--[Speed ref alarm]
1521[RAM fault]
1622[ROM fault]
1723[CPU fault]
1824[Communication error trip]
1A26[Current detector fault]
1B27[Optional circuit board type error]
1C28[Graphic keypad communication error]
1D29[Small-current trip]
1E30[Trip due to undervoltage in main circuit]
2032[Over-torque trip]
2234[Ground fault trip] (hardware detection)
2537[Overcurrent flowing in element during acceleration]
2638[Overcurrent flowing in element during deceleration]
2739[Overcurrent flowing in element during operation]
2941[Inverter type error]
2E46[External thermal input]
2F47[VIA cable break]
3250[Break in an analog signal cable]
3351[CPU fault]
3452[Excess torque boost]
3553[CPU fault]
5484[Auto-tuning error]
4872[Closed damper 1 fault]
4973[Closed damper 2 fault]
--[Download transfer fault]
Value
(decimal number)
Parameter list
Description
54S1A53844 01/2011
Page 55
Parameter list
Monitoring and control of I/O from communication
The digital inputs, digital outputs, analog input and output signals of the drives can be controlled by
communication.
Digital inputs status (Fd06, FE06)
Digital inputs status immediately before the occurrence of a trip: [Status of input terminal block] (FE06)
Current digital inputs status: [Status of input terminal block] (Fd06)
In case "0: No assignment function" is selected in function selection, drive operations will not be affected even
when terminals are turned
on and off. Therefore, the terminals can be used as input terminals for customer's own use.
The input terminal function selection parameter is used to select a function for each input terminal.
BitTerminal nameFunction (parameter title)01
0F
1R
2RES
3 to 6Reserved---
7VIA (1)
8 to 15Reserved-
[LI F selection](
[LI R selection](
[LI RES selection](
[VIA LI selection](
F111)
F112)
F113)
F118)
OFFON
OFFON
OFFON
OFFON
(1): It is valid only when it is selected as contact input by [VIA Input Function](F109).
Example: When both F and RES terminals are ON: FE06 = 16#0005
Digital outputs status (Fd07, FE07)
Digital outputs status immediately before the occurrence of a trip: [Status of output terminal block] (FE07)
Current digital outputs status current status: [Status of output terminal block] (Fd07)
The output terminal function selection parameter is used to select a function for each output terminal.
BitTerminal name (extended)Function (parameter title)01
0RY
1Reserved---
2FL
3 to 15Reserved---
BIT 15BIT 0
FE06:0 0000 0000 0000 1 0 1
000 5
Output terminal selection1 (
Output terminal selection3 (
F130)
F132)
OFFON
OFFON
Example: When both the RY and FL terminals are ON: FE07 = 16#0005
BIT 15BIT 0
FE07:0 0000 000 0 0000 10 1
000 5
S1A53844 01/201155
Page 56
Analog inputs values (FE35, FE36)
U
M
3
VW0RpP24LIp
Control
Feedback
ATV 212
Damper
Damper opening
Fan
Flow of air
Damper
open contact
[Analog input VIA value](FE35)
[Analog input VIB value](FE36)
Data: 10bit resolution (Data range 0 to 1023)
Digital outputs command (FA50)
The digital outputs (relays) of the drive can be controlled directly by communication.
Before controlling them, select Function Number 38 or 39 in Output terminal function selection ([FL Relay
Function](F132)) and select Function Number 40 or 41 in Output terminal function selection ([RY Relay
Function 1](F130) ,[RY Relay Function 2](F137)).
BitOutput Terminal Function01
0Relay FL (F132)OFFON
1Relay RY (F130 and F137)OFFON
2 to 15Reserved--
Example: Controlling only relay RY by communication
Set 40[Ser. data relay RY] in F130 in advance.
Set "0002H" in FA50 to turn relay RY on.
Parameter list
Analog outputs command (FA51)
The analog output FM on the drive can be controlled directly by communication.
Select 18[Com data] in [AO funct. selection](FMSL) parameter before controlling them.
The data adjustment range is 0 to 1023 (10bit resolution). Refer to "Meter Setting and adjustment" in the
ATV 212 programming manual for complete information.
Communication feedback (FA49)
Damper function. This function applies to the ventilation ducts. The aim is to control the opening of the duct
(shutter device called a "damper") when the fan starts up.
Damper opening command
The opening command can be assigned to a relay via the F130 or F132 parameters to the function
[Damper] 68 or [Inv. damper] 69. The damper is closed automatically when there is no longer an opening
command.
Damper opening feedback
Opening is controlled by a bit or a logic input that can be assigned via the F111 or F112 or F113
parameters to the function 73. The corresponding logic input or bit can be configured via the parameter
[Damper fdb type]F580.
When there is an inconsistency, the drive goes on a [Damper fault 1]Fd1 if the damper does not open and
on a [Damper fault 2]Fd2 if it does not close.
The parameter [Time open damper]F581 can be used to delay tripping on an opening fault when a run
command is sent and the parameter [Time close damper]F582 delays the closing fault when a stop
command is sent.
56S1A53844 01/2011
Page 57
Parameter list
Fan speed
Run command
Opening command
Rx
Open
Position of damper
Closed
Damper open contact
FA49 = 1
FA49 = 0
F580 = 3 (1)
1
0
t
1
0
t
1
0
t
1
0
F581
F582
t
1
0
t
1
(1) [Com channel choice] F807 must be set to 0[RJ45] to manage the damper feedback on RJ45 port or set to
1 [Open style] to manage the damper feedback on Open Style port.
FA49 can only be active when
[Com. LIL set]: Serial link to communication bit selected by
[Com. LIH set]: Serial link to communication bit selected by
0
t
[Damper fdb type]F580 is set to 3[Com. LIL set] or 4 [Com. LIH set].
F807 and active at level 0 (shunt).
F807 and active at level 1 (open).
S1A53844 01/201157
Page 58
Identification
drive model code (F805)
ModelVoltage Power RatingCode (FB05)Class (FB72:bit8)
ATV212H075M3X3ph 200V 0.75kW40
ATV212HU15M3X3ph 200V 1.5kW60
ATV212HU22M3X3ph 200V 2.2kW70
ATV212HU30M3X3ph 200V 3kW80
ATV212HU40M3X3ph 200V 3.7kW / 4kW90
ATV212HU55M3X3ph 200V 5.5kW100
ATV212HU75M3X3ph 200V 7.5kW110
ATV212HD11M3X3ph 200V 11kW1080
ATV212HD15M3X3ph 200V 15kW1090
ATV212HD18M3X3ph 200V 18.5kW1100
ATV212HD22M3X3ph 200V 22kW1110
ATV212HD30M3X3ph 200V 30kW1120
ATV212H075N43ph 400/460V 0.75kW360
ATV212HU15N43ph 400/460V 1.5kW380
ATV212HU22N43ph 400/460V 2.2kW390
ATV212HU30N43ph 400/460V 3.0kW400
ATV212HU40N43ph 400/460V 3.7/4 kW410
ATV212HU55N43ph 400/460V 5.5kW420
ATV212HU75N43ph 400/460V 7.5kW430
ATV212HD11N43ph 400/460V 11kW440
ATV212HD15N43ph 400/460V 15kW450
ATV212HD18N43ph 400/460V 18.5kW460
ATV212HD22N4S3ph 400/460V 22kW320
ATV212HD22N43ph 400/460V 22kW470
ATV212HD30N43ph 400/460V 30kW480
ATV212HD37N43ph 400/460V 37kW490
ATV212HD45N43ph 400/460V 45kW500
ATV212HD55N43ph 400/460V 55kW510
ATV212HD75N43ph 400/460V 75kW520
ATV212W075N43ph 400/460V 0.75kW IP5401360
ATV212WU15N43ph 400/460V 1.5kW IP5401380
ATV212WU22N43ph 400/460V 2.2kW IP5401390
ATV212WU30N43ph 400/460V 3.0kW IP5401400
ATV212WU40N43ph 400/460V 3.7/4 kW IP5401410
ATV212WU55N43ph 400/460V 5.5kW IP5401420
ATV212WU75N43ph 400/460V 7.5kW IP5401430
ATV212WD11N43ph 400/460V 11kW IP5401440
ATV212WD15N43ph 400/460V 15kW IP5401450
ATV212WD18N43ph 400/460V 18.5kW IP5401460
ATV212WD22N4S3ph 400/460V 22kW IP54320
ATV212WD22N43ph 400/460V 22kW IP5401470
ATV212WD30N43ph 400/460V 30kW IP5401480
Parameter list
58S1A53844 01/2011
Page 59
Parameter list
ModelVoltage Power RatingCode (FB05)Class (FB72:bit8)
The RS485 standard (ANSI/TIA/EIA-485-A-1998) allows variants of certain characteristics:
• Polarization
• Line termination
• Distribution of a reference potential
• Number of slaves
• Length of bus
It does not specify the connector type or pinout.
The Modbus specification published on www.modbus.org in 2002 contains precise details of these
characteristics. They are also summarized in the next sections (Modbus 2-wire and 4-wire standard
schematics). The latest generation Schneider Electric devices conform to this specification.
Modbus 2-wire standard schematic
The standard schematic corresponds to the Modbus specification published in 2002 on www.modbus.org
(Modbus_over_serial_line_V1.pdf, Nov 2002) and, in particular, to the 2-wire multipoint serial bus schematic.
Schematic diagram
Appendix
62S1A53844 01/2011
Page 63
Migration
Migration
What's in this Chapter?
This chapter contains the following topics:
Migration ATV21 - ATV21264
7
TopicPage
S1A53844 01/201163
Page 64
Migration ATV21 - ATV212
General
The ATV212 is compatible with the ATV21
Migration Modbus ATV21 to ATV212: When controlling ATV21 using Modbus RJ45, parameter [Network
protocol] (F829) should be set to 1.
With ATV212, parameter F829 should also be set to 1 and parameter[Com channel choice](F807) set
to[RJ45](0). Factory setting is [Network] (1).
Settings of other communication parameters described in the programming manual remain the same as on
ATV21.
A configuration transfer from ATV21 to ATV212 is possible.
For example:
You can upload a configuration from an ATV21 via PC Soft (and selected the drive Type : ATV21) and download
it into ATV212.
After a transfer from ATV21 to ATV212, the new parameters stay at their factory setting:
[Damper fdb type] (F580), [Time open Damper] (F581), [Time close Damper] (F582) ,[Damper flt
behavior] (F583),[Forced fire control] (F650), [Forced fire function] (F659), [Com channel
choice] (F807), [Mdb network baud] (F820), [Mdb network parity] (F821) and
[LL for ov.cur. prev.] (F390).
The download configuration is not allowed if the drive is running.
In case of an interruption of download configuration transfer to the drive and detected fault, the
This detected fault code keeps also present even after power off of the drive.
To reset the download transfer detected fault code CFI2:
z Make a new successful transfer
z Make a factory setting on the drive (using tYP parameter)
Migration
CFI2 is set.
Commissioning
At the end of download transfer, the drive cannot run if a logic input configured to a function is active. To use the
function and run the motor, it's necessary to disable and enable the logic input.
Compatible loader tool with ATV21
z PC Soft V1.0 and higher
Compatible loader tools with ATV212:
z PC Soft V1.06 and higher,
z Multi-Loader V3.11 and higher,
z SoMoveMobile V2.2 and higher,
64S1A53844 01/2011
Page 65
ATV212_Modbus manual_EN_S1A53844_01
S1A53844 01/2011
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.