GV3000/SE 230 VAC 30-100 HP
General Purpose (Volts/Hertz)
and Vector Duty Drive
Software Start-Up and Reference Manual
Version 6.04
Instruction Manual D2-3416-1
The information in this manual is subject to change without notice.
Throughout this manual, the following notes are used to alert you to safety considerations:
ATTENTION: Identifies information about practices or circumstances that can lead to personal
injury or death, property damage, or economic loss.
!
Important: Identifies information that is critical for successful application and understanding of the product.
ATTENTION: Only qualified electrical personnel familiar with the construction and operation of
this equipment and the hazards involved should install, adjust, operate, or service this equipment.
!
Read and understand this manual and other applicable manuals in their entirety before
proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
ATTENTION: DC bus capacitors retain hazardous voltages after input power has been
disconnected. After disconnecting input power, wait five (5) minutes for the DC bus capacitors
to discharge and then check the voltage with a voltmeter to ensure the DC bus capacitors are
discharged before touching any internal components. Failure to observe this precaution could
result in severe bodily injury or loss of life.
ATTENTION: The drive can operate at and maintain zero speed. The user is responsible for
assuring safe conditions for operating personnel by providing suitable guards, audible or visual
alarms, or other devices to indicate that the drive is operating or may operate at or near zero
speed. Failure to observe this precaution could result in severe bodily injury or loss of life.
ATTENTION: Do not install modification kits with power applied to the drive. Disconnect and
lock out incoming power before attempting such installation or removal. Failure to observe this
precaution could result in severe bodily injury or loss of life.
ATTENTION: The user must provide an external, hardwired emergency stop circuit outside of
the drive circuitry. This circuit must disable the system in case of improper operation.
Uncontrolled machine operation may result if this procedure is not followed. Failure to observe
this precaution could result in bodily injury.
ATTENTION: The user is responsible for conforming with all applicable local, national, and
international codes. Failure to observe this precaution could result in damage to, or destruction
of, the equipment.
DeviceNet is a trademark of the Open DeviceNet Vendor Association.
ControlNet is a trademark of ControlNet International, Ltd.
PROFIBUS is a trademark of PROFIBUS International.
GV3000/SE, AutoMax, ControlNet, and Reliance are trademarks of Rockwell International.
Table 4.2 –Function Selection for Digital Inputs 6, 7, and 8 .........................4-14
Table 4.3 –Acceptable P.007 and P.008 Selection Combinations ...............4-18
Table 4.4 –Preset Speed Digital Inputs ........................................................4-33
Table 4.5 –Faults That Can Be Auto Reset ..................................................4-37
Table 4.6 –AUTO/MAN Key Status Based on P.000 and P.052 ..................4-41
Table 4.7 –STOP/RESET Key Status Based on P.000 and P.055 ..............4-46
Table 5.1 –List of Alarm Codes.....................................................................5-2
Table 5.2 –List of Fault Codes ......................................................................5-3
Table 5.3 –Fatal Fault Codes That Can Be Reset........................................5-9
Table F.1 –Analog Input Conversion Scaling for Speed or Trim Reference.F-2
Table F.2 –Analog Input Conversion Scaling for Torque Reference ............F-4
Table of Contents
V
PREFACE
This manual is a start-up and programming reference guide for the version 6.04
GV3000/SE (Sensorless Enhanced) drive. The drive can be set up for either volts
per hertz (V/Hz) or vector regulation. This manual provides a start-up procedure for
both.
The start-up procedures are followed by reference information. This information
includes a complete list of all parameters and a description of the keypad/display.
•You will need to know to use the keypad to perform the start-up procedures
described in chapters 1 and 2. If you do not, refer to chapter 3 first.
•For drives that will be set up for V/Hz regulation, go to chapter 1 for the start-up
procedure.
•For drives that will be set up for vector regulation, go to chapter 2 for the start-up
procedure.
•For a description of all the parameters, go to chapter 4.
•For troubleshooting guidelines, go to chapter 5.
•For a description of the drive hardware, refer to the GV3000/SE 230 VAC Drive
Hardware Reference, Installation, and Troubleshooting instruction manual
(D2-3417-1).
New Features in Version 6.04
The GV3000/SE version 6.04 software includes support for the following features:
•Optional outer control loop without requiring an option board (vector control
only). See U.040 through U.048.
•Enhanced analog input configuration. See P.011 (Analog Input Configure).
•Enhanced output relay configuration. See P.013 (Output Relay Configuration).
Getting Assistance from Reliance Electric
If you have any questions or problems with the products described in this instruction
manual, contact your local Reliance sales office. For technical assistance, call
1-800-726-8112.
Preface
VII
CHAPTER 1
Starting Up the Drive
for Volts/Hertz Regulation
This chapter describes the basic start-up procedure for drives which utilize open-loop
V/Hz regulation. V/Hz regulation is the default method of regulation. You do not
need to select it.
If you are starting up a drive which will perform vector regulation, refer to the vector
start-up procedure in chapter 2.0 instead. Do not perform the start-up procedure in
this chapter.
The start-up procedure below provides step-by-step instructions for:
•powering up
•checking monitor mode displays
•accessing program mode
•configuring General parameters (designated with a "P")
•configuring specific V/Hz parameters (designated with an "H")
•checking motor rotation direction
•running the drive
This start-up procedure describes how to program the minimum set of parameters
that usually need to be programmed for applications using V/Hz regulation. Once
you program these parameters, their values are retained even if power is lost. You
only need to re-program them if you want to change how the drive operates.
Your application may require programming other parameters in addition to the ones
described in this start-up procedure. Refer to chapter 4 for a description of all the
parameters to verify whether you need to program any additional parameters as
well. Appendix A provides a list of parameters listed alphabetically.
Throughout this manual, you will see references to parameter names and the
numbers that identify them for the drive. This manual uses the same format that will
be shown on the keypad/display to refer to parameters:
P.nnn
U.nnn
H.nnn
r.nnn
where: nnn is a number
P designates General parameters
U designates Vector parameters
H designates Volts/Hertz parameters
r designates optional RMI parameters
Starting Up the Drive for Volts/Hertz Regulation
1-1
1.1Preparing for Start Up (Volts/Hertz)
Read through the following sections to prepare for the start-up procedure.
What You Need To Know:
•You must be qualified to perform the procedure and be familiar with V/Hz
regulation.
•You should be familiar with the keypad/display. If you are not familiar with the
keypad/display, refer to chapter 3, which describes it.
What You Need To Do:
•Complete all hardware installation as described in the hardware reference
manual. This includes connecting input power, input transformers (if required),
disconnects, fuses, and the terminal strip on the drive.
•Record the following motor data from each motor nameplate for use during the
procedure. Space is provided for recording information from three motors:
Motor rated amps:
Motor rated volts:
Motor base frequency:
Motor rated amps:
Motor rated volts:
Motor base frequency:
Motor rated amps:
Motor rated volts:
Motor base frequency:
•Connect the drive to the motor.
•Check that you have not been prevented from programming the drive. If the
PASSWORD LED on the keypad is on, programming has been prevented in
parameter P.051, Programming Disable. Refer to section 4.4 in this manual for
the procedure to enable programming.
If You Have a Problem:
To Exit:
During most of the start-up procedure, you will be in program mode, which is used
to program parameters. If you want to stop programming parameters, you can exit
program mode. You can do this by pressing the PROGRAM key until the
PROGRAM LED turns off. This will place the keypad/display in monitor mode, the
default. You can read more about these modes in chapter 3.
1-2
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
To Restore a Default Parameter Value after Writing over It:
If you enter the wrong value while programming parameters, you can restore the
default if you have not yet pressed the ENTER key. To do so:
1.Press the PROGRAM key.
2.Press the ENTER key. The default value of the parameter will be displayed
again. You can select it with ENTER or enter a new one and press ENTER.
To Restore All the Default Values to General (P) Parameters:
If you need to restore all the default values for General (P) parameters after
programming them, you can do so using the Restore Defaults parameter (P.050).
1.2Start-Up Procedure (Volts/Hertz)
This section describes the start-up procedure for drives set up for V/Hz regulation.
Before using this procedure, you should have read section 1.1 for information you
need to know before working with the drive.
Step 1. Power Up the Drive
This step verifies that the drive powers up and passes the power-up diagnostics.
After the drive passes the diagnostics, the keypad/display automatically enters
monitor mode, with speed displayed.
Turn power on.
STOP
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RESET
AUTO
MAN
PROGRAM
ENTER
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Forward
Reverse
RUN
JOG
The initial display shows SELF, with all
monitor mode and status LEDs on, indicating
the drive is performing power-up
diagnostics.
After diagnostics are complete (5-6
seconds), the SPEED LED is on and the
keypad/display is in monitor mode. The
displayed value is zero. You can move
through the five items accessible in monitor
mode - Speed, Volts, Amps, Hz, and Kw - by
pressing the ENTER key.
Starting Up the Drive for Volts/Hertz Regulation
1-3
Step 2. Select Program Mode
In this step, you will select program mode, which will give you access to the First
Menu General (P) parameters.
Press the PROGRAM key.
The PROGRAM LED is on and the First
Menu General (P) parameters can be
accessed.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 3. Program First Menu General Parameters P.000 - P.005
This step describes how to change First Menu General (P) parameters P.000
through P.005. P.000 selects where the drive is controlled from. This procedure
assumes local control from the keypad (P.000 = LOCL), which is the default setting
for the parameter.
Step 3.1 Press the ENTER key to display the first parameter, P.000, Control Source.
The default setting for P.000 is LOCL, or
local control.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 3.2 Press the £ key to display P.001, Accel Time 1 (RAMP 1).
This parameter sets the acceleration time in
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
seconds.
1-4
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 3.3 Press the ENTER key to display the default setting of P.001.
This displays the default setting for
acceleration time (20.0 seconds).
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 3.4 Press the £ key to increase acceleration time, or the ¥ key to decrease
acceleration time.
The adjustment range is:
1.0 to 999.9 seconds.
VALUE ENTERED:
Step 3.5 Press the ENTER key to save the changed value.
After pressing ENTER, the same parameter
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
number is displayed. You can now go to the
next parameter.
Step 3.6 Press the £ key to display P.002, Decel Time 1 (RAMP 1).
This parameter sets the deceleration time in
seconds. The default stop method is
coast-to-stop, set in P.025.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Starting Up the Drive for Volts/Hertz Regulation
1-5
Step 3.7 Press the ENTER key to display the default setting of P.002.
This displays the default setting for
deceleration time (20.0 seconds).
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 3.8 Press the £ key to increase deceleration time, or the ¥ key to decrease
deceleration time.
The adjustment range is:
1.0 to 999.9 seconds.
VALUE ENTERED:
Step 3.9 Press the ENTER key to save the changed value.
After pressing ENTER, the same parameter
number is displayed. You can now go to the
next parameter.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 3.10 Press the “ key to display P.003, Minimum Speed.
This parameter sets the minimum speed in
Hz.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
1-6
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 3.11 Press the ENTER key to display the default setting of P.003.
This shows that the default setting for
Minimum Speed is 5.0 Hz.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 3.12 Press the £ key to increase minimum speed or the ¥ key to decrease
minimum speed.
The adjustment range is:
0.5 Hz to the value set for P.004 (Maximum
Speed).
VALUE ENTERED:
Step 3.13 Press the ENTER key to save the changed value.
After pressing ENTER, the same parameter
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
number is displayed. You can now go to the
next parameter.
Step 3.14 Press the £ key to display P.004, Maximum Speed.
This parameter sets the maximum speed in
Hz.
In addition, the drive has overfrequency
protection by means of H.022. Refer to the
description of this parameter and be sure to
set it appropriate to your application.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Starting Up the Drive for Volts/Hertz Regulation
1-7
Step 3.15 Press the ENTER key to display the default setting of P.004.
ATTENTION: The user is responsible for ensuring that driven machinery,
all drive-train mechanisms, and application material are capable of
!
safe operation at the maximum operating speed of the drive. In V/Hz
regulation, overfrequency protection in the drive is provided by means
of H.022. Failure to observe this precaution could result in bodily
injury.
This shows that the default setting for
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Maximum Speed is 60.0 Hz.
Step 3.16 Press the £ key to increase maximum speed or the ¥ key to decrease
maximum speed.
The adjustment range is:
15.0 Hz to the value set for H.022
(Overfrequency Limit).
The maximum value is 210 Hz.
VALUE ENTERED:
Step 3.17 Press the ENTER key to save the changed value.
After pressing ENTER, the same parameter
number is displayed. You can now go to the
next parameter.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
1-8
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 3.18 Press the £ key to display P.005, Current Limit.
This parameter sets Current Limit, which
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
corresponds to the value in parameter
P.095, Power Module Output Amps.
Step 3.19 Press the ENTER key to display the default setting of P.005.
This shows that the default setting for
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Current Limit is 100.
Step 3.20 Press the ¥ key to decrease current limit. Decrease current limit only
if the motor nominal current rating is less than the drive nominal current
rating.
Use the following equation to calculate
current limit:
x 100
Motor Rated Amps
Rated Drive Output Amps
(1)
From motor nameplate
(2)
See the hardware reference manual for
(1)
(2)
ratings.
Adjustment Range: 50 to 110
VALUE ENTERED:
Starting Up the Drive for Volts/Hertz Regulation
1-9
Step 3.21 Press the ENTER key to save the entered value.
After pressing ENTER, the same parameter
number is displayed. You can now move to
the next parameter.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 4. Enter the Second Menu Password
This step is required in order to access the Second Menu General (P) parameters
and the Volts/Hertz (H) parameters.
Step 4.1 Press the £ key to display parameter P.006, Second Menu Password.
This parameter allows you to enter the
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
factory preset password that allows access
to the Second Menu.
The Second Menu provides access to all
parameters and the error log.
1-10
Step 4.2 Press the ENTER key.
AUTO
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Zero is displayed.
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 4.3 Press the £ key until the password number "107" is displayed.
Note that the password, and access to the
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Second Menu, will be retained if the drive
loses and regains power.
Step 4.4 Press the ENTER key to save the password number.
After pressing ENTER, P.006 is displayed.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
You now have access to all parameters and
the error log.
After the password is entered, the parameter
value is reset to 0.
Step 5. Program the Second Menu Volts/Hertz (H) Parameters
This step describes how to program the parameters that apply to V/Hz regulation
only.
Step 5.1 Press the PROGRAM key to return to the First Menu.
The display returns to the General (P)
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
parameters in the First Menu.
Starting Up the Drive for Volts/Hertz Regulation
1-11
Step 5.2 Press the £ key twice.
The error log (Err) is bypassed, then ......
AUTO
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
.... the Volts/Hertz (H)
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
parameter main menu is
displayed.
Step 5.3 Press the ENTER key to access the first Volts/Hertz parameter: H.000,
Motor Nameplate Volts.
AUTO
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 5.4 Press the ENTER key.
AUTO
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Default value varies.
This parameter sets the Motor Nameplate
Volts and is taken directly from the motor
nameplate.
The default setting for H.000 is displayed.
The default setting is 230.
1-12
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 5.5 If no change was made, press the ENTER key to return to the parameter. If
you changed the value, press ENTER to accept the change and return to
the parameter.
After pressing ENTER, the same parameter
is displayed. You can now move to the next
parameter.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 5.6 Press the £ key to display H.001, Motor Nameplate Base Frequency.
Note that if Motor Nameplate Base Frequency is not set correctly, the
monitor mode SPEED display will also not be scaled correctly.
This parameter adjusts the volts/hertz ratio.
Base frequency is the set frequency at which
the output voltage reaches the Motor
Nameplate Voltage.
See figure 4.10 for more information.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 5.7 Press the ENTER key.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
Step 5.8 Press the ¥ key to decrease base frequency, if necessary.
Starting Up the Drive for Volts/Hertz Regulation
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
The default setting of 60.0 Hz is displayed.
This value will typically not need to be
changed from 60 Hz.
1-13
Step 5.9 Press the ENTER key.
After pressing ENTER, the same parameter
is displayed. You can now move to the next
parameter.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 5.10 Press the £ key to display H.002, Motor Nameplate Amps.
ATTENTION: This parameter setting must not exceed the rated amps
found on the nameplate. Overcurrent or excess heating of the motor
!
could result if this is not the case. Failure to observe this precaution
could result in damage to, or destruction of, the equipment.
This parameter specifies the Motor
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Nameplate Amps and is taken directly from
the motor nameplate.
1-14
Step 5.11 Press the ENTER key.
AUTO
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
The default setting depends on the drive
rating. The display shown here is only an
example.
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 5.12 Press the £ key to increase the motor nameplate amps, or the ¥ key
to decrease motor nameplate amps.
The adjustment range depends on the drive
rating. See Appendix C.
VALUE ENTERED:
Step 5.13 Press the ENTER key to save the changed value.
After pressing ENTER, the same parameter
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
is displayed. You can now move to the next
parameter.
Step 5.14 Press the £ key to display H.003, Torque Boost Voltage.
AUTO
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 5.15 Press the ENTER key.
AUTO
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
This parameter is required to offset the
voltage drop of the motor at low speeds and
produce constant torque. For example, high
friction loads may require high starting
torque.
Refer to figure 4.11 for more information.
The default setting is 0.5.
Starting Up the Drive for Volts/Hertz Regulation
1-15
Step 5.16 Press the £ key to increase the torque boost voltage, or the ¥ key to
decrease torque boost voltage.
Important: If you set H.003 = 0, you must perform the identification test, controlled by
H.020, prior to running. Refer to the H.020 parameter description for
more information.
The adjustment range is:
0.0% to 20.0%
VALUE ENTERED:
Step 5.17 Press the ENTER key to save the changed value.
After pressing ENTER, the same parameter
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
is displayed. You can now move to the next
parameter.
Step 5.18 Press the £ key until H.017, Input Power/Snubber Configuration, is
displayed.
This parameter selects the input power
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
supply type/snubber resistor kit
configuration. See chapter 4 for more
information.
1-16
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 5.19 Press the ENTER key.
The default setting is 0.
AUTO
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 5.20 Press the £ key to increase the selection value, or leave it at 0.
If you do not have AC input or you are using a snubber resistor, see the
H.017 parameter description for more information.
The adjustment range is:
AUTO
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
0 = AC input; snubber resistor not used;
ride-through enabled.
1 = AC input; snubber resistor used;
ride-through enabled.
2 = DC input; snubber resistor not used;
ride-through disabled.
3 = DC input; snubber resistor used;
ride-through disabled.
4 = DC input, snubber resistor not used;
ride-through enabled.
5 = DC input; snubber resistor used;
ride-through enabled.
Step 5.21 Press the ENTER key to save the changed value.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
Starting Up the Drive for Volts/Hertz Regulation
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
VALUE ENTERED:
After pressing ENTER, the same parameter
is displayed. You can now move to the next
parameter.
1-17
Step 5.22 Press the £ key until H.018, Volts/Hertz Curve Type, is displayed.
This parameter selects the type of curve for
volt/hertz regulation. See chapter 4 and step
5.24 for more information.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 5.23 Press the ENTER key.
The default setting is 0 for linear curve.
AUTO
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 5.24 Press the £ key to increase the selection value to 1 or 2, or leave it at 0.
The adjustment range is:
0 =Linear curve
1 =Optimized curve for Reliance Electric
RPM AC motors
2 = For centrifugal pump and fan motor
applications
VALUE ENTERED:
Step 5.25 Press the ENTER key to save the changed value.
After pressing ENTER, the same parameter
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
is displayed. You can now move to the next
parameter.
1-18
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 6. Return to Monitor Mode
This step describes how to exit program mode and return to monitor mode.
Step 6.1 The display should now show the last parameter adjusted in Step 5,
H.018.
AUTO
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 6.2 Press the PROGRAM key twice to exit program mode.
The display returns to monitor mode with
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
speed displayed. The SPEED LED is on
and the PROGRAM LED is off.
Starting Up the Drive for Volts/Hertz Regulation
1-19
ATTENTION: The subsequent steps require rotating parts and/or
electrical circuits to be exposed. Stay clear if unit must be running, or
!
disconnect and lock out or tag power source if contact must be made.
Failure to observe this precaution could result in severe bodily injury or
loss of life.
Important: The stop input on the terminal strip is not active when the Control
Source parameter (P.000) is set to LOCL, as it is during this start-up
procedure. Use the STOP/RESET key if you need to stop the drive.
Step 7. Check Motor Rotation Direction
This step involves verifying the speed reference is set to minimum speed, starting
the drive, and checking that the motor rotates in the correct direction. It is
performed with the motor disconnected from the load.
Step 7.1 Press the PROGRAM key until the PROGRAM LED turns off.
The keypad/display will enter monitor mode.
AUTO
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 7.2 Verify that the AUTO LED is off (press the AUTO/MAN key until the
AUTO LED turns off).
This selects the local keypad as the speed
reference source.
Step 7.3 Press the £ key or the ¥ key once.
The monitor mode LEDs will all turn off and
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
the manual speed reference value will be
displayed. The speed reference value is in
the units defined in P.028. The display
shown here is only an example.
Step 7.4 If the speed reference is at minimum speed, then proceed to Step 7.6.
If the speed reference is not at minimum speed, proceed to Step 7.5.
1-20
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 7.5 Press the ¥ key to decrease the speed reference value.
Step 7.6 Press the ENTER key to return to monitor mode.
AUTO
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Step 7.7 Verify that you have selected RUN and FORWARD. Press the START key.
The drive is now running. The keypad/
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
display is in monitor mode and the SPEED,
RUNNING, and FORWARD LEDs are on.
The drive should be running at minimum
speed. The sample display shows 150
RPM.
Step 7.8 Visually check that the motor rotates counter-clockwise (CCW) when
viewed from the driven motor shaft end.
CCW
Starting Up the Drive for Volts/Hertz Regulation
1-21
Step 7.9
•If the rotation direction is NOT correct, press the STOP/RESET key and
continue with Step 7.10.
•If the rotation direction is correct, continue with Step 7.14.
When the STOP/RESET key is pressed, the
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
RUNNING LED turns out.
Step 7.10 Turn off and lock out or tag power to the drive.
Step 7.11 Verify that the DC bus capacitors are discharged. Refer to the
hardware reference manual for this procedure.
Step 7.12 Switch any two of the motor leads (U, V, or W).
Step 7.13 Turn power on, and press the START key. Repeat Step 7.8.
Step 7.14 To make sure that the drive is not inadvertently started, turn off and
lock out or tag power to the drive. Verify that the motor direction is
appropriate for the required machine direction, and then connect the
motor to the load.
Step 8. Run the Drive
This step describes how to adjust the speed reference from the keypad and run the
motor up to maximum speed in Hz. At maximum Hz, you must check values in
monitor mode. This step assumes you have connected motor to the load.
Step 8.1 Press the ENTER key until the Hz LED turns on. (If the drive is not
running, press the START key.)
This example shows the minimum hertz
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
setting of parameter P.003.
1-22
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 8.2 Press the £ or ¥ key once. All of the monitor mode LEDs turn off.
Increase the speed reference to the maximum value by using the £ key.
Wait five seconds or press the ENTER key to return to monitor mode.
This increases the drive speed reference
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
and the motor will rotate up to maximum
speed.
The monitor mode LEDs turn off when the
reference is changed.
The display now shows the drive speed.
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Your speed display may be different.
Step 8.3 Press the ENTER key to move to the VOLTS display.
This example shows the output volts at
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
START
AUTO
MAN
PROGRAM
ENTER
Forward
Reverse
RUN
JOG
Maximum Speed (P.004). Your actual
reading may be different.
VALUE READ:
Starting Up the Drive for Volts/Hertz Regulation
1-23
Loading...
+ 180 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.