GuardLogix 5580 and
Compact GuardLogix 5380
Controller Systems
Bulletin 1756 and 5069
Safety Reference Manual
Original Instructions
GuardLogix 5580 and Compact GuardLogix 5380 Controller Systems Safety Reference Manual
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may
lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or
economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may
be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach
dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc
Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements
for safe work practices and for Personal Protective Equipment (PPE).
2Rockwell Automation Publication 1756-RM012D-EN-P - August 2020
6Rockwell Automation Publication 1756-RM012D-EN-P - August 2020
Preface
Top icPag e
Summary of Changes7
Catalog Numbers7
Terminology8
This manual describes the GuardLogix® 5580 and Compact GuardLogix 5380
controller systems, which are type-approved and certified for use in safety
applications as detailed in SIL Certification
Use this manual for the development, operation, and maintenance of a
GuardLogix 5580 or Compact GuardLogix 5380 controller-based safety system
that uses the Studio 5000 Logix Designer® application. Read and understand the
safety concepts and the requirements that are presented in this manual and
familiarize yourself with applicable standards (for example IEC 61508,
IEC 62061, IEC 61511, and ISO 13849-1) before operating a
GuardLogix 5580 or Compact GuardLogix 5380 controller-based safety system.
Rockwell Automation Publication 1756-RM012D-EN-P - August 20207
Preface
Terminology
In this publication, the terms ‘GuardLogix controller’ or ‘GuardLogix system’
apply to both GuardLogix 5580 and Compact GuardLogix 5380 controllers
unless otherwise noted.
Also, the term ‘SIL 2’ represents SIL 2, SIL CL2, and PLd, and ‘SIL 3’ represents
SIL 3, SIL CL3, and PLe.
For common abbreviations and other definitions, see the Glossary on page 107
.
8Rockwell Automation Publication 1756-RM012D-EN-P - August 2020
Safety Integrity Level (SIL) Concept
Top icPa ge
SIL Certification9
Proof Tests10
GuardLogix Architecture11
Controller Specifications13
System Reaction Time13
Contact Information If Device Failure Occurs14
Chapter 1
SIL Certification
This section provides the SIL certifications and Performance Level for the
controllers.
Table 1 - Safety Ratings for Safety Controllers
Controller SystemIEC 61508IEC 62061 ISO 13849-1
Type-approved and
certified for use in
safety applications up
to and including:
GuardLogix® 5580
controller systems
Compact GuardLogix 5380
controller systems
(1) SIL 2 Compact GuardLogix 5380 controller catalog numbers end with a 2 (example: 5069-L3 xxxxxS2).
SIL 3 Compact GuardLogix 5380 controller catalog numbers end with a 3 (example: 5 069-L3xxxxxS3).
(2) Primary controller that is used without a safety partner.
(3) Primary controller that is used with a safety partner.
(1)
SIL 2
SIL 3
SIL 2
SIL 3
(2)
(3)
Suitable for use in
safety applications up
to and including:
(2)
SIL CL2
(3)
SIL CL3
SIL CL2
SIL CL3
Suitable for use in safety
applications up to and including:
TÜV Rheinland has approved GuardLogix 5580 and Compact GuardLogix
5380 controller systems for use in safety-related applications where the
de-energized state is considered to be the safe state.
All I/O examples in this manual are based on achieving de-energization as the
safe state for typical machine safety and emergency shutdown (ESD) systems.
Rockwell Automation Publication 1756-RM012D-EN-P - August 20209
Chapter 1Safety Integrity Level (SIL) Concept
IMPORTANTAs the system user, you are responsible for these items:
•The setup, SIL rating, and validation of any sensors or actuators that are
connected to the GuardLogix system
•Project management and functional test
•Access control to the safety system, including password handling
•Programming the application and the device configurations in
accordance with the information in this safety reference manual and
these publications:
- ControlLogix® 5580 and GuardLogix 5580 Controllers User Manual,
publication 1756-UM543
- CompactLogix™ 5380 and Compact GuardLogix 5380 User Manual,
publication 5069-UM001
When applying Functional Safety, restrict access to qualified, authorized
personnel who are trained and experienced.
Use the Studio 5000 Logix Designer® application to create programs for
GuardLogix 5580 and Compact GuardLogix 5380 controllers. Only the safety
task, not standard tasks, can be used for safety functions.
Proof Tests
IEC 61508 requires you to perform various proof tests of the equipment that is
used in the system. Proof tests are performed at user-defined times. For
example, proof tests can be once a year, once every 15 years, or whatever time
frame is appropriate.
GuardLogix 5580 and Compact GuardLogix 5380 controllers have a useful life
of 20 years, no proof test required. Other components of the system, such as
safety I/O devices, sensors, and actuators can have different useful life times.
IMPORTANTYour specific applications determine the time frame for the useful life.
10Rockwell Automation Publication 1756-RM012D-EN-P - August 2020
Safety Integrity Level (SIL) ConceptChapter 1
Safety
Controller
Sensor
Actuator
HMI Display
Stratix® 5400 Switch
Programming Software
To Plant-wide Ethernet Network
Actuator
Sensor
Safety I/O Module on
Ethernet Network
Safety System
GuardLogix 5580 Controller With
Safety Partner
or
Compact GuardLogix 5380 SIL 3
Control ler
EtherNet/IP™ Adapter
I/O Modules
Safety I/O Modul es
Safety I/O Module on
Ethernet Network
= Safety Network
GuardLogix Architecture
This section provides examples of SIL 3 and SIL 2 systems, including:
• The overall safety function
• The GuardLogix portion of the overall safety function
• How other devices (for example, HMI) are connected, while operating
Figure 1 - Example SIL 3 System
-
outside the function
Rockwell Automation Publication 1756-RM012D-EN-P - August 202011
Chapter 1Safety Integrity Level (SIL) Concept
Actuator
Sensor
EtherNet/IP Adap ter
I/O Modules
Safety I/O Modules
Compact GuardLogix 5380 SIL 2 Controller,
or GuardLogix 5580 Controller, with local
safety I/O and standard I/O modules
HMI Display
Stratix 5400 Switch
Programming Software
To plant-wide Ethernet Network
Safety System
= Safety Network
Figure 2 - Example SIL 2 System
Safety
Controller
12Rockwell Automation Publication 1756-RM012D-EN-P - August 2020
Safety Integrity Level (SIL) ConceptChapter 1
Sensor Reaction
Time
Input Reaction
Time
Safety Task
Reaction Time
Output Reaction
Time
Actuator
Reaction Time
Controller Specifications
System Reaction Time
These publications list the specifications and the agency certifications for the
products:
Agency certifications are also marked on the product labels.
See http://www.rockwellautomation.com/global/certification/overview.page
for Declarations of Conformity, Certificates, and other certification details.
The system reaction time is the worst-case time from a safety-related event as
input to the system or as a fault within the system, until the time that the
system is in the safe state.
This worst-case definition includes the effects of asynchronous
communications, and multiple potential faults, occurring within the system.
Actual reaction times may be faster.
Each of the reaction times is dependent on factors such as the type of I/O
device and instructions that are used in the program.
IMPORTANTFor more information on reaction time calculation, see Appendix C
page 83
.
on
Safety Task Reaction Time
The safety task reaction time is the worst-case delay from any input change that
is presented to the controller until the output producer sets the processed
output. Use this equation to determine the safety task reaction time:
Safety task reaction time = (safety task period + safety task watchdog) × 1.01
The multiplier is for potential clock drift.
Rockwell Automation Publication 1756-RM012D-EN-P - August 202013
Chapter 1Safety Integrity Level (SIL) Concept
Safety Task Period and Safety Task Watchdog
The safety task period is the interval at which the safety task executes.
The safety task watchdog time is the maximum permissible time for safety task
processing. If the time to process a safety task exceeds the safety task watchdog
time, a nonrecoverable safety fault occurs in the controller, which results in a
transition to the safe state (off).
You define the safety task watchdog time, which must be less than or equal to
the safety task period.
The safety task watchdog time is set in the task properties window of the
Studio 5000 Logix Designer application. This value can be modified online,
regardless of controller mode, but it cannot be changed when the controller is
safety-locked or once a safety signature is created.
Contact Information If Device
Failure Occurs
If you experience a failure with any safety device, contact Rockwell
Automation Technical Support: https://rockwellautomation.custhelp.com/
Your local Rockwell Automation sales office or Allen-Bradley distributor can
also initiate the following actions:
• Return the device to us so the failure is logged for the catalog number
that is affected, and a record is made of the failure.
• Request a failure analysis (if necessary) to try to determine the cause of
the failure.
14Rockwell Automation Publication 1756-RM012D-EN-P - August 2020
Chapter 2
GuardLogix Controller System
Top icPag e
GuardLogix 5580 Controller Hard ware15
Compac t GuardLogix 5380 Cont roller Hardware17
Network Communication19
Programming Overview23
For safety certificate information, see http://www.rockwellautomation.com/
global/certification/safety.page. Use the filters to search for your products.
GuardLogix 5580 Controller
Hardware
See Additional Resources on page 8
GuardLogix® 5580 and Compact GuardLogix 5380 controllers.
The GuardLogix controller consists of a primary controller (1756-L8xES),
which can be used alone in SIL 2 applications, and a safety partner
(1756- L8SP), which is added
Both the primary controller and safety partner perform power-up and runtime
functional-diagnostic tests of all safety-related components in the controller.
• Primary controller that is used without a safety partner is up to SIL 2.
• Primary controller that is used with a safety partner is up to SIL 3.
You can fill slots of a SIL 2 or SIL 3 system chassis that are not used by the
GuardLogix SIL 2 or SIL 3 system with other ControlLogix® (1756) modules
that are certified to the Low Voltage and EMC Directives.
To find certificates for the controllers and I/O modules, see
Rockwell Automation Publication 1756-RM012D-EN-P - August 202015
.
Chapter 2GuardLogix Controller System
Primary Controller
The primary controller is the processor that performs standard and safety
control functions and communicates with the safety partner for safety-related
functions in the GuardLogix control system. The primary controller consists of
a central processor, I/O interface, and memory.
Safety Partner
To satisfy SIL 3 requirements, you must install a 1756-L8SP safety partner in
the slot immediately to the right of the primary controller. The safety partner is
a co-processor that provides 1oo2 architecture for safety-related functions in
the system. The 1oo2 system does not run degraded. If the two processors
disagree, or cannot communicate with each other, the result is a major nonrecoverable controller fault. For information on how to respond to this
situation, see Knowledgebase Article GuardLogix and CompactGuardLogix
Safety error codes.
For SIL 2 requirements, do not install a safety partner.
The primary controller configures the safety partner. Only one download of
the user program to the primary controller is required. The primary controller
controls the operating mode of the safety partner.
Chassis
The chassis provides the physical connections between modules and the 1756
GuardLogix system. Any failure, though unlikely, would be detected as a failure
by one or more of the active components of the system. Therefore, the chassis is
not relevant to the safety discussion.
Power Supply
No extra configuration or wiring is required for SIL 2 or SIL 3 operation of the
ControlLogix power supplies. Any failure would be detected as a failure by one
or more of the active components of the GuardLogix system. Therefore, the
power supply is not relevant to the safety discussion.
16Rockwell Automation Publication 1756-RM012D-EN-P - August 2020
GuardLogix Controller SystemChapter 2
Compact GuardLogix 5380
Controller Hardware
The Compact GuardLogix 5380 controller is a SIL 2 or SIL 3 capable
controller that performs standard and safety control functions for safetyrelated functions in the Compact GuardLogix control system.
ControllerSIL Rating Cat. No.
Compac t
GuardLogix
5380
SIL 25069-L306ERMS2, 5069-L306ERS2, 5069-L310ERMS2, 5069-L310ERS2,
IMPORTANTThis equipment is supplied as open-type equipment for indoor use. It must
be mounted within an enclosure that is suitably designed for those specific
environmental conditions that are present and appropriately designed to
prevent personal injury resulting from accessibility to live parts.
The enclosure must have suitable flame-retardant properties to prevent or
minimize the spread of flame, complying with a flame spread rating of 5VA
or be approved for the application if nonmetallic. The interior of the
enclosure must be accessible only by the use of a tool.
For more information regarding specific enclosure type ratings that are
required to comply with certain product safety certifications, see:
Expansion slots of the system bus can be populated with Compact 5000™ I/O
expansion modules that are certified to the Low Voltage and EMC Directives
and populated per the instructions that are listed under Power Supply
.
To find certificates for the controllers and I/O modules, see
Rockwell Automation Publication 1756-RM012D-EN-P - August 202017
.
Chapter 2GuardLogix Controller System
Compact GuardLogix 5380 SIL3 Controllers
For SIL 3/PLe safety applications, the Compact GuardLogix 5380 SIL 3
controller system consists of a primary controller with an internal safety
partner, that function together in a 1oo2 architecture.
The primary controller configures the safety partner. Only one download of
the user program to the primary controller is required. The primary controller
controls the operating mode of the safety partner.
Power Supply
For Functional Safety applications, SELV/PELV-listed power supplies are
required for both module power (MOD) and sensor/actuator (SA) power.
Consider the following when you choose a power supply:
• The MOD power of the Compact GuardLogix 5380 controller must be
powered by a 24V DC SELV/PELV-listed power supply.
• All local 24V DC safety I/O must be powered by a SELV/PELVlisted
power supply.
• If the SA power connector of the Compact GuardLogix 5380
controller is used, it must be powered by a 24V DC SELV/PELV-listed
power supply.
• If local 120/240V AC I/O are used in the Compact GuardLogix 5380
chassis, their 120/240V AC I/O SA power must be connected to a
catalog number 5069-FPD module.
• If any standard I/O are used that are not powered by a SELV/PELVlisted power supply, their I/O power must be connected to a catalog
number 5069-FPD module.
IMPORTANTFor more information on how to power the 5069 platform when a
CompactLogix™ or Compact GuardLogix Controller is present, see the
CompactLogix 5380 and Compact GuardLogix 5380 User Manual, publication
5069-UM001
18Rockwell Automation Publication 1756-RM012D-EN-P - August 2020
.
GuardLogix Controller SystemChapter 2
Network Communication
This section provides examples of network communication configurations.
EtherNet/IP Network
The GuardLogix 5580 controller connects directly to an EtherNet/IP network
through the onboard Ethernet port and supports 10/100/1000 Mbps network
speeds. A separate Ethernet communication module is not required, but can be
used in the local chassis.
Contact your local Rockwell Automation sales office or Allen-Bradley
distributor for other communication interface modules are available for use in
the GuardLogix 5580 system.
Peer-to-peer safety communication between GuardLogix controllers is possible
via the EtherNet/IP network. GuardLogix controllers can control and
exchange safety data with safety I/O devices on an EtherNet/IP network, via
the onboard Ethernet ports or EtherNet/IP bridges.
IMPORTANTA remote GuardLogix or Compact GuardLogix controller that has firmware
earlier that revision 28 cannot consume data from a GuardLogix 5580 or
Compact GuardLogix 5380 controller
Older consumer controllers must be updated to at least to firmware revision
28, or use a dedicated, separate EtherNet/IP module in the same rack as the
5580 GuardLogix, making a connection for produced/consumed tags that
bridges through the Logix backplane.
See Knowledgebase Article Safety Tags produced by a GuardLogix 5580
controller consumed by an older GuardLogix 5570 controllers.
Rockwell Automation Publication 1756-RM012D-EN-P - August 202019
Chapter 2GuardLogix Controller System
EtherNet/IP™ Adapter
I/O Modules
Safety I/O Modul es
Stratix® 5410 Switch
PowerFlex® 527 Drive
(CIP Safety™ enabled)
Kinetix® 5700 Drives
(with Safe Monitor Functions)
1732ES ArmorBlock®
Guard I/O™ Module
1734 POINT I/O™ Adapter
1734 POINT Guard I/O™ Modules
1734 POINT I/O Modules
Compact GuardLogix 5380 controllers connect directly to the EtherNet/IP
network through the onboard Ethernet ports. They also support 10/100/1000
Mbps network speeds. A local Ethernet communication module is not used.
Figure 4 - Compact GuardLogix 5380 Peer-to-peer Communication Via the EtherNet/IP
Network
Rockwell Automation Publication 1756-RM012D-EN-P - August 202021
Compact GuardLogix 5380 Controller
with local safety I/O and standard I/O
modules
DeviceNet Safety Network
DeviceNet® bridges let the GuardLogix controller control and exchange safety
data with safety I/O modules on a DeviceNet network.
Figure 5 - GuardLogix 5580 Communication Via a DeviceNet Bridge
Compact GuardLogix 5380 controllers can communicate with safety devices
on a DeviceNet network via a 1788-EN2DNR EtherNet/IP to DeviceNet
linking device.
Figure 6 - Compact GuardLogix 5380 Controller with a DeviceNet Network
22Rockwell Automation Publication 1756-RM012D-EN-P - August 2020
GuardLogix Controller SystemChapter 2
Programming Overview
Use the Studio 5000 Logix Designer® application to program GuardLogix
safety controllers.
Use the Studio 5000 Logix Designer application to define the location,
ownership, and configuration of I/O devices and controllers and create, test,
and debug program logic. Only ladder diagram is supported in the GuardLogix
safety task.
See Appendix
available for safety projects.
IMPORTANTWhen the GuardLogix controller is in Run or Program mode and you have
A on page 73 for information on the set of logic instructions
not validated the application program, you are responsible for maintaining
safe conditions.
Rockwell Automation Publication 1756-RM012D-EN-P - August 202023
Chapter 2GuardLogix Controller System
Notes:
24Rockwell Automation Publication 1756-RM012D-EN-P - August 2020
Chapter 3
Safety Network
Safety Status
Safety Output, OFF
Safety
Input
Data
Safety I/O for the GuardLogix Control System
Top icPag e
Typical Safety Functions of Safety I/O Devices25
Reaction Time26
Safety Considerations for Safety I/O Devices27
Before you operate a GuardLogix® safety system with safety I/O devices, you
must first read, understand, and follow all safety information in the product
documentation for those products.
Safety I/O devices can be connected to safety input and output devices, like
sensors and actuators. The GuardLogix controller monitors and controls the
devices. For safety data, I/O communication is performed through safety
connections by using the CIP Safety™ protocol; safety logic is processed in the
GuardLogix controller.
Typical Safety Functions of
Safety I/O Devices
The following is treated as the safe state by safety I/O devices:
•Safety outputs: OFF
• Safety input data to controller: OFF
Use safety I/O devices for applications that are in the safe state when the safety
output turns OFF.
Diagnostics
Safety I/O devices perform self-diagnostics when the power is turned ON and
periodically during operation. If a diagnostic failure is detected, safety input
data (to the controller) and local safety outputs are set to their safe state (OFF).
Rockwell Automation Publication 1756-RM012D-EN-P - August 202025
Chapter 3Safety I/O for the GuardLogix Control System
Status Data
In addition to safety input and output data, safety I/O devices support status
data to monitor device and I/O circuit health. See the product documentation
for your device for specific product capabilities.
Status Indicators
The safety I/O devices include status indicators. For details on status indicator
operation, see the product documentation for your specific device.
On-delay or Off-delay Function
Some safety I/O devices can support on-delay and off-delay functions for input
signals. In some applications, you must include off-delay, on-delay, or both
when you calculate system reaction time.
Reaction Time
For example, the On-to-Off delay filter helps to filter out noise that affects the
input logic level.
See Appendix
The input reaction time is the time from when the signal changes on an input
terminal to when safety data is sent to the GuardLogix controller.
The output reaction time is the time from when safety data is received from the
GuardLogix controller to when the output terminal changes state.
For information on how to determine the input and output reaction times, see
the product documentation for your specific safety I/O device.
See Appendix
reaction time.
C on page 83 for information on system reaction time.
C on page 83 for information on how to calculate the system
26Rockwell Automation Publication 1756-RM012D-EN-P - August 2020
Safety I/O for the GuardLogix Control SystemChapter 3
Safety Considerations for
Safety I/O Devices
You must commission all devices with a node or IP address and communication
rate, if necessary, before their installation on a safety network.
Ownership
One GuardLogix controller owns each safety I/O device in a GuardLogix
system. Multiple GuardLogix controllers and multiple safety I/O devices can
be used without restrictions in chassis or on networks, as needed. When a
controller owns an I/O device, it stores the configuration data that you define
for that device. This configuration controls how the devices operate in the
system.
From a control standpoint, one controller controls safety output devices. One
controller also owns each safety input device. However, safety input data can be
shared (consumed) by multiple GuardLogix controllers.
Safety I/O Configuration Signature
IMPORTANTThe safety I/O configuration signatures apply to individual safety modules.
This is different than the controller safety signature, which applies to the
entire safety portion of the controller.
The configuration signature is calculated from the configuration of the safety
I/O device. The configuration signature is used to verify that the device is
configured as expected by the safety application. When you use a GuardLogix
controller, you do not have to monitor this signature. The GuardLogix
controller automatically monitors the signature. If the configuration signature
changes unexpectedly, the safety connection between the controller and I/O
module is broken which causes the I/O module to enter its safe state.
Rockwell Automation Publication 1756-RM012D-EN-P - August 202027
Chapter 3Safety I/O for the GuardLogix Control System
When using a third-party module, if you connect to a safety I/O device
without a configuration signature, you must verify that a valid configuration
exists in the safety I/O device.
IMPORTANTRockwell Automation® safety I/O modules typically default to using the
configuration signature; and do not allow your system to run without
configuration signature.
Safety I/O Device Replacement
The replacement of safety devices requires that the replacement device is
properly configured, and that the operation of the replacement device is
verified.
ATTENTION: During replacement or functional testing of a device, the safety
of the system must not rely on any portion of the affected device.
Two options for I/O device replacement are available on the Safety tab of the
Controller Properties dialog box in the Studio 5000 Logix Designer®
application:
• Configure Only When No Safety Signature Exists
•Configure Always
28Rockwell Automation Publication 1756-RM012D-EN-P - August 2020
Safety I/O for the GuardLogix Control SystemChapter 3
Figure 7 - Safety I/O Replacement Options
Configure Only When No Safety Signature Exists
This setting instructs the GuardLogix controller to configure a safety device
when the safety task does not have a safety signature, and the replacement
device is in an out-of-box condition with no safety network number.
If the controller has a safety signature, the GuardLogix controller automatically
configures the replacement safety I/O device if all of the following are true:
• The device already has the correct safety network number.
• The device electronic keying is correct.
• The node or IP address is correct.
To set the proper safety network number (SNN) when a controller safety
signature exists, a manual action is required to download the proper SNN. Go
online to the GuardLogix or CompactGuardLogix controller with the Studio
5000 Logix Designer® application, then open the Module Properties dialog,
General tab, and click the “…” button next to the Safety Network Number. Use
the Set button to write the SNN to the module manually. After the manual
action, the remainder of the configuration is automatically downloaded.
For detailed information, see the Replace a Safety I/O Device procedure in the
user manual for the controller:
• ControlLogix 5580 and GuardLogix 5580 Controllers User Manual,
publication 1756-UM543
• CompactLogix 5380 and Compact GuardLogix 5380 User Manual,
publication 5069-UM001
Rockwell Automation Publication 1756-RM012D-EN-P - August 202029
Chapter 3Safety I/O for the GuardLogix Control System
Configure Always
The GuardLogix controller attempts to configure a replacement safety I/O
device automatically if the device is in an out-of-box condition. (When a safety
network number does not exist in the replacement safety device, and the node
number and I/O device keying matches the configuration of the controller.)
ATTENTION: Enable the Configure Always feature only if the entire routable
Safety control system is not being relied on to maintain SIL 2 or SIL 3 behavior
during the replacement and functional testing of a device. See Routable
Safety System on page 32.
If other parts of the Safety control system are being relied upon to maintain SIL 2
or SIL 3, make sure that the Configure Always feature of the controller is
disabled.
It is your responsibility to implement a process to make sure that proper safety
functionality is maintained during device replacement.
CIP
ATTENTION: To place a device in the out-of-box condition on a Safety
network when the Configure Always feature is enabled, follow the device
replacement procedure in the user manual:
• ControlLogix 5580 and GuardLogix 5580 Controllers User Manual,
publication 1756-UM543
• CompactLogix 5380 and Compact GuardLogix 5380 User Manual,
publication 5069-UM001
30Rockwell Automation Publication 1756-RM012D-EN-P - August 2020
Loading...
+ 90 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.