Rockwell Automation 1784-KTCX15 User Manual

DH+, FLEX I/O, PanelView, and PLC-5/40C are trademarks of Rockwell Automation. ControlNet is a trademark of ControlNet International. WINtelligent LINX and WINtelligent LINX Gateway are trademarks of Rockwell Software Inc. Ethernet is a registered trademark of Digital Equipment Corporation, Intel, and Xerox Corporation.
Installation Instructions
ControlNet Communication Interface Card
Catalog Number 1784-KTCX15
To the Installer
This
document describes how to install and use the 1784-KTCX15 ControlNet
Topic Page
Worldwide representation.
Argentina • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador Finland Indonesia • Mexico Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore Africa, Republic • Spain • Sweden United Kingdom • United States • Uruguay • V
Rockwell Automation Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication
Supersedes
October 1995
Australia • Austria • Bahrain • Belgium
France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India
Ireland • Israel • Italy • Jamaica •
Netherlands
1784-5.33 – September 1997
Publication 1784-5.33 – July 1997
New
Zealand • Norway
Switzerland T
Brazil
Bulgaria • Canada • Chile • China, PRC
Japan • Jordan • Korea • Kuwait • Lebanon
Pakistan
enezuela • Y
E
Peru
Philippines
aiwan
Thailand T ugoslavia
1997 Rockwell International Corporation. All rights reserved. Printed in USA.
Poland • Portugal
Slovakia Slovenia
urkey • United Arab Emirates
Malaysia
PN 955130-38
South
Introduction to the KTCX15 Card
2 About the Application Software 3 Compliance to European Union Directives 3 Configuring the Card 5 Selecting the Base Memory Address Location 6 Selecting the Base I/O Space Address Location 9 About the Jumpers 14 Installing the Card 16 Running the Installation Check Utility 18
Connecting the Card 23 Connecting to a ControlNet Network 24 Interpreting the Status Indicators 28 CSA Hazardous Location Approval 29
Specifications 31
Publication 1784-5.33 – September 1997
2 ControlNet Communication Interface Card
If you are connecting the card directly to a ControlNet network, you also need to read:
ControlNet Tap Installation Instructions, publication 1786-5.7
ControlNet Cable Planning and Installation Manual, publication 1786-6.2.1
Important
Because for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1,
of Solid State Control
dif
ferences between solid-state equipment and electromechanical devices that should be taken into
consideration when applying products such as those described in this publication. Reproduction of the contents of this copyrighted publication, in whole or in part, without written
permission of Allen-Bradley Company Throughout this document we use notes to make you aware of safety considerations:
!
Attention statements help you to:
Important:
of the product.
User Information
of the variety of uses for the products described in this publication, those responsible
(available from your local Allen-Bradley of
ATTENTION:
personal injury or death, property damage or economic loss.
S
identify a hazard
S
avoid the hazard
S
recognize the consequences
Identifies information that is critical for successful application and understanding
Safety Guidelines for the Application, Installation, and Maintenance
fice), describes some important
, Inc., is prohibited.
Identifies information about practices or circumstances that can lead to
Introducing the 1784-KTCX15 Communication Interface Card
The KTCX15 Communication Interface card lets a 16-bit ISA- or 32-bit EISA­compatible computer communicate directly with other ControlNet products.
Publication
1784-5.33 – September 1997
ControlNet Communication Interface Card 3
About the Application Software
The Allen-Bradley standard application programming interfaces (APIs) are INTERCHANGE Software Inc. Contact your local Rockwell Automation sales representative or distributor for further information.
, WINtelligent LINX, and RSLinxsoftware from Rockwell
Compliance to European Union Directives
If this product bears the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file:
marking, it is approved for installation within the
EN 50081-2EMC - Generic Emission Standard, Part 2 - Industrial Environment
EN 50082-2EMC - Generic Immunity Standard, Part 2 - Industrial Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 - Equipment Requirements and Tests.
For specific information required by EN 61 the following Allen-Bradley publications:
131-2, see the appropriate sections in
Industrial Automation Wiring and Grounding Guidelines for Noise Immunity,
publication 1770-4.1
Automation Systems Catalog, publication B111
Publication
1784-5.33 – September 1997
4 ControlNet Communication Interface Card
ATTENTION:
limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le présent appareil numérique n’émet pas de bruits radioélectriques dépassant les limites applicables aux appareils numériques de la class A prescrites dans le Règlement sur le brouillage radioélectrique édicté par le ministère des Communications du Canada.
Handling the Card
ATTENTION:
sensitive to electrostatic dischar whenever you are handling the card. Handling a card without any ESD protection can cause internal circuit damage that may not be apparent during installation or initial use. A grounding wrist strap has been shipped with the card and is to be worn during the installation procedure. Instructions for use of the strap are found on the back of its package.
This digital apparatus does not exceed the Class A
The card uses CMOS technology
, which is highly
ge (ESD). ESD may be present
wrist-strap grounding device
T
ake these precautions to guard against ESD damage:
Before handling the card, be sure to wear the provided static strap and touch
a grounded object to discharge any built-up static charge.
Avoid touching the backplane connector or interface connector pins located
on the card.
If the card is not in use, store it in the anti-static clamshell that the card was
shipped in.
Important: Remember
grounded object.
You are now ready to configure your card.
Publication
1784-5.33 – September 1997
, a computer with ac power disconnected is
not
a
32 ControlNet Communication Interface Card
ControlNet Communication Interface Card 5
Configuring the Card Hardware
Before you install the card inside your computer, you must set the card’s physical addresses for the:
ROM I/O expansion area of the host processor’s system memoryso the card and the host computer can exchange data through the dual-port interface. This is the base memory address.
host processor from the host computer
Y
ou can have as many as four KTCX15 cards in one computer as long as each
card has dif
T
o configure these addresses, you set switches on the card. The card comes
factory-set with these default addresses:
Address Type Address Setting (hex)
s I/O mapso the card
. This is the
s I/O devices can receive commands
base I/O space addr
ferent base memory and base I/O space addresses.
ess.
Publication
1784-5.33 September 1997
base memory base I/O space memory 220
Important: When
deciding which addresses to use, remember that each card
in your computer must have a unique
D000:0000
base memory address and a unique base I/O space memory address. If another card in the host computer is using one or both of the factory-set addresses, you must change a card
If you are: go to:
changing addresses on the card
using the factory-set addresses Installing the Card on page 16
s switch settings to an available address.
Selecting the Base Memory Address Location on page 6
Publication
1784-5.33 – September 1997
6 ControlNet Communication Interface Card
ControlNet Communication Interface Card 31
Selecting the Base Memory Address Location
The host computer and the card exchange data via a dual-port interface. The dual-port interface is 16 Kbytes long and it begins at the specified base memory address location.
The card comes set to memory address D000:0000. Y selected memory address has been allocated to other interface cards or expansion memory cards you have installed in your computer system. If this occurs, change the switch settings to an available memory address.
T
o select a new base memory address:
1.
Pick an available address from the ROM I/O adapters area of the host computers memory
2.
Use W
orksheet
3.
Use W
orksheet B to determine the proper switch settings.
. Be sure to choose a block that is 16 Kbytes long.
A to select a new memory address for the card.
Follow this guide to properly set your switches.
Side ViewFront View
down (0)
S2 S1
up (1)
ou may find that this
Front View
up (1)
12 1234
MSBLSB
Specifications
The operating parameters describe the environment within the KTCX15 slot. Refer to the documentation for your computer for environmental requirements. The card should not exceed those specifications.
General
Characteristic Value
Power Requirements
Conductor Category 2
Environmental
Slot Temperature Humidity 5 to 95% without condensation 5 to 95% without condensation Vibration 10 to 150 Hz, constant .012 in
Shock 30G peak/11 ms 50G peak/11 ms
Specifications
5V dc, 640mA Maximum
Specifications
Operating Nonoperating
0 to 50° C (32 to 122° F) –40 to 85° C (–40 to 185° F)
not applicable
displacement 10 to 150 Hz, constant 2.0G
acceleration
down (0)
4. Fill in Worksheet C after youve determined your switch settings.
5. Follow the instructions that begin on page 11.
Publication
1784-5.33 – September 1997
Agency Certification
(when product or packaging is marked)
Class 1, Division 2 Groups A, B, C, D
marked for all applicable directives
Publication
1784-5.33 – September 1997
30 ControlNet Communication Interface Card
Approbation
d’utilisation dans des emplacements dangereux par la CSA
La CSA certifie les produits dutilisation générale aussi bien que ceux qui sutilisent dans des emplacements dangereux. La certification CSA en vigueur est indiquée par l’étiquette du produit et non par des affirmations dans la documentation à lusage des utilisateurs.
Exemple d’étiquette de certification dun produit par la CSA
I
W
orksheet
Base
Base Memory Address
0000:0000–7000:FFFF
A
memory allocation worksheet
(hex)
512K Read/W System Board
ControlNet Communication Interface Card 7
Host Computer Assignments Your System
rite Memory on
Pour satisfaire à la certification de la CSA dans des endroits dangereux, les informations suivantes font partie intégrante de la documentation ce produit industriel de contrôle certifié par la CSA.
Cet équipement convient à lutilisation dans des emplacements de Classe 1, Division 2, Groupes A, B, C, D, ou ne convient qu’à l’utilisation dans des endroits non dangereux.
Les produits portant le marquage approprié de la CSA (cest à dire, Classe 1, Division 2, Groupes A, B, C, D) sont certifiés à l’utilisation pour d’autres équipements où la convenance de combinaison (application ou utilisation) est déterminée par la CSA ou le bureau local dinspection qualifié.
Important: Par suite de la nature modulaire du système de contrôle programmable, le produit ayant le taux le plus élevé de température détermine le taux densemble du code de température du système de contrôle dun programmable dans un emplacement de Classe 1, Division 2. Le taux du code de température est indiqué sur l’étiquette du produit.
Taux du code de température
I
Le taux du code de température est indiqué ici
Les avertissements suivants sappliquent aux produits ayant la certification CSA pour leur utilisation dans des emplacements dangereux.
AVERTISSEMENT: Risque d’explosion
La substitution de composants peut rendre ce matériel inacceptable pour lesemplacements de Classe I, Division 2.
Couper le courant ou s’assurer quelemplacement est désigné non
!
dangereux avant de remplacer lescomposants.
Avant de débrancher l’équipement, couper le courant ou sassurer que lemplacement est désigné non dangereux.
Avant de débrancher les connecteurs, couper le courant ou sassurer que lemplacement est reconnu non dangereux. Attacher tous connecteurs fournis par lutilisateur et reliés aux circuits externes de cet appareil à l ’aide de vis, loquets coulissants, connecteurs filetés ou autres moyens permettant aux connexions de résister à une force de séparation de 15 Newtons (3,4 lb. - 1,5 kg) appliquée pendant au moins une minute.
Afin d’eviter tout risque dexplosion, sassurer que lemplacement est designe non dangereux avant de changer la batterie.
Le
sigle CSA est la marque déposée de lAssociation des Standards pour le Canada.
8000:0000–9000:FFFF
A000:0000– V A400:0000– A800:0000– AC00:0000– B000:0000– B400:0000– B800:0000– BC00:0000– C000:0000– C400:0000– C800:0000– CC00:0000– D000:0000– D400:0000– D800:0000– DC00:0000– E000:0000–F000:FFFF
128K Read/W Expansion in I/O Channel
ideo Buf
Expansion Card Area (area available for
KTCX15 memory addresses)
Factory Default
128K ROM Reserved on System Board
rite Memory
fer
Publication
1784-5.33 – September 1997
Publication
1784-5.33 – September 1997
8 ControlNet Communication Interface Card
W
orksheet B
KTCX15
W Your
switch settings
Base Memory Addr
(hex)
C000:0000
C400:0000
C800:0000
CC00:0000
orksheet C
base memory address
Switch Settings
up (1)
12 1234
down (0)
up (1)
12 1234
down (0)
up (1)
12 1234
down (0)
up (1)
12 1234
down (0)
Base Memory Addr
(hex)
D000:0000
factory
set default address & recommended setting
D400:0000
D800:0000
DC00:0000
Record the base memory address for the KTCX15 card:
Card: Slot number:
Using default address:
yes no
If no, new memory address:
Switch Settings
up (1)
12 1234
down (0)
up (1)
12 1234
down (0)
up (1)
12 1234
down (0)
up (1)
12 1234
down (0)
up (1)
S2 S1
12 1234
down (0)
ControlNet Communication Interface Card 29
CSA Hazardous Location Approval
CSA certifies products for general use as well as for use in hazardous locations. Actual CSA certification is indicated by the product label as shown below, and not by statements in any
user documentation.
Example of the CSA certification product label
To comply with CSA certification for use in hazardous locations, the following information becomes a part of the product literature for this CSA-certified industrial control product.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous locations only.
The products having the appropriate CSA markings (that is, Class I Division 2, Groups A, B, C, D), are certified for use in other equipment where the suitability of combination (that is, application or use) is determined by the CSA or the local inspection office having jurisdiction.
Important: Due to the modular nature of a programmable control system, the product with the highest temperature rating determines the overall temperature code rating of a programmable control system in a Class I, Division 2 location. The temperature code rating is marked on the product label as shown.
Temperature code rating
I
The following warnings apply to products having CSA certification for use in hazardous locations.
WARNING: Explosion hazard
Substitution of components may impair suitability for Class I, Division 2.
Do not replace components unless power has been switched off or the area
is known to be non-hazardous.
Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
!
area is known to be non-hazardous.
Do not disconnect connectors unless power has been switched off or the area is known to be non-hazardous. Secure any user-supplied connectors that mate to external circuits on this equipment by using screws, sliding latches, threaded connectors, or other means such that any connection can withstand a 15 Newton (3.4 lb.) separating force applied for a minimum of one minute.
Batteries must be changed only in an area known to be non-hazardous.
I
Look for temperature code rating here
Publication
1784-5.33 – September 1997
CSA
logo is a registered trademark of the Canadian Standards Association.
Publication
1784-5.33 – September 1997
28 ControlNet Communication Interface Card
ControlNet Communication Interface Card 9
Interpreting the Status Indicators on the KTCX15
The status indicators on the card give you information about the card and the network when youre connected via the BNC connectors. T states and explains what each state means to you and the action you should take, if any, to correct that state.
T
able B
ControlNet
steady – indicator
alternating – the
flashing – the
A B
off steady red
alternating red/green alternating red/of
off
steady green flashing green/of
flashing red/of
flashing red/green
The
status interpretation
is on continuously in the defined state.
two indicators alternate between the two defined states at the same time (applies to
both indicators
independent
and
configuration keeper node is the node responsible for distributing ControlNet configuration data to all nodes on the
network.
viewed together
indicator alternates between the two defined states (applies to each indicator
of the other). If both indicators are flashing, they must flash together
f
f
f
). The two indicators are always in opposite states, out of phase.
Cause: Action:
no power faulted unit
self-test none incorrect node configuration
channel disabled
normal operation temporary errors node is not configured to go on line
media fault
no other nodes present on network incorrect network configuration
none or power up cycle power or reset unit If fault persists, contact your Rockwell
Automation representative or distributor
check network address and other ControlNet configuration parameters
program network for redundant media, if required
none none; unit will self-correct make sure the configuration keeper node
is present and working check media for broken cables, loose
connectors, missing terminators, etc. add other nodes to the network cycle power or reset unit If fault persists, contact your Rockwell
Automation representative or distributor
able B outlines the
viewed
, in phase.
.
.
Selecting the Base I/O Space Address Location
The
host addresses I/O devices on the card by using their I/O space address. The host addresses individual devices through registers that have addresses based on the I/O space base address. The registers are 2 bytes long.
The card comes set to base I/O space address 220. Y selected address has been allocated to other interface cards or expansion memory cards you have installed in your computer system. If this occurs, change the switch settings to an open address.
Important: When selecting configuration settings, check for conflicts with
other interface cards and system memory. If there is a conflict, the system will not operate properly.
T
o select a new base I/O space address:
1. Pick an available address from the I/O map area of the host computer’s
memory
. Be sure to choose a block that is 2 bytes long.
Important: Each card requires 2 bytes of I/O space.
2.
Use W
orksheet D to select a new base I/O space address for the card
(i.e., to determine the switch settings for the new address). Follow this guide to properly set your switches:
Side ViewFront View
down (0)
up (1)
3. Fill in Worksheet E after youve determined your switch settings.
4. Follow the instructions that begin on page 11.
ou may find that this
Front View
MSBLSB
up (1)
S3
1234
down (0)
Important: When
(NAP), the LEDs are meaningless.
Publication
1784-5.33 – September 1997
you have a cable connected to the network access port
Publication
1784-5.33 – September 1997
10 ControlNet Communication Interface Card
W
orksheet D
KTCX15
switch settings
Base
I/O Address
(hex)
200
potential device conflict: game port
220
Switch Settings
up (1)
1234
down (0)
up (1)
Base I/O
Address
(hex)
300
potential device conflict: prototype cards
320
Switch Settings
up (1)
1234
down (0)
up (1)
Figure 6 Connecting
a portable host computer to ControlNet through a
desktop host computer
portable host computer
ControlNet Communication Interface Card 27
1784-KTCX15 1784-KTCX15
desktop host computer
factory-set
default address & recommended setting
240
260
280
2A0
2C0
potential device conflict: EGA
2E0
1234
down (0)
up (1)
1234
down (0)
up (1)
1234
down (0)
up (1)
1234
down (0)
up (1)
1234
down (0)
up (1)
1234
down (0)
up (1)
potential device conflict: HDD
340
360
380
potential device conflict: SDLC
3A0
potential device conflict: SDLC
3C0
potential device conflict: EGA
3E0
1234
down (0)
up (1)
1234
down (0)
up (1)
1234
down (0)
up (1)
1234
down (0)
up (1)
1234
down (0)
up (1)
1234
down (0)
up (1)
1786-CP cable
ControlNet network
Connecting the Card Directly to the ControlNet Network
To connect the card directly to a ControlNet network as shown below, follow the instructions in these publications:
ControlNet Tap Installation Instructions, publication 1786-5.7
ControlNet Cable Planning and Installation Manual, publication 1786-6.2.1
desktop host computer
1784-KTCX15
1786-TPR, -TPS, -TPYR, or -TPYS tap
potential device conflict: GPIB
Publication
1784-5.33 – September 1997
1234
down (0)
1234
down (0)
ControlNet network
Publication
1784-5.33 – September 1997
26 ControlNet Communication Interface Card
Figure 5 Connecting
a portable host computer to a ControlNet network through
a programmable controller or an I/O adapter
ControlNet Communication Interface Card 11
W
orksheet E
Your
base I/O space address
Record the base I/O space address for the KTCX15 card:
programming terminal
1784-KTCX15
1786-CP
ControlNet network
The
1786-CP cable can be plugged into any ControlNet product programming capability on the ControlNet network. A programming terminal connected through this cable is counted as a node and must have a unique address.
ATTENTION:
If you connect the product to a cable system that does
s NAP to provide
BATT
BATT
CH 0
CH 0
ControlNet product
not support redundant media, connect the tap dropline to the BNC connector labeled channel A. Channel B is left open.
If the cable system is redundant, connect the product such that all devices on the network use the same cable for the same channel. That is, all channel A connectors connect to one cable; all channel B connectors connect to the other.
Card: Slot number:
Using default address:
yes no
up (1)
S3
1234
If no, new I/O space address:
down (0)
Setting the Card’s Switches
ATTENTION:
other components on the card.
1. Follow the card handling instructions on page 4.
2. Remove the card from the anti-static clamshell.
Important: When selecting configuration settings, check for conflicts with
other interface cards and system memory. If there is a conflict, the host computer will not operate properly.
You must find a way to disable caching and shadow memory for at least the 16K of memory space occupied by each card. This can usually be accomplished through your CMOS setup program and/or memory manager before running applications with the KTCX15 cards.
When setting the switches, be sure to avoid touching
, and must be done
Publication
1784-5.33 – September 1997
Publication
1784-5.33 – September 1997
12 ControlNet Communication Interface Card
ControlNet Communication Interface Card 25
3. If you are using the card’s default memory addr If you are setting a new base memory address
, set the switches to the up or
down position to reflect the selected address from W
Front of Switches
D000:0000
Factory-set (recommended setting)
address
up (1)
S2 S1
12 1234
down (0)
ess setting
orksheet C.
down (0)
up (1)
, go to step 4.
20629–M
Side ViewFront View
T
able
A shows the wiring for the cable.
T
able
A
for 1786-CP connector cable
Wiring
Connector 1
Wire Number Signal Mnemonic Signal Name
1 ISO-GND Isolated Ground 2 N.C. No Connection 3 PTTX-H Transmit Data High 4 PTTX-L Transmit Data Low 5 PTRX-L Receive Data Low 6 PTRX-H Receive Data High 7 N.C. No Connection 8 ISO-GND Isolated Ground
Connector 2
Wire Number Signal Mnemonic Signal Name
1 ISO-GND Isolated Ground 2 N.C. No Connection 3 PTRX-H Receive Data High 4 PTRX-L Receive Data Low 5 PTTX-L Transmit Data Low 6 PTTX-H Transmit Data High 7 N.C. No Connection 8 ISO-GND Isolated Ground
Publication
1784-5.33 – September 1997
Publication
1784-5.33 – September 1997
24 ControlNet Communication Interface Card
ControlNet Communication Interface Card 13
Important: If you are using a non-redundant cabling system, all ControlNet
devices must be on the same channel, channel
A.
Connecting to a Device on the ControlNet Network
By using the card NAP), you can connect the card to a ControlNet network, without a tap, through a programmable controller, I/O adapter, or another KTCX15 card (Figure 5 and Figure 6).
The 1786-CP cable (Figure 4) connects a portable host computer to another computer; it has two RJ-45 8-pin connectors.
Figure 4 1786-CP
cable
s RJ-45 connector (known as the network access port or
RJ-45 8-pin connectors
4. If you are using the card’s default base I/O space addr
next section, Installing the Card Inside the Computer. If you are setting a
new base I/O space addr
ess
, set the switches to the up or
down position to reflect the selected address from Worksheet E.
Front of Switches
220h Factory-set (recommended setting)
address
S3
up (1)
1234
down (0)
down (0)
up (1)
ess setting
, go to the
20629–M
Side ViewFront View
Publication
1786-CP cable
ATTENTION:
Use the
1786-CP
cable when connecting a
programming terminal to the network through the network access port (NAP); using another cable could result in possible network failures or product damage.
1784-5.33 – September 1997
Publication
1784-5.33 – September 1997
14 ControlNet Communication Interface Card
ControlNet Communication Interface Card 23
About the Jumpers
Important: When you receive your card, the jumpers are in the default
Figure 1 KTCX15
positions, as shown in Figure 1. Do See Figure 2 for an explanation of these jumpers.
jumpers
E2
E1
E3
not
alter these positions.
20628-M
Connecting the Card
After
you have installed the card, you can connect it:
to a device already connected to the ControlNet network (page 24)
directly to a ControlNet network, which requires a tap (page 27)
Figure 3 shows the card connector.
Figure 3 KTCX15
card connector
Diagnostic status
indicators
Redundant media
BNC connectors
A
B
1784KTCX15
Network Access Port (NAP)
RJ-45 connector for connecting programming terminals to devices on a ControlNet network
Channel A
BNC connectors for connecting directly to a ControlNet network
Channel B
TIP: The light icon is channel A;
the dark icon is channel B.
Publication
1784-5.33 – September 1997
ATTENTION: Do not use the card to connect to more than one network at a time. Attempting to connect to a second network will cause your communication system to operate erraticly.
See page 28 for information about status indicators. Indicators diagnose only redundant media BNC connections.
Publication
1784-5.33 – September 1997
22 ControlNet Communication Interface Card
ControlNet Communication Interface Card 15
5. Press
6. Press
7. Press
any key
Y
ou see a window similar to this one:
MSDOS a:\KTCINSTNT.EXE
Success...Hard resetting card Success...Starting cards processor Success...Attempting to locate DualPort address...
Success...Searching for version mailbox
Success...Testing Mail Boxes Waiting...Soft Resetting the KTCX15 as network
any key
Waiting... Setting KTCX to online. Press any key.
any key
Y
ou see a similar message:
Success... Setting KTCX to online. KTCX LEDs should show flashing red. Waiting... Setting KTCX to offline. Press any key.
.
Found at 0Xd0000
bootcode version: 2.1 3/17/97 Serial#: 2222 <8AE> Main Code Version 99.60 4/29/97
address ID8. Press any key.
. Y
ou see a similar message:
.
Flashing red LEDs indicate that the card can communicate on a network, if it
s connected to a network.
8.
Press any key
.
Figure 2 Series
B Jumper Explanations
E2
E1
E2
E1
E3
If you have this computer: then:
286-based or older 386-based or newer these address lines are usually latched
Use these jumper positions for:
normal card operation field flash upgrade of the cards main code
Use these jumper positions for field flash upgrade of the cards boot code.
IMPORTANT: All other E1 and E2 jumper combinations are illegal. Unknown card operation will result.
When installed, use this jumper to latch certain address lines that some 286 and older machines may not latch.
you may need to install this jumper
in the computer and, thus, the jumper is not usually required
Y
ou see a similar message:
Success... Setting KTCX to offline. KTCX LEDs should show flashing green. Waiting... Resetting KTCX. Press any key.
Alternate green and red LEDs indicate that your card reset successfully. If this test fails, make certain that you are not connected to a network.
Contact your local Rockwell Automation sales representative or distributor, or Rockwell Automation Technical Support at (440) 646-6800.
Publication
1784-5.33 – September 1997
Publication
1784-5.33 – September 1997
16 ControlNet Communication Interface Card
ControlNet Communication Interface Card 21
Installing the Card Inside the Computer
Important: Before you install the card, make sure you know how to configure
the computer
s options, e.g., disabling cache memory
, memory manager, and shadowing of memory, and that you know how to install hardware in your computer. Consult your computers documentation for specific information.
To install the card, you need to:
access to the computer’s expansion slots You need a Phillips-head or a flat-head screwdriver, depending on your
system.
insert the card into the computer
Accessing the Computer’s Expansion Slots
To
install the card, you must access the computer’s expansion slots. Follow these general steps, or refer to your computers user guide for more explicit instructions.
1. Power down the host computer by turning off the power switch.
2. Remove the computer
3. Select a vacant 16- or 32-bit expansion slot.
Important: The card will function only in a 16- or 32-bit ISA/EISA
expansion slot.
4.
Remove the slot (rear bracket) of the computer.
s cover
.
s expansion cover by loosening the screw on the back
Running the KTCX15 Card Installation Check Utility in Windows NT
To make sure you have installed the card properly, run the installation check utility
. Follow these steps:
1. Place the utility disk in drive A of the host computer.
If you are running the utility software from another drive, use the appropriate drive letter.
2. From the W
The Run dialog box appears.
3. Type the path and command to run the utility.
a:\ktcinstnt 8
4.
Click OK. Y
ou see a window similar to this one:
MSDOS a:\KTCINSTNT.EXE
Success...Copying KTCLDSRV.SYS to System Directory Success...Registering Service with Service Manager Success...MacID 0X008 <8> IOBase:0X220 Success...Starting Device KTCLDSRV Success...Opening driver KTCLDSRV
Working...Make sure card is not connected Press any key.
Important: Make sure that the card is not connected to a network.
indows NT Start Menu, select RUN.
(where 8
ControlNet 1784–KTCX15 Card
Installation Check Utility
Version 1.x, MMM DD, YYYY, hh:mm:ss
Copyright 1997 by Allen–Bradley Company
is the network address youve selected)
Publication
1784-5.33 – September 1997
Publication
1784-5.33 – September 1997
20 ControlNet Communication Interface Card
ControlNet Communication Interface Card 17
7. Press
any key
Y
ou see:
Succeeded Setting KTCX to online. KTCX LEDs should show flashing red.
.
Flashing red LEDs indicate that the card can communicate on a network, if it
s connected to a network.
If this test fails, contact your local Rockwell Automation sales representative or distributor, or Rockwell Automation Technical Support at (440) 646-6800.
Waiting.. Setting KTCX to offline. Press any key.
The utility takes the card off of the network.
8.
Press any key Y
ou see:
Succeeded Setting KTCX to offline. KTCX LEDs should show flashing green.
Flashing green LEDs indicate that the card successfully made the transition from online to offline, i.e., from simulating network communication to operating independently.
If this test fails, contact your local Rockwell Automation sales representative or distributor, or Rockwell Automation Technical Support at (440) 646-6800.
Inserting the Card
To insert the card inside the computer:
1. Follow the card handling instructions on page 4.
2.
Make sure you have correctly set all of the switches on the card.
3. Insert the card into the edge connector and tighten the expansion slot screw.
4. Turn on the computer to make sure it comes up correctly.
If the computer: then:
powers up hangs up you probably have a memory or I/O conflict
5. Replace the CPU cover (when computer comes up correctly).
go to step 5
You should
change switch settings and cycle power, or
remove all other cards and try again
If you are still unsuccessful, contact your local Rockwell Automation sales representative or distributor, or Rockwell Automation Technical Support at (440) 646-6800.
Waiting.. Resetting KTCX. Press any key.
The utility re-initializes the card.
9.
Press any key Y
ou see:
Succeeded Resetting KTCX. KTCX LEDs should alternate green and red. Test of KTCXs basic functionality succeeded. Installation successful.
.
Alternate green and red LEDs indicate that your card reset successfully. If this test fails, contact your local Rockwell Automation sales representative
or distributor, or Rockwell Automation Technical Support at (440) 646-6800.
Publication
1784-5.33 – September 1997
Publication
1784-5.33 – September 1997
18 ControlNet Communication Interface Card
ControlNet Communication Interface Card 19
Running the KTCX15 Card Installation Check Utility in DOS or WIN95
To make sure you have installed the card properly, run the installation check utility
. Follow these steps:
1. Place the utility disk in drive A of the host computer.
If you are running the utility software from another drive, use the appropriate drive letter.
If you are using WIN95: a. From the W
The Run dialog box appears.
b. Type the path and command to run the utility.
a:\ktcinst 8 (where 8
c.
Click OK. If you are using DOS or a DOS window in WIN95: a. At the DOS prompt, type:
a:\ktcinst
Y
ou see a screen/window similar to this one:
indows 95 Start Menu, select RUN.
is the network address youve selected)
1784–KTCX15 Card Installation Check Utility
Copyright 1997 Allen–Bradley Company, Inc.
Version 1.xx DD–MMM–YY
2. Type:
a:\ktcinst 8
Y
ou see:
Warning.. Make sure that the card is not connected to a network. Press any key.
3. Press
any key
Y
ou see a similar message:
Succeeded Make sure that the card is not connected to a network. Succeeded Hard resetting KTCX.
.
(where 8
is the network address youve selected)
4. Recheck the I/O address if hard resetting fails.
Succeeded I/O Address: 220, Dual Port Address: D000:0000
Are these your intended address settings? [y/n]
5. Press Y for yes or N for no.
Y
ou see a similar message:
Boot code version: 1.3 8/20/96, Serial #: 20 (14) Main code version: 99.65 4/29/97
Succeeded Testing dual-port interface.
If
this test fails, contact your local Rockwell Automation sales representative
or distributor, or Rockwell Automation Technical Support at (440) 646-6800.
Waiting.. Soft resetting KTCX as network address 8. Press any key.
The utility initializes the network media access controller.
Usage: KTCINST NetworkAddress [IOaddress]
NetworkAddress= KTCX Network Address, in hex IOaddress = KTCX I/O base address (Default 220), in hex
In order to run the KTCX installation utility, you must specify the network address and the I/O address, if other than 220.
For a network address of 3 and I/O address of 260, type the following:
For a network address of 2 and I/O address of 220, (default) type the following:
c:\
Publication
1784-5.33 – September 1997
KTCINST 3 260
KTCINST 2
6.
Press any key Y
ou see a similar message:
Succeeded Soft resetting KTCX as network address 8.
.
If this test fails, make certain that you are not connected to a network. Contact your local Rockwell Automation sales representative or distributor, or Rockwell Automation Technical Support at (440) 646-6800.
Waiting.. Setting KTCX to online. Press any key.
The utility tests the card’s ability to connect to the network.
Publication
1784-5.33 – September 1997
Loading...