Rockwell Automation 1772-LS, 1772-LSP, D17726.8.6 User Manual

AllenBradley
1772 Mini PLC2/05 Processor
(Cat. No. 1772-LS, LSP)
Programming and Operations Manual
Important User Information
Because of the variety of uses for this product and because of the differences between solid state products and electromechanical products, those responsible for applying and using this product must satisfy themselves as to the acceptability of each application and use of this product. For more information, refer to publication SGI-1.1 (Safety Guidelines For The Application, Installation and Maintenance of Solid State Control).
The illustrations, charts, and layout examples shown in this manual are intended solely to illustrate the text of this manual. Because of the many variables and requirements associated with any particular installation, Allen-Bradley Company cannot assume responsibility or liability for actual use based upon the illustrative uses and applications.
No patent liability is assumed by Allen-Bradley Company with respect to use of information, circuits, equipment or software described in this text.
Reproduction of the contents of this manual, in whole or in part, without written permission of the Allen-Bradley Company is prohibited.
Throughout this manual we make notes to alert you to possible injury to people or damage to equipment under specific circumstances.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss.
Attention helps you:
- Identify a hazard
- Avoid the hazard
- recognize the consequences
Important: Identifies information that is critical for successful application and understanding of the product.

Summary of Changes

Summary of Changes
Summary of Changes
This release of the publication contains updated information:
For this updated information: See:
revised conventions chapter 1
clarification to switch settings for 1772LSP chapter 3
description of keys on keytop overlay (1770KCB) chapter 3
corrections to the discussion about automatic restart
corrections to the discussion about program control
addition of ZCL to glossary appendix B
new format all chapters and appendices
chapter 18
chapter 18
To help you find new information in this publication, we have included change bars as shows to the left of this paragraph.
i
Part
Hardware Overview
Industrial Terminal
(rear view)
Channel A PLC2 Family
1 Before You Begin 2 An Introduction to Programmable Con­trollers 3 Hardware
MiniPLC2/05
Program Panel Interconnect Cable
Interface
RUN
P R O C
FAULT
ON
MEMORY
STORE
ON
AB
INTFC
MINI PLC2/05
W/O Power Supply
P R O
P/S
C
ACTIVE
MEMORY
STORE
P/S
PARALLEL
AB
POWER
ON
OFF I.0A 125V
SLOW BLOW
120V
GND
MINI PLC2/05
W Power Supply
AC
RUN
FAULT
ON
ON
INTFC
L1
N
4 Memory Organization 5 Scan Theory 6 Relay-type Instructions 7 Program Control Instructions 8 Timers and Counters 9 Data Manipulation Instructions 10 Math Instructions 11 Data Transfer File Instructions 12 Sequencers 13 Jump
Instructions and
Subroutines 14 Block Transfer 15 Selectable Timed Interrupt
Part
Memory / Instruction Set
Data Table
Main Program
User Program
Subroutine
Message Storage Area
110
110 110
00
10
11
110
110
12
11
110
13
010
00
16 Program Editing
Part
Program Editing
( )
( P )
FOR
USE WITH PLC2 F
1982 ALLENBRADLEY 97534302
AMILY CAT
. NO. 1770 KCB
Part
Report Generation /
Application Programming Techniques
17 Report Generation 18 Programming Techniques
MS.0
198 MESSAGES SELECTED
MESSAGE CONTROL WORDS ( ENTER 5 DIGIT WORD ADDRESS)
ADDRESS 00200 – 00227
MESSAGE MESSAGE MESSAGE MESSAGE MESSAGE MES­SAGE CONTROL NUMBERS CONTROL NUMBERS CONTROL NUM­BERS WORDS WORDS WORDS
027 1–6
00200 010–017 00210 1010–1017 00220 2010–2017 00201 110–117 00211 1110–1117 00210 2110–2117 00202 210–217 00212 1210–1217 00203 310–317 00213 1310–1317 00204 410–417 00214 1410–1417 00205 510–517 00215 1510–1517 00206 610–617 00216 1610–1617
19 Program Troubleshooting
Part
Program Troubleshooting
hr.mn.sec.
OFF or ON 00:00'00.00
ON 00:00:00.00OFF 00:00:00.00ON 00:00:00.00
On Time
WORD ADDRESS: 0030
BIT NO.: 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
STATUS : 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
FORCE :
Off Time
On Time
Part
Appendices
A Number Systems B Glossary C Quick Reference Index
Key Sequences:
[SEARCH]
[Instruction key]
(Address)
[SEARCH]
[5][3]
[
] or []
[1] or [0]
This appendix contains defines terms and abbreviations that because of their complexity or recent introduction are not widely understood. These terms are:
AC Input Module
An I/O module that converts various AC signals originating at user devices to the appropriate logic level signal for use within the processor.
AC Output Module
An I/O module that converts the logic level signal of the processor to a usable output signal to control a user AC device.
[SEARCH]
[5][3]
[Address]
[
]or[]
357
8
3 x 82 = 192
1
= 40
5 x 8
0
= 7
7 x 8
192
40
7
239
10
23910 = 357
8

Table of Contents

Summary of Changes
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before You Begin 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
An Introduction to Programmable Controllers 21. . . . . . . . . .
Hardware 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Memory Organization 41. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scan Theory 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relaytype Instructions 61. . . . . . . . . . . . . . . . . . . . . . . . . . .
Program Control Instructions 71. . . . . . . . . . . . . . . . . . . . . .
Timers and Counters 81. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Manipulation Instructions 91. . . . . . . . . . . . . . . . . . . . .
i
Math Instructions 101. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ThreeDigit Expanded Chapter Summary 1021
Math
Math
101. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
104. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Transfer File Instructions 111. . . . . . . . . . . . . . . . . . . . . .
Types
of File Instructions
111. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sequencers 121. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comparison Chapter Summary 1222
with File Instructions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
121. . . . . . . . . . . . . . . . . . . . . . . .
Jump Instructions and Subroutines 131. . . . . . . . . . . . . . . . . .
Label Instruction 133. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Subroutine Area Instruction 134 Chapter Summary 137
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contentsii
Block Transfer 141. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selectable Timed Interrupt 151. . . . . . . . . . . . . . . . . . . . . . . . .
Program
Rules
Editing
for Editing Instructions
Report Generation 171. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming Techniques 181. . . . . . . . . . . . . . . . . . . . . . . . .
Program Troubleshooting 191. . . . . . . . . . . . . . . . . . . . . . . . .
Number Systems A1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Glossary B1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quick Reference C1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
161. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
161. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter
1
Before You Begin
Important: Read this chapter before you use the Mini-PLC-2/05 Processor (cat. no. 1772-LS,-LSP). It tells you how to use this manual.
Purpose
To the Reader
The Mini-PLC-2/05 processor is functionally similar to the Mini-PLC-2/15 processor. The Mini-PLC-2/05 processor has some additional features:
selectable timed interrupt memory protect switch fast I/O scan user selectable PROM/RAM backup 3K memory expanded mathematics
However, this processor does not have a mode select switch.
This manual is divided into six parts (Table 1.A).
Table 1.A
of the MiniPLC2/05 Processor Programming and Operations Manual
Parts
Part Title What's Covered
A Hardware Overview basic theory concerning the hardware features available when using
this processor
B Memory/Instruction Set describes the memory and informs you about the techniques you can
use when programming this processor
C Program Editing how to edit your program once it has been entered into the memory
D Report Generation/Application
Program Techniques
E Program Troubleshooting acts as a guide so you can minimize production down time
F Appendices contains tables and reference information useful when programming
how to do report generation and use special program techniques
your processor
This manual is procedure oriented. It tells you how to program and operate your Mini-PLC 2/05 Processor. If you need to learn more about the Mini-PLC-2/05 Processor, contact your local Allen-Bradley representative or distributor.
11
Chapter 1
Before You Begin
Vocabulary
Conventions
To make this manual easier to read and understand, we refer to the:
We Refer to the: As the:
MiniPLC2/05 Processor processor
Electrically Erasable Programmable Read Only Memory
Execute Auxiliary Function EAF
Complementary Metal Oxide Semiconductor Random Access Memory
Industrial Terminal (cat. no. 1770T3) 1770T3 terminal
EEPROM
CMOS RAM
A glossary at the back of this manual clarifies technical terms.
A word equals 16 bits; a byte equals 8 bits (1/2 a word).
Words in [ ] denote the key name or symbol. Words in < > denote information that you must provide - for example, an address value.
Word values are displayed in:
decimal (0-9) for timers, counters, and mathematics
010
00
Decimal
030
CTU
PR 555 AC 123
hexadecimal values (0-9, A-F) for gets and puts
010
010
011 012
GG
00
00
Hexadecimal
030
00FFF 123
Important: Numbers 0-9 are displayed the same in decimal and hexadecimal.
octal for byte values
0101 030
B
237
Octal
00
12
Chapter 1
Before You Begin
Keystroke directions are divided into two columns:
tells you what key or keys to press
Related Publications
tells you the processor’s action.
The publication index, publication SD 499, lists all available publications to further inform you about products related to the Mini-PLC-2/05 processor. Consult your local Allen-Bradley distributor or sales engineer for information regarding this publication or any needed information.
13
Chapter
2
An Introduction to Programmable Controllers
Chapter Objectives
Traditional Controls
In this chapter, you review general fundamentals common to our programmable controllers. This chapter:
describes what a programmable controller does describe the four major sections of a programmable controller describes how the four major sections of a programmable controller interact gives an example of a simple program
You are probably familiar with the traditional methods of machine control.
Relays
Machine
Sensing Devices
Sensing devices located on the machine detect changes in the machine’s condition. For instance, a part arriving at a work station contacts and closes a limit switch, the sensing device. As a result, an electrical circuit is completed and a signal is sent to the control panel.
Control Panel
Output Devices
11591
At the control panel, the electrical signal enters a bank of relays or other devices, such as solid state modules. Circuits within the control panel open or close causing additional electrical signals to be sent to output devices at the machine. For example, a relay energized by the limit switch closed by the arriving part may complete another circuit energizing the output device, a clamp, which secures the part at the work station.
21
Chapter 2
An Introduction to Programmable Controllers
Programmable Controls
Programmable controllers can perform many of the functions of traditional controls. Sensing devices report to the processors. The output devices at the machine operate the same as they would with traditional controls.
Programmable Controller
Conditons
Machine
Sensing Devices
Control Panel
Output Devices
Action Command
11592
The field wiring between the machine and the control panel provides electrical paths from the sensing devices to the control panel, and from the control panel to the output devices.
However, inside the control panel you’ll find a programmable controller rather than relays or discrete solid state devices. Instead of wiring those devices and relays together to produce a desired response, you simply tell your programmable controller by means of a program how you want it to respond to the same conditions.
The Four Major Sections
22
Programming is telling your programmable controller what you want it to do. A program is nothing more than a set of instructions you give the programmable controller telling it how to react to different conditions within the machine.
Let’s take a closer look at a typical programmable controller. It usually consists of four major sections:
processor input output power supply
Power Supply
Processor
(Decision Making)
Chapter 2
An Introduction to Programmable Controllers
Information
Input Output
Limit, Proximity, Pressure,
Temperature Switches
Push Buttons
Logic
BCD
Analog
Action
Solenoids
Motor Starters
Indicators
Alarms
Logic
BCD
Analog
Processor
The first section of a programmable controller is the processor. The processor might be called the “brains” of the programmable controller. It is divided into halves:
central processing unit memory
CPU
Processor Section
Data
Table
Program
Storage
Message Storage
Memory
Central Processing Unit
The central processor unit (CPU) makes decisions about what the processor does.
23
Chapter 2
An Introduction to Programmable Controllers
Memory
Memory serves three functions:
stores information in the data table that the CPU may need stores sets of instructions called a program stores messages
Data Table
The area of memory where data is controlled and used, is called the data table. The data table is divided into several smaller sections according to the type of information to be remembered. These smaller sections are called:
output image table input image table timer/counter storage
Data Table
Output Image Table
Input Image Table
Timer/Counter
Storage
At this time, we will only discuss the input and output image tables and program storage.
I/O Image Tables
The input image table reflects the status of the input terminals. The output image table reflects the status of bits controlled by the program.
Each image table is divided into a number of smaller units called bits. A bit is the smallest unit of memory. A bit is a tiny electronic circuit that the processor can turn on or off. Bits in the image table are associated with a particular I/O terminal in the input or output section.
When the processor detects a voltage at an input terminal, it records that information by turning the corresponding bit on. Likewise, when the processor detects no voltage at an input terminal, it records that information by turning the corresponding bit off. If, while executing your program, the CPU decides that a particular output terminal should be turned on or off, it records that decision by turning the corresponding bit on or off. In other words, each bit in the I/O image tables corresponds to the on or off status of an I/O terminal.
24
When people who work with personal computers talk about turning a bit on, they use the term “set.” For example - “The processor sets the bit” means “turns it on.” On the other hand, we use the term “reset” when we talk about turning the bit off - for example, “The processor reset the bit.”
Chapter 2
An Introduction to Programmable Controllers
Picture memory as a page that has been divided into many blocks. Each block represents one bit. Since each bit is either on or off, we could show the state of each bit by writing “on” or “off” in each block. However, there is an easier way. We can agree that the numeral one (1) means on and that the numeral zero (0) means off. We can show the status of each bit by writing 1 or 0 into the appropriate block. For example, you might hear expressions like, “The CPU responded by writing a one into the bit when the limit switch closed.” Of course, the processor didn’t really write a one into memory: it simply set the bit by turning it on.
When the I/O device is: The bit status is said to be:
on
on
off
1
set
off
0
reset
If you heard the expression, “The processor wrote a zero into that bit location.” What actually happened? If you said the processor merely reset the bit by turning it off, you’re right.
Program Storage
The other major area of memory, program storage, takes up the largest portion of memory. You’ll recall that this is where your instructions to the programmable controller are stored. You’ll also recall that this set of instructions is called a program.
Program Language
A program is made up of set of statements. Each statement does two things:
It describes an action to be taken. For instance, it might say, “Energize motor
starter number one.”
It describes the conditions that must exist in order for the action to take place.
Statement
Statement
Statement
Statement
Statement
Program
Statement
Program Storage Area
of Memory
ActionConditions
Program Statement
25
Chapter 2
An Introduction to Programmable Controllers
For example, you may want this action to take place: ”Whenever a certain limit switch closes.” So your condition could be: “If limit switch number two is closed,...” The action would be: “energize motor starter number one.” The entire statement is then: “If limit switch number two is closed, then energize motor starter number one.” Therefore, when limit switch number two at the machine closes, the programmable controller energizes the motor starter. If limit switch number two does not close, the programmable controller does not energize the motor starter. Thus, when limit switch number two opens, the programmable controller de-energizes the motor starter because that action is implied in the statement.
A program is made up of a number of similar statements. Typically, there is one statement for each output device on the machine. Each statement lists the conditions that must be met and then, states the action to be taken.
Instructions
Each condition is represented by a specific instruction; therefore, each action is represented by a specific instruction. These instructions tell the processor to do something with the information stored in the data table.
Some instructions tell the processor to read what’s written in the image table. When the processor is instructed to read from an image table, it examines a specific bit to see if a certain I/O device is on or off.
Other instructions tell the processor to write information into the image table. When the processor is instructed to write into the output image table, it writes a one or a zero into a specific bit. The corresponding output device will turn on or off as a result.
Input
The second section is the input, which serves four very important functions:
termination indication conditioning isolation
Termination
The input provides terminals for the field wiring coming from the sensing devices on the machine.
Indication
The input of most modules also provides a visual indication of the state of each input terminal with indicators. The indicator is on when there is a voltage applied to it terminal. It is off when there is no voltage applied to its terminal. Since the indicator reveals the status of its terminal, it’s usually called an input status indicator.
26
Chapter 2
An Introduction to Programmable Controllers
You should also notice another important characteristic of input indicators. They are only associated with terminals used for wiring sensing devices to the input section. The terminal that’s used to provide a ground for the sensing circuits has no indicator.
Conditioning
Another function of the input is signal conditioning. The electrical power used at the machine is usually not compatible with the signal power used within the programmable controller. Therefore, the input section receives the electrical signal from the machine and converts it to a voltage compatible with the programmable controller’s circuitry.
Isolation
The input isolates the machine circuitry from the programmable controller’s circuitry. Isolation helps protect the programmable controller’s circuitry from unwanted and dangerous voltage levels that may occur occasionally at the machine or in the plant’s wiring system.
Output
The third section is the output, which serves functions similar to those of the input image table:
termination indication conditioning isolation
Termination
The output provides terminals for the field wiring going to the output devices on the machine.
Indication
The output of most modules provides a visual indication of the selected state of each output device with indicators.
The output status indicator is on when the output device is energized. A common term applied to either input status indicators or output status indicators is I/O status indicators. I/O stands for either input or output.
In addition, the output section of modules with fuses has blown fuse indicators. When one of the fuses in the group opens, the blown fuse indicator lights.
Conditioning
The output conditions the programmable controller’s signals for the machine. That is, it converts the low-level dc voltages of the programmable controller to the type of electrical power used by the output devices at the machine.
27
Chapter 2
An Introduction to Programmable Controllers
Isolation
The output isolates the more sensitive electronic circuitry of the programmable controller from unwanted and dangerous voltages that occasionally occur at the machine or the plant’s wiring system. Some situations require additional external protection.
Power Supply
The fourth section is the power supply. It provides a low level dc voltage source for the electronic circuitry of the processor. It converts the higher level line voltages to low level logic voltages required by the processor’s electronic circuitry.
Control Sequence
Let’s look at a simple example to see the sequence of events that take place in controlling a machine with a programmable controller (Figure 2.1). Suppose you are making a part. The motor driven conveyor carries a unit to the work area. The limit switch detects wen the part arrives at the work area. When that happens, we want the conveyor to stop so you can work on the part.
Figure 2.1
Simplified Example of a Machine with a Programmable Controller
A
Controller
Input Output
Conveyor
Motor
Limit Switch
28
Conveyor
Unit
11594
Notice how the limit switch and motor are wired to the programmable controller. The limit switch, wired to terminal 02, is normally-closed. The arriving part will open the switch. Therefore, the program statement controlling the conveyor motor must read: “If there is voltage at input terminal 02 (limit switch), then energize output terminal 02 (conveyer motor).” The conveyor motor is wired to output terminal 02.
Chapter 2
An Introduction to Programmable Controllers
Important: Figure 2.1 is for demonstration purposes only. We do not show the associated wiring, a motor starter, or an emergency stop button.
Since the limit switch is wired normally-closed, the conveyor motor will run until the arriving part opens the switch. At that time, the condition for energizing the motor is not longer met. Therefore, the motor is de-energized.
When the condition is met, we say it is true. When the condition is not met, we say it is false. There may be more than one condition which must be met before an action is executed. When all the conditions are met, the action is executed and we say the statement is true. When one or more of the conditions are false, the action is not executed and we say the statement is false.
Scan Sequence
On power up, the processor begins the scan sequence (Figure 2.2) with the I/O scan. During the I/O scan, data from input modules is transferred to the input image table. Data from output image table is transferred to the output modules.
29
Chapter 2
An Introduction to Programmable Controllers
Figure 2.2
Sequence
Scan
I/O
Scan
Program
Scan
Output Image Table
Copy output image table status into output terminal circuits.
Input
Terminals
Copy input terminal status into input image table.
Program Statement
Output
Terminals
Input Image Table
210
Execute each program rung in sequence, writing into bits in the data table, including the output image table.
11597
Chapter 2
An Introduction to Programmable Controllers
Next, the processor scans the program. It does this statement by statement. Each statement is scanned in this way:
1. For each condition, the processor checks, or “reads,” the image table to see
if the condition has been met.
2. If the set of conditions has been met, the CPU writes a one into the bit
location in the output image table corresponding to the output terminal to be energized. On the other hand, if the set of conditions has not been met, the processor writes a zero into the bit location, indicating that the output terminal should not be energized.
Here is a simple explanation of the program. If input 02 is on, then turn on output 02. If input 02 is off, then turn off output 02. The program could be written this way:
If (condition) Then (action)
Input bit 02 is on Turn output bit 02 on
In this example, the processor reads a 1 at input bit location 02 and knows that the condition has been met. The processor then carries out the action instruction by writing a 1 into output bit location 02.
If there were more statements in the program, the processor would continue in this same manner scanning each statement and executing each instruction until it reached the end of the program. Statement by statement, the processor would write a 0 or a 1 into an output bit as directed by the program. Then, the processor would read specific image table bits to see if the proper set of conditions were met. After reading and executing all program statements, the processor scans the output image table and energizes or de-energizes output terminals. The processor then goes to the input modules to update the input image table.
Now the entire process is repeated. In fact, it’s repeated over and over again, many times a minute. Each time, the processor sets or resets output bits. Next, the processor senses the status of the input terminals. Finally, the processor scans the program and orders each output terminal on or off according to the state of its corresponding bit in the output image table.
When forcing is attempted, the processor’s I/O scan slows down to do the forcing (see chapter 19). When forcing is terminated, the processor automatically switches back to the faster I/O scan mode.
When this example begins, the processor is energizing output terminal 02 because output bit 02 is on.
When the part is conveyed to the work station, it turns the limit switch off. When the limit switch is off, there is no voltage at input terminal 02. The processor scans the input image table, senses no voltage, and responds by writing a zero into bit 02 in the input image table.
211
Chapter 2
An Introduction to Programmable Controllers
The processor scans the program. Our program states that if (conditions) input bit 02 is on, turn on output 02. If input bit 02 is off then output bit 02 is off. Since the alter condition is not true, the processor turns off output bit 02.
When the processor next scans the output image table, it sees the zero in output bit 02 and responds by de-energizing output terminal 02. The action causes the conveyor to stop.
Chapter Summary
We reviewed fundamentals common to A-B processors. The next chapter summarizes hardware features of the Mini-PLC-2/05 processors.
212
Hardware
Chapter
3
Chapter Objectives
Major Features
General Features
This chapter is a summary of the Mini-PLC-2/05 Processor Assembly and Installation Manual, publication 1772-6.6.6. In this chapter, you will read about:
major features general features hardware features optional features
A complete processor system consists of the following major components:
Mini-PLC-2/05 processor I/O chassis power supply I/O modules (up to 16 modules) industrial terminal (cat. no. 1770-T3)
The processor has the following features:
3K CMOS RAM memory 488 timers up to 2944 word capacity data table (23 blocks) ladder diagram and functional block instruction set four function arithmetic capabilities remote mode selection on-line programming block transfer capability 70 message storage (with the 1770-T3 terminal only) 198 message storage with the PLC-2 Family Report Generation Module
(catalog number 1770-RG)
data highway compatibility selectable timed interrupts expanded math capability
3-1
Chapter 3
Hardware
Hardware Features
MiniPLC2/05 Processor (cat. no. 1772LS)
The Mini-PLC-2/05 Processor (cat. no. 1772-LS) comes equipped with the following hardware features (Figure 3.1):
Figure 3.1 MiniPLC2/05
Processor (cat. no. 1772LS)
RUN
P R O C
FAULT
ON
MEMORY
STORE
ON
AB
INTFC
3-2
MINI PLC2/05
W/O Power Supply
10663I
Chapter 3
Hardware
Processor
Status Indicator
PROC RUN/FAULT: This red/green LED keeps you informed of the processor’s operating conditions.
Table 3.A
Indication
Status
Status
Indicator
PROC RUN/FAULT Green
P/S ACTIVE Green
If the
color is
Blinking Green
Red
Off
Off
MEMORY STORE (Switch)
Purpose: Enables you to backup or copy the program into the optional EEPROM Memory Module.
Then the Indication represents
The processor module is in the run mode and will begin operation. The EEPROM memory module (if present) is being programmed. There is a fault. Recycle power to reset the processor module. Either program mode of operation, run time error, memory error or a program error.
AC and DC is all right. There has been a power supply fault, overcurrent condition, improper input voltage or the module has been turned off.
Hardware: An optional EEPROM Memory Module (cat. no. 1772-MJ) can be installed in the module.
INTFC
(Interface socket)
Purpose: The 15 pin socket, labeled INTFC, provides communication between the processor and the programming terminal (1770-T3 or 1784-T50), the 1770-RG report generation module, the 1770-T11 hand held terminal, the 1772-KG interface module or 1771-KA communications interface module.
Processor Module and: Through: Catalog Number:
Industrial Terminal (cat. no. 1770T3) PLC2 Program Panel
Interconnect Cable
Industrial Terminal (cat. no. 1784T50) PLC2 Program Panel
Interconnect Cable
Data Highway Communication Modules Data Highway/Processor Cables 1771CN, CO, or CR
PLC2 Family Report Generation Module (cat. no. 1770RG)
PLC2 Program Panel Interconnect Cable
1772TC
1772TC or 1784CP2
1772TC (with external ground wire only)
The 1784-T50 also requires PLC-2 6200 programming software (cat. nos. 6201-PLC2, 6203-PLC2, 6211-PLC2, or 6213-PLC2).
Function: Provides interface to the above devices.
3-3
Chapter 3
Hardware
MiniPLC2/05 Processor (cat. no. 1772LSP)
The Mini-PLC-2/05 Processor (cat. no. 1772-LSP) contains all the hardware features of the LS processor and in addition contains the following (Figure 3.2):
Figure 3.2 MiniPLC2/05
RUN
P R O
P/S
C
FAULT
ACTIVE
MEMORY
STORE
P/S
PARALLEL
AB
INTFC
POWER
ON
OFF
I.0A 125V
SLOW BLOW
120V
AC L1
N
GND
MINI PLC2/05
W Power Supply
Processor with Power Supply (cat. no. 1772LSP)
ON
ON
10717I
3-4
Processor
Status Indicator
P/S ACTIVE: This green LED keeps you informed of the power supply section’s operating conditions (table 3.A).
P/S PARALLEL (socket)
Purpose: Enables paralleling connections between these two sockets on two power supply modules.
POWER (switch)
Purpose: This is on/off toggle switch lets you provide power to your processor.
If the switch is: Then you are:
On Supplying power to your processor module.
Off Not supplying power to your processor module.
Loading...
+ 259 hidden pages