Rockwell Automation 1771-ILB, D17716.5.91 User Manual

Isolated Analog Input Module Cat. No. 1771-IL Series B
User Manual

Important User Information

Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI–1.1, “Safety Guidelines For The Application, Installation and Maintenance of Solid State Control” (available from your local Allen-Bradley office) describes some important differences between solid-state equipment and electromechanical devices which should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or in part, without written permission of Allen–Bradley Company, Inc. is prohibited.
Throughout this manual we make notes to alert you to possible injury to people or damage to equipment under specific circumstances.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss.
Attention helps you:
Identify a hazard. Avoid the hazard. Recognize the consequences.
Important: Identifies information that is especially important for successful application and understanding of the product.
Important: We recommend you frequently backup your application programs on appropriate storage medium to avoid possible data loss.

Summary of Changes

Summary of Changes
Summary of Changes
This release of this publication contains new and revised information from the last release.
New Information
This manual covers the series B version of the 1771-IL isolated input module. The 1771-IL series B module has 16-bit resolution, improved sample time, and auto-calibration.
Revised Information
Many areas in this manual have been modified. Change bars (as shown to the right side of this paragraph) are used to indicate new or revised information. Every chapter in this manual has been revised. Please read carefully.
S-1
Using This Manual
Preface
Purpose of Manual
Audience
Vocabulary
Manual Organization
This manual shows you how to use your Isolated Analog Input module with an Allen-Bradley programmable controller. It helps you install, program, calibrate, and troubleshoot your module.
You must be able to program and operate an Allen-Bradley programmable controller to make efficient use of your input module. In particular, you must know how to program block transfers.
We assume that you know how to do this in this manual. If you do not, refer to the appropriate programming and operations manual for your programmable controller before you attempt to program this module.
In this manual, we refer to:
- the 1771-IL series B analog input module as the “input module,” or the “1771-IL/B”
- the Programmable Controller as the “controller”
This manual is divided into seven chapters. The following chart shows each chapter with its corresponding title and a brief overview of the topics covered in that chapter.
Chapter Title Topics Covered
1 Overview of the input module
2 Installing the module
3
4 Configuring your module
5 Module status and input data Reading data from the module 6 Calibrating your module Information on calibrating your module 7 Troubleshooting Troubleshooting guide for problem diagnosis
Communicating with your module
Description of the module including general and hardware features
Module power requirements, keying, chassis location Wiring of the field wiring arm
Reading data from your module Sample programs
Hardware and software configuration Input range selection Data format
P-1
Preface
mb
ck
Using This Manual
Appendix Title Topics Covered
A Specifications B Configuration Example
Related Products
Product Compatibility
C Data Formats
D
Block transfer with Mini-PLC-2 and PLC-2/20 processors
Information on BCD, 2s complement binary, signed magnitude
How to use GET-GET instructions
You can install your input module in any system that uses Allen-Bradley programmable controllers with block transfer capability and the 1771 I/O structure.
Contact your nearest Allen-Bradley office for more information about your programmable controllers.
The 1771-IL series B module can be used with any 1771 I/O chassis. Communication between the analog module and the processor is bidirectional; the processor block-transfers output data through the output image table to the module and block-transfers input data from the module through the input image table. The module also requires an area in the data table to store the read block and write block. I/O image table use is an important factor in module placement and addressing selection. The module’s data table use is listed in Table P.A.
P-2
T
able P
.A
Compatibility
Catalog Number
1771-IL/B 8 8 15 37 Y Y Y A, B
A
= Compatible with 1771-A1, -A2, -A4 B = Compatible with 1771-A1B, -A2B, -A3B, -A4B Y = Compatible without restriction.
and Use of Data T
Use of Data Table Compatibility
Input
Bits
Output
Image
Bits
Image
able
Read-
Blocks
Words
Write­Blo
Words
Addressing
1/2-Slot 1-Slot 2-slot
Chassis
Chassis
Series
Preface
Using This Manual
You can place your input module in any I/O module slot of the I/O chassis. You can put two input modules in the same module group. You can put an input and an output module in the same module group.
Do not put the module in the same module group as a discrete high density module unless using 1- or 2-slot addressing. Avoid placing output modules close to ac modules or high voltage dc modules.
Related Publications
For a list of publications with information on Allen-Bradley programmable controller products, consult our publication index (SD499).
P-3
T
able of Contents
Overview of the Input Module
Installing the Input Module
Chapter 1
Chapter Objectives 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Descriptions 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Features 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How Analog Modules Communicate with Programmable Controllers 1-2.
Accuracy 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter Summary 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2
Chapter Objectives 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before You Install Your Input Module 2-1. . . . . . . . . . . . . . . . . . . . . . . . . .
Electrostatic Damage 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Requirements 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Location in the I/O Chassis 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Keying 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Your Input Module 2-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Grounding 2-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Voltage/Current Selection Jumpers 2-6. . . . . . . . . . . . . . . . . . . .
Module Installation 2-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Indicator Lights 2-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter Summary 2-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communicating With Your Module
Configuring Your Module
Chapter 3
Chapter Objectives 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Block Transfer Programming 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLC-2 Programming 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLC-3 Programming 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLC-5 Programming 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Scan Time 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter Summary 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 4
Chapter Objectives 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Your Input Module 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input Range Selection 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Block Transfer Write Format 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Format 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Digital Filtering 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Real Time Sampling 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scaling 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Default Configuration 4-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter Summary 4-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I
T
able of Contents
Module Status and Input Data
Calibrating Your Module
Troubleshooting
Specifications
Chapter 5
Chapter Objectives 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reading Data From Your Module 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter Summary 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 6
Chapter Objective 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tools and Equipment 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Calibrating your Input Module 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About Auto-calibration 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Performing Auto-calibration 6-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter Summary 6-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 7
Chapter Objective 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostics Reported by the Module 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . .
Status Reported by the Module 7-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix A
Specifications A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration Example
Data Formats
Block Transfer (Mini–PLC–2 and PLC–2/20 Processors)
Appendix B
Sample Configuration of the Analog Input Module B-1. . . . . . . . . . . . . . . .
Appendix C
4–Digit Binary Coded Decimal (BCD) C-1. . . . . . . . . . . . . . . . . . . . . . . . . .
Signed–magnitude Binary C-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Two’s Complement Binary C-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix D
Multiple GET Instructions–Mini–PLC–2 and PLC–2/20 Processors D-1. . .
Setting the Block Length (Multiple GET Instructions only) D-3. . . . . . . . . .
II
Chapter
Overview of the Input Module
1
Chapter
Objectives

Module Descriptions

This chapter gives you information on:
features of the module how the input module communicates with programmable
controllers
The input module is an intelligent block transfer module that interfaces analog input signals with any Allen-Bradley programmable controllers that have block transfer capability. Block transfer programming moves input data words from the module’s memory to a designated area in the processor data table in a single scan. It also moves configuration words from the processor data table to module memory.
The input module is a single-slot module that requires no external power supply. After scanning the analog inputs, the input data is converted to a specified data type in a digital format to be transferred to the processor’s data table on request. The block transfer mode is disabled until this input scan is complete. Consequently, the minimum interval between block transfer reads is the same as the total input update time for each analog input module.

Features

This module senses up to eight analog signals at its inputs and converts them to a proportional four-digit BCD or 16-bit binary value while providing channel to channel and channel to ground isolation of +1000V. You can select from five voltage or three current input ranges. Each input is software selectable on a per channel basis.
This module’s features include:
Eight software configurable differential inputs User program selectable input ranges on a per channel basis (see
Table 1.A) Selectable real-time sampling Selectable scaling to engineering units Selectable digital filtering +1000V input isolation, channel-to-channel, channel-to-ground
Selectable high and low input alarms
1-1
Chapter 1
Overview of the Input Module
T
able 1.A
Program
Selectable Input Ranges
Voltage Ranges Current Ranges
1 to 5V dc 4 to 20mA 0 to 5V dc 0 to 20mA
-5 to +5V dc -20 to +20mA
-10 to +10V dc 0 to 10V dc

How Analog Modules Communicate with Programmable Controllers

The processor transfers data to the module (block transfer write, BTW) and from the module (block transfer read, BTR) using BTW and BTR instructions in your ladder diagram program. These instructions let the processor obtain input values and status from the module, and let you establish the module’s mode of operation (Figure 1.1).
1. The processor transfers your configuration data, and alarm values to
the module via a block transfer write instruction.
2. External devices generate analog signals that are transmitted to the
module.
Figure 1.1 Communication
+
2
-
Between Processor and Module
3
I/O Chassis
Backplane
4
56
1-2
Input Module
Cat. No. 1771-IL/B
1
Programmable Controller
11845-I
Chapter 1
Overview of the Input Module
3. The module converts analog signals into binary or BCD format, and
stores these values until the processor requests their transfer.
4. When instructed by your ladder program, the processor performs a
read block transfer of the values and stores them in a data table.
5. The processor and module determine that the transfer was made
without error, and that input values are within specified range.
6. Your ladder program can use and/or move the data (if valid) before it
is written over by the transfer of new data in a subsequent transfer.
7. Your ladder program should allow write block transfers to the module
only when enabled by operator intervention or at power-up.

Accuracy

Chapter Summary

The accuracy of your input module is described in Appendix A.
In this chapter you read about the functional aspects of the input module and how the module communicates with the programmable controller.
1-3
Chapter
Installing the Input Module
2
Chapter
Objectives

Before You Install Your Input Module

This chapter gives you information on:
calculating the chassis power requirement choosing the module’s location in the I/O chassis configuring your module voltage/current selection jumpers keying a chassis slot for your module wiring the input module’s field wiring arm installing the input module
Before installing your input module in the I/O chassis you should:
You need to: As described under:
Calculate the power requirements of all modules in each chassis.
Determine where to place the module in the I/O chassis.
Select the input for each channel. Key the backplane connector in the I/O chassis. Module Keying, page 2-4. Make connections to the wiring arm.
Power Requirements, page 2-2.
Module Location in the I/O Chassis, page 2-2. Setting the Voltage/Current Selection Jumpers,
page 2-2.
Wiring Your Input Module, page 2-5, and Grounding, page 2-7

Electrostatic Damage

Electrostatic discharge can damage semiconductor devices inside this module if you touch backplane connector pins. Guard against electrostatic damage by observing the following precautions:
ATTENTION: Electrostatic discharge can degrade performance or cause permanent damage. Handle the module as stated below.
Wear an approved wrist strap grounding device, or touch a grounded
object to rid yourself of electrostatic charge before handling the module.
Handle the module from the front, away from the backplane connector.
Do not touch backplane connector pins.
Keep the module in its static-shield bag when not in use.
2-1
Chapter 2
Installing the Input Module

Power Requirements

Module Location in the I/O Chassis

Your module receives its power through the 1771 I/O power supply. The Isolated Analog input module requires 1.2A at 5V from the power supply.
Add this current to the requirements of all other modules in the I/O chassis to prevent overloading the chassis backplane and/or backplane power supply.
Place your module in any I/O module slot of the I/O chassis except for the extreme left slot. This slot is reserved for programmable controller processors or adapter modules.
Group your modules to minimize adverse affects from radiated electrical noise and heat. We recommend the following.
Group analog input and low voltage dc modules away from ac modules
or high voltage dc modules to minimize electrical noise interference.
Do not place this module in the same I/O group with a discrete
high-density I/O module when using 2-slot addressing. This module uses a byte in both the input and output image tables for block transfer.

Setting the Voltage/Current Selection Jumpers

After determining the module’s location in the I/O chassis, connect the wiring arm to the pivot bar at the module’s location.
The Isolated Analog Input Module (1771-IL/B) is shipped with each channel set for voltage mode. If a milliamp input is desired, you must set a jumper on the functional analog block (FAB) for that particular channel.
To set the selection jumpers for your desired inputs, proceed as follows:
1. Remove the module’s left hand cover plate (the one without
the labels).
2. Locate the selection plugs (Figure 2.1).
3. Position the jumpers as shown in Figure 2.1 for your
particular module.
4. Reassemble the module after you have finished checking and/or
setting the selection plugs.
2-2
Functional Analog Block
Figure 2.1 Configuration
Chapter 2
Installing the Input Module
Jumper Settings for 1771-IL/B Inputs
Voltage/Current
Jumper
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Jumper in
Current position.
Edge View (enlarged)
Jumper in
Voltage position.
Side V
Channel 6
Channel 7
Channel 8
iew
11847-I
2-3
Chapter 2
Installing the Input Module

Installing the Analog Module

locking-bar pins
front of chassis
12453-I
To install your module in an I/O chassis:
1. First, turn off power to the I/O chassis:
ATTENTION: Remove power from the 1771 I/O chassis
backplane and disconnect the cable from the module before removing or installing an I/O module.
Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.
Failure to remove power from the backplane could cause module damage, degradation of performance, or injury.
2. Lift the locking latch holding the module into the chassis. (On chassis
equipped with a chassis locking bar, pull the locking-bar pins to release the locking bar and swing it up.)
3. Position the keying bands (Figure 2.2) in the backplane connectors to
correspond to the key slots on the module. This prevents you from inserting the wrong module in this slot. This analog module uses:
between 10 and 12 between 32 and 34
ATTENTION: Observe the following precautions when inserting or removing keys:
insert or remove keys with your fingers make sure that key placement is correct
Incorrect keying or the use of a tool can result in damage to the backplane connector and possible system faults.
You can change the position of these bands if subsequent system design and rewiring makes insertion of a different type of module necessary. Use needlenose pliers to insert or remove keying bands.
2-4
Keying Band Location
Between 10 and 12 Between 32 and 34
Figure 2.2 Keying
Positions
I/O chassis
Keying Bands
ATTENTION: Insert or remove
keying bands with your fingers.
Chapter 2
Installing the Input Module

Connecting Wiring to Your Input Module

Upper Connector
11022-I
4. Place the module in the plastic tracks on the top and bottom of the
slot that guides the module into position.
5. Do not force the module into its backplane connector. Apply firm
even pressure on the module until it is firmly seated in the chassis. Note: The chassis locking bar will not close if all modules are not seated properly.
6. Snap the chassis locking bar (or locking latch on earlier chassis) over
the top of the module to secure it. Make sure the locking pins on the locking bar are fully engaged.
7. Connect the wiring to the module as explained under “Connecting
Wiring” below.
Connect your input devices to the cat. no. 1771-WF wiring arm shipped with the module. Attach the wiring arm to the pivot bar at the bottom of the I/O chassis. It pivots upward and connects with the module so you can install or remove the module without disconnecting the wires.
Connect inputs to the 1771-IL/B module as shown in Figure 2.3. This module is shipped from the factory configured for voltage inputs but can be configured for any combination of current and voltage inputs. If you want to change the configuration, refer to “Setting the Voltage/Current Selection Jumpers” as explained earlier in this chapter.
Important: The module configuration jumpers must be set for either voltage or current before inserting the module into the I/O chassis.
2-5
Chapter 2
Installing the Input Module
Figure 2.3 Wiring
Connections for the Isolated Analog Input Module (1771-IL/B)
18
17
16
15 14 13
12
11 10
9 8
7 6
5 4
3 2
1
Ground
Ground
+
Analog Source
+
Analog Source
18 17
16 15
14 13
12 11
10
9
8
7
6 5
4 3
2
1
Channel 1 Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
NOTE: The 1771-IL/B module does not supply loop power for loop
powered analog sources (transmitters, transducers, etc.). Loop power must be supplied by the user.
2-6
Field Wiring Arm Cat. No. 1771-WF
11846-I
Chapter 2
Installing the Input Module

Grounding

Remove a length of cable jacket from the Belden 8761 cable.
Belden
8761 Cable
When using shielded cable wire, ground the foil shield and drain wire only at one end of the cable. We recommend that you wrap the foil shield and drain wire together and connect them to a chassis mounting bolt (Figure 2.4). At the opposite end of the cable, tape exposed shield and drain wire with electrical tape to insulate it from electrical contact.
Figure 2.4 Cable
Grounding
Pull the foil shield and bare drain wire from the insulated wires.
Bare
drain
wire
Insulated wires
Foil shield
Twist the foil shield and drain wire together to form a single strand.
Attach a ground lug.
20104
Chassis Ground Single-point Grounding
When you connect grounding conductors to the I/O chassis grounding stud, place a star washer under the first lug, then place a nut with captive lock washer on top of each ground lug.
Ground Lug
Nut
Grounding Stud
Star Washer
I/O Chassis Side Plate
1
Use
the cup washer if crimp-on lugs are not used.
Ground Lug
Nut and Captive Washer
1
19480
19923
#10 Thread-forming screw
External-tooth Washers
Refer to Wiring and Grounding Guidelines, publication 1770-4.1, for additional information.
2-7
Chapter 2
Installing the Input Module

Indicator Lights

The front panel of the input module contains a green RUN and a red FLT (fault) indicator (Figure 2.5). At powerup, an initial module self-check occurs. If there is no fault, the red indicator turns off. The green indicator will blink until the processor completes a successful write block transfer to the module. Upon completion of a block transfer write (BTW), the green RUN indicator will be on and the red FLT indicator will be off. If a fault is found initially or occurs later, the red FLT indicator lights. Possible module fault causes and corrective actions are discussed in Chapter 7, Troubleshooting.
Figure 2.5 Diagnostic
Indicators
ISOLATED
ANALOG INPUT
RUN
FLT
10528-I

Chapter Summary

In this chapter you learned how to install your input module in an existing programmable controller system and how to wire to the field wiring arm.
2-8
Loading...
+ 44 hidden pages