Because of the variety of uses for the products described in this
publication, those responsible for the application and use of these
products must satisfy themselves that all necessary steps have been
taken to assure that each application and use meets all performance
and safety requirements, including any applicable laws, regulations,
codes and standards. In no event will Rockwell Automation be
responsible or liable for indirect or consequential damage resulting
from the use or application of these products.
Any illustrations, charts, sample programs, and layout examples
shown in this publication are intended solely for purposes of
example. Since there are many variables and requirements associated
with any particular installation, Rockwell Automation does not assume
responsibility or liability (to include intellectual property liability) for
actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation and Maintenance of Solid-State Control
(available from your local Rockwell Automation office), describes
some important differences between solid-state equipment and
electromechanical devices that should be taken into consideration
when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole
or part, without written permission of Rockwell Automation, is
prohibited.
Throughout this publication, notes may be used to make you aware of
safety considerations. The following annotations and their
accompanying statements help you to identify a potential hazard,
avoid a potential hazard, and recognize the consequences of a
potential hazard:
WARNING
Identifies information about practices or
circumstances that can cause an explosion in a
hazardous environment, which may lead to personal
injury or death, property damage, or economic loss.
!
ATTENTION
Identifies information about practices or
circumstances that can lead to personal injury or
death, property damage, or economic loss.
!
IMPORTANT
Identifies information that is critical for successful
application and understanding of the product.
Allen-Bradley, MicroLogix, RSLogix, and RSLinx are trademarks of Rockwell Automation.
Overview
Table of Contents
Preface
Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . P-1
How to Use This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Read this preface to familiarize yourself with the rest of the manual.
This preface covers the following topics:
• who should use this manual
• how to use this manual
• related publications
• conventions used in this manual
• Rockwell Automation support
Who Should Use This
Manual
How to Use This Manual
Use this manual if you are responsible for designing, installing,
programming, or troubleshooting control systems that use
MicroLogix 1200 controllers and 1762 Expansion I/O.
As much as possible, we organized this manual to explain, in a
task-by-task manner, how to install, configure, program, operate and
troubleshoot a control system using the 1762-IR4.
Manual Contents
If you want...See
An overview of the RTD/resistance input moduleChapter 1
Installation and wiring guidelinesChapter 2
Module addressing, configuration and status informationChapter 3
Information on module diagnostics and troubleshootingChapter 4
Specifications for the moduleAppendix A
Information on programming the module using MicroLogix 1200 and
RSLogix 500
Information on understanding two’s complement binary numbersAppendix C
Appendix B
Definitions of terms used in this manualGlossary
1Publication 1762-UM003A-EN-P - February 2003
2 Preface
Related Documentation
The table below provides a listing of publications that contain
important information about MicroLogix 1200 systems.
ForRead this documentDocument number
A user manual containing information on how to install,
use and program your MicroLogix 1200 controller
An overview of the MicroLogix 1200 System, including
1762 Expansion I/O.
In-depth information on programming and using
MicroLogix 1200 controllers.
In-depth information on grounding and wiring
Allen-Bradley programmable controllers.
If you would like a manual, you can:
• download a free electronic version from the internet at
• purchase a printed manual by:
MicroLogix™ 1200 User Manual1762-UM001
MicroLogix™ 1200 Technical Data1762-TD001
MicroLogix 1200 Instruction Set Reference Manual1762-RM001
Allen-Bradley Programmable Controller Grounding and
Wiring Guidelines
1770-4.1
www.theautomationbookstore.com
– contacting your local distributor or Rockwell Automation
representative
– visiting www.theautomationbookstore.com and placing your
order
– calling 1.800.963.9548 (USA/Canada) or 001.330.725.1574
(Outside USA/Canada)
Conventions Used in This
Manual
Publication 1762-UM003A-EN-P - February 2003
The following conventions are used throughout this manual:
• Bulleted lists (like this one) provide information not procedural
steps.
• Numbered lists provide sequential steps or hierarchical
information.
• Italic type is used for emphasis.
Preface 3
Rockwell Automation
Support
Rockwell Automation tests all of our products to ensure that they are
fully operational when shipped from the manufacturing facility.
If you are experiencing installation or startup problems, please review
the troubleshooting information contained in this publication first. If
you need technical assistance to get your module up and running,
please contact Customer Support (see the table below); our trained
technical specialists are available to help.
If the product is not functioning and needs to be returned, contact
your distributor. You must provide a Customer Support case number
to your distributor in order to complete the return process.
PhoneUnited
States/Canada
Outside United
States/Canada
InternetWorldwideGo to http://support.rockwellautomation.com/
1.440.646.5800
You can access the phone number for your country via
the Internet:
1. Go to http://support.rockwellautomation.com/
2. Under Contacting Customer Support and Other
Countries, click on Click here
Your Questions or Comments on the Manual
If you find a problem with this manual, please notify us. If you have
any suggestions for how this manual could be made more useful to
you, please contact us at the address below:
Rockwell Automation
Automation Control and Information Group
Technical Communication, Dept. A602V
P.O. Box 2086
Milwaukee, WI 53201-2086
Publication 1762-UM003A-EN-P - February 2003
4 Preface
Publication 1762-UM003A-EN-P - February 2003
Chapter
1
Overview
This chapter describes the four-channel 1762-IR4 RTD/resistance Input
module and explains how the controller reads resistance temperature
detector (RTD) or direct resistance-initiated analog input data from the
module. Included is:
• a general description of hardware features
• an overview of module and system operation
• compatibility
General Description
The 1762-IR4 module supports RTD and direct resistance signal
measurement applications that require up to four channels. The
module digitally converts analog data and then stores the converted
data in its image table.
The module supports connections from any combination of up to four
input devices. Each channel is individually configurable via software
for 2- or 3-wire RTD or direct resistance input devices. Channels are
compatible with 4-wire sensors, but the fourth sense wire is not used.
Two programmable excitation current values (0.5mA and 1.0mA) are
provided, to limit RTD self-heating. When configured for RTD inputs,
the module can convert the RTD readings into linearized digital
temperature readings in °C or °F. When configured for resistance
analog inputs, the module can convert voltages into linearized
resistance values in ohms. The module assumes that the direct
resistance input signal is linear prior to input to the module.
Each channel provides open-circuit (all wires), short-circuit (excitation
and return wires only), and over- and under-range detection and
indication.
IMPORTANT
1Publication 1762-UM003A-EN-P - February 2003
The module accepts input from RTDs with up to 3
wires. If your application requires a 4-wire RTD, one
of the two lead compensation wires is not used, and
the RTD is treated like a 3-wire sensor. The third wire
provides lead wire compensation. See Chapter 2,
Installation and Wiring, for more information.
1-2 Overview
The following data formats are supported by the module.:
• raw/proportional
• engineering units x 1
• engineering units x 10
• scaled-for-PID
• percent full scale
Available filter frequencies are:
• 10 Hz
• 50 Hz
• 60 Hz
• 250 Hz
• 500 Hz
• 1 kHz
The module uses six input words for data and status bits and five
configuration words. Module configuration is stored in the controller
memory. Normally configuration is done via the controller’s
programming software. In addition, some controllers support
configuration via the user program. Refer to your controller manual
for additional information. See Chapter 3, Module Data, Status, and Channel Configuration, for details on module configuration.
RTD Compatibility
An RTD consists of a temperature-sensing element connected by two,
three, or four wires that provide input to the module. The following
table lists the RTD types that you can use with the module, including
their temperature range, effective resolution, and repeatability for both
excitation currents, 0.5 and 1.0 mA.
Publication 1762-UM003A-EN-P - February 2003
Table 1.1 RTD Specifications
Overview 1-3
RTD Type
(1)
Temperature Range Using
0.5 mA Excitation
Temperature Range Using
1.0 mA Excitation
Maximum
Scaled
Resolution
Maximum
Scaled
Repeatability
Copper 42610ΩNot allowed-100 to 260°C (-148 to 500°F)0.1°C (0.1°F)±0.2°C (±0.4°F)
(2)
Nickel 618
120Ω-100 to 260°C (-148 to 500°F)-100 to 260°C (-148 to 500°F)0.1°C (0.1°F)±0.1°C (±0.2°F)
Nickel 672120Ω-80 to 260°C (-112 to 500°F)-80 to 260°C (-112 to 500°F)0.1°C (0.1°F)±0.1°C (±0.2°F)
Nickel-Iron
604Ω-100 to 200°C (-148 to 392°F)-100 to +200°C (-148 to 392°F)0.1°C (0.1°F)±0.1°C (±0.2°F)
518
Platinum 385100Ω-200 to 850°C (-328 to 1562°F)-200 to 850°C (-328 to 1562°F)0.1°C (0.1°F)±0.2°C (±0.4°F)
200Ω-200 to 850°C (-328 to 1562°F)-200 to 850°C (-328 to 1562°F)0.1°C (0.1°F)±0.2°C (±0.4°F)
500Ω-200 to 850°C (-328 to 1562°F)-200 to 850°C (-328 to 1562°F)0.1 °C (0.1 °F)±0.2°C (±0.4°F)
1000Ω-200 to 850°C (-328 to 1562°F)Not Allowed0.1°C (0.1°F)±0.2°C (±0.4°F)
Platinum 3916100Ω-200C to 630°C (-328 to
-200 to 630°C (-328 to 1166°F)0.1°C (0.1°F)±0.2°C (±0.4°F)
1166°F)
200Ω-200 to 630°C (-328 to 1166°F)-200 to 630°C (-328 to 1166°F)0.1°C (0.1°F)±0.2°C (±0.4°F)
500Ω-200 to 630°C (-328 to 1166°F)-200 to 630°C (-328 to 1166°F)0.1°C (0.1°F)±0.2°C (±0.4°F)
1000Ω-200 to 630°C (-328 to 1166°F)Not Allowed0.1°C (0.1°F)±0.2°C (±0.4°F)
(1) Digits following the RTD type represent the temperature coefficient of resistance (α) , which is defined as the resistance change per ohm per °C. For instance,
platinum 385 refers to a platinum RTD with α = 0.00385 ohm/ohm -°C, or simply 0.00385/°C.
(2) Actual value at 0°C is 100
Ω per DIN standard.
Publication 1762-UM003A-EN-P - February 2003
1-4 Overview
The tables below provide specifications for RTD accuracy and
temperature drift.
For example, when you are using any platinum (385)
RTDs with 0.5 mA excitation current, the module’s
accuracy is:
• ±0.5°C (0.9°F) after you apply power to the
module or perform an autocalibration at 25°C
(77°F) ambient, with module operating
temperature at 25°C (77°F).
• ±[0.5°C (0.9°F) ± DT x 0.026 deg./°C
(0.026 deg./°F)] after you apply power to the
module or perform an autocalibration at 25°C
(77°F) ambient, with module operating
temperature between 0 (32°F) and 55°C (131°F).
DT is the temperature difference between the
actual module operating temperature and 25°C
(77°F). The value 0.026 deg./°C (0.026 deg./°F) is
the temperature drift shown in the table above.
• ±0.9°C after you apply power to the module or
perform an autocalibration at 55°C (131°F)
ambient, with module operating temperature at
55°C (131°F).
Publication 1762-UM003A-EN-P - February 2003
Table 1.3 Resistance Device Specifications
Overview 1-5
Resistance Device Compatibility
The following table lists the specifications for the resistance devices
that you can use with the module.
Resistance
Device
Ty pe
150Ω0 to 150Ω0 to 150Ω±0.15Ω±0.007Ω/°C
500Ω0 to 500Ω0 to 500Ω±0.5Ω±0.023Ω/°C
1000Ω0 to 1000Ω0 to 1000Ω±1.0Ω±0.043Ω/°C
3000Ω0 to 3000ΩNot allowed±1.5Ω±0.072Ω/°C
(1) Accuracy values are based on the assumption that the module has been calibrated to the temperature range of 0 to 55°C (32 to 131°F).
Resistance Range
(0.5 mA Excitation)
Resistance Range
(1.0 mA Excitation)
Accuracy
(1)
Temperature DriftResolutionRepeatability
0.01Ω±0.04Ω
(±0.012Ω/°F)
0.1Ω±0.2Ω
(±0.041Ω/°F)
0.1Ω±0.2Ω
(±0.077Ω/°F)
0.1Ω±0.2Ω
(±0.130Ω/°F)
Publication 1762-UM003A-EN-P - February 2003
1-6 Overview
Hardware Features
The RTD/resistance module provides connections for four 3-wire
inputs for any combination of RTD and resistance input devices.
Channels are wired as differential inputs. The illustration below shows
the hardware features of the module.
2power diagnostic LED
3module door with terminal identification label
4bus connector with male pins
5bus connector cover
6flat ribbon cable with bus connector (female)
7terminal block
8DIN rail latch
9pull loop
General Diagnostic Features
A single diagnostic LED helps you identify the source of problems that
may occur during power-up or during normal channel operation. The
LED indicates both status and power. See Chapter 4, Diagnostics and Troubleshooting, for details on power-up and channel diagnostics.
Publication 1762-UM003A-EN-P - February 2003
Overview 1-7
System Overview
The modules communicate to the local controller or communication
adapter through the 1762 bus interface. The modules also receive 5
and 24V dc power through the bus interface.
System Operation
At power-up, the module performs a check of its internal circuits,
memory, and basic functions. During this time, the module status LED
remains off. If no faults are found during power-up diagnostics, the
module status LED is turned on.
After power-up checks are complete, the module waits for valid
channel configuration data. If an invalid configuration is detected, the
module generates a configuration error. Once a channel is properly
configured and enabled, the module continuously converts the RTD
or resistance input to a value within the range selected for that
channel.
Each time the module reads an input channel, it tests the data for a
fault (over- or under-range, short-circuit, or open-circuit condition). If
it detects a fault, the module sets a unique bit in the channel status
word. See Input Data File on page 3-3.
Using the module image table, the controller reads the two’s
compliment binary converted input data from the module. This
typically occurs at the end of the program scan or when commanded
by the control program. If the controller and the module determine
that the data transfer has been made without error, the data is used in
the control program.
Publication 1762-UM003A-EN-P - February 2003
1-8 Overview
Input
EXC
Module Operation
As shown in the block diagram below, each input channel of the
module consists of an RTD/resistance connection that accepts
excitation current; a sense connection that detects lead wire
resistance; and a return connection. The signals are multiplexed to an
A/D converter that reads the RTD or resistance value and the lead
wire resistance.
Current
Source
A/D
Converter
MCU
ASIC
SENSE
RTN
Multiplexer
Te rm in al
+15V
+5V
A-GND
-15V
Opto-coupler
BUS
+24V dc
Isolation
Power Supply
S-GND
From the readings taken by the converter, the module returns an
accurate temperature or resistance to the controller user program
through the microprocessor. The module uses two bidirectional serial
ports for communication, each using an optocoupler for isolation. A
third optocoupler is used to reset the microprocessor if the module
detects a loss of communication.
Module Field Calibration
The input module performs autocalibration when a channel is initially
enabled. Autocalibration compensates for offset and gain drift of the
A/D converter caused by temperature change within the module. An
internal, high-precision, low drift voltage and system ground reference
is used for this purpose. In addition, you can program the module to
perform a calibration cycle once every 5 minutes. See Selecting
Enable/Disable Cyclic Autocalibration (Word 4, Bit 0) on page 3-20 for
information on configuring the module to perform periodic
calibration.
Publication 1762-UM003A-EN-P - February 2003
Installation and Wiring
This chapter tells you how to:
• determine the power requirements for the modules
• avoid electrostatic damage
• install the module
• wire the module’s terminal block
• wire input devices
Chapter
2
Compliance to European
Union Directives
This product is approved for installation within the European Union
and EEA regions. It has been designed and tested to meet the
following directives.
EMC Directive
The 1762-IR4 module is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in
whole or in part, documented in a technical construction file:
• EN 50081-2
EMC – Generic Emission Standard, Part 2 - Industrial
Environment
• EN 50082-2
EMC – Generic Immunity Standard, Part 2 - Industrial
Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low
Voltage, by applying the safety requirements of EN 61131-2
Programmable Controllers, Part 2 – Equipment Requirements and
Tests.
1Publication 1762-UM003A-EN-P - February 2003
2-2 Installation and Wiring
For specific information required by EN61131-2, see the appropriate
sections in this publication, as well as the following Allen-Bradley
publications:
• Industrial Automation, Wiring and Grounding Guidelines for
Noise Immunity, publication 1770-4.1
• Automation Systems Catalog, publication B113
Power Requirements
General Considerations
The module receives +5V dc and 24V dc power from the system
power supply through the bus interface.
The maximum current drawn by the module is shown in the table
below.
5V dc24V dc
40 mA50 mA
TIP
When you configure your system, ensure that the
total current draw of all the modules does not
exceed the maximum current output of the system
power supply.
1762 I/O is suitable for use in an industrial environment when
installed in accordance with these instructions. Specifically, this
equipment is intended for use in clean, dry environments (Pollution
(1)
degree 2
) and to circuits not exceeding Over Voltage Category II
(IEC 60664-1).
(3)
(2)
Publication 1762-UM003A-EN-P - February 2003
(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that
occasionally a temporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient
voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)
designations.
Installation and Wiring 2-3
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, D or non-hazardous locations only. The following WARNING
statement applies to use in hazardous locations.
WARNING
!
EXPLOSION HAZARD
• Substitution of components may impair
suitability for
Class I, Division 2.
• Do not replace components or disconnect
equipment unless power has been switched off
or the area is known to be non-hazardous.
• Do not connect or disconnect components
unless power has been switched off or the area
is known to be non-hazardous.
• This product must be installed in an enclosure.
• All wiring must comply with N.E.C. article
501-4(b).
Prevent Electrostatic Discharge
ATTENTION
Electrostatic discharge can damage integrated circuits
or semiconductors if you touch I/O module bus
connector pins or the terminal block on the input
module. Follow these guidelines when you handle
the module:
!
• Touch a grounded object to discharge static
potential.
• Wear an approved wrist-strap grounding device.
• Do not touch the bus connector or connector
pins.
• Do not touch circuit components inside the
module.
• If available, use a static-safe work station.
• When it is not in use, keep the module in its
static-shield box.
Publication 1762-UM003A-EN-P - February 2003
2-4 Installation and Wiring
Remove Power
ATTENTION
Remove power before removing or inserting this
module. When you remove or insert a module with
power applied, an electrical arc may occur. An
electrical arc can cause personal injury or property
damage by:
!
• sending an erroneous signal to your system’s
field devices, causing unintended machine
motion
• causing an explosion in a hazardous
environment
Electrical arcing causes excessive wear to contacts
on both the module and its mating connector and
may lead to premature failure.
Selecting a Location
Reducing Noise
Most applications require installation in an industrial enclosure to
reduce the effects of electrical interference. RTD inputs are highly
susceptible to electrical noise. Electrical noise coupled to the RTD
inputs will reduce the performance (accuracy) of the module.
Publication 1762-UM003A-EN-P - February 2003
Group your modules to minimize adverse effects from radiated
electrical noise and heat. Consider the following conditions when
selecting a location for the module. Position the module:
• away from sources of electrical noise such as hard-contact
switches, relays, and AC motor drives
• away from modules which generate significant radiated heat.
Refer to the module’s heat dissipation specification.
In addition, route shielded, twisted-pair wiring away from any high
voltage I/O wiring.
Mounting
Installation and Wiring 2-5
ATTENTION
!
Do not remove protective debris strip until after the
module and all other equipment near the module is
mounted and wiring is complete. Once wiring is
complete and the module is free of debris, carefully
remove the protective debris strip. Failure to remove
the strip before operating can cause overheating.
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment,
etc. Allow 50.8 mm (2 in.) of space on all sides for adequate
ventilation, as shown below:
To p
SideSide
TIP
ATTENTION
MicroLogix
1200
1762 I/O may be mounted horizontally only.
During DIN rail or panel mounting of all devices, be
sure that all debris (metal chips, wire strands, etc.) is
kept from falling into the module. Debris that falls
into the module could cause damage at power up.
1762 I/O
1762 I/O
Bottom
!
1762 I/O
Publication 1762-UM003A-EN-P - February 2003
2-6 Installation and Wiring
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5
mm (EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latch.
Press the DIN rail mounting area of the module against the DIN rail.
The latch will momentarily open and lock into place.
Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or
1492-EAH35) for environments with vibration or shock concerns.
End Anchor
End Anchor
Publication 1762-UM003A-EN-P - February 2003
TIP
For environments with extreme vibration and
shock concerns, use the panel mounting method
described below, instead of DIN rail mounting.
Panel Mounting
Use the dimensional template shown below to mount the module.
The preferred mounting method is to use two M4 or #8 panhead
screws per module. M3.5 or #6 panhead screws may also be used, but
a washer may be needed to ensure a good ground contact. Mounting
screws are required on every module.
For more than 2 modules: (number of modules - 1) x 40.4 mm (1.59 in.)
14.5
(0.57)
100
90
(3.94)
(3.54)
NOTE:
Hole spacing tolerance:
±0.4 mm (0.016 in.).
MicroLogix 1200
Installation and Wiring 2-7
40.4
(1.59)
Expansion I/O
MicroLogix 1200
MicroLogix 1200
MicroLogix 1200
Expansion I/O
Expansion I/O
40.4
(1.59)
System Assembly
The expansion I/O module is attached to the controller or another I/O
module by means of a ribbon cable after mounting as shown below.
IMPORTANT
WARNING
Use the pull loop on the connector to disconnect
modules. Do not pull on the ribbon cable.
EXPLOSION HAZARD
!
• In Class I, Division 2 applications, the bus
connector must be fully seated and the bus
connector cover must be snapped in place.
• In Class I, Division 2 applications, all modules
must be mounted in direct contact with each
other as shown on page 2-1. If DIN rail mounting
is used, an end stop must be installed ahead of
the controller and after the last 1762 I/O module.
Publication 1762-UM003A-EN-P - February 2003
2-8 Installation and Wiring
Field Wiring Connections
System Wiring Guidelines
Consider the following when wiring your system:
General
• This product is intended to be mounted to a well-grounded
mounting surface such as a metal panel. Additional grounding
connections from the module’s mounting tabs or DIN rail (if
used) are not required unless the mounting surface cannot be
grounded.
• Channels are isolated from one another by ±10V dc maximum.
• Do not use the modules NC terminals as connection points.
• Route field wiring away from any other wiring and as far as
possible from sources of electrical noise, such as motors,
transformers, contactors, and ac devices. As a general rule, allow
at least 15.2 cm (6 in.) of separation for every 120V of power.
• Routing field wiring in a grounded conduit can reduce electrical
noise.
• If field wiring must cross ac or power cables, ensure that they
cross at right angles.
• To ensure optimum accuracy, limit overall cable impedance by
keeping your cable as short as possible. Locate the I/O system
as close to your sensors or actuators as your application will
permit.
• Tighten terminal screws with care. Excessive tightening can strip
a screw.
Publication 1762-UM003A-EN-P - February 2003
Shield Grounding
• Use Belden shielded, twisted-pair wire to ensure proper
operation and high immunity to electrical noise. Refer to the
following table and the RTD Wiring Considerations below.
Configuration
2-wireBelden™ 9501 or equivalent
3-wire
less than 30.48 m (100ft.)
3-wire
greater than 30.48 m (100 ft.) or high
humidity conditions
(1) For additional information, see page A-4.
• Under normal conditions, the drain wire and shield junction
should be connected to earth ground, via a panel or DIN rail
mounting screw at the 1762-IR4 module end.
Recommended Cable
Belden™ 9533 or equivalent
Belden™ 83503 or equivalent
(1)
Installation and Wiring 2-9
• Keep shield connection to ground as short as possible.
• If noise persists for a device, try grounding the opposite end of
the cable. (You can only ground one end at a time.)
• Refer to Industrial Automation Wiring and Grounding
Guidelines, Allen-Bradley publication 1770-4.1, for additional
information.
RTD Wiring Considerations
Since the operating principle of the RTD module is based on the
measurement of resistance, take special care when selecting your
input cable. For 2-wire or 3-wire configurations, select a cable that has
a consistent impedance throughout its entire length. See Cable
Specifications on page A-4.
IMPORTANT
The RTD module requires three wires to
compensate for lead resistance error. We
recommend that you do not use 2-wire RTDs if long
cable runs are required, as it reduces the accuracy of
the system. However, if a two-wire configuration is
required, reduce the effect of the lead wire
resistance by using a lower gauge wire for the cable
(for example, use AWG #16 instead of AWG #24).
The module’s terminal block accepts two AWG #14
gauge wires.
When using a 3-wire configuration, the module compensates for
resistance error due to lead wire length. For example, in a 3-wire
configuration, the module reads the resistance due to the length of
one of the wires and assumes that the resistance of the other wire is
equal. If the resistances of the individual lead wires are much
different, an error may exist. The closer the resistance values are to
each other, the greater the amount of error that is eliminated.
IMPORTANT
To ensure temperature or resistance value accuracy,
the resistance difference of the cable lead wires
must be equal to or less than 0.01
Ω .
To insure that the lead values match as closely as possible:
• Keep lead resistance as small as possible and less than 25
• Use quality cable that has a small tolerance impedance rating.
• Use a heavy-gauge lead wire which has less resistance per foot.
Publication 1762-UM003A-EN-P - February 2003
Ω .
2-10 Installation and Wiring
Wiring the Finger-Safe Terminal Block
ATTENTION
Be careful when stripping wires. Wire fragments that
fall into a module could cause damage when power
is applied. Once wiring is complete, ensure the
module is free of all metal fragments.
!
When wiring the terminal block, keep the finger-safe cover in place.
1. Route the wire under the terminal pressure plate. You can use
the stripped end of the wire or a spade lug. The terminals will
accept a 6.35 mm (0.25 in.) spade lug.
2. Tighten the terminal screw making sure the pressure plate
secures the wire. Recommended torque when tightening
terminal screws is 0.904 Nm (8 in-lbs).
3. After wiring is complete, remove the debris shield.
TIP
If you need to remove the finger-safe cover, insert a
screw driver into one of the square wiring holes and
gently pry the cover off. If you wire the terminal
block with the finger-safe cover removed, you will
not be able to put it back on the terminal block
because the wires will be in the way.
Publication 1762-UM003A-EN-P - February 2003
Installation and Wiring 2-11
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
Wire TypeWire SizeTerminal Screw Torque
SolidCu-90°C (194°F)#14 to #22 AWG0.904 Nm (8 in-lbs)
StrandedCu-90°C (194°F)#16 to #22 AWG0.904 Nm (8 in-lbs)
Wiring Input Devices to the Module
ATTENTION
To prevent shock hazard, care should be taken when
wiring the module to analog signal sources. Before
wiring any module, disconnect power from the
system power supply and from any other source to
the module.
!
After the module is properly installed, follow the wiring procedure
below and the RTD and potentiometer wiring diagrams on pages 2-12
through 2-15. To ensure proper operation and high immunity to
electrical noise, always use Belden™ shielded, twisted-pair or
equivalent wire.
Cut foil shield
and drain wire
signal wire
signal wire
signal wire
signal wire
drain wire
cable
foil shield
signal wire
signal wire
signal wire
drain wire
foil shield
cable
Publication 1762-UM003A-EN-P - February 2003
Cut foil shield
and drain wire
signal wires (3)
2-12 Installation and Wiring
To wire your module follow these steps:
1. At each end of the cable, strip some casing to expose the
individual wires.
2. Trim the signal wires to 2-inch (5 cm) lengths. Strip about 3/16
inch (5 mm) of insulation away to expose the end of the wire.
ATTENTION
Be careful when stripping wires. Wire fragments that
fall into a module could cause damage at power up.
!
3. At the module end of the cable, twist the drain wire and foil
shield together, bend them away from the cable, and apply
shrink wrap. Then earth ground via a panel or DIN rail
mounting screw at the end of the module. Keep the length of
the drain wire as short at possible.
4. At the other end of the cable, cut the drain wire and foil shield
back to the cable and apply shrink wrap.
5. Connect the signal wires to the terminal block as described for
each type of input. See Wiring RTDs on page 2-12 or Wiring
Resistance Devices (Potentiometers) on page 2-14.
6. Connect the other end of the cable to the analog input device.
Publication 1762-UM003A-EN-P - February 2003
7. Repeat steps 1 through 6 for each channel on the module.
Wiring RTDs
Three types of RTDs can be connected to the 1762-IR4 module:
• 2-wire RTD, which is composed of an RTD EXC (excitation) lead
wire and a RTN (return) lead wire
• 3-wire RTD, which is composed of a Sense and 2 RTD lead
wires (RTD EXC and RTN)
• 4-wire RTD, which is composed of a Sense and 2 RTD lead
wires (RTD EXC and RTN). The second sense wire from the
4-wire RTD is left open.
Loading...
+ 74 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.