Important User Information2
Overview3
North American Hazardous Location Approval4
Module Description5
Install the DC-Input/Relay-Output Combination Module6
Mount the Module on a DIN Rail6
Mount the Module on a Panel7
Wire the DC-Input/Relay-Output Combination Module8
Ground the DC-Input/Relay-Output Combination Module9
Wire the Finger-safe Terminal Block9
System Assembly10
Input Memory Map11
Output Memory Map12
Specifications13
Additional Resources17
Publication 1762-IN018B-EN-P - July 2013
Page 2
2 DC-Input/Relay-Output Combination Module
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
SGI-1.1
available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
) describes some important differences between solid state
Publication 1762-IN018B-EN-P - July 2013
Identifies information about practices or circumstances that can cause an explosion in
a hazardous environment, which may lead to personal injury or death, property
damage, or economic loss.
Identifies information that is critical for successful application and understanding of
the product.
Identifies information about practices or circumstances that can lead to personal injury
or death, property damage, or economic loss. Attentions help you identify a hazard,
avoid a hazard and recognize the consequences.
Labels may be located on or inside the equipment (for example, drive or motor) to alert
people that dangerous voltage may be present.
Labels may be located on or inside the equipment (for example, drive or motor) to alert
people that surfaces may be dangerous temperatures.
Page 3
DC-Input/Relay-Output Combination Module 3
ATTENTION
ATTENTION
Overview
The 1762 I/O is suitable for use in an industrial environment when installed in accordance with
these instructions. Specifically, this equipment is intended for use in clean, dry environments
(Pollution degree 2
(3)
60664-1).
.
(1)
) and to circuits not exceeding Over Voltage Category II
(2)
(IEC
Prevent Electrostatic Discharge
Electrostatic discharge can damage integrated circuits or semiconductors if
you touch bus connector pins. Follow these guidelines when you handle the
module.
• Touch a grounded object to discharge static potential.
• Wear an approved wrist-strap grounding device.
• Do not touch the bus connector or connector pins.
• Do not touch circuit components inside the module.
• Use a static-safe work station, if available.
• Keep the module in its static-shield box when not in use.
Remove Power
(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
Remove power before removing or installing this module. When you remove
or install a module with power applied, an electrical arc may occur. An
electrical arc can cause personal injury or property damage by:
• sending an erroneous signal to your system’s field devices, causing
unintended machine motion.
• causing an explosion in a hazardous environment.
• causing permanent damage to the module’s circuitry.
Electrical arcing causes excessive wear to contacts on both the module and its
mating connector. Worn contacts may create electrical resistance.
temporary conductivity caused by condensation shall be expected.
controlled and do not exceed the impulse voltage capability of the product’s insulation.
Publication 1762-IN018B-EN-P - July 2013
Page 4
4 DC-Input/Relay-Output Combination Module
WARNING
AVERTISSEMENT
North American Hazardous Location Approval
The following modules are North American Hazardous Location approved: 1762-IQ8OW6
The following information applies when
operating this equipment in hazardous
locations:
Products marked "CL I, DIV 2, GP A, B, C, D" are
suitable for use in Class I Division 2 Groups A, B, C,
D, Hazardous Locations and nonhazardous
locations only. Each product is supplied with
markings on the rating nameplate indicating the
hazardous location temperature code. When
combining products within a system, the most
adverse temperature code (lowest "T" number) may
be used to help determine the overall temperature
code of the system. Combinations of equipment in
your system are subject to investigation by the
local Authority Having Jurisdiction at the time of
installation.
EXPLOSION HAZARD
• Do not disconnect equipment
unless power has been removed
or the area is known to be
nonhazardous.
• Do not disconnect connections to
this equipment unless power has
been removed or the area is
known to be nonhazardous.
Secure any external connections
that mate to this equipment by
using screws, sliding latches,
threaded connectors, or other
means provided with this product.
• Substitution of components may
impair suitability for Class I,
Division 2.
• If this product contains batteries,
they must only be changed in an
area known to be nonhazardous.
• All wiring must comply with
N.E.C. article 501-4(b).
• The interior of the enclosure must
be accessible only by the use of a
tool.
• For applicable equipment (relay
modules, etc.), exposure to some
chemicals may degrade the
sealing properties of materials
used in the following devices:
Relays, Epoxy. It is recommended
that the User periodically inspect
these devices for any degradation
of properties and replace the
module if degradation is found.
Informations sur l’utilisation de cet
équipement en environnements dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements de
Classe I Division 2 Groupes A, B, C, D dangereux et non
dangereux. Chaque produit est livré avec des
marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés
dans un système, le code de température le plus
défavorable (code de température le plus faible) peut
être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements
dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de l'installation.
RISQUE D’EXPLOSION
• Couper le courant ou s’assurer que
l’environnement est classé non
dangereux avant de débrancher
l'équipement.
• Couper le courant ou s'assurer que
l'environnement est classé non
dangereux avant de débrancher les
connecteurs. Fixer tous les
connecteurs externes reliés à cet
équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou
autres moyens fournis avec ce
produit.
• La substitution de composants peut
rendre cet équipement inadapté à une
utilisation en environnement de
Classe I, Division 2.
• S’assurer que l’environnement est
classé non dangereux avant de
changer les piles.
Publication 1762-IN018B-EN-P - July 2013
Page 5
DC-Input/Relay-Output Combination Module 5
1a
7
6
1b
4
5
3
9
1a
6
8
1b
2
Module Description
Item DescriptionItemDescription
1aupper panel mounting tab5bus connector cover
1blower panel mounting tab6flat ribbon cable with bus connector
2I/O diagnostic LEDs7terminal block
3module door with terminal identification label 8DIN rail latch
4bus connector with male pins9pull loop
(female pins)
Publication 1762-IN018B-EN-P - July 2013
Page 6
6 DC-Input/Relay-Output Combination Module
ATTENTION
TIP
ATTENTION
Install the DC-Input/Relay-Output Combination Module
Do not remove protective debris strip until after the module and all other
equipment near the module is mounted and wiring is complete. Once wiring
is complete and the module is free of debris, carefully remove protective
debris strip. Failure to remove strip before operating can cause overheating.
Maintain spacing from enclosure walls, wireways, and adjacent equipment. Allow 50.8 mm
(2 in.) of space on all sides for adequate ventilation, as shown:
MicroLogix
1200
1762 I/O
1762 I/O
1762 I/O
Mount the Module on a DIN Rail
The module can be mounted using the following DIN rails: 35 x 7.5 mm
(EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN-rail, close the DIN-rail latch. Press the DIN-rail
mounting area of the module against the DIN-rail. The latch will momentarily open and lock
into place.
Use DIN-rail end anchors (Allen-Bradley part number 1492-EA35 or 1492-EAH35) for
vibration or shock environments.
Publication 1762-IN018B-EN-P - July 2013
1762 expansion I/O is only mounted horizontally.
During panel or DIN-rail mounting of all devices, be sure that all debris
(metal chips or wire strands) is kept from falling into the module. Debris
that falls into the module could cause damage when power is applied to the
module.
Page 7
DC-Input/Relay-Output Combination Module 7
TIP
End Anchor
End Anchor
MicroLogix 1200
Controller
MicroLogix 1200
Expansion I/O
MicroLogix 1200
Expansion I/O
MicroLogix 1200
Expansion I/O
90
(3.54)
100
(3.94)
40.4
(1.59)
40.4
(1.59)
14.5
(0.57)
For more than two modules: (number of modules - 1) x 40 mm (1.58 in.)
NOTE: All dimensions are in mm (inches). Hole spacing tolerance: ±0.4 mm (0.016 in.).
For environments with greater vibration and shock concerns, use the panel
mounting method described below, instead of DIN-rail mounting.
Mount the Module on a Panel
Use the dimensional template shown below to mount the module. The preferred mounting
method is to use two M4 or #8 panhead screws per module. M3.5 or #6 panhead screws may also
be used, but a washer may be needed to ensure a good ground contact. Mounting screws are
required on every module.
Publication 1762-IN018B-EN-P - July 2013
Page 8
8 DC-Input/Relay-Output Combination Module
ATTENTION
Wire the DC-Input/Relay-Output Combination Module
Basic wiring of inputs
+DC (Sinking)
-DC (Sourcing)
-DC (Sinking)
+DC (Sourcing)
(1)
and outputs
(2)
is shown below.
IN 0
IN 1
IN 2
IN 3
DC
COM 0
IN 4
IN 5
IN 6
IN 7
DC
COM 1
+DC (Sinking)
-DC (Sourcing)
-DC (Sinking)
+DC (Sourcing)
A write-on label is provided with the module. Mark the identification of each terminal with
permanent ink, and slide the label back into the door.
(1) Sinking/Sourcing Inputs - Sinking/Sourcing describes the current flow between the I/O module and the field device.
(2) Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay
L1 or +DC
VAC
VDC
OUT 0
OUT 2
CR
OUT 4
VAC
VDC
OUT 1
OUT 3
OUT 5
Connected Internally
L1 or +DC
L2 or -DC
CR
CR
CR
Be careful when stripping wires. Wire fragments that fall into a module
could cause damage when power is applied. Once wiring is complete, ensure
the module is free of all metal fragments.
Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are driven by a current sourcing
field device. Field devices connected to the negative side (DC Common) of the field power supply are sinking field devices.
Field devices connected to the positive side (+V) of the field supply are sourcing field devices.
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication
1770-4.1.
Publication 1762-IN018B-EN-P - July 2013
Page 9
DC-Input/Relay-Output Combination Module 9
ATTENTION
Miswiring of the module to an AC power source will damage the module.
Ground the DC-Input/Relay-Output Combination Module
This product is intended to be mounted to a well-grounded mounting surface such as a metal
panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used)
are not required unless the mounting surface cannot be grounded. Refer to Industrial
Automation Wiring and Grounding Guidelines, Allen-Bradley publication
additional information.
1770-4.1, for
Wire the Finger-safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1. Route the wire under the terminal pressure plate.
You can use the stripped end of the wire or a spade lug. The terminals will accept a
6.35 mm (0.25 in.) spade lug.
2. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.90 Nm (8 lb-in.).
Publication 1762-IN018B-EN-P - July 2013
Page 10
10 DC-Input/Relay-Output Combination Module
TIP
TIP
If you need to remove the finger-safe cover, insert a screw driver into one of
the square wiring holes and gently pry the cover off. If you wire the terminal
block with the finger-safe cover removed, you will not be able to put it back
on the terminal block because the wires will be in the way.
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
Wire TypeWire SizeTerminal Screw Torque
SolidCu-90 °C (194 °F)
StrandedCu-90 °C (194 °F)
0.325…2.080 mm
(22…14 AWG)
0.325…1.310 mm
(22…16 AWG)
2
2
0.90 Nm (8 lb-in.)
0.90 Nm (8 lb-in.)
System Assembly
The expansion I/O module is attached to the controller or another I/O module by means of a
flat ribbon cable after mounting.
Use the pull loop on the connector to disconnect modules. Do not pull on
the ribbon cable.
Publication 1762-IN018B-EN-P - July 2013
Page 11
DC-Input/Relay-Output Combination Module 11
ATTENTION
I1:x.0/0
Input
Data File
Slot Number
(1)
Word (Always Zero for This Module)
Bit (0…15)
Bit Delimiter
Word Delimiter
Slot Delimiter
EXPLOSION HAZARD
• In Class I, Division 2 applications, the bus connector must be fully
seated and the bus connector cover must be snapped in place.
• In Class I, Division 2 applications, all modules must be mounted in
direct contact with each other as shown on page 6. If DIN-rail
mounting is used, an end stop must be installed ahead of the controller
and after the last 1762 I/O module.
Input Memory Map
For each input module, the input data file contains the current state of the field input points. Bit
positions 0…15 correspond to input terminals 0…15.
Bit Position
1514131211109876543210
Word
000000000r r r r r rr r
r = read only 0 = always at 0 or OFF state.
The input addressing scheme for 1762 expansion I/O is shown below.
(1) I/O located on the controller (embedded I/O) is slot 0. I/O added to the controller (expansion I/O) begins with slot 1.
Publication 1762-IN018B-EN-P - July 2013
Page 12
12 DC-Input/Relay-Output Combination Module
O0:x.0/0
Output
Data File
Slot Number
(1)
Word (Always Zero for This Module)
Bit (0… 15)
Bit Delimiter
Word Delimiter
Slot Delimiter
Output Memory Map
For each output module, the output data file contains the controller-directed state of the digital
output points. Bit positions 0…15 correspond to output terminals 0…15.
Bit Position
1514131211109876543210
Word
000000000w*w*wwwwww
w = write only, w* = user can write but outputs not available, 0= always at 0 or OFF state
The output addressing scheme for 1762 expansion I/O is shown below.
(1) I/O located on the controller (embedded I/O) is slot 0. I/O added to the controller (expansion I/O) begins with slot 1.
Publication 1762-IN018B-EN-P - July 2013
Page 13
DC-Input/Relay-Output Combination Module 13
Specifications
Input Specifications
SpecificationValue
Voltage Category
Operating Voltage Range10…30V DC @ 30 °C (86 °F)
Number of Inputs8
On-state Voltage, (Min)10V DC
Off-state Voltage, (Max)5V DC
On-state Current, (Min)2.0 mA
Off-state Current, (Max)1.5 mA
Inrush Current, (Max)250 mA
Nominal Impedance3 kΩ
Input CompatibilityIEC Type 1+
Signal Delay Time, (Max)On-delay: 8 ms
(1) Sinking/Sourcing Inputs - Sinking/Sourcing describes the current flow between the I/O module and the field device.
Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are driven by a current sourcing field
device. Field devices connected to the negative side (DC Common) of the field power supply are sinking field devices. Field
devices connected to the positive side (+V) of the field supply are sourcing field devices.
24V DC (Sink/Source)
10…26.4V DC @ 65 °C (149 °F)
Off-delay: 8 ms
(1)
Publication 1762-IN018B-EN-P - July 2013
Page 14
14 DC-Input/Relay-Output Combination Module
Output Specifications
SpecificationValue
Voltage Range 5…265V AC
5…125V DC
Commons per Module6
Output Type6-Form A (normally open)
Signal Delay TimeOn-delay: 10 mS (max) Off-delay: 10 mS (max)
Off Leakage Current0 mA
On-state Current (Min.)10 mA @ 5V DC
Continuous Current per PointSee table on page 14.
Continuous Current per Module8 A
Total Controlled Load1440VA/Module max
Relay Contact Ratings
Volts (max.)Continuous
Amps per
Point (Max.)
Amperes
(1)
Voltamperes
MakeBreakMakeBreak
240V AC2.5 A7.5 A0.75 A1800VA180VA
120V AC15 A1.5 A
125V DC1.0 A
0.22 A
(2)
24V DC2.0 A1.2 A
(1) Surge Suppression - Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(2) For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 14V, the make/break rating
for relay contacts cannot exceed 2A.
28VA
28VA
(2)
(2)
Publication 1762-IN018B-EN-P - July 2013
Page 15
DC-Input/Relay-Output Combination Module 15
General Specifications
SpecificationValue
Dimensions, HxWxD90 x 40.4 x 87 (3.54 x 1.59 x 3.43 in.)
Approximate Shipping Weight
(with carton)
Bus Current Draw, (Max)110 mA @ 5V DC
Heat Dissipation5.0 W @ 30V DC
Power Supply Distance Rating6
Isolated GroupGroup 1 (input 0…3) Group 2 (input 4…7) Group 3 (output 0…5)
VibrationOperating: 10…500 Hz, 5 g, 0.030 in. max. peak-to-peak,
ShockOperating: 30 g panel mounted, 3 pulses per axis
Vender ID Code1
Product Type Code7
Product Code98
Hazardous Environment ClassClass I, Division 2, Hazardous Location, Groups A, B, C, D
(1) Conducted Immunity frequency range may be 150 kHz…30 MHz if the Radiated Immunity frequency range is
30…1000 MHz.
height including mounting tabs is 110 mm (4.33in.)
280g (0.62 lbs.)
80 mA @ 24V DC
4.4 W @ 26.4V DC
(The Watts per point, plus the minimum W, with all points energized.)
2 hours per axis.
Relay Operation: 1.5 g
Relay Operation: 7 g
Non-Operating: 50 g panel mounted, 3 pulses per axis
(40 g DIN Rail mounted)
ISA/ANSI 12.12.01
(C-UL under CSA C22.2 No. 213)
EN50081-2 Class A
carrier
10V, 0.15…80 MHz
(1)
Publication 1762-IN018B-EN-P - July 2013
Page 16
16 DC-Input/Relay-Output Combination Module
Environmental Specifications
SpecificationValue
Operation Temperature Range-20…+65 °C (-4…+149 °F)
Storage Temperature Range-40…+85 °C (-40…+185 °F)
Operating Humidity5…95% non-condensing
Operating Altitude2000 m (6561 ft)
Certifications
Certification (when
product is marked)
c-UL-usUL Listed Industrial Control Equipment, certified for US and Canada.
CEEuropean Union 2004/108/EC EMC Directive, compliant with:
KCKorean Registration of Broadcasting and Communications Equipment,
(1) See the Product Certification link at http://www.rockwellautomation.com/products/certification for Declaration of
Conformity, Certificates, and other certification details.
Valu e
(1)
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for
U.S. and Canada. See UL File E334470.
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable
Controllers (Clause 11)
AS/NZS CISPR 11; Industrial Emissions
compliant with:
Article 58-2 of Radio Waves Act, Clause 3
Publication 1762-IN018B-EN-P - July 2013
Page 17
DC-Input/Relay-Output Combination Module 17
Additional Resources
Refer toFor More Information on this Topic
MicroLogix 1200 Programmable Controllers
User Manual (Bulletin 1762 Controllers and
Expansion I/O), publication 1762-UM001
Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1
.
.
.
If you would like a manual, you can:
• download a free electronic version from the internet:
http://literature.rockwellautomation.com
• purchase a printed manual by contacting your local Allen-Bradley distributor or
Rockwell Automation representative
Information on installing, wiring, and operating a
MicroLogix 1200 programmable controller system
.
Installation guide for the MicroLogix 1200
programmable controller.
A more detailed description of how to install and use
your MicroLogix 1100 programmable controller and
expansion I/O system.
Installation guide for the MicroLogix 1100
programmable controllers
More information on proper wiring and grounding
techniques.
.
Publication 1762-IN018B-EN-P - July 2013
Page 18
18 DC-Input/Relay-Output Combination Module
Notes:
Publication 1762-IN018B-EN-P - July 2013
Page 19
Notes:
DC-Input/Relay-Output Combination Module 19
Publication 1762-IN018B-EN-P - July 2013
Page 20
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/
technical and application notes, sample code and links to software service packs, and a MySupport feature that
you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer
TechConnect support programs. For more information, contact your local distributor or Rockwell Automation
representative, or visit http://www.rockwellautomation.com/support/
, you can find technical manuals, a knowledge base of FAQs,
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's
contained in this manual. You can also contact a special Customer Support number for initial help in getting your
product up and running.
United States or
1.440.646.3434
Canada
Outside United
States or
Canada
Use the
Worldwide Locator at
http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your
local Rockwell Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these
procedures.
United StatesContact your distributor. You must provide a Customer Support case
number (call the phone number above to obtain one) to your distributor
to complete the return process.
Outside United StatesPlease contact your local Rockwell Automation representative for the
return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002
http://www.rockwellautomation.com/literature/
Allen-Bradley, Rockwell Automation, MicroLogix, and TechConnect are trademarks of Rockwell Automation, Inc.
Tra demarks not belonging to Rockwell Automation are property of their respective companies.